2 Update Information
Update Information
Contents
Update Information 1
General ................................................................................................................ 2
Remarks to the Document ....................................................................... 2
Working steps ......................................................................................... 2
Languages ........................................................................................................... 3
Update CEMAT V8.0 to CEMAT V8.2 .................................................................. 4
Requirements .......................................................................................... 4
Save Project data .................................................................................... 5
Modified/new functions ............................................................................ 5
Migration to PCS 7 V8.2 .......................................................................... 5
Installation of CEMAT V8.2 ..................................................................... 5
Update of S7 Program ............................................................................. 6
Update of the OS-Projects..................................................................... 10
Compile and Download.......................................................................... 13
Update CEMAT V8.0 SP1 to CEMAT V8.2......................................................... 14
Requirements ........................................................................................ 14
Save Project data .................................................................................. 15
Modified/new functions .......................................................................... 15
Migration to PCS 7 V8.2 ........................................................................ 15
Installation of CEMAT V8.2 ................................................................... 15
Update of S7 Program ........................................................................... 16
Update of the OS-Projects..................................................................... 20
Compile and Download.......................................................................... 22
Update CEMAT V8.1 to CEMAT V8.2 ................................................................ 23
Requirements ........................................................................................ 23
Save Project data .................................................................................. 24
Modified/new functions .......................................................................... 24
Migration to PCS 7 V8.2 ........................................................................ 24
Installation of CEMAT V8.2 ................................................................... 24
Update of S7 Program ........................................................................... 25
Update of the OS-Projects..................................................................... 29
Compile and Download.......................................................................... 31
General
This document will help you to upgrade Cemat Projects of an older Version into the actual
PCS 7 and Cemat Version. The document only describes the steps required for Cemat,
regarding PCS 7 Update we like to refer to the corresponding PCS 7 Manual.
For the Cemat Update we assume that the Cemat engineering rules have been followed. If
your project contains additional functions and own applications, you have to consider these in
addition.
At this point we would like to refer to the document readme_V82.pdf, which you find on the
Cemat Installation-DVD. There you find detailed information about the modifications from
Version to Version.
We also like to refer to the Cemat Documentation. This you find in the Intranet and after the
Cemat Installation the documents are available online on your PC.
Working steps
Each upgrade basically consists of the following steps:
- Check Hardware- and Software Requirements
- Save the project data
- For saving the PCS 7 Multiproject use the SIMATIC Manager
- For saving the User Archives use Export Function
- For saving the Modifications in the CEMAT_CS Configuration copy the folders Config,
Multimedia und Sounds.
- Check for changes/new Functions in the readme_V82.pdf and in the Cemat Object
descriptions.
- Upgrade the PCS 7 Project to PCS 7 V8.2.
- Installation of Cemat V8.2
- Adaptations in the Config files
- Update of the S7 Programs (Master data Library and AS)
- Update of the OS-Projects
- Compile and Download
Languages
The blocks of the APL Library use the following standard languages:
- German (Germany)
- English (US)
- French (France)
- Italian (Italy) *)
- Spanish (Spain, international sort)
For this reason the CEMAT blocks (messages) are provided with the same languages.
Requirements
Before the installation of Cemat V8.2, you have to upgrade your PC Stations to the permitted
Windows Operating System and to PCS 7 V8.2.
The following Windows Operating Systems are supported by PCS 7 V8.2, but not all versions
are compatible with each Configuration.
- Windows 7 Professional SP1 (64-Bit, only English Windows Language Version)
(permitted for ES, non-red. OS-Single Station, OS-Client, Web-Client)
- Windows 7 Ultimate/Enterprise SP1 (32-Bit)
(permitted for OS-Client and Web-Client)
- Windows 7 Ultimate / Enterprise SP1 (64-Bit)
(permitted for ES, OS-Single Station, OS-Client, Web-Server (only on ES or OS-Single)
and Web-Client)
- Windows 10 Enterprise 2015 LTSB (64-Bit)
(permitted for OS-Client and Web-Client)
- Windows Server 2008 R2 SP1 Standard Edition (64-Bit)
(permitted for ES, OS-Single Station, OS-Server, OS-Client, Web-Server, Web-Client)
- Windows Server 2012 R2 Update Standard Edition (64-Bit)
(permitted for OS-Single Station, OS-Server, OS-Client, Web-Server, Web-Client
Further details about the installation of the operating system and PCS 7 are explained in the
PCS 7 manuals and in the readme and therefore not part of this description.
