Вы находитесь на странице: 1из 7

IX International Symposium on

Lightning Protection
26th-30th November 2007 – Foz do Iguaçu, Brazil

LIGHTNING CURRENT ARRESTER TECHNOLOGIES –


COMPARISON OF SPARK-GAP- AND MOV-TECHNOLOGY

Dipl.-Ing. Holger Heckler Dr.-Ing. Martin Wetter


PHOENIX CONTACT GmbH & Co. KG, Germany PHOENIX CONTACT GmbH & Co. KG, Germany
hheckler@phoenixcontact.com mwetter@phoenixcontact.com

Prof. Dr.-Ing. Klaus Scheibe Dipl.-Ing. Joachim Schimanski


University of Applied Sciences, Kiel, Germany PHOENIX CONTACT GmbH & Co. KG, Germany
klaus.scheibe@fh-kiel.de jschimanski@phoenixcontact.com

Dr.-Ing. Martin Wetter, Flachsmarktstraße 8, D – 32825 Blomberg Germany

Abstract – Surge protective devices (SPDs) are classified The reason for this efficiency in protection is the relative
according to IEC 61643-1. Depending on the discharge low impedance of spark gaps during the discharge of
capability SPDs are classified as lightning current arresters lightning currents. During the discharge, when a spark
(Class I), surge voltage arresters (Class II) or device gap has become fully conductive, the arc-burning voltage
protection (Class III).
is usually in the range between U = 100V...500 V.
Up to now in most cases spark-gap based Class I SPDs have Varistor-based SPDs behave totally different.
been used for the protection against full-grown lightning
strikes. Class I spark gaps can lead through lightning SPD with varistor:
currents up to Iimp = 100 kA (10/350 μs). Due to • The residual voltage stays nearly during the
improvements in MOV technology varistor-based SPDs are whole duration of a surge current at a high level.
nowadays able to lead through lightning currents up to
Iimp = 25 kA (10/350 μs) – even with a relative low protection SPD with spark gap:
level. Nowadays varistor-based Class I SPDs compete with
• During the short amount of time in which the
spark-gap-based Class I SPDs
space between the main electrodes of a spark gap
This paper discusses spark-gap- and varistor-technology has not been fully ionized, the residual voltage
with the help of measurements taken in the laboratory. The stays at a high level.
advantages and disadvantages of both technologies are • As soon as the space between the main
discussed having in mind real-world power supply systems electrodes gets fully ionized – and therefore
and end devices which shall be protected efficiently by SPDs. becomes low-impedant – the residual voltage
Also an arrester combination, consisting of a Class I spark drops immediately to voltage levels of
gap and a Class II varistor, has been tested. This report not
U < 500 V.
only describes the general operating behavior of spark gaps
and varistors, it discusses as well the energetic coordination
of multi-stage SPDs. Lightning current capability, line- Because of the low course of the residual voltage with
follow current, protection level and prospective lifetime are spark-gap-based SPDs, the amount of energy which is
some of the compared parameters. converted to heat inside spark gaps is much lower than
the amount of energy which is converted to heat inside a
1 INTRODUCTION varistor-based SPD.

The usage of powerful Class I lightning-current arresters 2 DISCHARGE CAPABILITY


with spark gaps is nowadays very common. The robust
design of SPDs with spark-gaps allows the discharge of For the simulation of powerful real-world lightning
full-grown lightning currents of the waveshape 10/350 µs strikes and the test of Class I SPDs, surge currents with
multiple times without damaging or degrading a surge the waveshape 10/350 µs are used. The 10/350 µs surge
protective device. At the same time sensitive electronic current emulates the first strike of a lightning current. The
devices are efficiently protected, even during high-energy technical parameters of 10/350 µs surge-current impulses
surge currents with amplitudes up to 100 kA (10/350 µs).
– e. g. waveshape and charge – are specified in IEC more sensitive electronic devices are used. A protection
62305-4. level of 4 kV is in most cases not acceptable for sensitive
electronic devices.

