3. SYSTEM...................................................................................................................................................................... SLZ-4
SUZ-KA15NA.TH.................................................................................................................................................... SLZ-15
SUZ-KA09NA.TH.................................................................................................................................................... SLZ-16
(2) Maximum Refrigerant Piping Length & Maximum Height Difference................................................................. SLZ-25
Due to continuing improvement, above specification may be subject to change without notice.
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-2 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
1. INDOOR UNITS
• SLZ-KA09NA.TH
• SLZ-KA12NA.TH
• SLZ-KA15NA.TH
Due to continuing improvement, above specification may be subject to change without notice.
• SUZ-KA09NA.TH
• SUZ-KA12NA.TH
• SUZ-KA15NA.TH
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-4 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3. SYSTEM
• Four-way 2’x2’ ceiling-cassette indoor unit for ceiling recessed application
• Built-in drain mechanism for condensate removal; lifts to 19-11/16”
• Choice of fan speeds: Low, Medium, and High
• Indoor unit powered from outdoor unit using A-control
• Self-check function -- onboard diagnostics
• Advanced microprocessor control
• Auto restart following a power outage
• Hand-held Wireless Remote Controller
• Anti-allergy Enzyme Filter
• Limited warranty: five years parts and seven years compressor
Due to continuing improvement, above specification may be subject to change without notice.
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
Operating range
Indoor intake air temperature Outdoor intake air temperature
Maximum D.B. 35°C(95°F), W.B. 21.7°C(71°F) D.B. 46°C(115°F)
Cooling
Minimum D.B. 19.4°C(67°F), W.B. 13.9°C(57°F) D.B. -10°C(14°F)
Heating Maximum D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) D.B. 24°C(75°F), W.B. 18°C(65°F)
Minimum D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) D.B. -20°C(-4°F), W.B. -21°C(-5°F)
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-6 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
Operating range
Indoor intake air temperature Outdoor intake air temperature
Maximum D.B. 35°C(95°F), W.B. 21.7°C(71°F) D.B. 46°C(115°F)
Cooling
Minimum D.B. 19.4°C(67°F), W.B. 13.9°C(57°F) D.B. -10°C(14°F)
Heating Maximum D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) D.B. 24°C(75°F), W.B. 18°C(65°F)
Minimum D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) D.B. -20°C(-4°F), W.B. -21°C(-5°F)
Due to continuing improvement, above specification may be subject to change without notice.
MOCP A 15
CMM 8 - 9 - 10 8 - 9 - 11 8 - 9 - 11
Air flow DRY
(Lo-Mid-Hi) WET
CMM 7-8-9 7 - 8 - 10 7 - 8 - 10
CFM 280 - 320 - 350 280 - 320 - 390 280 - 320 - 390
Air flow DRY
(Lo-Mid-Hi) WET
CFM 250 - 290 - 320 250 - 290 - 350 250 - 290 - 350
dB (A)
Dimension
Unit <Grille> W:mm 570 <650> [22-7/16 <25-19/32>]
[inch]
kg 16.5 <3>
Weight
Unit <Grille>
lbs 36 <7>
Field Drain pipe mm [inch] 32 [1-1/4]
O.D.
Remote Controller Optional parts
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
Operating range
Indoor intake air temperature Outdoor intake air temperature
Maximum D.B. 35°C(95°F), W.B. 21.7°C(71°F) D.B. 46°C(115°F)
Cooling
Minimum D.B. 19.4°C(67°F), W.B. 13.9°C(57°F) D.B. -10°C(14°F)
Heating Maximum D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) D.B. 24°C(75°F), W.B. 18°C(65°F)
Minimum D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) D.B. -20°C(-4°F), W.B. -21°C(-5°F)
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-8 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS
MOCP A 15
Oil L [oz] 0.32 (NEO 22) [10.8] 0.45 (NEO 22) [15.2]
Refrigerant Gas side O.D. mm [inch] 9.52 [3/8] 12.7 [1/2]
pipe size
Liquid side O.D. mm [inch] 6.35 [1/4]
Refrigerant Height difference Max. 12 m [Max. 40 ft]
pipe length
Length Max. 20 m [Max. 65 ft]
Refrigerant Piping Not Supplied
Connection Method Flared
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
Due to continuing
Operating range improvement, above specification may be subject to change without notice.
