Longitudinal Section
1341
1340
Elevation
1339
1338
1337
1336
1335
0 20 40 60 80 100
Floor Level Water Surface 120Column X 140
Distance (m)
Design Criteria
Assumptions
i) Design is based on Colebrook-White equation with 'k s' of 0.155mm for concrete pipes
ii). If calculated velocity is within the limits, then the flow is compared to the actual flow. If Flow calcul
Otherwise the next bigger pipe size is selected and V and Q calculated again. If it meets the requirement
V= -2(2gdi)1/2.Log10[k/(3.7d) + 2.51v/{d(2gdi)1/2}]
Q= -6.96d2(di)1/2.Log10[k/(3.7d) + 7.4E-7/d(di)1/2]
LINE MANHOLE
Drain 2 IN OUT
(Cukverts) MH. A1 MH.A2 0.334 0.8 26 3.1% 0.03076923 0.450
MH.A2 MH.A3 0.334 0.8 26 3.1% 0.03076923 0.450
(-)2*(2*g*d*i)^0.5 k/3.7d (2.51*v)/ log((k/ V (m/s) Check V Pipe capacity l/s Remarks.
(d*(2g*d*i) (3.7*d)+ (0.75<V>3. (m3/s) Q=VA,
^0.5) ((2.51*v)/ 5) A=3.14d^2/4
(d*(2*g*d*i
)^0.5)))
-1.04242 0.00009 1.0734E-05 -3.9837 4.153 4.153 0.6607 661 Adopt 450mm pipe
-1.04242 0.00009 1.0734E-05 -3.9837 4.153 4.153 0.6607 661 Adopt 450mm pipe
Ok
Ok
DESIGN CALCULATIONS
Detail Pages
Locality
Functional System
Number
1 Calulations are produced with any system as required, i.e. spreadsheet, by hand, by other software.
2 All calculations should have this cover sheet completed.
3 When calulations are complete a hard copy should be produced.
4 The checker shall check the calulations and sign the hard copy with a red pen.
5 The checked calulations shall be scanned and sent to the document controller.
Please refer to Design Management and Document Control Procedures for additional information.