NOTES:
01) THE RATING AND DETAIL OF EQUIPMENT INDICATED IN THIS DOCUMENT
H INCOMING FDR -1 INCOMING FDR -2 IS PRELIMINARY & FOR BID PURPOSE ONLY. H

02) PROTECTION FUNCTION & METERING INDICATED ARE PRELIMINARY.


FROM GETCO S/S FROM GETCO S/S
EPC CONTRACTOR TO DEVLOP DETAILED SINGLE LINE DIAGRAM.
-Z1 -Z1
03) ALL EQUIPMENT (INDOOR/ OUTDOOR) RATING SHALL BE RATED FOR

50 DEG°C.
-F1 -F1

WINDING 2: 132KV : 3 / 0.11KV : 3, CLASS 3P, 50VA


ATTACHMENT-1 WINDING 2: 132KV : 3 / 0.11KV : 3, CLASS 3P, 50VA
04) PROTECTION RELAY SHALL BE NUMERICAL TYPE.
05) INCOMER & BUS COUPLER OF 11KV SWITCH GEAR SHALL BE PROVIDED
WINDING 1: 132KV : 3 / 0.11KV : 3, CLASS 0.2, 50VA WINDING 1: 132KV : 3 / 0.11KV : 3, CLASS 0.2, 50VA WITH AUTO-CHANGEOVER AND NORMAL CHANGE OVER BETWEEN INCOMERS.
-Q61 -Q61

-T9 -T9 06) PROTECTION FUNCTIONS OF LINE BAYS SHALL BE FINALISED IN


H H
CO-ORDINATION WITH GETCO.

07) QUANTITY AND DETAIL OF CURRENT TRANSFORMER ARE PRELIMINARY.


-Q8 -Q8
08) FAST BUS TRANSFER WILL BE CONSIDERED AS AN OPTIONAL FEATURE FOR

02 11 KV SWITCHGEAR.
G M M G
-Q9 M -Q9 M 09) CT/PT FOR GETCO METERING (IF REQUIRED) SHALL BE CONSIDERED TO BE PART OF

132KV GIS SWITCHGEAR.


-Q52 -Q52 10) DETAILS OF CT, PT AND PROTECTION FUNCTION FOR REPLACED 11KV SWGR

P2

P2
RELAY PANEL RELAY PANEL SHALL BE SAME AS EXISTING 11KV SWGR.

-T1-4 -T1-4 11) LOCATION OF LIGHTNING ARRESTER (WITHIN GIS OR NEAR TRANSFORMER) SHALL
BUSZONE BUSZONE
600 /1A, CL : PS 87B 50BF 600 /1A, CL : PS 87B 50BF BE DECIDED BY BIDDER AFTER CARRYING OUT INSULATION CO-ORDINATION STUDY.
Vk≥ 600V, Rct ≤ 6Ω, PROTECTION Vk≥ 600V, Rct ≤ 6Ω, PROTECTION
Imag≤25 mA Imag≤25 mA
RCC RCC
LCC LCC ABBREVATION :
-T1-3 -T1-3 BCU : BAY CONTROL UNIT
300/1A, CL:0.2 s, BCU TM MW MVAR A V PF F MFM 300 /1A, CL:0.2 s, BCU TM MW MVAR A V PF F MFM
ISF ≤ 5 ISF ≤ 5 LCC : LOCAL CONTROL CUBICLE
RCC : REMOTE CONTROL CABINET
RELAY PANEL (REFER NOTE-6) RELAY PANEL (REFER NOTE-6) SPBD : SEGREGATED BUS DUCT
VCB : VACUUME CIRCUIT BREAKER
F -T1-2 -T1-2
BACKUP BACKUP
300/1A, CL:5P10, 67 67N 50 50N 51 51N 300 /1A, CL:5P10, 67 67N 50 50N 51 51N
PROTECTION PROTECTION
15VA 15VA PROTECTION FUNCTIONS F

-T1-1 -T1-1 24: OVER FLUXING PROTECTION


300/1A, CL : PS MAIN 300 /1A, CL : PS MAIN 25: SYNCH CHECK RELAY
Vk≥600V, Rct<6Ω, 87L Vk≥600V, Rct<6Ω, 87L
PROTECTION PROTECTION 27: UNDERVOLTAGE RELAY
Imag≤25 mA Imag≤25 mA
50: DIRECTIONAL TIME OVERCURRENT RELAY
50N: DIRECTIONAL EARTH FAULT RELAY
P1

P1
51: IDMT OVERCURRENT RELAY
51N: IDMT EARTH FAULT RELAY
86 74 95 25 86 74 95 25
64R: RESTRICTED EARTH FAULT RELAY
-Q0 -Q0 64S: STANDBY EARTH FAULT RELAY
-Q51 -Q51
74: DC SUPERVISION RELAY
86: LOCK-OUT RELAY
M M
87: DIFFERENTIAL RELAY
M M M M
95: TRIP CIRCUIT SUPERVISION RELAY
-Q1 -Q1
NG.

