Академический Документы
Профессиональный Документы
Культура Документы
ARCHITECT
M/S ARCOP ASSOCIATES PVT. LTD.
New Delhi – 110048
CLIENT
M/S CPWD
STRUCTURAL CONSULTANT
CDPL
INDEX
DESIGN BASIS REPORT
4. Loads 8-11
7. Concrete Cover 15
8. Fire Rating 15
Construction of AIIMS AWANTIPORA, Kashmir
Design Basis Report
The proposed project is located at Awantipora, Srinagar (J&K), the site terrain is having varying
contours resulting in major level difference within various buildings as well as within the same
building among the larger structures. The Hospital Block has been conceived as composite structure,
while all other buildings have been designed as RCC structures. A system of retaining walls has been
evolved to meet the landscaping requirements of the project. Looking at the local features,
topography and the split-level terracing needs, the smaller height (up to 2.5m) retaining walls are
kept in RRM masonry and the higher ones in RCC.
COMPOSITE STRUCTURE(S):
The most prominent building within the complex is ‘Hospital Building’ (Composite Structure) which is
a cluster of 6 no. blocks suitably stacked around the ramp which goes to maximum level 11 floor
levels and terrace above. The various blocks start at different levels to match with contour
requirements of the terrain and also have varying number of floors based on architectural
requirements.
The floor levels at which various blocks have been stacked together are as below:
B1 1758.0M/1762.2M
B2 1758.0M/1762.2M/1766.4M/1770.6M/1775.1M/1779.6M/1784.1M/1788.3M/1792.5M/1
796.7M/1800.9M/TERRACE
B3 1766.4M/1770.6M/1775.1M/1779.6M/1784.1M/1788.3M/1792.5M1796.7M/
1800.9M/TERRACE
B4 1762.2M/1766.4M/1770.4M/1774.8M/1779.3M/1783.8M/1788.3M/1792.5M/
1796.7M/1800.9M/TERRACE
B5 1766.4M/1770.4M/1774.8M/1779.3M/1783.8M/1788.3M/1792.5M/1796.7M/
1800.9M/TERRACE
B6 1758.0M/1762.2M/1766.4M/1770.6M/1775.1M/1779.6M/1784.1M/1788.3M/
1792.5M/1796.7M/1800.9M/TERRACE
Future Expansion- All the blocks shall have sloped metal roof above RCC terraces so as to facilitate
rainwater/snow exit suitably. All adjoing services are meticulously planned along with the stacking of
the various blocks. As a result, scope of future expansion has not been planned either vertically or
horizontally.
According to the architectural planning and site terrain, at various locations, retaining walls shall be
provided which can go up to 2-3 floor heights in some cases. These will be optimally planned by
taking propping action of the floor slabs as well as considering the limited finite extent of filling
towards the hill side and the resulting earth pressures due to same. For the smaller retaining walls
towards building front & sides, snow accumulation may happen for which extra resulting pressure/
loading will be considered depending upon the gathering of snow expected as falling from sloped
roof and also from direct snowfall in such areas.
The hospital blocks house various departments, OTs & wards based on the Hospital planning aspects
including placement of various services & Medical Equipment. Structurally the plans (framing, slab
details, wall details) will respond to the requirements of loads, levels, platforms, openings, cut-outs
etc so as to permit seamless installation of all such items. Of particular interest is the RCC structure
for LINAC (Linear Accelerator equipment used for radiation Oncology treatment) which emits high
radiation & calls for suitable RCC walls to arrest the radiation extent within the required enclosures.
The structure is suitably located in one extreme edge of the building so as to isolate the same. The
wall thicknesses/ bottom/top slab thickness may vary from 1.0m to 2.5m at locations depending upon
vendor details and
the exact structural requirements as necessary for shielding aspects/ primary and secondary barrier
design, consideration of heavier aggregates etc.
Since the project location is Srinagar, appropriate insulation to the building envelope (walls & roof)
shall be used so as to meet the temperature gradient and other requisite aspects. The loads for the
insulation shall be considered in the design of walls & roof slab.
