Вы находитесь на странице: 1из 2

ETAP

Project: Page: 1
Location: 12.6.0H Date: 07-21-2020
Contract: SN:

Engineer: Study Case: LF


Filename: TA FIXXX Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow

ID kV
% Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF

* Bus1 150.000 100.000 0.0 21.240 20.457 0 0 Bus2

Bus2 20.000 89.823 -6.5 0 0 0 0 Bus4 2.984

Bus5 3.759 2.842 151.4 79.8

Bus6 2.720 2.118 110.8 78.9

Bus1 -21.022 -16.114 851.3 79.4

Bus3 11.560 8.884 468.6 79.3

Bus3 20.000 89.823 -6.5 0 0 0 0 Bus7 2.510

Bus8 3.093 2.331 124.5 79.9

Bus9 1.685 1.282 68.0 79.6

Bus10 1.217 0.927 49.2 79.5

Bus11 3.055 2.418 125.2 78.4

Bus2 -11.560 -8.884 468.6 79.3

Bus4 20.000 85.617 -6.8 0 0 2.859 2.144 Bus2 -2.859

Bus5 20.000 87.439 -6.7 0 0 3.670 2.752 Bus2 -3.670

Bus6 20.000 78.714 -7.5 0 0 2.416 1.812 Bus2 -2.416

Bus7 20.000 82.894 -7.1 0 0 2.336 1.752 Bus3 -2.336

Bus8 20.000 88.449 -6.6 0 0 3.051 2.288 Bus3 -3.051

Bus9 20.000 85.709 -6.8 0 0 1.616 1.212 Bus3 -1.616

Bus10 20.000 85.169 -6.9 0 0 1.161 0.870 Bus3 -1.161

Bus11 20.000 73.827 -7.9 0 0 2.562 1.921 Bus3 -2.562

Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
*
# Indicates a bus with a load mismatch of more than 0.1 MVA
Revision: Base

XFMR

%Tap

21.240 20.457 113.5 72.0

2.270 120.5 79.6

1.927 101.7 79.3

-2.144 120.5 80.0

-2.752 151.4 80.0

-1.812 110.8 80.0

-1.752 101.7 80.0

-2.288 124.5 80.0

-1.212 68.0 80.0

-0.870 49.2 80.0

-1.921 125.2 80.0