Indoor intake air temperature Outdoor intake air temperature SLZ-9
M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015Cooling
Maximum
Mitsubishi Electric US, Inc.
D.B. 35°C(95°F), W.B. 21.7°C(71°F) D.B. 46°C(115°F)
Minimum D.B. 19.4°C(67°F), W.B. 13.9°C(57°F) D.B. -10°C(14°F)
Maximum D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) D.B. 24°C(75°F), W.B. 18°C(65°F)
3-1. SPECIFICATIONS
Efficiency Ratings
COP COP Energy
Outdoor Unit Indoor Unit SEER EER HSPF
@ 47° F @ 17° F Star
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-10 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-2. EXTERNAL DIMENSIONS
Fresh air
intake
Ceiling hole
[3-15/16([100) 1(25)
[2-7/8([73.4)
20-7/8(530) 3-[1/8([2.8) Cut out hole
Burring hole
Suspension bolt pitch
Suspension bolt pitch
16-17/32(420)
22-7/16(570)
13-3/16(335)
22-11/16~24-13/32(576~620)
4-21/32(118)
120-
19/32~1-15/32(15~37)
22-7/16(570)
0-
12
1-7/32(31)
Ceiling surface
3-7/16(87)
2-7/32(56)
2-1/4(57)
7-27/32(199)
13-27/32(352)
13-3/16(335)
19/32~1-15/32(15~37) 22-11/16~24-13/32(576~620) Ceiling hole 19/32~1-15/32(15~37)
VP-25 connection
Refrigerant 21/32(17) 7-15/16(202) 9-1/16(230)
(O.D.[1-1/4([32))
pipe (gas) Suspension bolt M10 or W3/8
Refrigerant
7-5/32(182)
pipe (liquid)
7-19/32(193)
8-3/16(208)
9-1/4(235)
4-3/4(121)
3-21/32(93)
1-7/8(48)
1-1/2~2-9/32(38~58)
25/32(20)
Suspension bolt
01-1/16
11-27/32(301)
1/4 inch 3/8 inch
Air outlet hole Brand label
SLZ-KA09NA ({ 6.35mm) ({ 9.52mm)
Grille flared connection flared connection
2-5/32(55)
14-27/32(377)
25-19/32(650)
V/M
Due to continuing improvement, above specification may be subject to change without notice.
Air in
1-3/4
e
mor
. or
4 in
4 in
Air in . or
mo
13-9/16
re
12 ~ 12-3/4
11/16
3-2. EXTERNAL DIMENSIONS
SUZ-KA12NA.TH
1-9/16 14
in
Air out . or
m ore mo
re
. or
2- 3/8 13/16 Oval hole 8 in
7/8 29/32 11-1/4 17/32
Open two sides of left,
handle right, or rear side.
Due to continuing improvement, above specification may be subject to change without notice.
21-5/8
Liquid pipe :1/4 (flared)
2
Gas pipe :3/8 (flared) (KA09/12)
11-1/32
5-7/8
1/2 (flared) (KA15)
11-29/32 6-23/32
13/32
5-15/16 19-11/16
31-1/2 2-23/32
Unit: mm (inch)
c
C
A B
a b
Unit: inch(mm)
Model name A B C a b c
SUZ-KA09NA.TH
11-1/16 5-9/16 9-1/2 31-1/2 11-1/4 21-5/8
SUZ-KA12NA.TH
(280) (140) (240) (800) (285) (550)
SUZ-KA15NA.TH
Due to continuing improvement, above specification may be subject to change without notice.
