Installation 2.

19
Rear-Panel Connections

Ethernet Port
You can order the SEL-751A with an optional single/dual 10/100BASE-T or
100BASE-FX Ethernet port. Connect to PORT 1 of the device by using a
standard RJ-45 connector for the copper port and an LC connector for the
fiber-optic port.

Fiber-Optic Serial Port


The optional fiber-optic serial port is compatible with the SEL-2812 (with
IRIG-B) or the SEL-2814 Fiber-Optic Transceivers and the SEL-2600 RTD
Module.

I/O Diagram A more functional representation of two of the control (I/O) connections is
shown in Figure 2.13 and Figure 2.14.

As Many as Four
Analog Outputs Fiber-Optic Cable
NOTE: All digital inputs External to SEL-2600 series
and digital outputs Contacts + +
(including high-current,
high-speed hybrid)
connections are polarity A01 A10 A12 A07 A05 A03 D01 D02 D07 D08
neutral. + — + —
+/H AO401 AO404 TX RX
OUT103

OUT102

OUT101
IN102
IN101

PS SEL-751A Relay
–/N AI401 AI404 IRIG-B
+ — + —
A02 A11 A08 A09 A06 A04 D09 D10 D15 D16 B01 B02

+ + +IRIG-B

As Many as Four –IRIG-B


Analog Inputs

Figure 2.13 Control I/O Connections—4 AI/4 AO Option in Slot D and Fiber-Optic Port in Slot B

As Many as Ten
RTD Inputs

NOTE: All RTD Comp/


RTD01 RTD10
Shield terminals are
internally connected to External
the relay chassis and Contacts
ground.

A01 A10 A12 A07 A05 A03 D01 D02 D03 D28 D29 D30
+ — COMP/ + — COMP/
+/H SHLD SHLD
OUT103

OUT102

OUT101
IN102
IN101

PS SEL-751A Relay
–/N IRIG-B
A02 A11 A08 A09 A06 A04 B01 B02

+IRIG-B
–IRIG-B
Figure 2.14 Control I/O Connections—Internal RTD Option

Date Code 20131025 Instruction Manual SEL-751A Relay