The above-mentioned details have been inferred from the architectural drawings issued to CDPL by
ARCOP. These drawings shall be used as a part of input data civil/ structural designs for various
buildings/structures in the project.
adequate sizes to control deflection under vertical and seismic loads. Ductility detailing shall be done
as per codal provisions. The lateral resistance system shall be SMRF + ductile shear walls to control
lateral forces/displacement. The beam depths (including peripheral beams) been chosen largely to
match architectural requirements besides meeting the structural aspects (such as deflection, flexure
& shear)
Functional Requirements:
In Block-3, most part of the lowest floor caters to staff parking requirements. For all other Blocks all
the floors are meant for various hospital departments.
Sr
. Structure Levels/ Floors
1 Academic Block Plinth, 1st to 6th floors, Terrace, Roof Truss
Lower Ground, Plinth, 1st, 2nd Floor, Terrace, Roof
2 Guest House Truss
3 Shopping-1 Plinth, Terrace, Roof Truss
4 Auditorium Plinth, 1st to 3rd floors, Terrace, Roof Truss
5 Fire Station Plinth, 1st floors, Terrace, Roof Truss
6 AYUSH building Plinth, 1st floor, Terrace, Roof Truss
7 Night Shelter Plinth, 1st to 6th floors, Terrace, Roof Truss
Other smaller buildings include Electric Substations (ESS), Under Ground Tanks (UGTs), HVAC Plant
Room, Autopsy building, STP, MGPS (Medical Gases Plant System) Room.
The various multi-storeyed Residential blocks include various hostels such as UG Boys Hostel, PG Boys
Hostel, Married Hostel, UG Girls Hostel, PG Girls Hostel, Nurses Hostel. Other category of residential
blocks are various Housing blocks categorized as Type 2, 3, 4, 5, 6, 7 & 8.
The common feature in all these buildings is that the sloping roof has been conceived above Terrace
(similar as explained in the Hospital Block)
Throughout this specification, references have been made to appropriate Indian Standards & AISC
code (as and when required) with approved level of workmanship and/or materials. A comprehensive
list of relevant standards is compiled below:
Loads:
IS:875 -1987/2015 Code of Practice for design loads (other than earthquake) for Buildings and
structure
(All parts)
IS: 1893-2016 Criteria for earthquake resistant design of structure.
Foundations:
IS:1080-1985(2016) Code of Practice for design and construction of shallow foundations on soils
(other than raft, ring and shell)
IS:1904-1986(2015) Code of Practice for design and construction of foundations in soils general
requirement
RCC:
IS:456 -2000(2016) Code of Practice for plain and reinforced concrete.
IS:458 -1988 Specification for precast concrete pipes.
IS:3370-2009 Code of Practice for concrete structures for the storage of liquids:(All parts).
IS:4326-2013 Code of Practice for earthquake resistant design and construction of buildings.
IS:5525-1969(2013) Recommendation for detailing of reinforced concrete works.
IS: 1786-2008 Specification for high strength deformed steel bars and wires for concrete
reinforcement.
IS:10262-2009 Recommended guidelines for concrete mix design.
IS: 1893 (Part-1)-2016 Criteria for earthquake resistant design of structures (General provisions
and building).
IS: 13920-2017 ductile design & detailing of RC structures subjected to seismic forces.
Miscellaneous:
IS: 432(part 2)-1995 Specification for mild steel and medium tensile steel bars and hard-drawn
steel wire for concrete reinforcement
Material:
IS: 269 -2015 Specification for Ordinary, rapid hardening and low heat Portland cement.
IS: 455 -1995 Specification for Portland blast furnace slag cement.
IS: 1489-1991 Specification for Portland pozzolana cement
IS: 4031-1991 Method of physical tests for Portland cement.
IS: 383 - 2016 Specification for coarse and fine aggregates from natural sources for concrete.
IS: 516 – 1999 Method of test for strength of concrete.
IS: 1199-1999 Method of sampling and analysis of concrete.
IS: 1566-2000 Specification for plain hard drawn steel wire fabric for concrete reinforcement.
IS: 4990-1998 Specification for plywood for concrete shuttering works.
IS: 2645-1999 Specification for integral cement water proofing compounds.
Welding standards:
ASME Sec II –Part C Specifications for welding Rods, Electrodes and Filler Metals.
Many of above listed standards may not be directly used in detailed design, however, the
comprehensive list is captured for DBR purpose. Wherever appropriate Indian standard does not
exist for any item, appropriate British standards/American standards will be used.