To achieve lower protection levels for end devices in


power supply systems the classical approach has been a
combination of different surge protective devices:
• Class I SPD: untriggered spark gap (1st stage of
protection)
• Decoupling element for coordination of SPDs:
certain length of wire or additional decoupling coil
• Class II SPD: varistor (2nd stage of protection)

This combination of arresters made it possible to reduce


surges to voltage levels below 2.5 kV or even 1.5 kV. The
Fig. 1 – Surge-current test impulses usage of a certain length of wire or additional decoupling
coils works well with fast-rising surge currents. Fast-
According to IEC 60364-5-53, the minimum discharge rising surge currents cause a voltage drop via the
capability for lightning-current arresters is Iimp = 12.5 kA terminals of a decoupling coil (or length of wire) –
(10/350 µs) for four-wire power supply systems. The because of the inductance of a conductor (coil, wire, etc.).
calculated discharge current to fulfill the requirements of The voltage drop via the terminals of the decoupling coil
the Lightning Protection Class I is – according to IEC plus the voltage drop via the Class II varistor has to be
62305-1 – an expected cumulative current of Iimp = high enough to trigger a Class I spark gap (untriggered).
100 kA (10/350 µs) in buildings. Therefore in four-wire This works pretty well for fast-rising surges.
systems, without any other conductive parts, an SPD has Unfortunately for slow-rising surges the voltage drop via
to be able to lead through at least Iimp = 25 kA (10/350 µs) a decoupling coil is relatively low – sometimes too low to
surge-current impulses, otherwise the requirements of ignite an untriggered spark gap. An untriggered Class I
Lightning Protection Class I are not fulfilled. spark gap (1st stage of protection) therefore may not
become conductive during the discharge of a slow-rising
According to the standards Class II SPDs are tested with high-energy lightning current. In this case a Class II
medium-energy or low-energy surge currents of the varistor (2nd stage of protection) may be overloaded by
waveshape 8/20 µs. The 8/20 µs surge current emulates high-energy surge currents. This non-triggering of spark
surge currents which are generated by switching action in gaps is called “blind spot behavior”. To address this
electrical installations or by partial lightning currents. problem electronically triggered spark gaps have been
invented. Electronically triggered spark gaps for
Electric charge Q of surge-current impulses: 230/400 V AC power supply systems have been
• Surge-current impulse 10/350 µs (25 kA): 12.5 C introduced first in 1998 by Phoenix Contact. The ignition
• Surge-current impulse 8/20 µs (25 kA): 0.5 C of electronically triggered spark gaps is voltage-
dependent and no longer depends on the rise time of a
On the condition that surge currents do have the same surge current. State-of-the-art Class I spark gaps are able
amplitude – the electric charge of an 10/350 µs surge to reach protection levels below Up = 1.5 kV – and this
current is about 25 times higher than the charge of an even with high-amplitude surge currents. Having
8/20 µs surge current. The difference in electric charge protection levels below Up = 1.5 kV let’s assume that
can be calculated by mathematical means. Another way to these SPDs provide a good protection for downstream
determine the difference in electric charge is to compare power supply systems and sensitive electronic equipment.
the areas below the 10/350 µs curve and the 8/20 µs
curve. If the protection level of a modern Class I SPD is already
so low, does it make sense to use - additional to Class I
3 PROTECTION LEVEL SPDs – as well Class II SPDs? A closer look at the
characteristic curves of the residual voltages of the
In the beginnings of electrical engineering electrical following types of SPDs gives us some guidance:
devices have been relatively robust regarding surge • Class II varistor
voltages. For robust electrical devices a protection level • Class I spark gap combined with Class II varistor
of Up = 4 kV in 230/400 V AC power supply systems is
often sufficient. Class I spark gaps without trigger
electronics have therefore in past been a good choice to
reach protection levels below 4 kV. Nowadays more and
Class II SPD (Uc = 350 V AC, Imax = 40 kA [8/20 µs],
varistor), the residual voltage has a maximum value of
1140 V (see fig. 3, lower curve). The residual voltage of a
Class I and Class II SPD combination stays significantly
below the residual voltage of a varistor-based Class II
SPD. After the ignition of the spark gap – in the Class I
SPD – the residual voltage drops very fast below 500 V.
Even with high-energy long-duration surge currents a
combination of a spark-gap-based Class I SPD and a
varistor-based Class II SPD in one device is very
effective to achieve low residual voltages for the whole
duration of surge currents.

