Вы находитесь на странице: 1из 1

1.

4 Introduction and Specifications


Models, Options, and Accessories

Table 1.1 Voltage Input Options

Option (71) Option (72) Option (73) Option (74) Option (75/76)
Voltage Input Options a b c d
SELECT 3AVI SELECT 5AVI SELECT 5AVI SELECT 3 AVI/4 AFDI SELECT 5 AVI/1 ACI e

Under- and overvoltage elements x x x x x


(27, 59)
Voltage based frequency x x x x x
measurement and tracking
Over-, underfrequency elements (81) x x x x x
Power factor elements (55) x x x x x
Loss of potential element (60LOP) x x x x x
Real, reactive, apparent power, and x x x x x
power factor metering
Energy metering x x x x x
Synchronism-check elements x x x
including under- and overvoltage
elements (25, 27S, 59S)
Station dc battery voltage monitor x x x
Demand and peak demand metering x x x
Residual overvoltage element (59G) x x x
Negative-sequence overvoltage x x x
element (59Q)
Rate-of-change-of-frequency x x x
element (81R)
Fast rate-of-change-of-frequency x x x
element (81RF), Aurora mitigation
Power elements (32) x x x
4-channel optical arc-flash sensor x
inputs with continuous self-testing
(AFD)
Arc-flash protection elements x
(50PAF, 50NAF)
Residual current (IG) CT-based x
residual overcurrent elements
(50G, 51G)
a
Voltage Options.
b
With Monitoring Package.
c
With Monitoring and Advanced Metering and Protection Packages.
d
With 4-channel Arc-Flash Detector Inputs and Protection.
e
SELECT 5AVI/1 ACI with Residual Ground CT Input.

Accessories Contact your Technical Service Center or the SEL factory for additional detail
and ordering information for the following accessories:
➤ External RTD protection
➢ SEL-2600 RTD Module (with ST® option only)
➢ A simplex 62.5/125 µm fiber-optic cable with ST
connector for connecting the external RTD module to
the SEL-751A
➤ Remote I/O with SEL-2505 Remote I/O Module SEL-2812
compatible (ST option only)

SEL-751A Relay Instruction Manual Date Code 20131025