100%(1)100% нашли этот документ полезным (1 голос)
1K просмотров2 страницы
This document discusses changes to criteria for hot water pipe lengths and delays in obtaining hot water at fixtures. It notes that the previous maximum length of 100 feet for uninsulated pipes has been changed due to concerns about water and energy waste. The new allowable distances represent a tradeoff between energy costs and insulation. Delays of 0-10 seconds are considered acceptable, 11-30 seconds marginal, and over 31 seconds unacceptable. The document recommends a maximum distance of 25 feet between the hot water source and fixtures to meet these time criteria.
Исходное описание:
Оригинальное название
ASPE-Domestic Water Heating Design Manual 2013.pdf
This document discusses changes to criteria for hot water pipe lengths and delays in obtaining hot water at fixtures. It notes that the previous maximum length of 100 feet for uninsulated pipes has been changed due to concerns about water and energy waste. The new allowable distances represent a tradeoff between energy costs and insulation. Delays of 0-10 seconds are considered acceptable, 11-30 seconds marginal, and over 31 seconds unacceptable. The document recommends a maximum distance of 25 feet between the hot water source and fixtures to meet these time criteria.
This document discusses changes to criteria for hot water pipe lengths and delays in obtaining hot water at fixtures. It notes that the previous maximum length of 100 feet for uninsulated pipes has been changed due to concerns about water and energy waste. The new allowable distances represent a tradeoff between energy costs and insulation. Delays of 0-10 seconds are considered acceptable, 11-30 seconds marginal, and over 31 seconds unacceptable. The document recommends a maximum distance of 25 feet between the hot water source and fixtures to meet these time criteria.
234 Domestic Water Heating Design Manual, Second Edition
Water
be circulated. However, this recommendation is subjective, and,
unfortunately, some engineers and contractors use the 100-ft (30.48-m) criterion as the maximum length for all uncirculated, uninsulated, dead-end hot water branches to fixtures in order to cut the cost of hot water distribution piping. These long, uninsulated, dead-end branches to fixtures create considerable problems, such as a lack of hot water at fixtures, inadequately sized water heater assemblies, and thermal temperature escala- tion in showers. The 100-ft (30.48-m) length criterion was developed in 1973 after the Middle East oil embargo, when energy costs were the paramount concern and water conservation was given little con- sideration. Since the circulation of hot water causes a loss of energy due to radiation and convection in the circulated system and such energy losses have to be continually replaced by water heaters, the engineering community compromised between energy loss and construction costs and developed the 100-ft (30.48-m) maximum length criterion.
LENGTH AND TIME CRITERIA
Recently, due to concern about not only energy conservation but also the extreme water shortages in parts of the country, the 100- ft (30.48-m) length criteria has changed. Water wastage caused by the long delay in obtaining hot water at fixtures has become as critical an issue as the energy losses caused by hot water tem- perature maintenance systems. To reduce the wasting of cooled hot water significantly, the engineering community has reevalu- ated the permissible distances for uncirculated, dead-end branches to periodically used plumbing fixtures. The new allowable distances for uncirculated, dead-end branches represent a trade-off between the energy utilized by the hot water maintenance system and the cost of the insulation, on the one hand, and the cost of energy to heat the excess cold water makeup, the cost of wasted potable water, and extra sewer surcharges, on the other hand. Further- more, engineers should be aware that various codes now limit the length between the hot water maintenance system and plumbing fixtures. They also should be aware of the potential for liability if an owner questions the adequacy of their hot water system de- sign. What are reasonable delays in obtaining hot water at a fix- ture? For anything beside very infrequently used fixtures (such as those in industrial facilities or certain fixtures in office bu buildings), a delay of 0 to 10 sec is normally considered acceptable ffor most Recirculating Domestic Hot Water Systems Water 235
residential occupancies and public fixtures in office buildings. A
delay of 11 to 30 sec is marginal but possibly acceptable, and a time delay longer than 31 sec is normally considered unaccept- able and a significant waste of water and energy. Therefore, when designing hot water systems, it is prudent for the designer to provide some means of getting hot water to the fixtures within these acceptable time limits. Normally this means that there should be a maximum distance of approximately 25 ft (7.6 m) between the hot water maintenance system and each of the plumb- ing fixtures requiring hot water, the distance depending on the water flow rate of the plumbing fixture at the end of the line and the size of the line. (See Tables 14.1, 14.2, and 14.3.) The plumb- ing designer may want to stay under this length limitation because the actual installation in the field may differ slightly from the engineer's design, and additional delays may be caused by either the routing of the pipe or other problems. Furthermore, with the low fixture discharge rates now mandated by national and local laws, it takes considerably longer to obtain hot water from non- temperature maintained hot water lines than it did in the past, when fixtures had greater flow rates. For example, a public lava- tory with a 0.50 or 0.25 gpm (0.03 or 0.02 L/sec) maximum discharge rate would take an excessive amount of time to obtain hot water from 100 ft (30.48 m) of uncirculated, uninsulated hot water piping. (See Table 14.3.) This table gives conservative ap- proximations of the amount of time it takes to obtain hot water at a fixture. The times are based on the size of the line, the fix- ture flow rate, and the times required to replace the cooled off hot water, to heat the pipe, and to offset the convection energy lost by the insulated hot water line.
Table 14.1 Water Contents and Weight of Tube or
Piping per Linear Foot Copper Copper Steel Pipe CPVC Pipe Nominal Pipe Pipe Schedule Schedule Diameter Type L Type M 40 40 Water Wgt. Water Wgt. Water Wgt. Water Wgt. (in.)a (gal/ft) (lb/ft) (gal/ft) (lb/ft) (gal/ft) (lb/ft) (gal/ft) (lb/ft) ½ 0.012 0.285 0.013 0.204 0.016 0.860 0.016 0.210 ¾ 0.025 0.445 0.027 0.328 0.028 1.140 0.028 0.290 1 0.043 0.655 0.045 0.465 0.045 1.680 0.045 0.420 1¼ 0.065 0.884 0.068 0.682 0.077 2.280 0.078 0.590 1½ 0.093 1.14 0.100 0.940 0.106 2.720 0.106 0.710 aPipe sizes are indicated for mild steel pipe sizing.