E -Q2 -Q2
-Q52
TI
N W RI

BB2 132 kV, 50Hz, 630A, 40kA for 3 sec.


LEGENDS
ON I

BB1 132 kV, 50Hz, 630A, 40kA for 3 sec.


SYMBOL DESIGNATION DESCRIPTION
SSI

-Q2 -Q1 -Q2 -Q1


-Q51
R PERM I

-Q0 CIRCUIT BREAKER SPRING OPERATED


-Q2 -Q1 M M M M -Q2 -Q1
M M M M
M

M
THOUT THEI

-Q1, -Q2, -Q9 DISCONNECTING SWITCH MOTOR OPERATED.


-T17 -T27 -Q52

-Q51 -Q51
-Q51, -Q52 EARTHING SWITCH MOTOR OPERATED.

M
5,50VA
5,50VA

11KV :3,CLASS 3P,50VA


11KV :3,CLASS 3P,50VA
ED OR LENT W I

86 74 95 86 74 95

P2
D -Q0 -Q0 -Q8

11KV :3,CLASS 0.
RELAY PANEL

11KV :3,CLASS 0.
HIGH SPEED EARTHING SWITCH MOTOR OPERATED.
P1

P1
H
O/C & E/F PROTECTION RELAY PANEL
RELAY PANEL
-T1-X, -T2-X,-T3-X,
-T1-1 FROM 27B1 27B2 51 51N -T1-2 -T1-1 CURRENT TRANSFORMER
300 /1A, CL : PS 87T 600 /1A, 5P10, 300 /1A, CL : PS 87T -T4-X,-T5-X
BUS PT
Vk≥600V, Rct<6Ω, 15 VA Vk≥600V, Rct<6Ω,
TED AND M UST NOT BE COPI

Imag≤25 mA Imag≤25 mA
VOLTAGE TRANSFORMER

NG 1:132KV :3/0.

NG 2:132KV :3/0.
NG 1:132KV :3/0.

NG 2:132KV :3/0.
-T1-2 -T1-2 -T8, -T9
300 /1A, CL:5P10, 50 51 51N 24 RELAY PANEL 300 /1A, CL:5P10, 50 51 51N 24
15VA 15VA
BUS ZONE-B
-T1-1 -F1 SURGE ARRESTER
RCC BUSZONE 600 /1A, CL : PS RCC
LCC 87B 50BF Vk≥ 600V, Rct ≤ 6Ω, LCC
PROTECTION
-T1-3 Imag≤25 mA -T1-3
300 /1A, CL:0.5, MFM BCU MW MVAR A F 300 /1A, CL:0.5, MFM BCU MW MVAR A F

P1
V PF V PF -Z1 132KV CABLE SEALING END
15F ≤ 5 15F ≤ 5

NDI

NDI
NDI

NDI

WI

WI
WI

WI
C 86 74 95 25
-Q61 DISCONNECTING LINK
RELAY PANEL -Q0 RELAY PANEL

P1
MI

-T1-4 RCC LCC -T1-4 C


LUNDY LI

600 /1A, CL : PS BUSZONE 600 /1A, CL : PS BUSZONE FROM


87B 50BF 87B 50BF TR#X POWER TRANSFORMER
Vk≥ 600 V, Rct< 6Ω, PROTECTION FROM -T2-1 Vk≥* V, Rct<*Ω, PROTECTION BUS PT
Imag≤25 mA BCU MW MVAR V PF F MFM 600 /1A, CL:0.5, Imag≤25 mA
BUS PT ISF≤ 5
P2

VACUUME CIRCUIT BREAKER


VCB
SARGENT &

-Q52 -Q52
RELAY PANEL
-Q9 BUS ZONE-A -Q9
-T2-2
M

M
M BUSZONE 600 /1A, CL : PS M
87B Vk≥ 600V, Rct ≤ 6Ω,
PROTECTION Imag≤25 mA
-Q8 -Q8
S THE PROPERTY OF L& T -

P2
B
H H
B -Q51

-F1

M
-F1 *NOTE-11 *NOTE-11

-Z1
BUS COUPLER -Z1
132KV CABLE
132KV CABLE
TR#1 -T4.1 TR#2
-T4.1 3000/1A -T4.1
NGR -T4.1
GN I

132/11.5KV, 40/50 MVA 1000/1A CL:PS VK≥675V 132/11.5KV, 40/50 MVA 3000/1A
NGR
5P10.15VA RCT ≤ 20Ω 1000A
1000/1A CL:PS VK≥675V
ONAN/ONAF COOLED ONAN/ONAF COOLED 5P10.15VA RCT ≤ 20Ω 1000A
NG AND DESI

