Вы находитесь на странице: 1из 2

®

DSEGenset

DSE7310/20 ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY

AUTO START & AUTO MAINS FAILURE BS EN 61000-6-2


EMC Generic Immunity Standard for
the Industrial Environment
CONTROL MODULES BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment

The DSE7310 is an Auto Start The DSE7320 will also monitor the The extensive list of features includes TEMPERATURE
Control Module and the DSE7320 is mains (utility) supply. The modules enhanced event and performance BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
an Auto Mains (Utility) Failure Control include USB, RS232 and RS485 monitoring, remote communications BS EN 60068-2-2
Module suitable for a wide variety of ports as well as dedicated DSENet® and dual mutual standby (DSE7310 Bb/Be Dry Heat +70 oC
single, diesel or gas, terminals for system expansion. only) to reduce engine wear. VIBRATION
gen-set applications. BS EN 60068-2-6
Both modules are compatible with The modules can be easily Ten sweeps in each of three
major axes
Monitoring an extensive number of electronic (CAN) and non-electronic configured using the DSE 5 Hz to 8 Hz @ +/-7.5 mm,
engine parameters, the modules will (magnetic pick-up/alternator sensing) Configuration Suite PC software. 8 Hz to 500 Hz @ 2 gn
display warnings, shutdown and engines and offer an extensive Selected front panel editing is also HUMIDITY
engine status information on the number of flexible inputs, outputs available. BS EN 60068-2-30
back-lit LCD screen, illuminated and extensive engine protections so Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
LEDs, remote PC and via SMS text the system can be easily adapted to BS EN 60068-2-78
alerts (with external modem). meet the most demanding industry Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
requirements.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
COMPREHENSIVE FEATURE LIST TO SUIT A control panel with the supplied sealing gasket.

WIDE VARIETY OF GEN-SET APPLICATIONS


MODEM MODBUS PC
DSE2130
DSE2157
DSE2548 8 4 4
DSE2510/20
232 485

®
DSENET RS232 AND USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT INPUTS SENDERS STOP SUPPLY 8-35V

DEUTZ
DSE7310/20 ISUZU
PERKINS
CATERPILLAR
7 MTU
VOLVO
OTHER
CUMMINS
SCANIA

MAINS (UTILITY) N/C VOLT FREE N/O VOLT GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
SENSING OUTPUT FREE OUTPUT ALTERNATOR OUTPUTS ENGINES &
DSE7320 ONLY (Flexible with CAN) MAGNETIC PICK-UP

VOLTS CURRENT VOLTS


D+
W/L +

1ph 1 1 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E N
N

ISSUE 6
®

DSEGenset

DSE7310/20 SPECIFICATION

DC SUPPLY

AUTO START & AUTO MAINS FAILURE CONTINUOUS VOLTAGE RATING


8 V to 35 V Continuous

CONTROL MODULES CRANKING DROPOUTS


Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
FEATURES DSE7320 supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


DSE7310 340 mA at 12 V, 160 mA at 24 V

MAXIMUM STANDBY CURRENT


160 mA at 12 V, 80 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

MAINS (UTILITY) DSE7320 ONLY


VOLTAGE RANGE
15 V - 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage
KEY FEATURES • Manual fuel pump control • Additional display screens to help
• 4-Line back-lit LCD text display • Engine exerciser with modem diagnostics OUTPUTS C & D
• Five key menu navigation • “Protections disabled” feature • DSENet® expansion compatible 8 A 250 V (Volt free)
• Front panel editing with PIN • kW overload protection
AUXILIARY OUTPUTS E,F,G,H
protection • Power monitoring (kW h, kV Ar, KEY BENEFITS 2 A DC at supply voltage
• LED and LCD alarm indication kV A h, kV Ar h) • 132 x 64 pixel ratio display for
GENERATOR
• Customisable status screens • Load switching (load shedding clarity
VOLTAGE RANGE
• Power save mode and dummy load outputs) • Real-time clock provides 15 V - 333 V AC (L-N)
• Support for up to three remote • Automatic load transfer (DSE7320) accurate event logging
FREQUENCY RANGE
display units • Unbalanced load protection • Multiple date and time scheduler
3.5 Hz to 75 Hz
• 9 configurable inputs • Independent Earth Fault trip • Set maintenance periods can be
• 8 configurable outputs • True dual mutual standby with configured to maintain optimum MAGNETIC PICK UP
VOLTAGE RANGE
• Flexible sender inputs load balancing timer (DSE7310 engine performance
+/- 0.5 V to 70 V
• Configurable timers and alarms only) • Ethernet communications (via
• 3 configurable maintenance alarms • USB connectivity DSE860/865 modules), provides FREQUENCY RANGE
10,000 Hz (max)
• Multiple date and time scheduler • Backed up real time clock advanced remote monitoring at
• Configurable event log (250) • Fully configurable via DSE low cost DIMENSIONS
• Control logic facilities Configuration Suite PC software • Modules can be integrated into OVERALL
240 mm x 181 mm x 42 mm
• Easy access diagnostic page • Configurable display languages building management systems
9.4” x 7.1” x 1.6”
• CAN and Magnetic Pick-up/Alt. • Remote SCADA monitoring via (BMS)
sensing DSE Configuration Suite PC • Increased input and output PANEL CUT-OUT
220 mm x 160 mm
• Fuel usage monitor and low fuel software expansion capability via DSENet®
8.7” x 6.3”
alarms • User selectable RS232 and • Licence-free PC software
• Charge alternator failure alarm RS485 communications • IP65 rating (with supplied gasket) MAXIMUM PANEL THICKNESS
8 mm
• Manual speed control (on • SMS Messaging (additional offers increased resistance to
0.3”
compatible CAN engines) external modem required) water ingress

RELATED MATERIALS
TITLE PART NO’S
DSE7310 Installation Instructions 053-028
DSE7320 Installation Instructions 053-029
DSE7200/7300 Quick Start Guide 057-101
DSE7200/7300 Operator Manual 057-074
DSE7200/7300 Configuration Suite PC Manual 057-077

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-051/08/10 (6) US
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457

Вам также может понравиться