4 RESPONSE TIMES

The purpose of Class I SPDs is on the one hand to lead


through high-energy lightning currents with high
Fig. 2 – Class I and Class II SPDs in one device
(FLASHTRAB compact)
amplitudes. On the other hand sensitive electronic devices
shall be protected against fast-rising voltage impulses
For the measurements, discussed below, a surge current which can be caused e. g. by switching action. Therefore
generator has been used which produces 8/20 µs surge it is essential that a surge protective device has as well a
currents and whose rise time is nearly independent of the short and therefore good response time.
impedance of the SPD under test. Another reason for the
usage of an 8/20 µs surge generator is the fact that, The dielectric strength of insulation material and the
because of the short rise time of the leading edge of an coordination of insulation is specified in IEC 60364-4-44.
8/20 µs impulse, the residual voltages at the terminals of For the testing of the insulation coordination the 1.2/50 µs
an SPD are higher than with 10/350 µs surge current surge-voltage impulse is used (see fig. 4). Power supply
impulses of the same amplitude. systems with a nominal voltage of 230/400 V AC are for
example tested with 1.5 kV, 2.5 kV, 4.0 kV and 6.0 kV
If a 25 kA (8/20 µs) surge current is discharged via a surge-voltage impulses (1.2/50 µs) – depending on the
varistor-based Class II SPD (Uc = 350 V AC, Imax = place of installation.
40 kA, 8/20 µs), the residual voltage has a maximum
value of 1300 V (see fig. 3, upper curve). It’s typical for
the behavior of varistors that, during the discharge of a
surge current, the residual voltage stays for a long time at
a high voltage level. A high voltage level for a long
duration of time causes stress for the insulation material
and for the devices to be protected.

Fig. 4 – Surge-voltage impulse 1.2/50 µs

With a rise time of only 1.2 µs the 1.2/50 µs surge-


voltage impulse has a very short rise time. The time until
the full-duration half maximum is 50 µs. For the testing
Fig. 3 – Residual voltages of a Class II varistor and a
combination of a Class I spark gap and a Class II varistor –
of the dielectric strength of insulation material not only
tested with 25 kA surge currents (8/20 µs) the peak voltage of a surge-voltage impulse is of
importance, but as well the time-course of the voltage
change. The testing of insulation material with the
With the combination of a Class I SPD (Uc = 350 V AC, 1.2/50 µs voltage impulse shows that insulation materials
Iimp = 25 kA [10/350 µs], spark gap) together with a can not only be overloaded during the front time of the
1.2/50 µs impulse. Very often insulation breakdown
happens during the relatively long full-duration half and Class II in one device) limits the 6 kV impulse to
maximum time. 840 V. During the discharge no measurable current has
flown through the main spark gap of the Class I SPD.
To be able to compare the response behavior of spark- This shows, that with a FLASHTRAB compact arrester
gap-based Class I SPDs with varistor-based Class II combination, low-energy surges are discharged only with
SPDs, measurements with fast-rising 1.2/50 µs surge- the help of the Class II varistor. If a high-energy long-
voltage impulses have been carried out. The surge- duration surge current reaches the arrester combination,
voltage generator, used for the tests is a so called "hybrid then the Class I spark gap becomes conductive and nearly
generator". A hybrid generator produces a 1.2/50 µs 100 % of the surge current flows through the Class I
voltage impulse when the device under test has a high spark gap. This function principle of energetic
impedance. In the very moment when the device under coordination of a Class I spark gap and a Class II varistor,
test becomes low-impedant a hybrid generator produces a which are connected in parallel, is called Active Energy
current impulse of the waveshape 8/20 µs. Control (AEC). Active Energy Control makes sure that
there is a proper coordination for the whole range of real-
world surge currents – beginning with slow-rising low-
energy surges up to fast-rising high-energy surges. Proper
coordination means that due to surge currents the stress
level for a Class II varistor stays at a very low level. A
low stress level during the discharge of lightning currents
is an essential factor for a long prospective lifetime of an
SPD.

