Вы находитесь на странице: 1из 8

CURRENT CONTROL AND CAPACITOR VOLTAGE BALANCING IN A FIVE-

LEVEL INVERTER FOR DSTATCOM APPLICATION

Mr. K. Jaganath and Mr. Mahesh K. Mishra


Indian Institute of Technology Madras, Chennai.

Abstract—In this paper, a slope based hysteresis the former. Optimal width of hysteresis band is
current control technique and capacitor voltage required for limiting the switching frequency and
balancing for a five level neutral clamped inverter in
distribution static compensator (DSTATCOM) are for reducing the tracking error, which is the
proposed. As the number of levels in a voltage source difference between the reference current and
inverter(VSI) increases, average error which is actual current, produced due to tracking. More
the difference between the reference current and actual the hysteresis bands lesser the switching
current also increases, due to the increase in hysteresis
and dead bands. This method reduces the average
frequency and more the tracking error, lesser the
error. The slope of the reference current is tracked and hysteresis band, vice versa.
a change in slope marks the transition across the lower
band and upper band. Similarly, with every increase in
Multi-level inverters are popularly used in various
the level of the inverter, due to unequal flow of applications because of their advantages listed in
capacitor current caused by switching logic and [4], [5]. A diode clamped five-level neutral
average neutral current, balancing capacitor voltages clamped VSI is used for its advantages
become very inherent. In this work, a simple external mentioned in [4]. The motive to use multilevel
balancing circuit consisting of aninverter-chopper
arrangement is employed, to correct capacitor inverter includes lower switching frequency and
voltages irrespective of the nature of loads. high power applications. The use of hysteresis
control in multilevel inverter based DSTATCOM
Index Terms—Capacitor voltage balancing, DSTATCOM, is described in [6]. In this work, a slope based
Multilevel inverter, Slope based hysteresis current
control.
hysteresis current control, for tracking the
reference current has been described. The
objective in here is to minimize the tracking error
Σ(ijref - ijact), j=a,b,c where j represents each
INTRODUCTION phase in the three phase four wire system. The
slopes of the reference currents are calculated
Distribution STAtic COMpensator (DSTATCOM) and the transition from lower band to upper and
is becoming increasing popular for their reactive vice versa depends on the change in slope
power compensation, load balancing and together with the magnitude of error. In this paper
harmonic elimination [1]. DSTACOM’s are also a five-level, three-leg, diode clamped, neutral
used in voltage regulation and voltage flicker point clamped (NPC) inverter topology is
mitigation [2]. DSTATCOM finds importance considered. Each leg consists of eight switches
these days as there are rapid load variations with an anti-parallel diode connected across
which leads to flow of more reactive power every switch and six clamping diodes for
oscillations. The usage of power electronic loads clamping capacitor voltages. The midpoint of the
introduces non-linearities in currents which four identical capacitors Cdc is connected to the
generates quite a high amount of harmonics. For neutral wire of the system. The five levels
operation of DSTATCOM, a number of control achievable using the inverter are Vdc/2, Vdc/4, 0, -
algorithms have been presented in literature for Vdc/4 and –Vdc/2, referred to as states +1, +1/2,
generating the desired reference currents from 0, -1/2 and -1 respectively. Different
voltage source inverter (VSI) based DSTATCOM combinations of capacitors are selected for
for compensation. Among them, hysteresis operation of the inverter switches for achieving
current control technique is commonly used due the desired voltage levels. Hence, due to
to its ease in implementation, peak current switching logic and average zero sequence
limiting capability, fast dynamic response and components there are capacitor voltage
independent of system parameters [3]. Major imbalance in multilevel inverters. The capacitor
disadvantages of hysteresis control are wide voltage imbalance in the considered five-level
variation in switching frequency and increased inverter is balanced by using external balancing
switching losses in the inverter switches due to circuits as described in [7], [8]. The organization
of this paper is as follows. Section II describes One of the main drawbacks in basic three-level
the slope based hysteresis current control scheme is the average tracking error between
technique. Section III focuses on the five-level the reference current and the actual current is
diode clamped inverter and balancing capacitor high when compared to a basic two level
voltages using external balancing circuits. The scheme. This happens because of the
paper is concluded in Section IV. introduction of zero state by the dead band (δ).
The instantaneous error and the average tracking
error are reduced by the improved three-level
SLOPE BASED HYSTERESIS CURRENT
scheme [9]. Here, the δ bands are shifted around
CONTROL TECHNIQUE
the reference current causing an overlap of the
Hysteresis current control is commonly used in dead bands. This method is mainly suited only
DSTATCOM applications due to their for a three-level inverter. As the number of levels
aforementioned advantages. The basic two level increase there are more number of δ and h
hysteresis control requires, the error in each bands at different current levels. Shifting of δ
phase to track between two hysteresis bands +h bands becomes more complicated and
and -h as described in [3]. In three-level inverters cumbersome, hence cannot be incorporated. The
an additional dead band (δ) is introduced to slope based current controller is thus designed in
accommodate for the zero state. As the number such a way that is independent on level of
of level in a VSI increases, the number of inverter. The dead zone bands are near the
hysteresis and dead bands has to increase for reference waveform and the hysteresis bands
accommodating the respective number of are quite a distance from the reference current as
achievable levels from the inverter [6]. Due to in the basic scheme.
this, the tracking error increases as the number
From basic three-level scheme [3], due to the
of voltage level increases. With every increase in
switching logic, whenever the slope of the
h and δ bands, the increase in average tracking
reference current is positive the actual current
error can be attributed to, taking more time for
tracks the lower band and when the slope is
the actual current to transit from one band to the
negative it tracks the upper band. Instead of
other. If this transition within bands is made
transition from lower band to upper band and
instantaneous, considerable reduction in tracking
vice-versa due to tracking error magnitude alone,
error is obtained. This method focuses on the
the results of tracking, the reference current is
instantaneous transition from lower band to the
improved if the transition in made according to
upper band and/or upper band to lower band on
the slope of reference current. The logic for a
the basis of the slope of the reference current in
slope based hysteresis current control for a
each phase. Before and after the transition basic
three-level inverter is given.
hysteresis technique is adopted.
error = iref - iact
The slope based hysteresis current control
technique uses the same band h and δ as in [3] if refslope > 0 then
to track the reference currents. This is illustrated
if (uprevious = -1 or uprevious = 0) then x = 1
in Fig. 1 for a three-level VSI. The same
technique is adopted for multilevel inverter with if (error ≤ δ and x = 1) then u = -1
corresponding increase in h and δ bands. if error ≥ h then u = 1
Reference current
h (i ref) if error ≤ δ then u = 0
δ 0
-1 δ elseif refslope < 0 then (1)
h -1
0
1 Else if refslope < 0 then

