Introduction :
The 4 pole contactors type 3RT13 and 3RT15 are specially designed to meet specific applications. These contactors
are highly reliable, user friendly and meets the expectation of world class Siemens products. They conform to the
latest IEC60947-4-1 standard and carry CE marking.
Selection Table
4Pole, AC1 Duty Contactors
No of main Contacts 4 NO 2 NO + 2 NC
Rating MLFB * MLFB *
Size Ie (AC1) amp (Pls. fill in .. with coil voltage) (Pls. fill in .. with coil voltage)
18A 3RT13 16 1A..0 3RT15 16 1A..0
S00
22A 3RT13 17 1A..0 3RT15 17 1A..0
35A 3RT13 25 1A..0 –
S0
40A 3RT13 26 1A..0 3RT15 26 1A..0
55A – 3RT15 35 1A..0
S2
60A 3RT13 36 1A..0 –
110A 3RT13 44 1A..0 –
S3
140A 3RT13 46 1A..0 –
(..) Coil voltage code for AC coils, 50Hz
3RT13/15 : F0 = 110V, P0 = 230V and V0 = 400V
* Contactors with DC coils are also available upon request.
Technical Data
Contactor Size S00 S0 S2 S3
4 NO Type 3RT13 16 3RT13 17 3RT1325 3RT1326 3RT1336 3RT1344 3RT1346
2 NO + 2 NC 3RT15 16 3RT15 17 3RT15 26 3RT1535
General Data
Rated Insulation Voltage V 690
Permissible Ambient Temperature in operation ºC -25..+60
in storage ºC -55..+80
Mechanical Endurance cycles 30 mill. 10 mill.
Electrical Endurance at Ie/AC1 cycles 0.5 mill.
Main Circuit
AC1 Duty(switching resistive loads)
Rated operational current Ie at 40º C upto 690V A 18 22 35 40 60 55 110 140
at 60º C upto 690V A 16 20 30 35 55 50 100 120
Rating of 3 phase loads (p.f = 0.95) at 230V kW 7 8.5 12.5 15 23 20 42 53
at 415V kW 12 14.5 22 26 39 36 72 92
AC2 and AC3 Duty
Rated operational current Ie at 415V A 9 12 17 25 26 40 – –
Maximum rating of slipring or squirrel
cage motors at 50/60Hz at 415V kW 4 5.5 7.5 11 11 18.5 – –
Control Circuit
Coil Voltage Tolerance AC/DC at 50 Hz AC/DC: 0.8-1.1 X Us
Power consumption of the coils Closing VA 26.5 61 145 270
AC operation, at 50Hz p.f 0.79 0.82 0.79 0.68
Closed VA 4.4 7.8 12.5 22
p.f 0.27 0.24 0.36 0.27
DC operation closing=closed W 3.3 5.6 13.3 15
Operating times at 0.8..1.1xUs
Closing time AC operation ms 8…35 6...30 4…35 20…50
DC operation ms 25…100 30…90 50…110 110…200
Opening time AC operation ms 4…30 13…25 10…30 10…25
DC operation ms 7…10 13…40 15…30 14…20
Operating frequency No Load AC cycles/hr 10000 5000 5000 5000 5000
DC cycles/hr 10000 1500 1500 1000 1000
at AC1 AC/DC cycles/hr 1000 1000 1000 1000 900
Short-Circuit Protection
Main Circuit (Fuse type 3NA) Co-ordination
Type-1 A 35 63 63 160 160 250 250
Type-2 A 20 25 35 63 80 125 160
Accessories
For Contactor 3RT13 16/17 3RT1325/26 3RT1336 3RT1344/46
3RT15 16/17 3RT1526 3RT1535
Aux. Contacts (front mounting)
1 NO – 3RH19 21 1CA10
1NC – 3RH19 21 1CA01
1NO+1NC 3RH19 11 1FA11 –
2NO+2NC 3RH19 11 1FA22 – 3RH19 21 1FA22
Surge Suppressors
AC 48V-127V 3RT1916 1BC00 3RT19 26 1BC00
AC 127V-240V 3RT1916 1BD00 3RT19 26 1BD00
AC 240V-400V 3RT1916 1BE00 3RT19 26 1BE00
Mechanical Interlocks
Front mountable 3RA19 12 2H 3RA19 24 1A
PCS
Dimensions (mm)
Siemens Ltd.
Automation & Drives Division
LV Controls & Distribution Products
Thane Belapur Road
Thane - 400 601
Fax: +91 22 27600076