M-SERIES SINGLE ZONE SYSTEMS

SLZ CEILING-RECESSED HEAT PUMP SYSTEMS


1. INDOOR UNITS.......................................................................................................................................................... SLZ-2

2. OUTDOOR UNITS...................................................................................................................................................... SLZ-3

3. SYSTEM...................................................................................................................................................................... SLZ-4

3-1. SPECIFICATIONS................................................................................................................................................... SLZ-5

SLZ-KA09NA.TH SLZ-KA12NA.TH SLZ-KA15NA.TH.......................................................................................... SLZ-5

SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH.......................................................................................... SLZ-6

SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH.......................................................................................... SLZ-7

SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH.......................................................................................... SLZ-8

Efficiency Ratings...................................................................................................................................................... SLZ-9

3-2. EXTERNAL DIMENSIONS.................................................................................................................................... SLZ-10

SLZ-KA09NA.TH SLZ-KD12NA.TH SLZ-KA15NA.TH...................................................................................... SLZ-10

SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH.....................................................................................SLZ-11

3-3. CENTER OF GRAVITY.......................................................................................................................................... SLZ-12

3-4. ELECTRICAL WIRING DIAGRAMS...................................................................................................................... SLZ-13

SLZ-KA09NA.TH SLZ-KD12NA.TH SLZ-KA15NA.TH...................................................................................... SLZ-13

SUZ-KA09NA.TH SUZ-KA12NA.TH.................................................................................................................... SLZ-14

SUZ-KA15NA.TH.................................................................................................................................................... SLZ-15

3-5. REFRIGERANT SYSTEM DIAGRAMS................................................................................................................. SLZ-16

SLZ-KA09NA.TH SLZ-KD12NA.TH SLZ-KA15NA.TH...................................................................................... SLZ-16

SUZ-KA09NA.TH.................................................................................................................................................... SLZ-16

SUZ-KA12NA.TH SUZ-KA15NA.TH.................................................................................................................... SLZ-17

3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE..................................................................................... SLZ-18

(1) Cooling Performance Curve.............................................................................................................................. SLZ-18

(2) Heating Performance Curve.............................................................................................................................. SLZ-19

3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE....................................................................................... SLZ-20

(1) Cooling Capacity................................................................................................................................................ SLZ-20

(2) Heating Capacity .............................................................................................................................................. SLZ-21

(3) M-Series Cooling Correction.............................................................................................................................. SLZ-22


(4) M-Series Defrost Correction.............................................................................................................................. SLZ-22

(5) M-Series Heating Correction............................................................................................................................. SLZ-23

3-8. CAPACITY CORRECTION CURVE BY REFRIGERANT PIPING LENGTH......................................................... SLZ-24

3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH........................................................... SLZ-25

(1) Cooling Capacity Correction.............................................................................................................................. SLZ-25

(2) Maximum Refrigerant Piping Length & Maximum Height Difference................................................................. SLZ-25

(3) M-Series Piping Correction Cooling................................................................................................................... SLZ-26

(4) M-Series Piping Correction Heating.................................................................................................................. SLZ-26

3-10. CHARGE CALCULATIONS................................................................................................................................. SLZ-27

(1) Additional Refrigerant Charge (R410A: oz.)...................................................................................................... SLZ-27

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-1


© 2015 Mitsubishi Electric US, Inc.
M-SERIES SINGLE ZONE SYSTEMS

3-11. AIR FLOW DATA.................................................................................................................................................. SLZ-28

Outlet Air Speed And Coverage.............................................................................................................................. SLZ-28

3-12. SOUND PRESSURE LEVELS............................................................................................................................. SLZ-29

(1) Indoor Unit......................................................................................................................................................... SLZ-29

(2) Outdoor Unit...................................................................................................................................................... SLZ-30

3-13. STANDARD OPERATION RANGE...................................................................................................................... SLZ-31

3-14. ACCESSORIES................................................................................................................................................... SLZ-32

(1) Indoor Unit......................................................................................................................................................... SLZ-32

(2) Outdoor Unit...................................................................................................................................................... SLZ-35

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-2 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
1. INDOOR UNITS

• SLZ-KA09NA.TH
• SLZ-KA12NA.TH
• SLZ-KA15NA.TH

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-3


© 2015 Mitsubishi Electric US, Inc.
2. OUTDOOR UNITS

• SUZ-KA09NA.TH
• SUZ-KA12NA.TH
• SUZ-KA15NA.TH

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-4 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3. SYSTEM
• Four-way 2’x2’ ceiling-cassette indoor unit for ceiling recessed application
• Built-in drain mechanism for condensate removal; lifts to 19-11/16”
• Choice of fan speeds: Low, Medium, and High
• Indoor unit powered from outdoor unit using A-control
• Self-check function -- onboard diagnostics
• Advanced microprocessor control
• Auto restart following a power outage
• Hand-held Wireless Remote Controller
• Anti-allergy Enzyme Filter
• Limited warranty: five years parts and seven years compressor

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-5


© 2015 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS

SLZ-KA09NA.TH SLZ-KA12NA.TH SLZ-KA15NA.TH


Model name Indoor unit SLZ-KA09NA.TH SLZ-KA12NA.TH SLZ-KA15NA.TH
Outdoor unit SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH
Cooling Max. Capacity Btu/h 10,900 13,300 17,700

Rated Capacity Btu/h 8,400 11,100 15,000

Min. Capacity Btu/h 3,100 3,400 3,800

Total input W 700 920 1,460

EER Btu/h 12 12 10.2

SEER Btu/h 15 15.4 16

Moisture Removal Pints/h 1.2 2.3 4.5

SHF 0.84 0.77 0.67


Heating Max. Capacity Btu/h 14,100 17,100 22,200

Rated Capacity Btu/h 10,900 13,600 18,000

Min. Capacity Btu/h 3,100 3,100 3,100

Total input W 930 1,180 1,950

COP W/W 3.44 3.38 2.71

HSPF(IV) Btu/h/W 9.6 9.6 9.6


Heating Capacity Btu/h 8,300 10,200 13,400
at low
ambient
Total input W 1,040 1,310 1,970

COP W/W 2.33 2.28 1.99


Power Phase,Cycle,Voltage 1phase, 60Hz, 208/230V
supply
Breaker size A 15
Voltage Indoor - Outdoor S1-S2 AC208 / 230V

Indoor - Outdoor S2-S3 DC 12 - 24V

Indoor - Remote controller DC 12V

NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
Operating range
Indoor intake air temperature Outdoor intake air temperature
Maximum D.B. 35°C(95°F), W.B. 21.7°C(71°F) D.B. 46°C(115°F)
Cooling
Minimum D.B. 19.4°C(67°F), W.B. 13.9°C(57°F) D.B. -10°C(14°F)
Heating Maximum D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) D.B. 24°C(75°F), W.B. 18°C(65°F)
Minimum D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) D.B. -20°C(-4°F), W.B. -21°C(-5°F)