Caution: For CEMAT V8.2 the following Updates for PCS 7 are essential:
! - AS-OS Eng. V8.3 Update 1
- CFC V8.2 Update 2
Make sure that the PCS 7 updates are installed before updating to CEMT V8.2!
Caution: The update to CEMAT V8.2 requires a complete reloading of the PLC and
! consequently cannot be carried out while the plant is running.
Follow the actual Manual "PCS 7 Software Update with utilization of the new functions" from
the PCS 7 V8.2 Documentation. The following description refers to this manual.
Please also pay attention to the hints for the OS-Migration. In order to maintain the runtime
data (curves and messages), the Server Projects have to be migrated on the Server-PCs
directly.
Consider also the project rules from the CEMAT manual 03_PCS7_Project_009.pdf,
“Installation of a PCS 7 Project” and the Cemat Object descriptions.
Modified/new functions
The modified/new functions are listed in file readme_V82.pdf on the CEMAT Installation-
DVD.
The Migration of the OS Project is carried out automatically when you open the OS Project
the first time with PCS 7 V8.2
After the installation, for all PC stations (ES, OS SINGLE STATION, OS SERVER and OS
CLIENT) the following steps have to be carried out:
1. The config files contain the default settings, which means if you changed them for your
project you have to make this adaptations again. (C_Config.cfg)
Also consider the settings in file C_Messages.cfg.
2. Probably you also added for your project some files under 'Multimedia', 'Sounds' ….
After the CEMAT installation these files can be restored from the backup directories and
copied into the new additional CEMAT_CS\MULTIMEDIA directories.
Update of S7 Program
Please also consider the instructions in the PCS 7 Service Manual "PCS 7 - Software
Update with utilization of the new functions“.
C_DAMPER:
Feature bit 20 and 23 are not used any more
OS Permision 9 is not used any more
C_GROUP, C_ROUTE
Feature bit 18 and 23 are not used any more
OS Permision 9 is not used any more
Additional Feature bits and OS Permissions are set to default values and must be
enabled if the function is needed. See Object description.
7. The Simulation rights for C_DAMPER and C_VALVE are no longer defined at parameter
OoSModOn.
The Simulation rights for C_DAMPER can be defined as follows.
Enable Simulation of position 1 is linked to FbkPos1 (default right = 24)
Enable Simulation of position 2 is linked to FbkPos2 (default right = 24)
The Simulation rights for C_VALVE can be defined as follows.
Simulation of active position is linked to FbkPos1 (default right = 24)
Simulation of idle position is linked to FbkPos2 (default right = 24)
Retain the last command if faulty is linked to ContOn (default right = 24)
CEMAT Update
After the CEMAT installation, the D:\CEMAT_CS\WinCC directory contains the current
version of the global scripts and the system pictures. These must be transferred to the
WinCC project.
Under OS Project Sub Directories you find the Subfolders which get copied during the
Press button 'Update OS Project' and the files will be copied to the corresponding
directories.
6. Open the WinCC project.
7. Open 'Global Script', ‘C_Editor’ and regenerate the header. (Menu/Options/Regenerate
Header)
8. Cemat needs a number of internal variables in the Tag Management. Via WinCC
Configuration Studio the variables can be imported from file Import_InternalTags.xlsx
which you find under D:\CEMAT_CS\IMPORT.
Message blocks and Message configuration can be imported via WinCC configuration
Studio for Alarm Logging from already prepared Excel files Import_MessageBlocks.xlsx
and Import_MessageConfiguration.xlsx which you find under D:\CEMAT_CS\IMPORT.