WHT
BRN
YLW
RED
BLU
BLK
WHT
ORN
RED
RED
RED
RED
YLW
YLW
BLU
BLU
MV I.B (RED)
5 1 3
1 3 5 7 9 WHT 1 3 RED 1 3 BLU 1 3 RED 1 3 ORN 1 3
(FAN) (D·HEATER) (D·U·M) (POWER (POWER)
FAN CNC CNP BOARD) CND BLU
CNDK DC13.1V
(CONTROL)
X1 FUSE CN3C
CN2S
(WHT)
1 2
X6 X5 X4 X7
WHT 1 BLK
(POWER
BOARD) WHT
CN2D 2
SWE
ON
OFF LED3
LED2 LED1
SW2 RED
CN2L CN24 CN105 CN30
ON GRN BLK RED
OFF (VANE) (2 PHASE) (INTAKE) 3 1
12345 2 1 2 1 5 1 CN6V
6 1 WHT CN29 CN20 WHT BLU
(DRAIN) (LIQUID) (REMOCON)
CN32 CN51 CN41 CN90 CN31 2 1 2 1 CN21 CN22
WHT
ORN
RED
YLW
BLU
<Fig: w 1>
MODELS SW2 1 3 5 1 4 1 9 1 3 1 2 1 2 1
ON
BLU
BLU
SLZ- See Fig:w 1
KA09NA OFF 5 5
12345
ON R.B
SLZ- t° t° t° t°
KA12NA OFF TB15 TB6
12345 RFI 2
DS TH5 TH1 TH2 1 1
SLZ- ON 2 2
KA15NA OFF
12345
The black square (■) indicates a switch position.
[LEGEND]
SYMBOL NAME SYMBOL NAME
P.B INDOOR POWER BOARD C1 CAPACITOR (FAN MOTOR)
I.B INDOOR CONTROLLER BOARD DP DRAIN PUMP
CN2L CONNECTOR (LOSSNAY) DS DRAIN SENSOR
CN24 CONNECTOR (BACK-UP HEATING) RFI RADIO FREQUENCY INTERFACE FOR
CN30 CONNECTOR (LLC) RF THERMOSTAT
CN32 CONNECTOR (REMOTE SWITCH) H2 DEW PREVENTION HEATER
CN41 CONNECTOR (HA TERMINAL-A) MF FAN MOTOR (WITH THERMAL FUSE)
CN51 CENTRALLY CONTROL MV VANE MOTOR
CN105 CONNECTOR (RADIO FREQUENCY INTERFACE) TB4 TERMINAL BLOCK
FUSE FUSE (T6.3AL250V) (INDOOR/OUTDOOR CONNECTING LINE)
LED1 POWER SUPPLY (I.B) TB15 TERMINAL BLOCK (REMOTE CONTROLLER
LED2 POWER SUPPLY (I.B) TRANSMISSION LINE)
LED3 TRANSMISSION (INDOOR-OUTDOOR) TH1 ROOM TEMP. THERMISTOR
SW2 SWITCH (CAPACITY CODE) (32°F / 15kΩ, 77°F / 5.4kΩ DETECT)
SWE SWITCH (EMERGENCY OPERATION) TH2 PIPE TEMP. THERMISTOR/LIQUID
X1 DRAIN PUMP/DEW PREVENTION HEATER (32°F / 15kΩ, 77°F / 5.4kΩ DETECT)
X4 RELAY (FAN MOTOR LL) TH5 COND. / EVA. TEMP. THERMISTOR
X5 RELAY (FAN MOTOR Lo) (32°F / 15kΩ, 77°F / 5.4kΩ DETECT)
X6 RELAY (FAN MOTOR Hi) OPTION PART
X7 RELAY (FAN MOTOR Me) R.B WIRED REMOTE CONTROLLER BOARD
TB6 TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
NOTES: 1. Since the outdoor side electric wiring may change be sure to check the
outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with poIarities, make wiring
matching terminal numbers (S1, S2, S3).
3. Use copper supply wires.
4. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
wFor details on how to operate self-diagnosis refer to the technical manuals etc.
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-14 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
SUZ-KA09NA, SUZ-KA12NA WIRING DIAGRAM
CN722
2 2 H
LD70 LD66 1 3 CN721 BLK
– X63 1 2 BLK
DB65 ~ DB61 X66
+ – ~ ~ C63 C62 X64 1 1
IC802
~ + + + T801 F701 4 (OPTION PARTS)
F801 LD63 PTC64
W RED 3 RED W N
MS V WHT WHT LDW F901
V IC932
3~ BLK BLK LDV TB1 CIRCUIT GROUND
CN931
3-4. ELECTRICAL WIRING DIAGRAMS
LDU U P BREAKER
MC U 1 1 1 5 L2 POWER SUPPLY
CN61 IPM 208/230V
5 LED L1 1 phase 60Hz
INVERTER P.C. BOARD 3 1 CN642 CN644 CN643 CN641 CN724
BRN
LD-S
BLU
Due to continuing improvement, above specification may be subject to change without notice.
