Вы находитесь на странице: 1из 2

Client: Saudi Electricity Company

Date 15-02-2019
Contractor Name Marine Services Co. Location: Rabigh Jetty-2

Circuit Breaker Test Panel ref:+ SA 9/Q1

1. GENERAL DATA AND INFORMATION

Manufacturer : ABB

Breaker Type: SACE Tmax

Breaker S/No. : NA

Rated Voltage : 480 V

Rated Current : 800 A

2. MECHANICAL CHECK AND VISUAL INSPECTION

Item Description Checked


1. Inspect for physical damage / defects. OK
2. Check tightness of all connections. OK
3. Control Wiring Continuity Check OK
4 Check Manual operation (Close and Open) OK
5. Control Transformer Operation Check OK
6. Fuse Healthiness and Continuity check OK
7. Residual Current Relay Operation OK

3. CONTACT RESISTANCE (10 A)

S. No L 1-L1’ L 2-L2’ L 3-L3’ Remarks


1 1.063 mΩ 1.015 mΩ 1.012 mΩ OK

Acceptance Criteria: (All the values should be in mΩ)

COMPANY ALFALGI Marine Services Co. SEC SEC


NAME
SIGNATURE
DATE
Client: Saudi Electricity Company
Date 15-02-2019
Contractor Name Marine Services Co. Location: Rabigh Jetty-2

Circuit Breaker Test Panel ref:+ SA 9/Q1

4. INSULATION RESISTANCE TEST (1 KV FOR 1 MIN)

BREAKER CLOSED POSITION


S. NO. REMARKS
L1-G L2-G L3-G L1-L2 L2-L3 L3-L1
1 >1GΩ >1GΩ >1GΩ >1GΩ >1GΩ >1GΩ OK

BREAKER OPEN POSITION


S. NO. REMARKS
L1-L1’ L2-L2’ L3-L3’
1
>1GΩ >1GΩ >1GΩ OK

Acceptance Criteria: ALL MESUREMENT SHOULD BE IN MORE THAN 100 MEGA OHMS

5. PRIMARY INJECTION TEST(Trip Test)

Setting Injected I Expected Measured Time (sec)


(A) Time (sec)
S.No Function I (A) T (sec) R Y B

1 Long Time Delay (L) 320A 3.00 1500 A 3.00 3.40 3.30 3.60
2 Short Time Delay (S) 480A 0.250 2200 A 0.250 0.350 0.350 0.350
3 Instantaneous Time 1200A 0 2200 A 0 0.200 0.200 0.200
Delay (I)
4 Ground (G) 160A 3.00 350A 3.00 3.30 3.30 3.30

Acceptance Criteria: Time Tolerance = +/- 20%

Testing Equipment:
1. COTEL 750N
2. DLRO 10A
3. KYORITSU 5KV
4. Multimeter

COMPANY ALFALGI Marine Services Co. SEC SEC


NAME
SIGNATURE
DATE

Вам также может понравиться