Actual current
0
if (uprevious = 1 or uprevious = 0) then y = 1
(i act)
if (error ≥ - δ and y = 1) then u = 1
Slope>0 Slope<0
if error ≤ -h then u = -1
if error ≥ - δ then u = 0
Figure 1 Slope based hysteresis current control. The logic represented in (1) clearly shows that,
the transition from one band to other is based on
the slope. Flags ’x’ and ’y’ are set in equation (1) occurrence of +1 and -1 states at the time of
to avoid repetition in the switching logic. Since transition. This increases the stress across the
the movement is much faster than the basic switches and is primarily avoided in the basic
three-level inverter the error between the multilevel scheme [6]. The occurrence of such a
reference current and the actual current is switching occurs only when the slope of the
considerably reduced. The slope of the reference reference current changes and the previous input
currents are just used to track the exact transition is either a +1 or -1. Since there is a slope
time, the magnitude of the current to be tracked change, according to (1) there is again a +1 or -1
will depend on the dead and hysteresis bands. depending on which band the current is tracking.
Here, there is a question as to what maximum
With the proposed switching logic, simulation is
value actual currents should be pushed so as to
carried out for a three-phase four-wire system
ensure perfect tracking. For this, consider the
using PSCAD. Compensator is a neutral clamped
current is tracking upper band and there is a
five-level VSI consisting of three legs having
change of slope. As mentioned in logic the
twenty four IGBT switches (S1i - S8i) where i = a,
current should come down to lower band. From
b, c and four identical DC storage capacitors
(1) it can be seen that, the current is pushed only
Cdc1, Cdc2, Cdc3 and Cdc4. A single phase
till δ band. This is because of two reasons as
illustration of a five-level VSI is shown in Fig. 2.
mentioned below.
Each IGBT switch has an antiparallel diode
ƒ If the actual current is pushed to a region connected across it. The inverter is connected to
between h and δ and if there is an the point of common coupling (PCC) through
immediate change in slope then there interfacing inductor Lf and resistance Rf. A
exists no condition in the logic as in (1) for Proportional-Integral (PI) controller maintains the
proper tracking. total voltage across the capacitors
(Vdc1+Vdc2+Vdc3+Vdc4) around the reference value
ƒ If the current is pushed till h band, then
4Vdcref. The source voltages are assumed to be
the switches are unnecessarily operated
balanced and sinusoidal as shown in Fig. 3(a).
for longer time which is not required.
The loads draw unbalanced and nonlinear
Due to these constraints the reference currents currents from the source, as illustrated in Fig.
are pushed till δ band. By doing so there are two 3(b). The compensator reference currents (ifa; ifb;
main advantages. ifc) are extracted using the instantaneous
ƒ When the current is pushed till δ band, if symmetrical component theory [10] and the
the slope changes, the logic from (1) reference current equations are given below.
pushes the current back to the upper vsa isa ila
N PCC
band.(It is considered that current initially n
tracks the upper band). ifa
ƒ The basic three-level switching logic is S1a
effectively utilized. As the actual current Cdc1 +
vdc1 S2a
reaches δ band then, as per equation (1) - Rf
there is a zero state i.e. when error ≤ δ +
LOAD