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-6 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS

SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH


Model name Indoor unit SLZ-KA09NA.TH SLZ-KA12NA.TH SLZ-KA15NA.TH
Outdoor unit SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH
Cooling Max. Capacity Btu/h 10,900 13,300 17,700

Rated Capacity Btu/h 8,400 11,100 15,000

Min. Capacity Btu/h 3,100 3,400 3,800

Total input W 700 920 1,460

EER Btu/h 12 12 10.2

SEER Btu/h 15 15.4 16

Moisture Removal Pints/h 1.2 2.3 4.5

SHF 0.84 0.77 0.67


Heating Max. Capacity Btu/h 14,100 17,100 22,200

Rated Capacity Btu/h 10,900 13,600 18,000

Min. Capacity Btu/h 3,100 3,100 3,100

Total input W 930 1,180 1,950

COP W/W 3.44 3.38 2.71

HSPF(IV) Btu/h/W 9.6 9.6 9.6


Heating Capacity Btu/h 8,300 10,200 13,400
at low
ambient
Total input W 1,040 1,310 1,970

COP W/W 2.33 2.28 1.99


Power Phase,Cycle,Voltage 1phase, 60Hz, 208/230V
supply
Breaker size A 15
Voltage Indoor - Outdoor S1-S2 AC208 / 230V

Indoor - Outdoor S2-S3 DC 12 - 24V

Indoor - Remote controller DC 12V

NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
Operating range
Indoor intake air temperature Outdoor intake air temperature
Maximum D.B. 35°C(95°F), W.B. 21.7°C(71°F) D.B. 46°C(115°F)
Cooling
Minimum D.B. 19.4°C(67°F), W.B. 13.9°C(57°F) D.B. -10°C(14°F)
Heating Maximum D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) D.B. 24°C(75°F), W.B. 18°C(65°F)
Minimum D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) D.B. -20°C(-4°F), W.B. -21°C(-5°F)

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-7


© 2015 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS

SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH


Model name Indoor unit SLZ-KA09NA.TH SLZ-KA12NA.TH SLZ-KA15NA.TH
Outdoor unit SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH
Indoor unit MCA A 1

MOCP A 15

Fan Motor (ECM) F.L.A 0.23 0.28 0.28

Fan Motor Output W 15 20 20

CMM 8 - 9 - 10 8 - 9 - 11 8 - 9 - 11
Air flow DRY
(Lo-Mid-Hi) WET
CMM 7-8-9 7 - 8 - 10 7 - 8 - 10

CFM 280 - 320 - 350 280 - 320 - 390 280 - 320 - 390
Air flow DRY
(Lo-Mid-Hi) WET
CFM 250 - 290 - 320 250 - 290 - 350 250 - 290 - 350
dB (A)

Sound level (Lo- 29 - 32 - 38 30 - 34 - 39 31 - 35 - 40


Mid-Hi)

Dimension
Unit <Grille> W:mm 570 <650> [22-7/16 <25-19/32>]
[inch]

D:mm 570 <650> [22-7/16 <25-19/32>]


[inch]

H:mm 235 <20> [9-1/4 <25/32>]


[inch]

kg 16.5 <3>
Weight
Unit <Grille>
lbs 36 <7>
Field Drain pipe mm [inch] 32 [1-1/4]
O.D.
Remote Controller Optional parts

NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
Operating range
Indoor intake air temperature Outdoor intake air temperature
Maximum D.B. 35°C(95°F), W.B. 21.7°C(71°F) D.B. 46°C(115°F)
Cooling
Minimum D.B. 19.4°C(67°F), W.B. 13.9°C(57°F) D.B. -10°C(14°F)
Heating Maximum D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) D.B. 24°C(75°F), W.B. 18°C(65°F)
Minimum D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) D.B. -20°C(-4°F), W.B. -21°C(-5°F)

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-8 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS

SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH


Model name Indoor unit SLZ-KA09NA.TH SLZ-KA12NA.TH SLZ-KA15NA.TH
Outdoor unit SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH
Outdoor unit MCA A 12

MOCP A 15

Fan Motor (ECM) F.L.A. 0.50

Fan Motor Output W 55

Compressor KNB073FQDHC KNB092FQAHC SNB130FQBH

R.L.A. 6.6 7.4

L.R.A. 8.2 9.3

CMM 32.6 / 34.7 34.8 / 33.2 35.2 / 34.8


Air flow
(Cooling/Heating)
CFM 1,151 / 1,225 1,229 / 1,172 1,243 / 1,229

Refrigerant Control Linear Expansion Valve

Defrost Method Reverse Cycle


Sound level at dB (A) 46 49 49
cooling
Sound level at dB (A) 50 51 51
heating
External finish Ivory Munsell 3Y 7.8/1.1
Dimension W:mm 800 [31-1/2]
[inch]
D:mm 285 [11-1/4]
[inch]
H:mm 550 [21-5/8]
[inch]
Weignt kg [lbs] 30 [66] 35 [77] 36 [80]
Refrigerant Type R410A

Charge kg [lbs,oz] 0.9 [1 lb 16 oz] 1.15 [2 lb 9 oz]

Oil L [oz] 0.32 (NEO 22) [10.8] 0.45 (NEO 22) [15.2]
Refrigerant Gas side O.D. mm [inch] 9.52 [3/8] 12.7 [1/2]
pipe size
Liquid side O.D. mm [inch] 6.35 [1/4]
Refrigerant Height difference Max. 12 m [Max. 40 ft]
pipe length
Length Max. 20 m [Max. 65 ft]
Refrigerant Piping Not Supplied
Connection Method Flared

NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Rating conditions(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
Due to continuing
Operating range improvement, above specification may be subject to change without notice.
Indoor intake air temperature Outdoor intake air temperature SLZ-9
M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015Cooling
Maximum
Mitsubishi Electric US, Inc.
D.B. 35°C(95°F), W.B. 21.7°C(71°F) D.B. 46°C(115°F)
Minimum D.B. 19.4°C(67°F), W.B. 13.9°C(57°F) D.B. -10°C(14°F)
Maximum D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) D.B. 24°C(75°F), W.B. 18°C(65°F)
3-1. SPECIFICATIONS

Efficiency Ratings
COP COP Energy
Outdoor Unit Indoor Unit SEER EER HSPF
@ 47° F @ 17° F Star

SLZ CEILING-RECESSED HEAT PUMP SYSTEMS


SUZ-KA09NA SLZ-KA09NA 15.0 12.0 9.6 3.44 2.46 Yes
SUZ-KA12NA SLZ-KA12NA 15.4 12.0 9.6 3.38 2.62 Yes
SUZ-KA15NA SLZ-KA15NA 16.0 10.2 9.6 2.70 2.38 Yes

Note: Efficiency values based on AHRI 210/240 test method.