For updating the Message blocks regarding name, flashing and field size use function
Edit Import, then browse to D:\CEMAT_CS\IMPORT, select Excel Workbook
Import_MessageBlocks.xlsx and press Button Import.
Further information you will find in the Engineering Manual 03_PCS7_Project under
Alarm logging.
10. During the update procedure the following GraCS files are overwritten by Cemat files.
These are:
@AlarmEmergency.pdl Extended Alarm line
@AlarmEmergencyOP.pdl Extended Alarm line
@AlarmOneLine.pdl Alarm line
@Buttons11.pdl Button keys1
@Buttons12.pdl Button keys 2
@Language.pdl Language Selection
@Overview1.pdl Overview Range
@TopAlarmNew.pdl Alarm lines
@PG_Intlk02_Standard.pdl Interlock faceplate
@PG_Intlk04_Standard.pdl Interlock faceplate
@PG_Intlk08_Standard.pdl Interlock faceplate
@PG_Intlk16_Screen2.pdl Interlock faceplate
@PG_Intlk16_Standard.pdl Interlock faceplate
@IM153_1N.bmp Bitmap
@apl_bi_automatic.empf APL Bitmap
For Single User Stations and for OS Clients this is correct. For OS Servers the OS
Project Editor must be started again, because in this case the standard pictures delivered
with PCS 7 have to be used (the Server has no Visualization). Please select the above
listed Pictures in order to be overwritten and confirm with OK.
For all other Station types the files have to be deselected if you run the OS Project Editor
again.
Caution: The files @TopAlarmNew.pdl and @Overview1.pdl cannot be deselected and
must therefore be copied again after running the OS Project Editor.
(Start the program D:\CEMAT_CS\CematProjectUpdate.exe; the button “Res” copies the
CEMAT “resolutions” pictures to the destination again).
11. During the Update of the OS-Project new template pictures
C_@PCS7Typicals_CemV82_001.pdl (or C_@PCS7Typicals_CemV82_001_004.pdl
have been copied to the GraCS folder. Most of the block icons in the new template
pictures are scalable and the drive and annunciation block icons have an additional
Attribute “PictureDirectory” for the references to a subfolder in GraCS.
This simplifies the exchange of symbols if different representation is needed.
Note: Compared to the former template picture the new block icons in template picture
C_@PCS7Typicals_CemV82_001.pdl are different in shape (square format), color
definitions, and the representation of “Out of Service” mode. Some of the former index
numbers have been removed because of duplicated representations with different size.
The new block icons in template picture C_@PCS7Typicals_CemV82_001_004.pdl
are scalable and the font size for drives and annunciation block has been increased to
12.
- Open the WinCC Configuration Studio for the User Archive and delete Archive
C_DriveList.
- In order to import the new structure use function Edit Import, then browse to
D:\CEMAT_CS\IMPORT, select Excel Workbook Import_UserArchives.xlsx and press
Button Import.
Requirements
Before the installation of Cemat V8.2, you have to upgrade your PC Stations to the permitted
Windows Operating System and to PCS 7 V8.2.
The following Windows Operating Systems are supported by PCS 7 V8.2, but not all versions
are compatible with each Configuration.
- Windows 7 Professional SP1 (64-Bit, only English Windows Language Version)
(permitted for ES, non-red. OS-Single Station, OS-Client, Web-Client)
- Windows 7 Ultimate/Enterprise SP1 (32-Bit)
(permitted for OS-Client and Web-Client)
- Windows 7 Ultimate / Enterprise SP1 (64-Bit)
(permitted for ES, OS-Single Station, OS-Client, Web-Server (only on ES or OS-Single)
and Web-Client)
- Windows 10 Enterprise 2015 LTSB (64-Bit)
(permitted for OS-Client and Web-Client)
- Windows Server 2008 R2 SP1 Standard Edition (64-Bit)
(permitted for ES, OS-Single Station, OS-Server, OS-Client, Web-Server, Web-Client)
- Windows Server 2012 R2 Update Standard Edition (64-Bit)
(permitted for OS-Single Station, OS-Server, OS-Client, Web-Server, Web-Client
Further details about the installation of the operating system and PCS 7 are explained in the
PCS 7 manuals and in the readme and therefore not part of this description.
