W2- H - 10 (50%) 0.225 5.55 1.000 1.

25
W2- H - 10 (50%) 0.225 5.55 1.000 1.25
Total of thermal bridges Sk Psik·lk·ek W/K 7.68
Total heat loss coefficient directly to the exterior Ht,ie = Sk Ak·Uk·ek + Sk Psik·lk·ek 45.48
Heat losses through unheated spaces
Code Building Ak (mІ) Uk (W/mІK) bu Ak·Uk·bu
Element (W/K)
F1 Floor 1 39.57 0.35 0.263 3.64
Total of building elements Sk Ak·Uk·bu W/K 3.64
Code Thermal bridge Шk (W/mK) lk (m) bu Шk·lk·bu (W/K)
Total of thermal bridges Sk Psik·lk·bu W/K 7.68
Total heat loss coefficient through unheated spaces Ht,iue = Sk Ak·Uk·bu + Sk Psik·lk·bu 3.64
Heat losses through the ground
Calculation of B Ag (mІ) P (m) B'=2·Ag/P (m)

Code Building Uk (W/mІK) Uequiv,k Ak (mІ) Ak·Uequiv,k


Element (W/mІK) (W/K)
Total of equivalent building elements Sk Ak·Uequiv,k W/K 0.00
Correction factors fg1 fg2 Gw fg1·fg2·Gw
1.45
Total heat loss coefficient through the ground Ht,ig = (Sk Ak·Uequiv,k)·fg1·fg2·Gw 0.00
Heat losses to spaces heated at different temperatures
Code Building fij Ak (mІ) Uk (W/mІK) fij·Ak·Uk (W/K)
Element
Total heat loss coefficient through spaces at different temperature Ht,ij = Sk fij·Ak·Uk 0.00
Total transmission heat loss coefficient Ht,i = Ht,ie + Ht,iue + Ht,ig + Ht,ij W/K 49.12
Temperature data
Design external temperature иe °C -18
Design internal temperature иint,i °C 20
Design temperature difference иint,i-иe °C 38
Total transmission heat loss Phit,i = Ht,i·(tint,i - te) W 1868
Increment % 20
Total design transmission heat loss with increment 2241

Ventilation heat loss calculation


Room internal volume Vi m3 118.7
Outdoor Temperature иe °C -18
Internal temperature иint,i °C 20
Minimum hygienic air exchange rate nmin,i 1/h 0.5
Minimum hygienic air flow rate Vmin,i m3/h 59.36
Air exchange rate/hour at 50 Pa (n50) n50 1/h 5
Shielding coefficient e 0.02
Height correction factor е 1.00
Infiltration air flow rate Vinf,i m3/h 23.74
Selected value for calculation Vi m3/h 59.36
Design ventilation heat loss coefficient Hv,i W/K 20.18
Temperature difference иint-иe °C 38
Design ventilation heat loss Цv,i W 766.9 766.9

Calculation of heating-up capacity


Reheat factor fRH W/mІ 23
Floor area Ai mІ 39.57
Heating-up capacity ЦRH,i W 0.00 0.00

Total design heat load


Total heat load ЦHL,i W 2008