1 phase 60Hz
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C62,C63 SMOOTHING CAPACITOR LEV EXPANSION VALVE COIL RT68 OUTDOOR HEAT EXCHANGER NOTES:
DB61,DB65 DIODE MODULE MC COMPRESSOR TEMP. THERMISTOR. 1.About the indoor side electric
F701,F801,F901 FUSE (T3.15AL250V) MF FAN MOTOR TB1,TB2 TERMINAL BLOCK
H DEFROST HEATER(OPTION PARTS) PTC64,PTC65 CIRCUIT PROTECTION TR821 SWITCHING POWER TRANSISTOR
wiring, refer to the indoor
IC802 INTELLIGENT POWER DEVICE RT61 DEFROST THERMISTOR T801 TRANSFORMER unit electric wiring diagram
IPM,IC932 INTELLIGENT POWER MODULE RT62 DISCHARGE TEMP.THERMISTOR X63,X64,X66 RELAY for servicing.
L61 REACTOR RT64 FIN TEMP.THERMISTOR 21S4 REVERSING VALVE COIL 2.Use copper conductors only.
LED LED RT65 AMBIENT TEMP.THERMISTOR 26H HEATER PROTECTOR(OPTION PARTS) (For field wiring).
2 2 26H
RED BLK BLK
ORN L61 YLW BLK BLK BLK
SUZ-KA15NA.TH
LD-S
BLU
Due to continuing improvement, above specification may be subject to change without notice.
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C61,C62,C63 SMOOTHING CAPACITOR LEV EXPANSION VALVE COIL OUTDOOR HEAT EXCHANGER NOTES:
RT68
DB61,DB65 DIODE MODULE MC COMPRESSOR TEMP. THERMISTOR. 1.About the indoor side electric
F701,F801,F901 FUSE (T3.15AL250V) MF FAN MOTOR TB1,TB2 TERMINAL BLOCK
wiring, refer to the indoor
H DEFROST HEATER(OPTION PARTS) PTC64,PTC65 CIRCUIT PROTECTION TR821 SWITCHING POWER TRANSISTOR
IC802 INTELLIGENT POWER DEVICE RT61 DEFROST THERMISTOR T801 TRANSFORMER
unit electric wiring diagram
IPM,IC932 INTELLIGENT POWER MODULE RT62 DISCHARGE TEMP.THERMISTOR X63,X64,X66 RELAY
for servicing.
L61 REACTOR RT64 FIN TEMP.THERMISTOR 21S4 REVERSING VALVE COIL 2.Use copper conductors only.
LED LED RT65 AMBIENT TEMP.THERMISTOR 26H HEATER PROTECTOR(OPTION PARTS) (For field wiring).
SUZ-KA09NA.TH
Refrigerant pipe ø3/8 4-way valve
(with heat insulator)
Muffler
Outdoor heat
exchanger
Stop valve temperature
(with service port) Outdoor thermistor
Muffler
Flared connection Discharge heat RT68
temperature exchanger
thermistor Service port
RT62
Compressor Ambient
Service port temperature
thermistor
RT65
Defrost
thermistor
RT61
Strainer
Capillary tube #100
Flared connection O.D. 0.118 × I.D. 0.079
× 9-7/16 LEV
(ø3.0 × ø2.0 × 240) R.V. coil
heating ON
cooling OFF
Stop valve
(with strainar)
Refrigerant pipe ø1/4 Refrigerant flow in cooling
(with heat insulator) Refrigerant flow in heating
Due to continuing improvement, above specification may be subject to change without notice.