5 LINE-FOLLOW CURRENT

One advantage of varistor-based SPDs is that they are


Fig. 5 – Residual voltages of a spark-gap-based Class I SPD and free of line-follow current. During the discharge of a
a varistor-based Class II SPD at 6 kV surge-voltage impulses surge current, the residual voltage of a varistor always
(1.2/50 µs). stays above the instantaneous voltage of the respective
power supply system – therefore no line-follow current
A 6 kV surge-voltage impulse (1.2/50 µs, hybrid
can flow.
generator) is limited by the varistor-based Class II SPD
VALVETRAB compact (Uc = 350 V AC, Imax = 40 kA,
If the protective element of an SPD is a spark gap, then
8/20 µs) to Ures = 840 V (see fig. 5). Fast rising surge-
there might flow a line-follow current. A line-follow
voltage impulses can be limited efficiently with the help
current will always flow if the instantaneous value of the
of varistors. For state-of-the-art Class I spark gaps higher
supply voltage is higher than the arc-burning voltage of a
voltage levels are measured. A peak value of 1410 V has
spark gap during the discharge of a lightning current. In
been measured at the terminals of a modern encapsulated
this case the supply voltage causes an additional current-
spark gap. This voltage level is still low enough for a
flow through the spark-gap based SPD. In the past line-
proper protection of sensitive electronic devices. After
follow currents of spark gaps have often been the cause
reaching it's peak value the instantaneous value of the
for discussions, because the flowing of line-follow
residual voltage is immediately reduced to about 650 V.
current causes additional stress for upstream back-up
The triggering circuit of the spark gap allows a nearly
fuses.
delayless response behavior of the spark gap. Already
during the very short front time of the 1.2/50 µs impulse
6 SPARK GAPS WITH REDUCED LINE-FOLLOW
the trigger circuit of the spark gap becomes conductive
CURRENT
and discharges the surge voltage via an auxiliary
electrode inside the encapsulated Class I spark gap.
In the beginning the design of spark-gap based SPDs has
Because of the design of the triggering electronics and the
been rather simple. The main electrodes have been
auxiliary electrode the power supply system is efficiently
relatively simple electrodes with low line-follow current
protected against fast-rising voltage surges – even if the
quenching capability. For this class of old-fashioned
main spark gap has not yet become fully conductive.
SPDs the occurrence of line-follow current has been
totally normal during or after the discharge of a surge
Additional tests with a combination of a Class I SPD
current. With the help of arc baffle plates, quenching
(with triggered spark gap) and a Class II SPD (with
plates and plastic material which releases quenching gas
varistor) have been carried out. During these tests with
during getting heated up by electric arcs, the line-follow
6 kV surge-voltage impulses (1.2/50 µs, hybrid generator)
current quenching capability has been significantly
the FLASHTRAB compact arrester combination (Class I
improved. These spark gaps still have one disadvantage.
They have not been encapsulated and ionized gases have spark-over voltage and therefore a high protection level –
been blown out during the discharge of lightning currents. which is not adequate for the protection of sensitive
In real-world applications this emission of ionized gases electronic devices. With the help of an auxiliary electrode
has never been a problem, because SPDs are installed in and the triggering electronics the space between the main
switching cabinets which are designed to deal properly electrodes gets artificially ionized during the beginning
with ionized gases. During the discharge of surge currents discharge of a surge current. The artificial ionization
a non-encapsulated spark gap behaves pretty much like a makes it possible to achieve low spark-over voltages and
circuit breaker during tripping. When a circuit breaker low protection levels – even if the distance between the
trips then it blows out as well ionized gases. Nevertheless main electrodes is pretty high.
end users had the wish that spark-gap-based SPDs are
developed which no longer blow out ionized gases. So 7 CABLE INDUCTANCE AND INDUCED
manufacturers of SPDs developed encapsulated spark VOLTAGES IN CABLES
gaps. State-of-the-art encapsulated spark gaps nowadays
can quench up to 50 kA prospective short-circuit current Cable inductance can usually be neglected at power
on their own. supply systems with nominal frequencies of 50/60 Hz.
However for surge protective devices the cable
To minimize line-follow currents, or to make sure that inductance plays an important role. The reason for this is
there are never line-follow currents, the residual voltage the fact that the frequency spectra created by transient
of an SPD has to be so high that it will never drop below surge currents and surge voltages can reach into the range
the instantaneous voltage of a power supply system of several megahertz. Real-world surges can have an
extremely fast change of the current. Therefore the
voltage boosts on the conductors, which can occur during
the leading-through of surge currents, can lie in the range
of several ten thousand volts. High voltage boosts on the
conductors can destroy electrical equipment (cables,
switches, end devices, etc.).

