Product Submittal for MVB® - Type H

Models 2503-4003

Date: Job: Location:

Equipment Tags: Engineer: Contractor:

Model: Notes:

Prepared by: Indoor Outdoor Gas Type: Natural Gas Propane

85% thermal efficiency at full rate

100% factory fire-tested

VERSA IC® modulating controller with 7” color touchscreen display

Raymote™ IoT connectivity standard

Full electronic modulation, constant ratio up to 7:1 turndown

Full safety diagnostics with history

Status display lights

Cascade up to 4 heaters - no external sequencer required

Modbus RTU BMS port

CSA low lead certified ≤ .25% lead

Maximum outlet water temperature: 235ºF

Minimum inlet water temperature: 120ºF

Limited twenty-five-year thermal shock warranty

Limited five-year copper/ten-year cupronickel heat exchanger warranty

Low NOx - BAAQMD Certified per Rule 9-7

Proudly assembled in the USA

Catalog No.: 2000.365C Effective: 04-15-19 Page 1 of 4


Product Submittal for MVB® - Type H
Job:

Standard Features Water temperature sensors (5) Options

Heat Exchanger Cold Water Protection Package B-31 Well assembly - system

Headers - bronze Variable speed pump (optional) B-32 Outdoor air sensor

ASME H stamped; 160 PSIG MAWP Proportional valve (optional) B-65 Indirect tank aquastat

National Board listed Modbus RTU BMS port (up to 115K Baud D-23 Flue support brackets
Rate, see Cat. No. 5000.73)
Finned tubing D-37 Motorized comb. air damper
B-85 BMS Gateway, Modbus RTU to
Copper (standard) E-5 Alarm with 4” bell with silence
Modbus TCP, N2 Metasys, BACnet IP, or
and reset switches
A-3 cupronickel (optional) BACnet MS/TP (optional)
F-10 Low water cut-off, manual
ASME powder-coated tube sheet B-86 BMS Gateway, Modbus RTU to
reset & test button
Silicone high-temp O-rings LonWorks (optional)
I-1 High limit, adj. auto reset -
ASME pressure relief valve 240ºF
Burner
60 PSIG (standard) I-2 High limit, adj. manual reset -
Hot surface ignition (HSI)
___ PSIG (optional) 240ºF
Radially-fired knitted burner
150 PSI air vent, auto (2) I-5 High limit, adj. manual reset -
200ºF
T&P gauge Gas Train
I-13 High limit, adj. auto reset -
Four-pass heat exchanger Fuel
200ºF
Stainless steel evaporator plate Natural gas
M-1 Safety valves, motorized
4-inch grooved copper water connections Propane
M-10 Safety valves, solenoid
Dual-seat combination valve
M-15 Safety valves, vent valve (must
Control
Manual shut-off firing valve be used with M-1 or M-10)
240V, 60Hz, 1ø power supply
S-1 Low gas pressure switch,
240/120V 60Hz transformer Construction manual reset
240/24V 60Hz transformer Indoor/outdoor construction S-3 Low water pressure switch,
E-16 208V, 60Hz, 1ø (optional) Enclosed front controls auto reset

VERSA IC® built-in controller PolyTuf powder coat finish Z-12 Condensate treatment kit

7” color HD touchscreen display Rear connections (water, gas, vent, electrical,


Additional Options or Accessories
comb. air)
Raymote™ IoT connectivity

Combustion air filter
Cascade up to 4 heaters
Front connection - low voltage wiring
Ignition module Pumps (optional)
Design certified ANSI Z21.13/CSA 4.9
3-try (standard)
CSA low lead certified ≤ .25% lead
C-6 single-try (optional)
Multi-Boiler Digital Temp Controllers
Remote flame sensor Venting
B-36 TempTracker Mod+ Hybrid,
Fixed high limit, manual reset, 240ºF Vent termination 2-4 boilers
On/off power switch D-11 Outdoor vent cap (Cat IV) B-37 TempTracker Mod+ Hybrid,
Flow switch 5-10 boilers
D-12 Barometric damper, single-acting
Blocked vent pressure switch (Cat I only) B-38 TempTracker Mod+ Hybrid,
11-16 boilers
Freeze protection D-15 Sidewall vent termination cap (Cat
IV) B-39 EMS 4-20 mA Remote
Alarm dry contact
Setpoint Interface Module
D-17 Air intake filter
High gas pressure switch, manual reset (may only be used with B-36
D-18 Boiler flue adapter (Cat III/IV) to B-38)
Pump outputs - pilot duty
D-19 Flue term cap adapter (Cat III/IV) B-62 BACnet MS/TP Interface
Boiler
D-20 Vent termination, vertical (Cat I) Module (may only be used
DHW indirect with B-36 to B-38)
D-22 Truseal air intake box, indoor
System
Extractor - optional
Programmable pump time delays
By others
Modulating temperature control, 7:1
turndown Not required