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-10 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-2. EXTERNAL DIMENSIONS

SLZ-KA09NA.TH SLZ-KD12NA.TH SLZ-KA15NA.TH Unit: mm (inch)

Detail drawing of fresh air intake


19/32~1-15/32(15~37)

Fresh air
intake
Ceiling hole
[3-15/16([100) 1(25)
[2-7/8([73.4)
20-7/8(530) 3-[1/8([2.8) Cut out hole
Burring hole
Suspension bolt pitch
Suspension bolt pitch
16-17/32(420)

22-7/16(570)
13-3/16(335)
22-11/16~24-13/32(576~620)

4-21/32(118)
120-
19/32~1-15/32(15~37)

22-7/16(570)

0-
12
1-7/32(31)
Ceiling surface

3-7/16(87)
2-7/32(56)
2-1/4(57)

7-27/32(199)
13-27/32(352)
13-3/16(335)
19/32~1-15/32(15~37) 22-11/16~24-13/32(576~620) Ceiling hole 19/32~1-15/32(15~37)

Drain pipe Wiring entry


2-19/32(66)

VP-25 connection
Refrigerant 21/32(17) 7-15/16(202) 9-1/16(230)
(O.D.[1-1/4([32))
pipe (gas) Suspension bolt M10 or W3/8
Refrigerant

7-5/32(182)
pipe (liquid)
7-19/32(193)
8-3/16(208)
9-1/4(235)
4-3/4(121)
3-21/32(93)

1-7/8(48)
1-1/2~2-9/32(38~58)

+3/16 (27 +5)

25/32(20)
Suspension bolt

Terminal block Grille


Ceiling surface
lower edge

01-1/16

Refrigerent pipe Refrigerent pipe


Models (liquid)
25-19/32(650) (gas)
1-3/8(35)

11-27/32(301)
1/4 inch 3/8 inch
Air outlet hole Brand label
SLZ-KA09NA ({ 6.35mm) ({ 9.52mm)
Grille flared connection flared connection
2-5/32(55)

V/M Drain hole 1/4 inch 3/8 inch


SLZ-KA12NA ({ 6.35mm) ({ 9.52mm)
V/M flared connection flared connection
Auto vane
1/4 inch 1/2 inch
SLZ-KA15NA ({ 6.35mm) ({ 12.7mm)
11-27/32(301)

14-27/32(377)
25-19/32(650)

Air intake hole

flared connection flared connection


Air outlet hole

V/M

V/M Air intake grille


Vane motor
14-27/32(377)
Air intake hole
1-3/8(35) 2-5/32(55)

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-11


© 2015 Mitsubishi Electric US, Inc.
SLZ-12
REQUIRED SPACE Basically open 4 inch or more
without any obstruction in front
15-3/4 Drain hole 1-5/8 and on both sides of the unit.
SUZ-KA09NA.TH

Air in

1-3/4
e
mor
. or
4 in
4 in
Air in . or
mo

13-9/16
re

12 ~ 12-3/4
11/16
3-2. EXTERNAL DIMENSIONS

SUZ-KA12NA.TH

1-9/16 14
in
Air out . or
m ore mo
re
. or
2- 3/8 13/16 Oval hole 8 in
7/8 29/32 11-1/4 17/32
Open two sides of left,
handle right, or rear side.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)


SUZ-KA15NA.TH

Due to continuing improvement, above specification may be subject to change without notice.
21-5/8
Liquid pipe :1/4 (flared)

2
Gas pipe :3/8 (flared) (KA09/12)

11-1/32
5-7/8
1/2 (flared) (KA15)
11-29/32 6-23/32

13/32
5-15/16 19-11/16
31-1/2 2-23/32
Unit: mm (inch)

© 2015 Mitsubishi Electric US, Inc.


3-3. CENTER OF GRAVITY

SLZ-KA09NA.TH 
SLZ-KD12NA.TH SLZ-KA15NA.TH




SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH

c
C

A B

a b

Unit: inch(mm)
Model name A B C a b c

SUZ-KA09NA.TH
11-1/16 5-9/16 9-1/2 31-1/2 11-1/4 21-5/8
SUZ-KA12NA.TH
(280) (140) (240) (800) (285) (550)
SUZ-KA15NA.TH

11-13/16 5-7/8 13-3/8 33-1/16 13 33-7/16


SUZ-KA18NA.TH
(300) (150) (340) (840) (330) (850)

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-13


© 2015 Mitsubishi Electric US, Inc.
3-4. ELECTRICAL WIRING DIAGRAMS

SLZ-KA09NA.TH SLZ-KD12NA.TH SLZ-KA15NA.TH


GRILLE TB4
S1
S2 TO
H2 MF OUTDOOR
DP S3 UNIT
RED 10
RED 5 M
M 1~
MV 1~
5 RED 7
MV ORN 6 1 3
5 YLW 3
ORN
MV 20 WHT 2 P.B
5 BLU 1 C1 CNSK

WHT
BRN
YLW
RED

BLU
BLK

WHT

ORN
RED
RED

RED

RED
YLW
YLW

BLU

BLU
MV I.B (RED)
5 1 3
1 3 5 7 9 WHT 1 3 RED 1 3 BLU 1 3 RED 1 3 ORN 1 3
(FAN) (D·HEATER) (D·U·M) (POWER (POWER)
FAN CNC CNP BOARD) CND BLU
CNDK DC13.1V
(CONTROL)
X1 FUSE CN3C
CN2S
(WHT)
1 2
X6 X5 X4 X7
WHT 1 BLK
(POWER
BOARD) WHT
CN2D 2
SWE
ON
OFF LED3
LED2 LED1
SW2 RED
CN2L CN24 CN105 CN30
ON GRN BLK RED
OFF (VANE) (2 PHASE) (INTAKE) 3 1
12345 2 1 2 1 5 1 CN6V
6 1 WHT CN29 CN20 WHT BLU
(DRAIN) (LIQUID) (REMOCON)
CN32 CN51 CN41 CN90 CN31 2 1 2 1 CN21 CN22
WHT
ORN
RED

YLW

BLU

<Fig: w 1>
MODELS SW2 1 3 5 1 4 1 9 1 3 1 2 1 2 1
ON

BLU
BLU
SLZ- See Fig:w 1
KA09NA OFF 5 5
12345
ON R.B
SLZ- t° t° t° t°
KA12NA OFF TB15 TB6
12345 RFI 2
DS TH5 TH1 TH2 1 1
SLZ- ON 2 2
KA15NA OFF
12345
The black square (■) indicates a switch position.