P1 P2
Z=11%,Dyn11 R Z=11%,Dyn11 P1 P2
R
(NO NEGATIVE TOLERANCE) (NO NEGATIVE TOLERANCE)
OLTC WITH ±10%, OLTC WITH ±10%,
IN STEPS OF 1.25% IN STEPS OF 1.25%
RELAY PANEL RELAY PANEL
SPBD SPBD
S DRAW I

64R 64R
THI

11 KV SWITCHGEAR 11 KV SWITCHGEAR
LINE PT LINE PT
-T8 -T8

P1 P1
-T3.1 -T3.1
3000/1A 3000/1A
64S 50 50N 51 51N 64S 50 50N 51 51N
CL:5P20,20VA CL:5P20,20VA

-T3.2 -T3.2
3000/1A 3000/1A
CL:0.5,ISF ≤ 5 MFM CL:0.5,ISF ≤ 5 MFM

-T3.3 -T3.3
3000/1A 3000/1A
CL:PS VK≥400V,RCT ≤ 20Ω CL:PS VK≥400V,RCT ≤ 20Ω

-T3.4 -T3.4
3000/1A 3000/1A
CL:PS VK≥675V,RCT ≤ 20Ω CL:PS VK≥675V,RCT ≤ 20Ω
P2 P2

CB CB
I/L 86 74 95 25
3150 A 3150 A
86 74 95 25

11 KV , 3150A,3PH,3WIRE,44KA FOR 3SEC, BUS-A 11 KV , 3150A,3PH,3WIRE,44KA FOR 3SEC, BUS-B

3150A NO
1600A 1600A 1600A 1600A 1600A 1600A 1600A 3150A 1600A 1600A 1600A 1600A 1600A 1600A 1600A
NO 3150A NC
BUS PT BUS PT
02 02
P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
-T5.1 -T5.1

-T5.2 -T5.2

-T5.3 P2

P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2

SPBD

FEEDER-1A FEEDER-2A FEEDER-3A FEEDER-4A FEEDER-5A FEEDER-6A FEEDER-7A FEEDER-1B FEEDER-2B FEEDER-3B FEEDER-4B FEEDER-5B FEEDER-6B FEEDER-7B

1C - CU-XLPE CABLE

SPBD 02 SPBD
I/C FROM 50MVA TRAFO. I/C FROM 50MVA TRAFO.
P1 P2 I/L P2 P1
LINE PT 3150A
3150A

02 ARS 07-06-2019 FOR BID


11 KV , 3150A,3PH,3WIRE,44KA FOR 3SEC, BUS-A 11 KV , 3150A,3PH,3WIRE,44KA FOR 3SEC, BUS-B
LINE PT LINE PT
01 ARS 19-03-2019 FOR BID
00 AB 26-02-2019 FOR BID
02 02
REV NO. ISSUED BY DATE REVISION DETAIL
3150A NO NC
2000A 2000A 1600A 3150A 3150A 1600A 2000A 2000A
NO PROJECT: NEW 132KV SWITCHYARD AND SUB-STATION PROJECT, GSFC, VADODARA
BUS PT BUS PT
OWNER: GUJARAT STATE FERTILIZERS AND CHEMICALS LIMITED
P1 P1 P1 P1 P1 P1 P1 P1 (GSFC LTD), VADODARA
OWNER'S
-T5.1 -T5.1 L & T - SARGENT & LUNDY LTD., VADODARA
CONSULTANT:
-T5.2 -T5.2 ---

P2 P2
---

P2 P2 P2 P2 P2 P2
DATE NAME TITLE:
ATTACHMENT-1

x 594m m )
DRAWN 26-02-2019 VPS

CHECKED 26-02-2019 MIT/ARS OVERALL SINGLE LINE DIAGRAM


CAPROLACTAM-2 AMMONIA -4 MELAMINE-2 AMMONIA -4 CAPROLACTAM-2
MELAMINE-2 APPROVED 26-02-2019 AB
A FDR-I & II A
FDR-I & II FDR-I & II FDR-I & II FDR-I & II EXISTING 11 KV SWITCHGEAR ROOM
FDR-I & II DEPARTMENT: ELECTRICAL

A1 (841m m
L&T-S&L JOB NO.: HO19115000 DRG. NO.:HO19115000-YU02-00-AEA-140002

GSFC JOB
GSFC JOB NO.:NO: PROJ/219
PROJ/219 SCALE- NTS SHEET: 01 OF 01 REV. 00