Catalog No.: 2000.365C Effective: 04-15-19 Page 2 of 4


Product Submittal for MVB® - Type H
Job:

Rear View Side View Front View

ØN

K
D E B
T

*Water connections are grooved copper tube.


Dimensions are shown in inches (mm).

MBTUH (kW) Dimensions - inches (mm) AHRI Shipping


Model Turn
B K N Thermal Weight -
(H7) Input Output D E M T Down
Efficiency lbs (kg)
Height Flue ø C/A ø
2501 2126 68-1/4 62 64-3/4 26-3/4 53-1/4 1150
2503 10 10
(733.0) (623.1) (1733.6) (1574.8) (1644.7) (679.5) (1352.6) (521.6)
3000 2550 73-1/4 67 69-3/4 29-1/4 58-1/4 1250
3003 10 10
(879.2) (747.3) (1860.6) (1701.8) (1771.7) (743.0) (1479.6) (567.0)
85% 7:1
3500 2975 78-1/4 71 74-3/4 31-3/4 63-1/4 1375
3503 12 12
(1025.7) (871.9) (1987.6) (1803.4) (1898.7) (806.5) (1606.6) (623.7)
4000 3400 83-1/4 76 79-3/4 34-1/4 68-1/4 1450
4003 12 12
(1172.3) (996.4) (2114.6) (1930.4) (2025.7) (870) (1733.6) (657.7)

Clearances - inches (mm)

Front Rear Access Side Other Side Top Floor Vent


Combustible 24 12 1 1 1
0 0
Minimum (609.6) (304.8) (25.4) (25.4) (25.4)
Minimum 30 36 24* 1 12
N/A N/A
Service (762.0) (914.4) (609.6) (25.4) (304.8)
*Service Clearance can be right side or left side.

Model Boiler Current Draw - amps


(H7-)
208VAC 240VAC
2503 14 12
3003 17.5 15
3503 20 17
4003 23 20

NOTE: Primary/Secondary plumbing arrangement is mandatory for proper operation.

Catalog No.: 2000.365C Effective: 04-15-19 Page 3 of 4


Product Submittal for MVB® - Type H
Job:

Pressure drop calculations

System Head System Head System Head System Head


20º ΔT 30º ΔT Minimum Flow Maximum Flow
Model Input Loss (ft) Loss (ft) Loss (ft) Loss (ft)
(H7) MBTUH 3” Pipe 4” Pipe 3” Pipe 4” Pipe 3” Pipe 4” Pipe 3” Pipe 4” Pipe
GPM ΔP GPM ΔP GPM ΔP ΔT GPM ΔP ΔT
Size Size Size Size Size Size Size Size

2503 2501 213 11.7 N/A 14.3 142 6.2 10.7 7.4 120 4.7 35 8.0 5.6 264 15.7 16 N/A 19.6

3003 3000 255 21.7 N/A 25.3 170 10.3 16.6 12.0 131 6.3 39 10.2 7.4 264 23.1 19 N/A 27.0

3503 3500 N/A N/A N/A N/A 198 15.2 N/A 17.5 153 9.1 39 14.3 10.5 264 26.8 23 N/A 30.6

4003 4000 N/A N/A N/A N/A 227 23.7 N/A 26.6 174 13.5 39 20.1 15.3 264 33.5 26 N/A 37.4
**ΔP & SHL are in feet of head based upon 100 equivalent feet of type “L” copper tubing.

Base Anchor Bolt Pattern

Dimensions are shown in inches.

NOTE: Primary/Secondary plumbing arrangement is mandatory for proper operation.