Академический Документы
Профессиональный Документы
Культура Документы
Jason Byerly
American Electric Power
1
AEP IEC-61850 History
Hard-Fiber
B95 Bus 1&2
Patch Panel
T60-T3
Hard-Fiber
Cables
F60-30
F60-9
F60-8
F60-7
F60-6
5
Roberts Continued
• AEP Protection Engineers were able to build confidence in
the digital signals supplied to the brick from the relays. All
oscillography data confirmed in service hard wired
protection system trips to be 1 – 2 ms faster
6
1st All Fiber P&C Substation - Flag City
• Distribution substation protected and controlled
entirely by fiber-optic technology
7
Flag City
• Planning and Engineering
2015/2016
• Service planned
December, 2016
8
Flag City
9
Flag City
10
Feeder Circuit Breaker
11
Feeder Protection
12
Feeder Protection
13
Feeder Cables
14
Feeder Bricks – Remote I/O 1
15
Feeder Brick – Remote I/O 2
16
Feeder Relay – GE UR F60
17
Network
• LAN consist of two Ethernet switches for failover redundancy
18
Factory Testing
• Factory tested at MEPPI the GE Bricks in May
• Wiring check
19
Flag City DICM Pictures
20
Next Steps
• September – DICM and switchyard equipment will be
installed and powered up
• Plug and work – Install fiber patch cables between
switchyard and DICM Fiber Splice Cabinet
• Re-test relays – Similar to Systems Control visit, relays
will be tested with GE Bricks
• In-service 12/1/2016
• New project at Roberts station
• Install SEL TiDL to validate technology
• Consideration for second relay system for
Transmission applications (Redundancy)
21
Roberts Sys2 – SEL TiDL
• Like 2013 GE Hard Fiber project, AEP must
validate SEL TiDL by installing and
monitoring performance
• Installation shall be completed by end of 2016
• TiDL will provide AEP transmission a
redundant and independent point-to-point
system to replicate existing relay standards
22
Simplicity of Pt-to-Pt Architecture
Time-Domain Link (TiDL) Technology
Direct Fiber
Direct Fiber
Direct Fiber
23
Digital Substations Using TiDL
24
What Is TiDL?
Time-Domain Link Technology
25
Discussion
Questions?
26