Вы находитесь на странице: 1из 1

10/25/18 Stenstrom-Schneider, Inc.

Page 17 of 28

Commercial Electric Water Heater

ASME Energy Saver Models Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed

Model Capacity A B C D E F Water Approx.


Number Height Jacket Height Floor to Floor to Floor to Conn. Shipping
Dia. to T&P Hot Water Cold Water Top of Weight
Max. Conn. Outlet Inlet Control Box
U.S. Imp. kW
Gal. Gal. Input in. in. in. in. in. in. in. lbs.
6A-kW-3 6 5 3 171/4 16 181/16 181/4 61/4 17 3/4 83
12A-kW-3 12 10 9 28 16 2815/16 29 61/4 28 3/4 118
20A-kW-3 20 17 18 271/2 20 28 281/2 61/4 27 3/4 145
30A-kW-3 30 25 36 38 20 401/4 39 61/4 38 3/4 180
40A-kW-3 40 33 36 481/4 20 501/2 491/4 61/4 38 3/4 220
50A-kW-3 50 42 81 473/4 24 503/8 491/4 6 461/2 11/2 270
80A-kW-3 80 67 81 601/4 26 617/8 613/4 6 461/2 11/2 335
120A-kW-3 119 100 81 641/2 301/4 665/16 66 6 501/4 11/2 430

Model Capacity A B C D E F Water Approx.


Number Height Jacket Height Floor to Floor to Floor to Conn. Shipping
Dia. to T&P Hot Water Cold Water Top of Weight
Max. Conn. Outlet Inlet Control Box
kW
Liters Input mm. mm. mm. mm. mm. mm. mm. kg.
6A-kW-3 23 3 438 406 459 464 159 432 19 38
12A-kW-3 45 9 711 406 735 737 159 711 19 54
20A-kW-3 76 18 699 508 711 724 159 686 19 66
30A-kW-3 114 36 965 508 1022 991 159 965 19 82
40A-kW-3 152 36 1226 508 1283 1251 159 965 19 100
50A-kW-3 190 81 1213 610 1280 1251 152 1181 38 123
80A-kW-3 303 81 1530 661 1570 1569 152 1181 38 152
120A-kW-3 451 81 1638 766 1681 1676 152 1276 38 195

Voltage and phase must be specified when ordering. Example: 80A-18-3, 240 Volt, 3 phase.

Number of Elements (Fused Models)* Full Load Current Amperes (Fused Models)*
208V 240V 277V 380V 415V 480V 600V 208V 240V 277V 380V 400V 415V 480V 600V
Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase Phase
Input Input
kW 1 3 1 3 1 3 3 1 3 3 kW 1 3 1 3 1 3 3 3 1 3 3
3 1 1 1 1 1 1 1 1 1 1 3 14 14 13 13 11 5 8 N/A 6 6 2.8
6 3 3 3 3 3 3 3 3 3 3 6 29(2) 17 25(2) 14 22(2) 9 9 8 13(2) 7 6
9 3 3 3 3 3 3 3 3 3 3 9 43 25 38 22 33 14 13 13 19 11 9
12 3 3 3 3 3 3 3 3 3 3 12 58 33 50 29 43(2) 18 17 17 25(2) 14 12
13.5 3 3 3 3 3 3 3 3 3 3 13.5 65 37 56 32 49 21 20 19 28 16 13
15 3 3 3 3 3 3 3 3 3 3 15 72 42 63 36 54 23 22 21 31 18 14
18 3 3 3 3 3 3 3 3 3 3 18 87 50 75 43 65 27 26 25 38 22 17
24 4 6 4 6 4 6 4 4 6 6 24 115 67 100 58 87 36 35 33 50 29 23
27 6 6 6 6 6 6 6 6 6 6 27 130 75 113 65 97 41 39 38 56 32 26
30 6 6 6 6 6 6 6 6 6 6 30 144 83 125 72 108 46 43 42 63 36 29
36 6 6 6 6 6 6 6 6 6 6 36 173 100 150 87 130 55 52 50 75 43 35
45 9 9 9 9 9 9 9 9 9 9 45 216 125 188 108 163 68 65 63 94 54 43
54 9 9 9 9 9 9 9 9 9 9 54 260 150 225 130 195 82 78 75 113 65 52
81 9 9 9 9 9 9 9 9 9 9 81 389 225 338 195 292 123 117 113 169 97 78
Units with amperage draw of 48 amps or more require factory installed internal fusing. *If the number of elements on non-fused models is
different, it is located in parentheses ( ), following the amp draw.

Recovery
GPH Temperature Rise °F
kW Input 40 50 60 70 80 90 100 120 140
3 31 25 21 18 16 14 12 10 9
6 62 50 41 35 31 28 25 21 18
9 93 74 62 53 47 42 37 31 27
12 124 99 83 71 62 55 50 41 35
13.5 140 112 93 80 70 62 56 47 40
15 155 124 103 89 78 69 62 52 44
18 186 149 124 106 93 83 74 62 53
24 248 199 164 142 124 110 99 83 71
27 279 223 186 160 140 124 112 93 80
30 310 248 207 177 155 138 124 103 89
36 372 298 248 213 186 165 149 124 106
45 465 372 310 266 233 207 186 155 133
54 558 447 372 319 279 248 223 186 160
81 852 671 558 477 418 371 334 278 238

SSI Job # 18222 Lush- Valley Fair By: RC