Caution: For CEMAT V8.2 the following Updates for PCS 7 are essential:
! - AS-OS Eng. V8.3 Update 1
- CFC V8.2 Update 2
Make sure that the PCS 7 updates are installed before updating to CEMT V8.2!
Caution: The update to CEMAT V8.2 requires a complete reloading of the PLC and
! consequently cannot be carried out while the plant is running.
Follow the actual Manual "PCS 7 Software Update with utilization of the new functions" from
the PCS 7 V8.2 Documentation. The following description refers to this manual.
Please also pay attention to the hints for the OS-Migration. In order to maintain the runtime
data (curves and messages), the Server Projects have to be migrated on the Server-PCs
directly.
Consider also the project rules from the CEMAT manual 03_PCS7_Project_009.pdf,
“Installation of a PCS 7 Project” and the Cemat Object descriptions.
Modified/new functions
The modified/new functions are listed in file readme_V82.pdf on the CEMAT Installation-
DVD.
The Migration of the OS Project is carried out automatically when you open the OS Project
the first time with PCS 7 V8.2
After the installation, for all PC stations (ES, OS SINGLE STATION, OS SERVER and OS
CLIENT) the following steps have to be carried out:
1. The config files contain the default settings, which means if you changed them for your
project you have to make this adaptations again. (C_Config.cfg)
Also consider the settings in file C_Messages.cfg.
2. Probably you also added for your project some files under 'Multimedia', 'Sounds' ….
After the CEMAT installation these files can be restored from the backup directories and
copied into the new additional CEMAT_CS\MULTIMEDIA directories.
Update of S7 Program
Please also consider the instructions in the PCS 7 Service Manual "PCS 7 - Software
Update with utilization of the new functions“.
C_DAMPER:
Feature bit 20 and 23 are not used any more
OS Permission 9 is not used any more
C_GROUP, C_ROUTE
Feature bit 18 and 23 are not used any more
OS Permission 9 is not used any more
Additional Feature bits and OS Permissions are set to default values and must be
enabled if the function is needed. See Object description.
6. The Simulation rights for C_DAMPER and C_VALVE are no longer defined at parameter
OoSModOn.
The Simulation rights for C_DAMPER can be defined as follows.
Enable Simulation of position 1 is linked to FbkPos1 (default right = 24)
Enable Simulation of position 2 is linked to FbkPos2 (default right = 24)
The Simulation rights for C_VALVE can be defined as follows.
Simulation of active position is linked to FbkPos1 (default right = 24)
Simulation of idle position is linked to FbkPos2 (default right = 24)
Retain the last command if faulty is linked to ContOn (default right = 24)
CEMAT Update
After the CEMAT installation, the D:\CEMAT_CS\WinCC directory contains the current
version of the global scripts and the system pictures. These must be transferred to the
WinCC project.
Under OS Project Sub Directories you find the Subfolders which get copied during the
Press button 'Update OS Project' and the files will be copied to the corresponding
directories.
6. Open the WinCC project.
7. Open 'Global Script', ‘C_Editor’ and regenerate the header. (Menu/Options/Regenerate
Header)
8. During the Update of the OS Project the settings in the Alarm logging have been
changed to the default settings of PCS 7 which need to be corrected for Cemat regarding
color definitions and acknowledgement/flashing behavior.
Message blocks and Message configuration can be imported in the WinCC configuration
Studio from already prepared Excel files Import_MessageBlocks.xlsx and
Import_MessageConfiguration.xlsx which you find under D:\CEMAT_CS\IMPORT.