S3a Lf
Then u=0. Cdc2
-
vdc2
i0 n S 4a
By increasing the number of h and δ bands, the
same procedure is used for multilevel inverters. ' a
The slope based hysteresis control has also Cdc3 + S5a
vdc3
been simulated on a five-level inverter using - S 6a
PSCAD. As the current level of δ and h bands is +
decreased a better tracking is achieved. This Cdc4 vdc4
- S7a
would in turn increase the switching frequency.
S 8a
Hence, a compromise is arrived between the
achievable frequency and the position of the
respective bands. The problem such as band Figure 2 Single phase five-level diode clamped
violation and finite sampling instants introduces inverter.
higher switching components. One of the primary
limitations of this method is the simultaneous
* vsa + γ ( vsb − v sc ) ⎫ 350 vsa vsb vsc 13 ila ilb
i fa = ila − isa = ila − ( Plavg + Ploss )⎪ ilc

Voltage (V)

C urrent (A)


* v sb + γ ( v sc − v sa ) ⎪ 0 0
i fb = ilb − isb = ilb − ( Plavg + Ploss ) ⎬ (2)
∆ ⎪
* v sc + γ ( v sa − v sb ) ⎪ -350 -13
= ilc − isc = ilc − ( Plavg + Ploss )
i fc
⎪ 0 10 Time (ms) 20 0 10 Time (ms) 20
∆ ⎭
(a) (b)
2
Where, ∆= ∑ v sj and γ = tan φ / 3 , φ being the 5 i* ifb*
j = a ,b ,c fa

C urrent(A)
desired power factor angle. For a unity power
factor (UPF) operation, γ =0. The term Plavg, 0
ifc*
which represents the average or mean power of
the load is obtained through a moving average -5
filter (MAF). The losses of the inverter, denoted 0 10 Time (ms) 20
as Ploss are generated using a PI controller. 10 (c) (d)
isa isb isc

C urrrent (A)
0
TABLE I
Simulation Parameters
230 V (L-N rms), 50 -10
0 10 Time (ms) 20
Supply voltages Hz
DC link voltage (2Vdcref) 1200 V Figure 3 (a) Balanced three-phase supply
voltages (b) Unbalanced and nonlinear load
DC capacitors (Cdc) 2200 µF each
currents (c) Compensator reference currents (d)
Compensated source currents.
Interface inductor (Lf, Rf) 20 mH, 1 Ω CAPACITOR VOLTAGE BALANCING IN FIVE-
Hysteresis band (±h) ±0.5 A LEVEL DIODE CLAMPED INVERTER
Dead zone (±δ) ±0.35 A A. Five-Level Diode Clamped Inverter
PI controller gains Kp = 5, Ki = 0.5 Multilevel inverters are growing increasingly due
Full Bridge Rectifier to their advantages mentioned in [5]. There are
Load 168 + j 16 Ω there different topologies in multilevel inverters.
Three pulse rectifier They are diode clamped, flying capacitor and
load 90 + j 48 Ω cascaded H-bridge multilevel inverters [5]. Owing
to advantages of diode clamped multilevel
Za = 39 + j 13 Ω inverter as mentioned in [4], a five-level diode
Unbalanced R-L Loads Zb = 61 + j 19 Ω clamped VSI is used. There are five different
voltage levels namely Vdc/2, Vdc/4, 0, -Vdc/2 and –
Zc = 130 + j 32 Ω Vdc/4, referred to as states +1, +1/2, 0, -1/2 and -
1 respectively. They are obtained by controlling
Parameters chosen for simulation are listed in the respective switches in each leg. A tabular
Table. I. The compensated source currents and column representing the possible switching
filter currents are in Fig. 3(c) and Fig. 3(d). combinations is given below. A schematic
diagram of a single phase five-level diode
clamped inverter is shown in Fig. 2.

