Standard Technical Specifications for Electrical Works

CABLES AND ACCESSORIES


( Data Sheets )

LV XLPE-Insulated Underground
Cable Accessories (Bimetallic/Aluminium)

ADWEA/ADDC/AADC STANDARD : D-AAA-CAB-ACC-LV_BM/AL


(Rev.0-2019)

________________________________________________________________________________________
D-AAA-CAB-ACC-LV (Rev.0-2019)BM-AL.xls Page 1 of 8
CABLES AND ACCESSORIES
LV XLPE-Insulated Underground Cable Accessories (Bimetallic/Aluminium)

Table of Content

Page

1.00 SEALING ENDS 3


1.01 Termination Lugs 3

2.00 STRAIGHT THROUGH JOINTS 3


2.01 Heat-Shrink Type 3
2.02 Cold-Shrink Type 5
2.03 Hybrid Type (Cold and Heat Shrink Combination Type) 7

3.00 SUPPORTING DOCUMENTS 8

_____________________________________________________________________________________________________________
D-AAA-CAB-ACC-LV (Rev.0-2019)BM-AL.xls Page 2 of 8
CABLES AND ACCESSORIES
LV XLPE-Insulated Underground Cable Accessories (Bimetallic/Aluminium)

Sl. No. REQUIRED TENDERED

1.00 SEALING ENDS

1.01 Termination Lugs


1.01.1 Manufacturer
1.01.1.1 name
1.01.1.2 country of manufacturing
1.01.2 Applicable standards IEC/BS/VDE IEC 61238-1-1

1.01.3 Material Bimetallic

1.01.4 Minimum external shrink hose/tube mm 100


overlapping after shrinking

2.00 STRAIGHT THROUGH JOINTS

2.01 Heat-Shrink Type


2.01.1 Jointing Ferrules
2.01.1.1 Manufacturer
2.01.1.1.1 name
2.01.1.1.2 country of manufacturing
2.01.1.2 Applicable standards IEC/BS/VDE

2.01.1.3 Material Aluminium

2.01.2 Complete Heat-Shrink Joint


2.01.2.1 Type test
2.01.2.1.1 carried out yes

2.01.2.1.2 date dd-mm-yy

2.01.2.1.3 applicable standards IEC/BS/VDE

2.01.2.1.4 testing station


2.01.2.1.4.1 name
2.01.2.1.4.2 country
2.01.2.2 Manufacturer
2.01.2.2.1 name
2.01.2.2.2 country of manufacturing

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-CAB-ACC-LV (Rev.0-2019)BM-AL.xls Page 3 of 8
CABLES AND ACCESSORIES
LV XLPE-Insulated Underground Cable Accessories (Bimetallic/Aluminium)

Sl. No. REQUIRED TENDERED

2.01.2.3 Applicable standards IEC 60502-4


BS 7888-4.1
VDE

2.01.2.4 Rated voltage (U0/U) kV 0.6 / 1

2.01.2.5 Highest system voltage (Umax) kV 1.2

2.01.2.6 Frequency Hz 50

2.01.2.7 Power frequency withstand voltage (dry) kVrms 2.7


(5 min/20°C), 4.5 x U0
2.01.2.8 Standard switching impulse withstand voltage kVpeak N/A
(peak value)
2.01.2.9 Impulse withstand voltage (+90°C) kVpeak N/A

2.01.2.10 AC breakdown stress for the design of insulated kV/mm


straight joint at crucial interface surfaces
2.01.2.11 Impulse breakdown stress for the design of kV/mm
insulated straight joint at crucial interface
surfaces
2.01.2.12 Maximum asymmetrical fault current
2.01.2.12.1 for 1.0 s kA 46

2.01.2.12.2 for 0.5 s kA

2.01.2.13 Total electrical losses per joint W/joint

2.01.2.14 Guarantee failure rate as a result of an internal %


breakdown
2.01.2.15 Weight of heat-shrink straight joint kg

2.01.2.16 The design life of heat-shrink straight joint year

2.01.2.17 Shelf life of joint component year


(e.g. tape, stress cone, tubes)
2.01.2.18 Dimensions of heat-shrink straight joint
2.01.2.18.1 length mm

2.01.2.18.2 diameter mm

2.01.2.19 Conductor connecting method compressed ferrule

2.01.2.20 Minimum external heat-shrink hose/tube mm 100


overlapping after shrinking
2.01.2.21 Date of first LV heat-shrink straight joint put in dd-mm-yy
commercial operation
2.01.2.22 The number of LV heat-shrink straight

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-CAB-ACC-LV (Rev.0-2019)BM-AL.xls Page 4 of 8
CABLES AND ACCESSORIES
LV XLPE-Insulated Underground Cable Accessories (Bimetallic/Aluminium)

Sl. No. REQUIRED TENDERED

joint sold till to-day


2.01.2.23 Requirement for special environmental yes/no
measures while jointing is in progress

2.02 Cold-Shrink Type


2.02.1 Jointing Ferrules
2.02.1.1 Manufacturer
2.02.1.1.1 name
2.02.1.1.2 country of manufacturing
2.02.1.2 Applicable standards IEC 60502-4
BS 7888-4.1
VDE

2.02.1.3 Material Aluminium

2.02.2 Complete Cold-Shrink Joint


2.02.2.1 Type test
2.02.2.1.1 carried out yes

2.02.2.1.2 date dd-mm-yy

2.02.2.1.3 applicable standards IEC/BS/VDE

2.02.2.1.4 testing station


2.02.2.1.4.1 name
2.02.2.1.4.2 country
2.02.2.2 Manufacturer
2.02.2.2.1 name
2.02.2.2.2 country of manufacturing
2.02.2.3 Applicable standards IEC/BS/VDE