For updating the Message blocks regarding name, flashing and field size use function
Edit Import, then browse to D:\CEMAT_CS\IMPORT, select Excel Workbook
Import_MessageBlocks.xlsx and press Button Import.
Further information you will find in the Engineering Manual 03_PCS7_Project under
Alarm logging.
9. During the update procedure the following GraCS files are overwritten by Cemat files.
These are:
@AlarmEmergency.pdl Extended Alarm line
@AlarmEmergencyOP.pdl Extended Alarm line
@AlarmOneLine.pdl Alarm line
@Buttons11.pdl Button keys1
@Buttons12.pdl Button keys 2
@Language.pdl Language Selection
@Overview1.pdl Overview Range
@TopAlarmNew.pdl Alarm lines
@PG_Intlk02_Standard.pdl Interlock faceplate
@PG_Intlk04_Standard.pdl Interlock faceplate
@PG_Intlk08_Standard.pdl Interlock faceplate
@PG_Intlk16_Screen2.pdl Interlock faceplate
@PG_Intlk16_Standard.pdl Interlock faceplate
@IM153_1N.bmp Bitmap
@apl_bi_automatic.empf APL Bitmap
@apl_bi_forced.emf APL Bitmap
@apl_bi_local.emf APL Bitmap
@apl_bi_manual.emf APL Bitmap
@apl_bi_on.emf APL Bitmap
@apl_bi_out_of_service.emf APL Bitmap
@Connections.emf Bitmap
@CONTROLLER.emf Bitmap
@CPU.emf Bitmap
For Single User Stations and for OS Clients this is correct. For OS Servers the OS
Project Editor must be started again, because in this case the standard pictures delivered
with PCS 7 have to be used (the Server has no Visualization). Please select the above
listed Pictures in order to be overwritten and confirm with OK.
For all other Station types the files have to be deselected if you run the OS Project Editor
again.
Caution: The files @TopAlarmNew.pdl and @Overview1.pdl cannot be deselected and
must therefore be copied again after running the OS Project Editor.
(Start the program D:\CEMAT_CS\CematProjectUpdate.exe; the button “Res” copies the
CEMAT “resolutions” pictures to the destination again).
10. During the Update of the OS-Project new template pictures
C_@PCS7Typicals_CemV82_001.pdl (or C_@PCS7Typicals_CemV82_001_004.pdl
have been copied to the GraCS folder. Most of the block icons in the new template
pictures are scalable and the drive and annunciation block icons have an additional
Attribute “PictureDirectory” for the references to a subfolder in GraCS.
This simplifies the exchange of symbols if different representation is needed.
Note: Compared to the former template picture the new block icons in template picture
C_@PCS7Typicals_CemV82_001.pdl are different in shape (square format), color
definitions, and the representation of “Out of Service” mode. Some of the former index
numbers have been removed because of duplicated representations with different size.
The new block icons in template picture C_@PCS7Typicals_CemV82_001_004.pdl
are scalable and the font size for drives and annunciation block has been increased to
12.
Requirements
Before the installation of Cemat V8.2, you have to upgrade your PC Stations to the permitted
Windows Operating System and to PCS 7 V8.2.
The following Windows Operating Systems are supported by PCS 7 V8.2, but not all versions
are compatible with each Configuration.
- Windows 7 Professional SP1 (64-Bit, only English Windows Language Version)
(permitted for ES, non-red. OS-Single Station, OS-Client, Web-Client)
- Windows 7 Ultimate/Enterprise SP1 (32-Bit)
(permitted for OS-Client and Web-Client)
- Windows 7 Ultimate / Enterprise SP1 (64-Bit)
(permitted for ES, OS-Single Station, OS-Client, Web-Server (only on ES or OS-Single)
and Web-Client)
- Windows 10 Enterprise 2015 LTSB (64-Bit)
(permitted for OS-Client and Web-Client)
- Windows Server 2008 R2 SP1 Standard Edition (64-Bit)
(permitted for ES, OS-Single Station, OS-Server, OS-Client, Web-Server, Web-Client)
- Windows Server 2012 R2 Update Standard Edition (64-Bit)
(permitted for OS-Single Station, OS-Server, OS-Client, Web-Server, Web-Client
Further details about the installation of the operating system and PCS 7 are explained in the
PCS 7 manuals and in the readme and therefore not part of this description.