TABLE II
Switching Logic For a Single Leg Diode Clamped
Five-Level Inverter
Switch Status Vin
S1i S2i S3i S4i S5i S6i S7i S8i Fig. 5 is faster and more accurate for
ON ON ON ON OFF OFF OFF OFF 1
compensating voltage imbalance for passive
loads.
OFF ON ON ON ON OFF OFF OFF 1/2
OFF OFF ON ON ON ON OFF OFF 0
OFF OFF OFF ON ON ON ON OFF - 1/2

Voltage (V)
OFF OFF OFF OFF ON ON ON ON -1 Vdc1

B. Capacitor Voltage Balancing Vdc4


Capacitor voltage balancing becomes more
significant as the number of voltage level Vdc3 Vdc2
increases, due to reasons like unequal flow of
capacitor current and average zero sequence
currents. In a two level inverter, capacitor voltage
balancing is not required when the neutral Time (s)
current Io does not have an average component. (a)
Though, capacitor voltage balancing becomes
essential when neutral current have an average
value. But, in the case of a multilevel inverter due
to unequal flow of currents caused due to inverter Voltage (V)
switches, causes imbalance in capacitor voltages V total
even when average neutral current is zero. A
simple external balancer circuit as explained in
[7] is used for correcting capacitor voltages.
Fig. 2 shows a single phase diagram of
DSTATCOM used for compensating an
unbalanced RL load. DSATCOM tracks the Time (s)
reference currents using slope based hysteresis (b)
current control technique as explained above and
the switches are operated according to switching Figure 4 (a) Uncompensated capacitor voltages
logic shown in Table. II. The average current for unbalanced RL load (b)Total capacitor
flowing through the neutral is zero, though there voltages for unbalanced RL load.
are zero sequence components. Therefore, Chopper
ideally, there should not be capacitor voltage
imbalance since, the sum of reactive power
across the three phases are zero. But, due to Dp Sch1 i Cdc1
switching combinations as seen from Table II, ch1

there are unequal flows of current in the Rch Lch


capacitors. The top two capacitors C1 and C2 are Dp Sch2 Cdc2 Five Level Filter
used for obtaining +1 state but only C2 is used for Diode Currents
Clampled
+1/2 state. The same procedure can be put forth Dp Sch3 ifa, ifb, ifc
Multilevel
for -1 and -1/2 for the bottom capacitors. Due to ich2 Cdc3
Inverter
this unequal flow of charges, the capacitor Rch Lch
voltages diverge. The capacitor voltages are Dp Sch4 Cdc4
shown in Fig. 4(a) for an unbalanced RL load. It
can be seen from Fig. 4(b) that the total voltage
across the capacitors is maintained constant by a
PI controller.
Figure 5 Inverter chopper circuit for five-level
Balancing capacitor voltages in multilevel VSI are
diode clamped inverter for passive loads.
tried for a long time. There are many theories in
literature [11],[12] explaining different methods
For controlling the switches carrier based Pulse
for balancing capacitor voltages. However, these
Width Modulated (PWM) method is employed as
techniques provide slow and less efficient
suggested in [13]. In this method charges from
operation. External balancing circuit as shown in
the overcharged capacitors are transferred to an
inductor (Lch) by controlling switches Sch1 and
Sch4. After a certain interval of time, the Where, Vdcref is the reference value of the DC
corresponding switches are turned off such that capacitor voltages and Lch is the inductance in
the charges from inductor are transferred back to the inverter chopper circuit. Using the equations
the other capacitors through the free wheeling (3), (4) and (5) the switching frequency of the
diodes Dch2 and Dch3 as shown in Fig. 5. The triangular carrier waveform is obtained.
capacitor voltages and the average capacitor
current i.e. Icap_avg flowing across each capacitor fs =(Vdcref * D)/(Lch * Ipeak) (6)
are measured. For balancing the capacitor
voltages a triangular carrier waveform with This value of fs decides the switching frequency
certain amplitude and frequency (fs) is chosen. of carrier triangular wave. This frequency is
The amplitude of the carrier wave depends on dependant on duty cycle of operation. The
the drift in capacitor voltage that can be tolerated. triangular carrier wave and the voltage error,
The frequency of the waveform depends on the which is the difference between the actual
average capacitor current and duty cycle (D) of capacitor voltage and reference capacitor
the switches. voltage, are compared such that pulses as
shown in Fig. 6 are obtained. The obtained
During the steady state operation of the chopper
pulses are given to either of the switches Sch1 and
it is assumed that the chopper voltages are
Sch4 for capacitor voltage balancing.
nearly equal to their reference value. Therefore,
For discontinuous operation, we have set the
the rate of rise of chopper current in the inductor
duty cycle less than 0.5, the above value of fs for
is same as the rate of fall of the inductor current
D < 0.5 guarantees discontinuous operation. The
where the current freewheels through the diodes.
duty cycle is varied depending on the chopper
In order to prevent the increase in the
inductor peak current capability. It is noted that
accumulation of inductor charge, the choppers
as Ipeak increases for a system, the value of D
are operated in discontinuous conduction mode.
decreases. But D from (6) is directly proportional
This mode of operation is achieved by fixing the
to the frequency of the triangular carrier wave.
duty cycle (D) of the choppers strictly lesser than
Therefore, as D decreases, frequency fs also
0.5. The average capacitor current (Icap-avg) is
decreases and the error increases as the time of
given by.
operation of the switches decreases. A trade off
Icap-avg = (1/2)(Ipeak)(ton + toff )/2 (3) is thus essential. Heuristically, a good trade off
for duty cycle is between 0.3 and 0.5. From,
Where, Ipeak, ton and toff are the peak chopper equation (6) the corresponding value of
current, on and off time of the choppers frequency for a chosen duty cycle is obtained.
respectively. Ts is the time period of the switches. The compensated capacitor voltages for the
The maximum limit up to which discontinuous simulation parameters in Table. I are shown in
current can flow through the inductor for proper Fig. 7(a). It is also seen the chopper current
operation is when duty cycle D = 0.5. Simplifying flowing in inverter chopper circuit is
the above equation. discontinuous as shown in Fig. 7(b).