[LEGEND]
SYMBOL NAME SYMBOL NAME
P.B INDOOR POWER BOARD C1 CAPACITOR (FAN MOTOR)
I.B INDOOR CONTROLLER BOARD DP DRAIN PUMP
CN2L CONNECTOR (LOSSNAY) DS DRAIN SENSOR
CN24 CONNECTOR (BACK-UP HEATING) RFI RADIO FREQUENCY INTERFACE FOR
CN30 CONNECTOR (LLC) RF THERMOSTAT
CN32 CONNECTOR (REMOTE SWITCH) H2 DEW PREVENTION HEATER
CN41 CONNECTOR (HA TERMINAL-A) MF FAN MOTOR (WITH THERMAL FUSE)
CN51 CENTRALLY CONTROL MV VANE MOTOR
CN105 CONNECTOR (RADIO FREQUENCY INTERFACE) TB4 TERMINAL BLOCK
FUSE FUSE (T6.3AL250V) (INDOOR/OUTDOOR CONNECTING LINE)
LED1 POWER SUPPLY (I.B) TB15 TERMINAL BLOCK (REMOTE CONTROLLER
LED2 POWER SUPPLY (I.B) TRANSMISSION LINE)
LED3 TRANSMISSION (INDOOR-OUTDOOR) TH1 ROOM TEMP. THERMISTOR
SW2 SWITCH (CAPACITY CODE) (32°F / 15kΩ, 77°F / 5.4kΩ DETECT)
SWE SWITCH (EMERGENCY OPERATION) TH2 PIPE TEMP. THERMISTOR/LIQUID
X1 DRAIN PUMP/DEW PREVENTION HEATER (32°F / 15kΩ, 77°F / 5.4kΩ DETECT)
X4 RELAY (FAN MOTOR LL) TH5 COND. / EVA. TEMP. THERMISTOR
X5 RELAY (FAN MOTOR Lo) (32°F / 15kΩ, 77°F / 5.4kΩ DETECT)
X6 RELAY (FAN MOTOR Hi) OPTION PART
X7 RELAY (FAN MOTOR Me) R.B WIRED REMOTE CONTROLLER BOARD
TB6 TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)

NOTES: 1. Since the outdoor side electric wiring may change be sure to check the
outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with poIarities, make wiring
matching terminal numbers (S1, S2, S3).
3. Use copper supply wires.
4. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).

wFor details on how to operate self-diagnosis refer to the technical manuals etc.

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-14 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
SUZ-KA09NA, SUZ-KA12NA WIRING DIAGRAM

© 2015 Mitsubishi Electric US, Inc.


2 2 26H
RED BLK BLK
SUZ-KA09NA.TH

ORN L61 YLW BLK BLK BLK


BLU 21S4 1 1
YLW

CN722
2 2 H
LD70 LD66 1 3 CN721 BLK
– X63 1 2 BLK
DB65 ~ DB61 X66
+ – ~ ~ C63 C62 X64 1 1
IC802
~ + + + T801 F701 4 (OPTION PARTS)
F801 LD63 PTC64

PTC65 LD-E1 BLK


3 TR821
SUZ-KA12NA.TH

W RED 3 RED W N
MS V WHT WHT LDW F901
V IC932
3~ BLK BLK LDV TB1 CIRCUIT GROUND
CN931
3-4. ELECTRICAL WIRING DIAGRAMS

LDU U P BREAKER
MC U 1 1 1 5 L2 POWER SUPPLY
CN61 IPM 208/230V
5 LED L1 1 phase 60Hz
INVERTER P.C. BOARD 3 1 CN642 CN644 CN643 CN641 CN724
BRN

LD-S
BLU

CN932 1 21 3 1 2 1 4 1 6 From INDOOR UNIT


LD61 LD62 CONNECTING WIRE
TB2
3 RED From INDOOR UNIT
MS t° t° t° t° t° 6 S3 CONNECTING WIRES
3~ RT64 RT68 RT65 RT61 RT62 DC12-24V
M S2
MF BLU TO INDOOR UNIT
BRN S1 CONNECTING WIRES
LEV 208/230V

Due to continuing improvement, above specification may be subject to change without notice.
1 phase 60Hz
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C62,C63 SMOOTHING CAPACITOR LEV EXPANSION VALVE COIL RT68 OUTDOOR HEAT EXCHANGER NOTES:
DB61,DB65 DIODE MODULE MC COMPRESSOR TEMP. THERMISTOR. 1.About the indoor side electric
F701,F801,F901 FUSE (T3.15AL250V) MF FAN MOTOR TB1,TB2 TERMINAL BLOCK
H DEFROST HEATER(OPTION PARTS) PTC64,PTC65 CIRCUIT PROTECTION TR821 SWITCHING POWER TRANSISTOR
wiring, refer to the indoor
IC802 INTELLIGENT POWER DEVICE RT61 DEFROST THERMISTOR T801 TRANSFORMER unit electric wiring diagram
IPM,IC932 INTELLIGENT POWER MODULE RT62 DISCHARGE TEMP.THERMISTOR X63,X64,X66 RELAY for servicing.
L61 REACTOR RT64 FIN TEMP.THERMISTOR 21S4 REVERSING VALVE COIL 2.Use copper conductors only.
LED LED RT65 AMBIENT TEMP.THERMISTOR 26H HEATER PROTECTOR(OPTION PARTS) (For field wiring).

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)


SLZ-15
SLZ-16
SUZ-KA15NA WIRING DIAGRAM

2 2 26H
RED BLK BLK
ORN L61 YLW BLK BLK BLK
SUZ-KA15NA.TH

BLU 21S4 YLW 1 1


CN722
2 2 H
LD70 LD66 1 3 CN721 BLK
– X63 1 2 BLK
DB65 ~ DB61 X66
+ – ~ ~ C63 C62 C61 X64 1 1
IC802
+ + + T801 F701 4 (OPTION PARTS)
~ +
F801 LD63 PTC64

PTC65 LD-E1 BLK


3 TR821
W RED 3 RED W N
WHT LDW F901
MS V WHT V
3~ BLK BLK LDV IC932
CN931 TB1 CIRCUIT GROUND
MC U LDU U P BREAKER
1 1 1 5 L2 POWER SUPPLY
3-4. ELECTRICAL WIRING DIAGRAMS

CN61 IPM 208/230V


5 LED L1 1 phase 60Hz
INVERTER P.C. BOARD 3 1 CN642 CN644 CN643 CN641 CN724
BRN

LD-S
BLU

CN932 1 21 3 1 2 1 4 1 6 From INDOOR UNIT


LD61 LD62 CONNECTING WIRE
TB2
MS 3 RED From INDOOR UNIT
t° t° t° t° t° 6 S3 CONNECTING WIRES
3~ RT64 RT68 RT65 RT61 RT62 DC12-24V
M S2
MF BLU

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)


TO INDOOR UNIT
BRN S1 CONNECTING WIRES
LEV 208/230V
1 phase 60Hz

Due to continuing improvement, above specification may be subject to change without notice.
SYMBOL NAME SYMBOL NAME SYMBOL NAME
C61,C62,C63 SMOOTHING CAPACITOR LEV EXPANSION VALVE COIL OUTDOOR HEAT EXCHANGER NOTES:
RT68
DB61,DB65 DIODE MODULE MC COMPRESSOR TEMP. THERMISTOR. 1.About the indoor side electric
F701,F801,F901 FUSE (T3.15AL250V) MF FAN MOTOR TB1,TB2 TERMINAL BLOCK
wiring, refer to the indoor
H DEFROST HEATER(OPTION PARTS) PTC64,PTC65 CIRCUIT PROTECTION TR821 SWITCHING POWER TRANSISTOR
IC802 INTELLIGENT POWER DEVICE RT61 DEFROST THERMISTOR T801 TRANSFORMER
unit electric wiring diagram
IPM,IC932 INTELLIGENT POWER MODULE RT62 DISCHARGE TEMP.THERMISTOR X63,X64,X66 RELAY
for servicing.
L61 REACTOR RT64 FIN TEMP.THERMISTOR 21S4 REVERSING VALVE COIL 2.Use copper conductors only.
LED LED RT65 AMBIENT TEMP.THERMISTOR 26H HEATER PROTECTOR(OPTION PARTS) (For field wiring).