Caution: For CEMAT V8.2 the following Updates for PCS 7 are essential:
! - AS-OS Eng. V8.3 Update 1
- CFC V8.2 Update 2
Make sure that the PCS 7 updates are installed before updating to CEMT V8.2!
Caution: The update to CEMAT V8.2 requires a complete reloading of the PLC and
! consequently cannot be carried out while the plant is running.
Follow the actual Manual "PCS 7 Software Update with utilization of the new functions" from
the PCS 7 V8.2 Documentation. The following description refers to this manual.
Please also pay attention to the hints for the OS-Migration. In order to maintain the runtime
data (curves and messages), the Server Projects have to be migrated on the Server-PCs
directly.
Consider also the project rules from the CEMAT manual 03_PCS7_Project_009.pdf,
“Installation of a PCS 7 Project” and the Cemat Object descriptions.
Modified/new functions
The modified/new functions are listed in file readme_V82.pdf on the CEMAT Installation-
DVD.
The Migration of the OS Project is carried out automatically when you open the OS Project
the first time with PCS 7 V8.2
After the installation, for all PC stations (ES, OS SINGLE STATION, OS SERVER and OS
CLIENT) the following steps have to be carried out:
1. The config files contain the default settings, which means if you changed them for your
project you have to make this adaptations again. (C_Config.cfg)
Also consider the settings in file C_Messages.cfg.
2. Probably you also added for your project some files under 'Multimedia', 'Sounds' ….
After the CEMAT installation these files can be restored from the backup directories and
copied into the new additional CEMAT_CS\MULTIMEDIA directories.
Update of S7 Program
Please also consider the instructions in the PCS 7 Service Manual "PCS 7 - Software
Update with utilization of the new functions“.
Additional Feature bits and OS Permissions are set to default values and must be
enabled if the function is needed. See Object description.
6. The Simulation rights for C_DAMPER and C_VALVE are no longer defined at parameter
OoSModOn.
The Simulation rights for C_DAMPER can be defined as follows.
Enable Simulation of position 1 is linked to FbkPos1 (default right = 24)
Enable Simulation of position 2 is linked to FbkPos2 (default right = 24)
The Simulation rights for C_VALVE can be defined as follows.
Simulation of active position is linked to FbkPos1 (default right = 24)
Simulation of idle position is linked to FbkPos2 (default right = 24)
Retain the last command if faulty is linked to ContOn (default right = 24)
7. Calculation for MV_Perc has been changed:
The percentage value MV_Perc of C_MEASUR is no longer calculated based on the
High limit of C_MEASUR.
Now two options for the calculation exist:
- If Feature bit 6 = FALSE the percentage value MV_Perc is calculated based on
PV_OpSca (Scale high value/ Scale Low value).
- If Feature bit 6 = TRUE the percentage value MV_Perc is calculated based on the
values
PercHigh and PercLow (new block parameters).
8. In the new version the size of the blocks may be different from the version before. This
may lead to overlapping in the CFC. Eventually it is necessary to move some of the
blocks in the CFC.
9. At this time you should also check,
- if all blocks (e. g. with Author BASISxx, TECHNxx, CHNxx or DRIVERxx, etc) are
actualized.
- that no S7-300 blocks (Author ELEM_300) are used (these blocks are not usable for
S7-400 and lead to sporadic faults!).
10. Make use of the CEMAT Check Tool “CematCheckTool.exe”. With this tool you can
check the correct runtime sequence the Group/Object interconnections and if the Feature
bit settings and OS Permissions are consistent.
For further details refer the CEMAT manual „10_Checkliste_009.pdf“.