Icap-avg=Ipeak = D ; D = ton=Ts; (4) V carrier


Ts = ton + toff + trest
error signal
Where, D is the duty cycle and trest is the time
during which no choppers nor freewheeling
diodes conduct. The above equation shows that t
D is directly proportional to the average current
and inversely proportional to the peak of the S7 , S8
chopper current. The value of Ipeak should be
decided based on the peak current ratings of the ton toff+trest t

chopper and inductor present. Based on the peak Ts


current, the value of D is obtained. Ipeak is given
by the equation Figure 6. Switches pulses to inverter chopper
circuit.
Ipeak = (Vdcref/Lch) * ton (5)
the inner loop on the average capacitor current
Icap-avg. The simulation results for DSTATCOM
compensating DC loads using the proposed logic
are shown in Fig. 9(a), Fig. 9(b). The external
Voltage (V)

inverter chopper circuit corrects the capacitor


Vdc1 Vdc2 Vdc3 Vdc4
voltages as seen from Fig. 9(b).

Chopper

Dp Sch1 i Cdc1
Time (s) Dp Sch5
ch1

(a) Rch Lch


Dp Sch2 Cdc2 Five Level Filter
Rch Lch Diode Currents
ichT Clampled ifa, ifb, ifc
Dp Sch3 Multilevel
ich2 Cdc3
Inverter
Dp Sch6 Rch Lch
Current (A)

Dp Sch4 Cdc4

I ch2 Figure 8. Inverter chopper circuit for five-level


I ch1 diode clamped inverter for DC loads.

Time (s)
Vdc3
(b)
Voltage (V)

Vdc4
Figure 7. (a) Compensated capacitor voltages for
unbalanced RL load (b) Discontinuous inverter
chopper currents.
DC loads are responsible for non-zero average Vdc1
zero sequence currents. In such cases, unequal
flow of capacitor current due to switching logic Vdc2
combined with average neutral current flowing
into neutral clamped point causes capacitor
voltage imbalance. An example of DC load is a
Time (s)
(a)
three phase half wave rectifier where, there is a
positive average neutral current. Therefore, from
Fig. 2 the bottom two capacitor voltages Vdc3, Vdc4
increases while the top two capacitor voltages
Vdc1, Vdc2 decreases. Also, the rate of increase in
Voltage (V)