© 2015 Mitsubishi Electric US, Inc.


3-5. REFRIGERANT SYSTEM DIAGRAMS

SLZ-KA09NA.TH SLZ-KD12NA.TH SLZ-KA15NA.TH


Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Thermistor TH5
(Cond./Eva. temperature)

Refrigerant flow in cooling


Refrigerant flow in heating

Refrigerant LIQUID pipe connection


(Flare)
Distributor Thermistor TH2
with strainer(#50) Pipe temperature (Liquid)
Thermistor TH1
(Room temperature) Strainer(#50)

SUZ-KA09NA.TH
Refrigerant pipe ø3/8 4-way valve
(with heat insulator)
Muffler
Outdoor heat
exchanger
Stop valve temperature
(with service port) Outdoor thermistor
Muffler
Flared connection Discharge heat RT68
temperature exchanger
thermistor Service port
RT62
Compressor Ambient
Service port temperature
thermistor
RT65
Defrost
thermistor
RT61

Strainer
Capillary tube #100
Flared connection O.D. 0.118 × I.D. 0.079
× 9-7/16 LEV
(ø3.0 × ø2.0 × 240) R.V. coil
heating ON
cooling OFF
Stop valve
(with strainar)
Refrigerant pipe ø1/4 Refrigerant flow in cooling
(with heat insulator) Refrigerant flow in heating

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-17


© 2015 Mitsubishi Electric US, Inc.
3-5. REFRIGERANT SYSTEM DIAGRAMS

SUZ-KA12NA.TH SUZ-KA15NA.TH
Refrigerant pipe ø3/8 (KA12)
Refrigerant pipe ø1/2 (KA15) 4-way valve
(with heat insulator)
Muffler
Outdoor heat
exchanger
Stop valve temperature
(with service port) Outdoor thermistor
Discharge Muffler
Flared connection heat RT68
temperature exchanger
thermistor
Service port
RT62
Compressor Ambient
Service port temperature
Defrost thermistor
thermistor RT65
RT61

Capillary tube
O.D. 0.118 × I.D. 0.071
× 23-5/8
Capillary tube (ø3.0 × ø1.8 × 600) (×2) Strainer
Flared connection O.D. 0.118 × I.D. 0.079 #100
× 9-7/16 LEV
(ø3.0 × ø2.0 × 240) R.V. coil
heating ON
cooling OFF
Stop valve
(with strainar)
Refrigerant pipe ø1/4 Refrigerant flow in cooling
(with heat insulator) Refrigerant flow in heating

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-18 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE

(1) Cooling Performance Curve

For The Combination Of Outdoor Unit SUZ-KA·NA

1.4 Indoo
1.3 r inta
ke air
WB t
1.2 empe
rature
1.1 (°F)
1.0
71
0.9
67
0.8 63

1.2
r e( °F) 71
er a t u
1.1 tem p 67
ir W B 63
1.0 ake a
r i n t
Ind oo
0.9
0.8
0.7

65 75 85 95 105 115
Outdoor intake air DB temperature (°F)

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-19


© 2015 Mitsubishi Electric US, Inc.
3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE

(2) Heating Performance Curve


For The Combination Of Outdoor Unit SUZ-KA·NA

65
1.3 70
1.2 ( °F) 75
ure
1.1 e rat
temp
B
1.0 ir D
ea
0.9 ak
int
0.8 o or
Ind
0.7
0.6
0.5
0.4

1.1 75
70
1.0 65
0.9
)
0.8 ratu re (°F
DB tempe
0.7 ir
r i n t ake a
Indo o
0.6

5 15 25 35 45 55 65 70
Outdoor intake air WB temperature (°F)

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-20 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE

SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH

(1) Cooling Capacity


Indoor
Outdoor intake air DB temperature (˚F)
air
Model 75 85 95 105 115
IWB
(˚ F) TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC

71 10.3 7.3 0.62 9.6 6.8 0.68 9.0 6.4 0.74 8.4 5.9 0.77 7.7 5.5 0.81
SUZ-KA09NA 67 9.7 8.2 0.59 9.1 7.6 0.65 8.4 7.1 0.70 7.8 6.6 0.74 7.2 6.0 0.78
63 9.2 8.9 0.56 8.5 8.3 0.62 7.9 7.7 0.67 7.2 7.0 0.71 6.6 6.4 0.74
71 13.6 8.7 0.82 12.7 8.1 0.90 11.9 7.6 0.97 11.1 7.1 1.02 10.2 6.5 1.06
SUZ-KA12NA 67 12.9 9.9 0.77 12.0 9.2 0.85 11.1 8.5 0.92 10.3 7.9 0.98 9.5 7.3 1.02
63 12.1 10.9 0.74 11.2 10.1 0.81 10.4 9.4 0.88 9.5 8.6 0.94 8.7 7.8 0.98
71 18.4 9.9 1.30 17.2 9.2 1.42 16.1 8.7 1.53 15.0 8.1 1.61 13.8 7.4 1.68
SUZ-KA15NA 67 17.4 11.7 1.23 16.2 10.9 1.35 15.0 10.1 1.46 14.0 9.3 1.55 12.8 8.6 1.62
63 16.4 13.1 1.17 15.2 12.2 1.29 14.1 11.3 1.39 12.8 10.3 1.49 11.7 9.4 1.55

NOTE: 1. IWB: Intake air wet-bulb temperature


TC: Total Capacity (×103 Btu/h)
SHC: Sensible Heat Capacity (×103 Btu/h)
TPC: Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor Intake air DB temperature.