2.02.2.4 Rated voltage (U0/U) kV 0.6 / 1

2.02.2.5 Highest system voltage (Umax) kV 1.2

2.02.2.6 Frequency Hz 50

2.02.2.7 Power frequency withstand voltage (dry) kVrms 2.7


(5 min/20°C), 4.5 x U0
2.02.2.8 Standard switching impulse withstand voltage kVpeak N/A
(peak value)

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-CAB-ACC-LV (Rev.0-2019)BM-AL.xls Page 5 of 8
CABLES AND ACCESSORIES
LV XLPE-Insulated Underground Cable Accessories (Bimetallic/Aluminium)

Sl. No. REQUIRED TENDERED

2.02.2.9 Impulse withstand voltage (+90°C) kVpeak N/A

2.02.2.10 AC breakdown stress for the design of insulated kV/mm


straight joint at crucial interface surfaces
2.02.2.11 Impulse breakdown stress for the design of kV/mm
insulated straight joint at crucial interface
surfaces
2.02.2.12 Maximum asymmetrical fault current
2.02.2.12.1 for 1.0 s kA 46

2.02.2.12.2 for 0.5 s kA

2.02.2.13 Total electrical losses per joint W/joint

2.02.2.14 Guarantee failure rate as a result of an internal %


breakdown
2.02.2.15 Weight of cold-shrink straight joint kg

2.02.2.16 The design life of cold-shrink straight joint year

2.02.2.17 Shelf life of joint component year


(e.g. tape, stress cone, tubes)
2.02.2.18 Dimensions of cold-shrink straight joint
2.02.2.18.1 length mm

2.02.2.18.2 width mm

2.02.2.19 Conductor connecting method compressed ferrule

2.02.2.20 Minimum external cold-shrink hose/tube mm 100


overlapping after shrinking
2.02.2.21 Date of first LV cold-shrink straight joint put in dd-mm-yy
commercial operation
2.02.2.22 The number of LV cold-shrink straight
joint sold till to-day
2.02.2.23 Requirement for special environmental measures yes/no
while jointing is in progress

2.03 Hybrid Type (Cold and Heat Shrink Combination Type)


2.03.1 Jointing Ferrules
2.03.1.1 Manufacturer
2.03.1.1.1 name
2.03.1.1.2 country of manufacturing

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-CAB-ACC-LV (Rev.0-2019)BM-AL.xls Page 6 of 8
CABLES AND ACCESSORIES
LV XLPE-Insulated Underground Cable Accessories (Bimetallic/Aluminium)

Sl. No. REQUIRED TENDERED

2.03.1.2 Applicable standards IEC 60502-4


BS 7888-4.1
VDE

2.03.1.3 Material Aluminium

2.03.2 Complete Joint


2.03.2.1 Type test
2.03.2.1.1 carried out yes

2.03.2.1.2 date dd-mm-yy

2.03.2.1.3 applicable standards IEC/BS/VDE

2.03.2.1.4 testing station


2.03.2.1.4.1 name
2.03.2.1.4.2 country
2.03.2.2 Manufacturer
2.03.2.2.1 name
2.03.2.2.2 country of manufacturing
2.03.2.3 Applicable standards IEC/BS/VDE

2.03.2.4 Rated voltage (U0/U) kV 0.6 / 1

2.03.2.5 Highest system voltage (Umax) kV 1.2

2.03.2.6 Frequency Hz 50

2.03.2.7 Power frequency withstand voltage (dry) kVrms 2.7


(5 min/20°C), 4.5 x U0
2.03.2.8 Standard switching impulse withstand voltage kVpeak N/A
(peak value)
2.03.2.9 Impulse withstand voltage (+90°C) kVpeak N/A

2.03.2.10 AC breakdown stress for the design of insulated kV/mm


straight joint at crucial interface surfaces
2.03.2.11 Impulse breakdown stress for the design of kV/mm
insulated straight joint at crucial interface
surfaces
2.03.2.12 Maximum asymmetrical fault current
2.03.2.12.1 for 1.0 s kA 46

2.03.2.12.2 for 0.5 s kA

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-CAB-ACC-LV (Rev.0-2019)BM-AL.xls Page 7 of 8
CABLES AND ACCESSORIES
LV XLPE-Insulated Underground Cable Accessories (Bimetallic/Aluminium)

Sl. No. REQUIRED TENDERED

2.03.2.13 Contact resistance of cable ferrule µΩ

2.03.2.14 Total electrical losses per joint W/joint

2.03.2.15 Guarantee failure rate as a result of an internal %


breakdown
2.03.2.16 Weight of hybrid type straight joint kg

2.03.2.17 The design life of hybrid type straight joint year

2.03.2.18 Shelf life of hybrid type joint component year


(e.g. tape, stress cone, tubes)
2.03.2.19 Dimensions of hybrid type straight joint
2.03.2.19.1 length mm

2.03.2.19.2 diameter mm

2.03.2.20 Conductor connecting method compressed ferrule

2.03.2.21 Minimum external heat-shrink hose/tube mm 100


overlapping after shrinking
2.03.2.22 Date of first LV hybrid type straight joint put in dd-mm-yy
commercial operation
2.03.2.23 The number of LV hybrid type straight joint
sold till to-day
2.03.2.24 Requirement for special environmental measures yes/no
while jointing is in progress

3.00 SUPPORTING DOCUMENTS

3.01 Whether all type test reports enclosed yes

3.02 Whether technical literature enclosed yes

3.03 Whether tables giving rating factors for variation yes


in standard conditions of installation enclosed