voltage Vdc3 is greater than that of voltage Vdc4. V


Similarly, Vdc2 falls steeper than Vdc1. Therefore, V Vdc3 Vdc1 dc2
dc4
two loops are required. The outer loop helps in
balancing the top pair Cdc1, Cdc2 and bottom pair
Cdc3, Cdc4 capacitors, while the inner loop
balances individual capacitors. The schematic of
such an external balancing circuit is shown in
Fig. 8. The same technique as explained above
is used for operation of such loads. The switching
pulse for the outer loop is decided by the average
Time (s)
(b)
neutral current Ioavg and the switching pulses to
Figure 9. (a) Uncompensated capacitor voltages [7] M. Mishra, A. Joshi, and A. Ghosh, “A new
for unbalanced RL and DC load (b) compensated closed loop control scheme for capacitor voltage
capacitor voltages for unbalanced RL and DC equalisationin shunt compensator using neutral
load. current injection,” in IEEE Power Engg. Society
Winter Meeting, 2001, vol. 1.
CONCLUSION [8] M. K. Mishra, A. Joshi, and A. Ghosh, “Control
In this paper, a slope based hysteresis current schemes for equalization of capacitor voltages in
control technique and capacitor voltage a neutral clamped shunt compensator,”Power
balancing for five-level neutral clamped voltage Engineering Review, IEEE, vol. 22, no. 12, pp. 64
source inverter are described. A new method for –64, dec. 2002.
tracking the reference currents based on their [9] S. Srikanthan, M. Mishra, and R. Rao,
slope has been discussed. The objective in here “Improved hysteresis current control of three-
is to reduce the average tracking error. With level inverter for distribution static compensator
Multi-level inverters the stress across the application,”Power Electronics, IET, vol. 2, no. 5,
switches are reduced and the switches are pp. 517 –526, sept. 2009.
operated at a lesser switching frequency for any [10] A. Ghosh and A. Joshi, “A new approach to
given load. A major disadvantage of using such load balancing and power factor correction
multilevel inverters is capacitor voltage inpower distribution system,” IEEE Trans. on
imbalance. It is seen that due to switching Power Delivery, vol. 15, no. 1, pp. 417–422,
combinations and average neutral current 2000.
capacitor voltage tends to diverge. External [11] H. Akagi and T. Hatada, “Voltage balancing
balancing circuit is used for balancing capacitor control for a three-level diode-clamped converter
voltages at the expense of additional switching in a medium-voltage transformerless hybrid
devices and additional losses. A heuristic value active filter,” IEEE Trans. on Power Electronics,
of duty cycle is also obtained for ensuring vol. 24, no. 3, p. 571, 2009.
discontinuous current in the inverter chopper [12] M. Marchesoni, M. Mazzucchelli, and P.
current. Tenca, “About the DC-link capacitors voltage
balance in multi-point clampedconverters,” in Ind.
REFERENCES Electronics Society, 1998. IECON’98.
[1] H. Akagi, Y. Kanazawa, and A. Nabae, Proceedings of the 24th Annual Conf. of the
Instantaneous reactive power compensators IEEE, vol. 1.
comprising switching devices without energy [13] S. Srikanthan, M. Mishra, B. Kumar, and K.
storage components,” IEEE Trans. on Ind. Bhaskar, “Capacitor Voltage Balancing in Neutral
Appln., vol. 20, no. 3, 1984. Clamped Inverters for DSTATCOM Application,”
[2] T. Larsson, C. Poumarede, A. Syst, and S. in Power Engineering, Energy and Electrical
Vasteras, “STATCOM, an efficient means for Drives, 2009. POWERENG ’09., 18-20 March
flicker mitigation,” in IEEE Power Engineering 2009.
Society 1999 Winter Meeting, vol. 2.
[3] G. Bode and D. Holmes, “Implementation of
three level hysteresis current control for asingle
phase voltage source inverter,” in 2000 IEEE
31st Annual Power Elec. Specialists Conference,
2000. PESC 00, vol. 1, 2000.
[4] J. Lai and F. Peng, “Multilevel converters-a
new breed of power converters,” IEEE Trans. on
Industry Appln., vol. 32, no. 3, pp. 509–517,
1996.
[5] J. Rodriguez, J. Lai, and F. Peng, “Multilevel
inverters: a survey of topologies, controls, and
applications,” IEEE Trans. on Ind. Electronics,
vol. 49, no. 4, pp. 724–738, 2002.
[6] A. Ghosh, A. Joshi, and R. Gupta, “Cascaded
multilevel control of DSTATCOM using multiband
hysteresis modulation,” 2009.

Вам также может понравиться