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-21


© 2015 Mitsubishi Electric US, Inc.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE

SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH

(2) Heating Capacity


Indoor
Outdoor intake air WB temperature (˚ F)
air
Model
IDB 5 15 25 35 43 45 55
(˚ F) TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
75 4.8 0.55 6.3 0.69 7.9 0.81 9.4 0.91 10.6 0.95 11.0 0.97 12.4 1.00
SUZ-KA09NA.TH 70 5.2 0.53 6.7 0.67 8.2 0.80 9.6 0.88 10.9 0.93 11.2 0.95 12.7 0.99
65 5.5 0.50 6.9 0.64 8.6 0.77 10.0 0.86 11.2 0.91 11.6 0.92 13.0 0.97
75 6.0 0.70 7.9 0.88 9.9 1.03 11.8 1.15 13.3 1.21 13.7 1.23 15.5 1.27
SUZ-KA12NA.TH 70 6.5 0.67 8.4 0.85 10.2 1.01 12.0 1.12 13.6 1.18 14.0 1.20 15.8 1.25
65 6.8 0.64 8.6 0.81 10.7 0.97 12.4 1.09 14.0 1.15 14.4 1.17 16.2 1.23
75 7.9 1.15 10.4 1.45 13.1 1.71 15.6 1.90 17.6 2.00 18.1 2.03 20.5 2.11
SUZ-KA15NA.TH 70 8.6 1.10 11.1 1.40 13.5 1.67 15.9 1.85 18.0 1.95 18.5 1.99 21.0 2.07
65 9.0 1.05 11.3 1.35 14.1 1.61 16.5 1.80 18.5 1.90 19.1 1.93 21.4 2.03

NOTE: 1. IDB: Intake air dry-bulb temperature


TC: Total Capacity (×103 Btu/h)
TPC: Total Power Consumption (kW)
2. Above data is for heating operation without any frost.

How to operate with fixed operational frequency of the compressor.


1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button
on the remote controller.

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-22 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE

(3) M-Series Cooling Correction


70 77 81 86 95 104 115
60 1.11 1.06 1.01 0.97 0.91 0.83 0.76
63 1.16 1.10 1.06 1.02 0.96 0.88 0.81
64 1.18 1.13 1.08 1.04 0.98 0.90 0.83
68 1.23 1.18 1.14 1.10 1.03 0.96 0.89
72 1.28 1.23 1.20 1.15 1.09 1.02 0.95
75 1.34 1.29 1.26 1.22 1.15 1.08 1.02
79 1.38 1.34 1.32 1.28 1.21 1.14 1.07

(4) M-Series Defrost Correction


Outdoor
intake
43 39 36 32 28 25 21 18 14
temperature
W.B. [° F]
Outdoor
intake
6 4 2 0 -2 -4 -6 -8 -10
temperature
W.B. [° C]
Correction
1.00 0.80 0.82 0.84 0.87 0.90 0.93 0.96 1.00
factor

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-23


© 2015 Mitsubishi Electric US, Inc.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE

(5) M-Series Heating Correction


Outdoor W.B. [° F]
-13 -4 5 14 23 32 41 50
Indoor
EAT DB
SUZ-KA09NA.TH 60 0.56 0.66 0.80 0.95 1.07 1.07
SUZ-KA12NA.TH 60 0.56 0.66 0.80 0.95 1.07 1.07
SUZ-KA15NA.TH 60 0.56 0.66 0.80 0.95 1.07 1.07
SUZ-KA18NA.TH 60 0.56 0.66 0.80 0.95 1.07 1.07

Interpolated Data Between 60 and 65 Indoor EAT DB data sets


SUZ-KA09NA.TH 63 0.55 0.65 0.79 0.93 1.05 1.05
SUZ-KA12NA.TH 63 0.55 0.65 0.79 0.93 1.05 1.05
SUZ-KA15NA.TH 63 0.55 0.65 0.79 0.93 1.05 1.05
SUZ-KA18NA.TH 63 0.55 0.65 0.79 0.93 1.05 1.05

SUZ-KA09NA.TH 65 0.54 0.64 0.78 0.92 1.03 1.03


SUZ-KA12NA.TH 65 0.54 0.64 0.78 0.92 1.03 1.03
SUZ-KA15NA.TH 65 0.54 0.64 0.78 0.92 1.03 1.03
SUZ-KA18NA.TH 65 0.54 0.64 0.78 0.92 1.03 1.03

SUZ-KA09NA.TH 70 0.52 0.62 0.75 0.885 1.00 1.00


SUZ-KA12NA.TH 70 0.52 0.62 0.75 0.885 1.00 1.00
SUZ-KA15NA.TH 70 0.52 0.62 0.75 0.885 1.00 1.00
SUZ-KA18NA.TH 70 0.52 0.62 0.75 0.885 1.00 1.00

SUZ-KA09NA.TH 75 0.50 0.60 0.72 0.85 0.96 0.96


SUZ-KA12NA.TH 75 0.50 0.60 0.72 0.85 0.96 0.96
SUZ-KA15NA.TH 75 0.50 0.60 0.72 0.85 0.96 0.96
SUZ-KA18NA.TH 75 0.50 0.60 0.72 0.85 0.96 0.96

SUZ-KA09NA.TH 80 0.48 0.58 0.70 0.82 0.93 0.93


SUZ-KA12NA.TH 80 0.48 0.58 0.70 0.82 0.93 0.93
SUZ-KA15NA.TH 80 0.48 0.58 0.70 0.82 0.93 0.93
SUZ-KA18NA.TH 80 0.48 0.58 0.70 0.82 0.93 0.93

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-24 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
TPC:Total Power Consumption (kW)
2. SHC is based on 80°F of indoor intake air DB temperature.

3-8. CAPACITY
COOLINGCORRECTION
M d l
Model
CAPACITY CORRECTION
R fi
Refrigerant
CURVE
t piping
i i length
l th (one
(
BYft.))REFRIGERANT PIPING LENGTH
way : ft
25(std.) 40 65 100
SUZ-KA09NA
SUZ-KA09NA.TH SUZ-KA12NA SUZ-KA12NA.TH
1.0 0.954 SUZ-KA15NA.TH
0.878 -
SUZ-KA15NA.TH
SUZ-KA15NA SUZ-KA18NA.TH
SUZ-KA18NA 1.0 0.954 0.878 0.771

1.00

0.95
Cooling capacity corrections

0.90

0.85

0.80

0.75

0.70
0 10 20 30 40 50 60 70 80 90 100 110
Refrigerant piping length (ft)

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-25


© 2015 Mitsubishi Electric US, Inc.
3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH

(1) Cooling Capacity Correction


Refrigerant piping length (one way: ft.)

25 (std.) 40 65 100

SUZ-KA09NA.TH
SUZ-KA12NA.TH 1.0 0.954 0.878 -
SUZ-KA15NA.TH

SUZ-KA18NA.TH 1.0 0.954 0.878 0.713

(2) Maximum Refrigerant Piping Length & Maximum Height Difference

Refrigerant piping: ft Piping size: in.