SUZ-KA12NA.TH SUZ-KA15NA.TH
Refrigerant pipe ø3/8 (KA12)
Refrigerant pipe ø1/2 (KA15) 4-way valve
(with heat insulator)
Muffler
Outdoor heat
exchanger
Stop valve temperature
(with service port) Outdoor thermistor
Discharge Muffler
Flared connection heat RT68
temperature exchanger
thermistor
Service port
RT62
Compressor Ambient
Service port temperature
Defrost thermistor
thermistor RT65
RT61
Capillary tube
O.D. 0.118 × I.D. 0.071
× 23-5/8
Capillary tube (ø3.0 × ø1.8 × 600) (×2) Strainer
Flared connection O.D. 0.118 × I.D. 0.079 #100
× 9-7/16 LEV
(ø3.0 × ø2.0 × 240) R.V. coil
heating ON
cooling OFF
Stop valve
(with strainar)
Refrigerant pipe ø1/4 Refrigerant flow in cooling
(with heat insulator) Refrigerant flow in heating
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-18 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE
1.4 Indoo
1.3 r inta
ke air
WB t
1.2 empe
rature
1.1 (°F)
1.0
71
0.9
67
0.8 63
1.2
r e( °F) 71
er a t u
1.1 tem p 67
ir W B 63
1.0 ake a
r i n t
Ind oo
0.9
0.8
0.7
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Due to continuing improvement, above specification may be subject to change without notice.
65
1.3 70
1.2 ( °F) 75
ure
1.1 e rat
temp
B
1.0 ir D
ea
0.9 ak
int
0.8 o or
Ind
0.7
0.6
0.5
0.4
1.1 75
70
1.0 65
0.9
)
0.8 ratu re (°F
DB tempe
0.7 ir
r i n t ake a
Indo o
0.6
5 15 25 35 45 55 65 70
Outdoor intake air WB temperature (°F)
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-20 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
71 10.3 7.3 0.62 9.6 6.8 0.68 9.0 6.4 0.74 8.4 5.9 0.77 7.7 5.5 0.81
SUZ-KA09NA 67 9.7 8.2 0.59 9.1 7.6 0.65 8.4 7.1 0.70 7.8 6.6 0.74 7.2 6.0 0.78
63 9.2 8.9 0.56 8.5 8.3 0.62 7.9 7.7 0.67 7.2 7.0 0.71 6.6 6.4 0.74
71 13.6 8.7 0.82 12.7 8.1 0.90 11.9 7.6 0.97 11.1 7.1 1.02 10.2 6.5 1.06
SUZ-KA12NA 67 12.9 9.9 0.77 12.0 9.2 0.85 11.1 8.5 0.92 10.3 7.9 0.98 9.5 7.3 1.02
63 12.1 10.9 0.74 11.2 10.1 0.81 10.4 9.4 0.88 9.5 8.6 0.94 8.7 7.8 0.98
71 18.4 9.9 1.30 17.2 9.2 1.42 16.1 8.7 1.53 15.0 8.1 1.61 13.8 7.4 1.68
SUZ-KA15NA 67 17.4 11.7 1.23 16.2 10.9 1.35 15.0 10.1 1.46 14.0 9.3 1.55 12.8 8.6 1.62
63 16.4 13.1 1.17 15.2 12.2 1.29 14.1 11.3 1.39 12.8 10.3 1.49 11.7 9.4 1.55
Due to continuing improvement, above specification may be subject to change without notice.
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-22 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
Due to continuing improvement, above specification may be subject to change without notice.
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-24 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
TPC:Total Power Consumption (kW)
2. SHC is based on 80°F of indoor intake air DB temperature.
3-8. CAPACITY
COOLINGCORRECTION
M d l
Model
CAPACITY CORRECTION
R fi
Refrigerant
CURVE
t piping
i i length
l th (one
(
BYft.))REFRIGERANT PIPING LENGTH
way : ft
25(std.) 40 65 100
SUZ-KA09NA
SUZ-KA09NA.TH SUZ-KA12NA SUZ-KA12NA.TH
1.0 0.954 SUZ-KA15NA.TH
0.878 -
SUZ-KA15NA.TH
SUZ-KA15NA SUZ-KA18NA.TH
SUZ-KA18NA 1.0 0.954 0.878 0.771
1.00
0.95
Cooling capacity corrections
0.90
0.85
0.80
0.75
0.70
0 10 20 30 40 50 60 70 80 90 100 110
Refrigerant piping length (ft)
Due to continuing improvement, above specification may be subject to change without notice.