Carry out the same steps for all S7 Program folders of your Multiproject.
CEMAT Update
After the CEMAT installation, the D:\CEMAT_CS\WinCC directory contains the current
version of the global scripts and the system pictures. These must be transferred to the
WinCC project.
Under OS Project Sub Directories you find the Subfolders which get copied during the
Press button 'Update OS Project' and the files will be copied to the corresponding
directories.
6. Open the WinCC project.
7. Open 'Global Script', ‘C_Editor’ and regenerate the header. (Menu/Options/Regenerate
Header)
8. During the Update of the OS Project the settings in the Alarm logging have been
changed to the default settings of PCS 7 which need to be corrected for Cemat regarding
color definitions and acknowledgement/flashing behavior.
Message blocks and Message configuration can be imported in the WinCC configuration
Studio from already prepared Excel files Import_MessageBlocks.xlsx and
Import_MessageConfiguration.xlsx which you find under D:\CEMAT_CS\IMPORT.
For updating the Message blocks regarding name, flashing and field size use function
Edit Import, then browse to D:\CEMAT_CS\IMPORT, select Excel Workbook
Import_MessageBlocks.xlsx and press Button Import.
Further information you will find in the Engineering Manual 03_PCS7_Project under
Alarm logging.
9. During the update procedure the following GraCS files are overwritten by Cemat files.
These are:
@AlarmEmergency.pdl Extended Alarm line
@AlarmEmergencyOP.pdl Extended Alarm line
@AlarmOneLine.pdl Alarm line
@Buttons11.pdl Button keys1
@Buttons12.pdl Button keys 2
@Language.pdl Language Selection
@Overview1.pdl Overview Range
@TopAlarmNew.pdl Alarm lines
@PG_Intlk02_Standard.pdl Interlock faceplate
@PG_Intlk04_Standard.pdl Interlock faceplate
@PG_Intlk08_Standard.pdl Interlock faceplate
@PG_Intlk16_Screen2.pdl Interlock faceplate
@PG_Intlk16_Standard.pdl Interlock faceplate
@IM153_1N.bmp Bitmap
@apl_bi_automatic.empf APL Bitmap
@apl_bi_forced.emf APL Bitmap
@apl_bi_local.emf APL Bitmap
@apl_bi_manual.emf APL Bitmap
@apl_bi_on.emf APL Bitmap
@apl_bi_out_of_service.emf APL Bitmap
@Connections.emf Bitmap
@CONTROLLER.emf Bitmap
@CPU.emf Bitmap
For Single User Stations and for OS Clients this is correct. For OS Servers the OS
Project Editor must be started again, because in this case the standard pictures delivered
with PCS 7 have to be used (the Server has no Visualization). Please select the above
listed Pictures in order to be overwritten and confirm with OK.
For all other Station types the files have to be deselected if you run the OS Project Editor
again.
Caution: The files @TopAlarmNew.pdl and @Overview1.pdl cannot be deselected and
must therefore be copied again after running the OS Project Editor.
(Start the program D:\CEMAT_CS\CematProjectUpdate.exe; the button “Res” copies the
CEMAT “resolutions” pictures to the destination again).
10. During the Update of the OS-Project new template pictures
C_@PCS7Typicals_CemV82_001.pdl (or C_@PCS7Typicals_CemV82_001_004.pdl
have been copied to the GraCS folder. Most of the block icons in the new template
pictures are scalable and the drive and annunciation block icons have an additional
Attribute “PictureDirectory” for the references to a subfolder in GraCS.
This simplifies the exchange of symbols if different representation is needed.
Note: Compared to the former template picture the new block icons in template picture
C_@PCS7Typicals_CemV82_001.pdl are different in shape (square format), color
definitions, and the representation of “Out of Service” mode. Some of the former index
numbers have been removed because of duplicated representations with different size.
The new block icons in template picture C_@PCS7Typicals_CemV82_001_004.pdl
are scalable and the font size for drives and annunciation block has been increased to
12.