Gas Liquid
Model Additional Additional
piping piping
Max. length Max. height Minimum Minimum
A B Outside Outside
Wall Wall
diameter diameter
thickness thickness

SUZ-KA09NA.TH
65 40 3/8 0.0315 1/4 0.0315
SUZ-KA12NA.TH

SUZ-KA15NA.TH 65 40 1/2 0.0315 1/4 0.0315

SUZ-KA18NA.TH 100 50 1/2 0.0315 1/4 0.0315

Indoor
unit

Max. Height Additional Piping


difference Max. length
B A

Outdoor unit

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-26 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH

(3) M-Series Piping Correction Cooling


Refrigerant piping length (ft)
25(std) 40 65 100
1.000 0.954 0.878 0.771

(4) M-Series Piping Correction Heating


Refrigerant piping length (ft)
25(std) 40 65 100
1.000 0.989 0.972 0.955

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-27


© 2015 Mitsubishi Electric US, Inc.
3-10. CHARGE CALCULATIONS

(1) Additional Refrigerant Charge (R410A: oz.)


NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calcualation.

Refrigerant piping length (one way): ft.


Outdoor unit
Model
precharged
25ft 30ft 40ft 50ft 60ft 65ft

SUZ-KA09NA.TH 2 lb. 0 oz.


SUZ-KA12NA.TH 0 1.62 4.86 8.10 11.34 12.96
2 lb. 9 oz.
SUZ-KA15NA.TH

NOTE: Calculation: X oz. = 1.62/5 oz./ft (Refrigerant piping length (ft) - 25)

Refrigerant piping length (one way): ft.

Outdoor unit
Model
precharged
25ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft

SUZ-KA18NA.TH 4 lb. 0 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20

NOTE: Calculation: X oz. = 1.08/5 oz./ft (Refrigerant piping length (ft) - 25)

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-28 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-11. AIR FLOW DATA

Outlet Air Speed And Coverage


Model name SLZ-KA09NA SLZ-KA12NA SLZ-KA15NA

m3/min 10 - 9 - 8 11 - 9 - 8 11 - 9 - 8
Air flow H-M-L
CFM 350-320-280 390-320-280 390-320-280

Air speed at Hi m/sec. 3.7 4.1 4.1

Coverage range m 3.7 4.1 4.1

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-29


© 2015 Mitsubishi Electric US, Inc.
3-12. SOUND PRESSURE LEVELS

(1) Indoor Unit <60Hz>


<60Hz>
SLZ-KA09NA.TH NOTCH SPL(dB) LINE SLZ-KA12NA.TH NOTCH SPL(dB) LINE
High 38 High 39
Medium 22 Medium 40
Low 29 Low 30

90 90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)


80 80

70 70
NC-70 NC-70

60
60
NC-60
NC-60

50
50
NC-50
NC-50

40
NC-40 40
NC-40

30
NC-30 30
NC-30
20 APPROXIMATE
THRESHOLD OF
HEARING FOR 20 APPROXIMATE
CONTINUOUS
NC-20 THRESHOLD OF
HEARING FOR
NOISE
CONTINUOUS
NC-20
10 NOISE
63 125 250 500 1000 2000 4000 8000
10
BAND CENTER FREQUENCIES, Hz 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz

<60Hz>
SLZ-KA15NA.TH NOTCH SPL(dB) LINE
High 40
Medium 35
Low 31

90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)

80 UNIT

70 CEILING
NC-70

60
NC-60

50
NC-50
5 ft
40
NC-40

30
NC-30 MICROPHONE
20 APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NC-20
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz

NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops.
The sound may be bigger than the indicated level in actual use due to surrounding echoes.
The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation.

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-30 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
OCTAVE BAND SOUND PRESSU

OCTAVE BAND SOUND PRESSU


NC-50 NC-50

40 40

3-12. SOUND PRESSURE LEVELS


NC-40 NC-40

30 30
NC-30 NC-30

(2) Outdoor
OUTDOOR Unit
UNIT
OUTDOOR UNIT 20 APPROXIMATE
THRESHOLD OF
20 APPROXIMATE
THRESHOLD OF
SUZ-KA09NA.TH
SUZ-KA09NA.TH
HEARINGSPL(dB(A))
FUNCTION
FUNCTION
FOR
SPL(dB(A))
CONTINUOUS
LINE
LINE
SUZ-KA12NA.TH
SUZ-KA12NA.TH NC-20 HEARINGSPL(dB(A))
FUNCTION
FUNCTION
FOR
SPL(dB(A))
CONTINUOUS
LINE
LINE
NC-20

NOISE
COOLING 46 NOISE
COOLING 49
10COOLING 46 10COOLING 49
63
HEATING 12550 250 500 1000 2000 4000 8000 63
HEATING 12551 250 500 1000 2000 4000 8000
HEATING 50 HEATING 51
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
90 90
90 90

SUZ-KA15NA.TH FUNCTION SPL(dB(A)) LINE SUZ-KA18NA.TH FUNCTION SPL(dB(A)) LINE


bar)

bar)
80 80
0.0002bar)

0.0002bar)
80 COOLING 49 80 COOLING 54
HEATING 51
0.0002

0.0002
HEATING 56
70 70
70 70
==

==
90 NC-70 NC-70
90
dB

dB
NC-70 NC-70
dB

dB
(0(0

(0(0
dB

dB
60 60
dB

dB
60 60
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
LEVEL,

LEVEL,
80

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)


NC-60 80 NC-60
LEVEL,

LEVEL,
NC-60 NC-60

50 50
PRESSURE

PRESSURE
50 50
PRESSURE

PRESSURE
70 NC-50 70 NC-50
NC-50 NC-70 NC-50 NC-70

40 40
40 40
SOUND

SOUND
60 NC-40 60 NC-40
SOUND

SOUND
NC-40 NC-40
NC-60 NC-60
BAND

BAND
30 30
BAND

BAND
30 50 30
NC-30 50 NC-30
NC-30 NC-30
NC-50
OCTAVE

OCTAVE
NC-50
OCTAVE

OCTAVE
APPROXIMATE APPROXIMATE
20 APPROXIMATE 20 APPROXIMATE
20 THRESHOLD OF
40 20 THRESHOLD OF
THRESHOLD
HEARING FOROF THRESHOLD
HEARING FOROF 40
NC-20 NC-20
HEARING FOR
CONTINUOUS NC-20 HEARING FOR
CONTINUOUS
NC-40 NC-20
CONTINUOUS CONTINUOUS NC-40
NOISE NOISE
10 NOISE 10 NOISE
10 63 125 250 30500 1000 2000 4000 8000 10 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000 63 125 250 30
500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz NC-30 BAND CENTER FREQUENCIES, Hz NC-30
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
APPROXIMATE
20 20 APPROXIMATE
THRESHOLD OF
SUZ-KA15NA.TH
THRESHOLD OF