25 (std.) 40 65 100
SUZ-KA09NA.TH
SUZ-KA12NA.TH 1.0 0.954 0.878 -
SUZ-KA15NA.TH
Gas Liquid
Model Additional Additional
piping piping
Max. length Max. height Minimum Minimum
A B Outside Outside
Wall Wall
diameter diameter
thickness thickness
SUZ-KA09NA.TH
65 40 3/8 0.0315 1/4 0.0315
SUZ-KA12NA.TH
Indoor
unit
Outdoor unit
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-26 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
Due to continuing improvement, above specification may be subject to change without notice.
NOTE: Calculation: X oz. = 1.62/5 oz./ft (Refrigerant piping length (ft) - 25)
Outdoor unit
Model
precharged
25ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft
SUZ-KA18NA.TH 4 lb. 0 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
NOTE: Calculation: X oz. = 1.08/5 oz./ft (Refrigerant piping length (ft) - 25)
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-28 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-11. AIR FLOW DATA
m3/min 10 - 9 - 8 11 - 9 - 8 11 - 9 - 8
Air flow H-M-L
CFM 350-320-280 390-320-280 390-320-280
Due to continuing improvement, above specification may be subject to change without notice.
90 90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
70 70
NC-70 NC-70
60
60
NC-60
NC-60
50
50
NC-50
NC-50
40
NC-40 40
NC-40
30
NC-30 30
NC-30
20 APPROXIMATE
THRESHOLD OF
HEARING FOR 20 APPROXIMATE
CONTINUOUS
NC-20 THRESHOLD OF
HEARING FOR
NOISE
CONTINUOUS
NC-20
10 NOISE
63 125 250 500 1000 2000 4000 8000
10
BAND CENTER FREQUENCIES, Hz 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
<60Hz>
SLZ-KA15NA.TH NOTCH SPL(dB) LINE
High 40
Medium 35
Low 31
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80 UNIT
70 CEILING
NC-70
60
NC-60
50
NC-50
5 ft
40
NC-40
30
NC-30 MICROPHONE
20 APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NC-20
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops.
The sound may be bigger than the indicated level in actual use due to surrounding echoes.
The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation.
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-30 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
OCTAVE BAND SOUND PRESSU
40 40
30 30
NC-30 NC-30
(2) Outdoor
OUTDOOR Unit
UNIT
OUTDOOR UNIT 20 APPROXIMATE
THRESHOLD OF
20 APPROXIMATE
THRESHOLD OF
SUZ-KA09NA.TH
SUZ-KA09NA.TH
HEARINGSPL(dB(A))
FUNCTION
FUNCTION
FOR
SPL(dB(A))
CONTINUOUS
LINE
LINE
SUZ-KA12NA.TH
SUZ-KA12NA.TH NC-20 HEARINGSPL(dB(A))
FUNCTION
FUNCTION
FOR
SPL(dB(A))
CONTINUOUS
LINE
LINE
NC-20
NOISE
COOLING 46 NOISE
COOLING 49
10COOLING 46 10COOLING 49
63
HEATING 12550 250 500 1000 2000 4000 8000 63
HEATING 12551 250 500 1000 2000 4000 8000
HEATING 50 HEATING 51
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
90 90
90 90
bar)
80 80
0.0002bar)
0.0002bar)
80 COOLING 49 80 COOLING 54
HEATING 51
0.0002
0.0002
HEATING 56
70 70
70 70
==
==
90 NC-70 NC-70
90
dB
dB
NC-70 NC-70
dB
dB
(0(0
(0(0
dB
dB
60 60
dB
dB
60 60
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
LEVEL,
LEVEL,
80
LEVEL,
NC-60 NC-60
50 50
PRESSURE
PRESSURE
50 50
PRESSURE
PRESSURE
70 NC-50 70 NC-50
NC-50 NC-70 NC-50 NC-70
40 40
40 40
SOUND
SOUND
60 NC-40 60 NC-40
SOUND
SOUND