3. MATERIAL OF CONSTRUCTION:
Reinforced Concrete:
The cement used for RCC work in the sub structure & super structure will be OPC (Grade 43 and 53)
conforming to IS: 8112-1989 and 12269-1987. All RCC works will be mechanically vibrated to produce
dense, sound and durable concrete as per specifications. The water quality used in all stages of
construction shall strictly conform to IS: 456-2000.
Reinforcing Steel:
High yield strength deformed TMT bars with a minimum yield stress of 500 D MPa, a minimum
elongation of 14.5% and other specifications conforming to IS: 1786 shall be adopted for 10 mm to
32mm dia bars.
Structural Steel:
Structural steel encased column shall be in high tensile steel with a yield stress of 450 MPa
conforming to IS: 2062.
Structural steel beam shall be built up section in high tensile steel with yield stress of 450 MPa
conforming to IS: 2062.
Where UB/ UC sections are used grade of steel shall be E350; for ISMB/ISMC/ ISA sections, the
grade of steel shall be Fy=250 MPa.
Deck sheet shall be TR-60 of 1mm thk. with yield stress of 350 MPa with minimum 275 gsm
galvanization of Corus/Jindal make.
Shear studs shall have Ultimate stress of 450 MPa.
Choice of steel material with 450 MPa for PG sections (built up) is done to optimize structural steel
quantities. For fabrication, automatic continuous submerged arc H beam welding machine is
conventionally used by the reputed agencies.
For various walls the material and thickness will be judiciously selected considering the application,
exposure conditions as well as suitability of mounting fixtures etc. The choice of LAAC blockwork is
preferred for structural considerations.
However, the Lift walls, Staircase walls and the Toilets and Pantries are all considered in Red Bricks.
4. LOADS
Dead Loads:
Following unit weights of building materials have been considered in accordance with IS: 875
(Part I)-1987 and IS: 1911.
Reinforced cement concrete - 2.5 T/m3
Plain cement concrete - 2.4 T/m3
Brick masonry including plaster - 2.2T/m3
Cement mortar / plaster - 2.1T/m3
Floor finish (stone/tile) - 2.4 T/m3
Moist, sweet earth for filling of planters - 2.0 T/m3
Foam Concrete - 1.0 T/m3
AAC Block Masonry - 0.75T/m3
Note: Floor Finish shall be considered 75mm thick.
Live Loads:
Following live loads have been considered in design in accordance with IS:875 (Part II)-1987.
Live loading Typical floor 0.40 T/m2
Live loading common passage staircase& balconies 0.40 T/m2
Live load at RCC terrace floor 0.15 T/m2
Snow Loads shall be considered (on the sloping metal roofs) as per IS:875 part 4, in line with
the roof slopes, shapes & geometry.
Live loads (for parking) 0.5 T/m2
Live loads (for construction) 0.20 T/m2
Fire Tender placed to cause the worst effect 60.0 MT
Electrical room & Storage Areas 0.50 T/m2
Refuge Area 0.50T/m2
Lift machine room 1.0 T/m2
Server room 1 T/m2
Cafeteria 0.50T/m2
AHU 0.750 T/m2
Toilet room 0.2 T/m2
Pump room 0.75 T/m2
DG 1.145 T/m2
UPS battery 1.0 T/m2
Services including false ceiling 0.05 T/m2
Partition 0.10 T/m2 (for LAAC blockwork walls of upto 100mm thickness)
(For thicker walls directly resting on slab, detailed design will be done & reinforcement
added as required)
Cafeteria Load 0.5 T/m2
Live loads for MRI , CT, laundry washer extractors , other heavy equipment shall be in line
with the vendor specific data, however, for present design purpose loading based on past
experience following loadings are assumed:
a. GC/PET/CT scan - 6T
b. MRI- 10T
c. ERCP/C-ARM- 4T
d. CATH-4T
e. Hybrid OT- 12T
f. CL simulator- 6T
g. Linear Acclerator-12T
h. Autoclave- 500 Kg/sqm
The locations of various equipment (rooms) are identified from architectural floor plans/
equipment layout plan. Loading in various areas are taken as per ‘Area Loading Plans’ which are
again based on usage and past experience. Floor-wise detailed loading plans shall be prepared
during detailed design stage.