SUZ-KA15NA.TH
HEARINGSPL(dB(A))
FUNCTION
FUNCTION
FOR
SPL(dB(A))
CONTINUOUS
LINE
LINE SUZ-KA18NA.TH
SUZ-KA18NA.TH
NC-20 HEARINGSPL(dB(A))
FUNCTION
FUNCTION
FOR
SPL(dB(A))
CONTINUOUS
LINE
LINE
NC-20
NOISE
COOLING 49 NOISE
10COOLING 49 COOLING 54
10COOLING 54
63
HEATING 12551 250 500 1000 2000 4000 8000 63 12556 250 500 1000 2000 4000 8000
HEATING 51 HEATING
BAND CENTER FREQUENCIES, Hz HEATING 56
BAND CENTER FREQUENCIES, Hz
90
90 OUTDOOR
90
90 UNIT

1m
bar)

80
bar)

80
0.0002bar)

80
0.0002bar)

80
MICROPHONE
0.0002

0.0002

70 70
70
==

NC-70 70
==

NC-70
dB

NC-70
dB

NC-70
dB

dB
(0(0

(0(0
dB

60
dB

60
dB

60
dB

60
LEVEL,

LEVEL,

NC-60 NC-60
LEVEL,

LEVEL,

NC-60 NC-60

50
PRESSURE

50
PRESSURE

50
PRESSURE

50
PRESSURE

NC-50 NC-50
NC-50 NC-50

40 40
40
SOUND

40
SOUND

NC-40
SOUND

NC-40
SOUND

NC-40 NC-40
BAND

30
BAND

30
BAND

30
BAND

NC-30 30
NC-30 NC-30
NC-30
OCTAVE

OCTAVE
OCTAVE

OCTAVE

APPROXIMATE
20 APPROXIMATE 20 APPROXIMATE
20 THRESHOLD OF
20 APPROXIMATE
THRESHOLD OF
THRESHOLD
HEARING FOROF THRESHOLD
HEARING FOR
NC-20 HEARING FOROF NC-20
CONTINUOUS NC-20 HEARING FOR
CONTINUOUS NC-20
CONTINUOUS
NOISE CONTINUOUS
NOISE
10 NOISE
10 NOISE
10 63 125 250 500 1000 2000 4000 8000 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
OUTDOOR
OUTDOOR UNIT
UNIT
1m
1m
MICROPHONE
MICROPHONE

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-31


© 2015 Mitsubishi Electric US, Inc.
3-13. STANDARD OPERATION RANGE

Rating Guaranteed Voltage

208/230V
Outdoor unit 60Hz Min. 187V 208V 230V Max. 253V
1 Phase

Intake Air Temperature Indoor Outdoor


Mode
Condition DB (°F) WB (°F) DB (°F) WB (°F)

Standard temperature 80 67 95 —

Maximum temperature 90 73 115 —


Cooling
Minimum temperature 67 57 14 —

Maximum humidity 78% —

Standard temperature 70 60 47 43

Heating Maximum temperature 80 67 75 65

Minimum temperature 70 60 6 5

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-32 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES

(1) Indoor Unit


Part Number Descriptions Applicable model

C13-103 Blue Diamond Sensor Extension Cable - 15 Ft.          

Relay Kit for external heater adapter connects to CN24 on


CN24RELAY-KIT-CM3
indoor control board

Portable Central Controller (PCC) - controls up to 16


DPLS1
RedLINK Zones - requires an MHK1 on each indoor unit

System Control Interface - MA, Contact terminal, and


MAC-333IF-E M-NET Control Adapter, Supplemental heat and humidifier
adaptor

Portable Central Controller (PCC) - controls up to 16


MCCH1
RedLINK Zones - requires an MHK1 on each indoor unit

Wireless wall-mounted remote controller (MRCH1) with a


MHK1
signal receiver (MIFH1) and cable (MRC1) all in one kit

All Models
Outdoor Air Sensor - reads both outside temperature and
MOS1
humidity displayed on MRCH1 and MCCH1 if installed

PAC-715AD Wire for Remote on/off with CN32 connector

Connector and wire for Operation status/error, booster fan


PAC-725AD
control for fresh air using CN51

PAC-SE41TS-E Remote temperature sensor for indoor units

Remote Operation Adapter with wire terminals for remote


PAC-SF40RM-E
on/off and operation status/error

PAR-FA32MA Wireless Signal Receiver used with PAR-FL32MA

PAR-FL32MA Wireless Remote Controller used with PAR-FA32MA

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-33


© 2015 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES

(1) Indoor Unit (cont.)


Part Number Descriptions Applicable model

PAC-YT53CRAU Simple MA Remote Controller

Wall mounted, hard wired, multi-functional controller: used


PAR-31MAA specifically for grouping (up to 16 units), twinning, lead/lag,
and 7 day programmable applications

Lockdown Bracket for wireless, hand-held, remote


RCMKP1CB
controllers
All Models

SI30-115 Mini-Condensation pump - 115 volt application

SI30-230 Mini-Condensation pump - 230 volt application

3-Pole Disconnect Switch 30 Amps 600 volts rated for


TAZ-MS303 interupting power supply at/near indoor unit - fits 2 X 4 utility
box

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-34 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)
© 2015 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES

(1) Indoor Unit (cont.)


Part Number Descriptions Applicable model

MLS143812T-15 1/4 x 3/8 x 15' / 1/2" Twin-Tube Insulation

MLS143812T-30 1/4 x 3/8 x 30' / 1/2" Twin-Tube Insulation

KA09,12

MLS143812T-50 1/4 x 3/8 x 50' / 1/2" Twin-Tube Insulation

MLS143812T-65 1/4 x 3/8 x 65' / 1/2" Twin-Tube Insulation

Diamondback
MLS141212T-15 1/4 x 1/2 x 15' / 1/2" Twin-Tube Insulation
Linesets

MLS141212T-30 1/4 x 1/2 x 30' / 1/2" Twin-Tube Insulation

MLS141212T-50 1/4 x 1/2 x 50' / 1/2" Twin-Tube Insulation KA15

MLS141212T-65 1/4 x 1/2 x 65' / 1/2" Twin-Tube Insulation

MLS141212T-100 1/4 x 1/2 x 100' / 1/2" Twin-Tube Insulation

Due to continuing improvement, above specification may be subject to change without notice.

M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015) SLZ-35


© 2015 Mitsubishi Electric US, Inc.
3-14. ACCESSORIES

(2) Outdoor Unit


Part Number Descriptions Applicable model

4 piece ( 1 pair) condensing unit wall mounting brackets -


CWMB1
painted steel
All Models

DSD-400P Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic

MAC-640BH-U Outdoor Unit Drain Pan Heater used during defrost cycle KA09,12,15

MAC-641BH-U Outdoor Unit Drain Pan Heater used during defrost cycle KA18

ULTRILITE1 Condensing Unit Mounting Pad 16” x 36” x 3” All Models

Due to continuing improvement, above specification may be subject to change without notice.
SLZ-36 M-Series - SLZ Ceiling-Recessed Heat Pump Systems (March 2015)