NC-40 NC-40
NC-60 NC-60
BAND
BAND
30 30
BAND
BAND
30 50 30
NC-30 50 NC-30
NC-30 NC-30
NC-50
OCTAVE
OCTAVE
NC-50
OCTAVE
OCTAVE
APPROXIMATE APPROXIMATE
20 APPROXIMATE 20 APPROXIMATE
20 THRESHOLD OF
40 20 THRESHOLD OF
THRESHOLD
HEARING FOROF THRESHOLD
HEARING FOROF 40
NC-20 NC-20
HEARING FOR
CONTINUOUS NC-20 HEARING FOR
CONTINUOUS
NC-40 NC-20
CONTINUOUS CONTINUOUS NC-40
NOISE NOISE
10 NOISE 10 NOISE
10 63 125 250 30500 1000 2000 4000 8000 10 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000 63 125 250 30
500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz NC-30 BAND CENTER FREQUENCIES, Hz NC-30
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
APPROXIMATE
20 20 APPROXIMATE
THRESHOLD OF
SUZ-KA15NA.TH
THRESHOLD OF
SUZ-KA15NA.TH
HEARINGSPL(dB(A))
FUNCTION
FUNCTION
FOR
SPL(dB(A))
CONTINUOUS
LINE
LINE SUZ-KA18NA.TH
SUZ-KA18NA.TH
NC-20 HEARINGSPL(dB(A))
FUNCTION
FUNCTION
FOR
SPL(dB(A))
CONTINUOUS
LINE
LINE
NC-20
NOISE
COOLING 49 NOISE
10COOLING 49 COOLING 54
10COOLING 54
63
HEATING 12551 250 500 1000 2000 4000 8000 63 12556 250 500 1000 2000 4000 8000
HEATING 51 HEATING
BAND CENTER FREQUENCIES, Hz HEATING 56
BAND CENTER FREQUENCIES, Hz
90
90 OUTDOOR
90
90 UNIT
1m
bar)
80
bar)
80
0.0002bar)
80
0.0002bar)
80
MICROPHONE
0.0002
0.0002
70 70
70
==
NC-70 70
==
NC-70
dB
NC-70
dB
NC-70
dB
dB
(0(0
(0(0
dB
60
dB
60
dB
60
dB
60
LEVEL,
LEVEL,
NC-60 NC-60
LEVEL,
LEVEL,
NC-60 NC-60
50
PRESSURE
50
PRESSURE
50
PRESSURE
50
PRESSURE
NC-50 NC-50
NC-50 NC-50
40 40
40
SOUND
40
SOUND
NC-40
SOUND
NC-40
SOUND
NC-40 NC-40
BAND
30
BAND
30
BAND
30
BAND
NC-30 30
NC-30 NC-30
NC-30
OCTAVE
OCTAVE
OCTAVE
OCTAVE
APPROXIMATE
20 APPROXIMATE 20 APPROXIMATE
20 THRESHOLD OF
20 APPROXIMATE
THRESHOLD OF
THRESHOLD
HEARING FOROF THRESHOLD
HEARING FOR
NC-20 HEARING FOROF NC-20
CONTINUOUS NC-20 HEARING FOR
CONTINUOUS NC-20
CONTINUOUS
NOISE CONTINUOUS
NOISE
10 NOISE
10 NOISE
10 63 125 250 500 1000 2000 4000 8000 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
OUTDOOR
OUTDOOR UNIT
UNIT
1m
1m
MICROPHONE
MICROPHONE
Due to continuing improvement, above specification may be subject to change without notice.
208/230V
Outdoor unit 60Hz Min. 187V 208V 230V Max. 253V
1 Phase
Standard temperature 80 67 95 —
Standard temperature 70 60 47 43
Minimum temperature 70 60 6 5
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-32 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES
All Models
Outdoor Air Sensor - reads both outside temperature and
MOS1
humidity displayed on MRCH1 and MCCH1 if installed
Due to continuing improvement, above specification may be subject to change without notice.
Due to continuing improvement, above specification may be subject to change without notice.
SLZ-34 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES
KA09,12
Diamondback
MLS141212T-15 1/4 x 1/2 x 15' / 1/2" Twin-Tube Insulation
Linesets
Due to continuing improvement, above specification may be subject to change without notice.
MAC-640BH-U Outdoor Unit Drain Pan Heater used during defrost cycle KA09,12,15
MAC-641BH-U Outdoor Unit Drain Pan Heater used during defrost cycle KA18
Due to continuing improvement, above specification may be subject to change without notice.