Seismic Loads:
As per IS1893-2016 (reaffirmed in 2017) the proposed building fall under seismic zone-V
Zone Factor (Zonal V–for Srinagar) Z= 0.36
Response reduction factor (Ductile shear wall + SMRF) R= 5
Importance factor I=1.5
Damping Dm= 5%
Minimum depth of foundation 1.25 m below from floor finish level
Soil Type =2
10
Roofing System
“Standing seam Metal Roofing System” will be adopted, which is the most durable type of
roofing and can last for many years without any maintenance. It is an innovative and
technologically advanced concealed fixed and Zipped-up standing seam system that creates a
continuous weather tight roof with design potential, performance and durability.
= shape coefficient (as per sec-4 of I:875, part-4, usual value of 0.8)
Based on the local conditions in the region, a depth of 1200mm of snow shall be
considered with an average density of 300 Kg/cum. Thus, minimum snow load of
360 Kg/sqm on projected plan area shall be considered on the metal roofing. This
shall be the governing load on the roofs.
12
Foundation are designed accordance to IS:456. The foundation for the proposed building shall be
isolated footing/combined footing. The foundation is designed by considering max allowable gross
bearing pressure as per soil investigation report. Analysis and design of raft/combined foundation is
done by using SAFE software and design of isolated footing, retaining wall base to be prepared in
excel sheet and provided in pdf format. Wherever foundations are going very deep in soil and the
column height up to plinth beam become excessive, a system of tie-beams is introduced
intermittently to control columns slenderness. Serviceability loads combinations with suitable live
load reduction factor as per IS: 875 (Part-2) will be used for foundation design.
Retaining Walls:
The retaining walls are analysed using STAAD software and designed using in-house developed
spread sheets, with PDF submissions.
Connection Design & Detailing (valid for Composite steel structure):
Design and detailing for connections, joints and fasteners is done in line with Section 12 of IS 800‐
2007 and other AISC/ Euro standards as those are more suitable for composite construction.
Stability:
Stability of structure against overturning and sliding as per Clause 20.0 of IS: 456 is followed in the
design and listed as below.
The free-standing steel structure column of height equivalent to four stories shall be considered
for design, so that all stages of erection, construction as well as composite stage considerations
are satisfied.
6. LOAD COMBINATIONS:
Load combinations considered for design of super structures are as follow: -
1.5(D. L+ Reduced L.L)
1.5(D. L± Eqx ± 0.3Eqz)
1.5(D. L ± Eqy ± 0.3Eqz
1.2(D. L+K1*L. L± Eqx ± 0.3Eqz)
13
Symbols:
D.L–Dead loads
L.L- Live loads
E.Q– Earthquake loads Symbols:
E.Q– Earth quake loads K1 - 0.5 for live load class 400Kg/m2 & 0.25 for live load class 200kg/m2
Additional Symbols:
D.L– Dead loads
SL- Live (Snow) loads
E.Q– Earthquake loads
W.L- wind Loads
T.L.- Temperature Load
14
Serviceability Requirement
This is given with following limitations:
For Vertical deflections (Total load deflections) =Span/240 for Serviceability.
Lateral displacement of Structure=Height/ 500.
for Cracking- For water retaining structure=Cracked section, limiting crack width to 0.2mm
7. CONCRETE COVER
Concrete Clear Cover to All Reinforcement Including Links (As per Clause26.4 of IS: 456- 2000)
Column: 40 mm
Beams continuous: 30 mm
Beams simply supported: 40 mm
Slabs: 30 mm
Foundation: 50 mm
Retaining wall: 40mm (earth face): 25mm (inside face)
Water Tank wall: 30mm
8. FIRE RATING
All columns & beams shall be provided as per stipulations of Type-2 construction with 50 years of
design life and fire rating shall be in line with NBC 2016 stipulations as below:
Columns – 4hrs
Beams - 2 hrs
slabs- 2 hrs
No primer/ paint is to be done on the fabricated structure so as to achieve bonding of steel surface
with concrete in columns and for beams based on the ‘fire rating’ suitable vermiculite/ Intumescent
coatings shall be used.
15