SYPM10K16H

A 16kW high efficiency


power module for the
Symmetra PX160kW &
PX48kW. This power
module is backward
compatible with the
SYPM10KH module and
will autodetect to deliver
...

Includes: Installation
guide

View Product Overview

Replacement battery
User replaceable battery
not available

User Product
Manual FAQs

Product
Registration
SYPM10K16H Features

Key Features

Run time for load 16000 W

Max. Capacity Used

100%

Output power capacity


16.0kWatts / 16.0kVA
Rack Height
3U
Output Connections
(1) Hard wire 5-wire (3P + N + E) (Battery Backup)

(1) Hard Wire 5-wire (3PH + N + G) (Battery Backup)


Nominal Output Voltage
230V, 400V 3PH
Nominal Input Voltage
400V 3PH
Input Connections
Hard wire 5-wire (3P + N + E)
Maximum Input Current
33.0A

APC Symmetra PX Power Module, 10/16kW, 400V

A 16kW high efficiency power module for the Symmetra PX160kW & PX48kW. This power module is
backward compatible with the SYPM10KH module and will autodetect to deliver only 10kW of power
protection if installed in a PX80kW, 40KW or 20kW all-in-one.

Includes: Installation guide

Input Power Factor Correction This product has a power factor corrected input side
ensuring that the input power factor is always 1
regardless of load and mains voltage. A power factor of
1 minimizes installation costs by allowing the use of
smaller cables and smaller fuses.
Modular design Increases adaptability with an open architecture
configurable to any IT environment.

Product Distribution
United Arab Emirates, Afghanistan, Albania, Armenia, Argentina, Austria, Australia, Aruba, Azerbaijan,
Bosnia and Herzegovina, Belgium, Bolivia, Brazil, Belarus, The Democratic Republic Of Congo,
Switzerland, Chile, Cameroon, China, Colombia, Cyprus, Czech Republic, Germany, Denmark,
Dominican Republic, Algeria, Estonia, Egypt, Eritrea, Spain, Ethiopia, Finland, Fiji, France, Georgia,
Gambia, Greece, Hong Kong, Honduras, Croatia, Hungary, Indonesia, Ireland, Israel, India, Iraq,
Iceland, Italy, Jamaica, Jordan, Japan, Kenya, Cambodia, South Korea, Cayman Islands, Lithuania,
Luxembourg, Latvia, Myanmar, Mongolia, Malaysia, Netherlands, Norway, New Zealand, Peru,
Philippines, Pakistan, Poland, Puerto Rico, Portugal, Paraguay, Romania, Russia, Saudi Arabia, Sweden,
Singapore, Slovenia, Slovakia, Senegal, Suriname, Thailand, Tunisia, Turkey, Ukraine, Uganda, Uruguay,
Venezuela, Vietnam, Yemen, South Africa, Zambia, Zimbabwe

Technical Specifications
Print
Download

Output
Max Configurable Power (Watts)
16.0kWatts / 16.0kVA
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load
95.0 %
Output Voltage Distortion
Less than 2 %
Output Frequency (sync to mains)
50 Hz +/- 0.1 % For 50 Hz nominal Unsynchronised, 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz Sync to
mains
Load Crest Factor
Unlimited
Topology
Double conversion online
Overload Operation
10 minutes at 125% and 60 seconds at 150%
Output Voltage THD
< 2% for 0 to 100% linear load and < 6% for full non-linear load
Output Voltage Tolerance
+/- 1% static and +/- 5% at 100% load step

Input
Input frequency
40 - 70 Hz
Input voltage range for main operations
340 - 477V
Efficiency at Full Load
95.0 %
Input Total Harmonic Distortion
Less than 5 % for full load
Maximum Short Circuit Withstand (Icw)
30.0kAmps
Input Power Factor at Full Load
0.99

Physical
Maximum Height
132MM, 13.2CM
Maximum Width
483MM, 48.3CM
Maximum Depth
700MM, 70.0CM
Net Weight
28.5KG
Shipping weight
31.55KG
Shipping Height
225MM, 22.5CM
Shipping Width
595MM, 59.5CM
Shipping Depth
700MM, 70.0CM
Units per Pallet
8.0

Environmental
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Operating Elevation
0 - 1015.9meters
Storage Temperature
-15 - 40 °C
Storage Elevation
0 - 4572meters
Audible noise at 1 meter from surface of unit
63.0dBA
Online thermal dissipation
2573.0BTU/hr
Protection Class
NEMA 1

Conformance
Approvals
CE, EN 50091-1, EN 50091-3, FCC part 15 class A, VFI-SS-111
Standard warranty
1 year repair or replace

Documentation

Manuals and Warranties

Symmetra PX 48, 96 and 160 kW 400 V and PDF 3875 KB 04/14/20

100 kW 208 V Operation


Operation manual containing information on how
to use, maintain, and troubleshoot the product.

Agency Approvals

Symmetra PX 48, Symmetra PX 96-160 kW PDF 77 KB 06/30/20


400 V Certificate of Origin
Certificate of Origin

Symmetra PX 48 kW, 96 kW, and 160 kW EU PDF 517 KB 06/30/20


Declaration of Conformity
EU Declaration of Conformity
Symmetra PX 48-160 kW Cmim Declaration PDF 124 KB 06/30/20

of Conformity
Cmim Declaration of Conformity

Services

Training Services

Certified Operator How to buy


Training for
Symmetra PX - 2
days - private
session up to 6
trainees
Increase your
knowledge and
confidence to
operate and manage
your data center
physical
infrastructure
learning from our
industry proven
professionals

WOT-PX-00

Customer Training How to buy


Service
Increase your
knowledge and
confidence to
operate and manage
your data center
physical
infrastructure
learning from our
industry proven
professionals

WTRAINING

SIGN UP FOR EMAIL


I'd like to receive news and commercial info from Schneider Electric and its affiliates via electronic communication
means such as email. For more details, please read our Privacy Policy.

Email

I am a...

Sign up

WHO WE ARE CONNECT WITH US

About APC Press

Investor Relations APC Blog

Careers Schneider Electric Data Centre Blog

Sustainability Contact Us

FIND A RESELLER

Zip/Postal Code Find

CATALOG KEYCODE

Enter Key Code Go

Вам также может понравиться