For the measurement of the residual voltage of SPDs, the


voltage is measured directly at the terminals of an SPD.
In real-world applications a feed-line which leads from a
busbar to a surge protective device always has a certain
length. To simulate the behavior of SPDs, which are
installed in real-world electrical systems, measurements
Fig. 6 – Modern high-performance spark gap (FLASHTRAB of residual voltages at 25 kA (10/350 µs) lightning-
compact) current impulses have been carried out with different
types of SPDs and with different lengths of feed-lines.
The latest generation of encapsulated and electronically
triggered spark gaps (see fig. 6) is able to control the arc-
Class I varistor (Iimp = 25 kA [10/350 µs], Uc = 320 V
burning voltage in a way that line-follow currents are
AC)
minimized – even under worst-case conditions. This
• SPD with 0.0 m feed-line
special operation behavior of the FLASHTRAB compact
series of SPDs has been achieved by the following design • SPD with 0.5 m feed-line
principles:
Class I spark gap in combination with Class II varistor
• Increasing the distance between the main
(Iimp = 25 kA [10/350 µs], Uc = 350 V AC)
electrodes
• SPD with 0.0 m feed-line
• Ignition of the electric arc between the main
electrodes with the help of an auxiliary electrode • SPD with 0.5 m feed-line
• Building-up pressure during the discharge of surge
The tests have been carried out with a 10/350 µs surge-
currents
current generator. This type of surge-current generator
• Using an arc-channel which is oriented transversal
has a rise time of 10 µs when it is operated in short-circuit
to the electrical field
mode. Test items with a certain impedance, like varistors
or spark gaps, increase significantly the rise time of
Because of the relative high distance between the main
current surges produced by 10/350 µs surge-current
electrodes, the spark gap has an high arc-burning voltage.
generators. IEC 61643-1 reflects this specific behavior of
Therefore this new design for encapsulated spark gaps
10/350 µs surge-current generators. It is allowed,
minimizes or prevents possible line-follow currents.
according to this standard, to use surge-current impulses
Usually a high arc-burning voltage as well causes a high
with rise times up to 50 µs. For the following
measurements, carried out with varistors and spark gaps,
the rise time of the surge-current impulses has been in the
range of 25 µs.

Nowadays more and more sensitive electronic devices are


used in direct proximity to the main distribution panel -
the place where a Class I SPD is usually installed.
Examples for such sensitive devices are e. g. PLCs or
devices for power-factor correction. For an efficient
protection of such sensitive devices it is important to limit
short-duration fast-rising voltage surges and to reach low- Fig. 8 – Residual voltages at 25 kA surge-current impulses
level residual voltages during long-duration current (10/350 µs). Length of feed line: 0.5 m
surges.
The surge current which flows through a 0.5 m feed-line,
A good way to evaluate the efficiency of an SPD is to causes an additional rise of the peak voltage of about
compare the residual voltage of an SPD with the 620 V during the rise time of the surge current.
1.2/50 µs surge-voltage impulse. This surge-voltage
impulse is used for the testing of the dielectric strength of The residual voltage of a Class I varistor stays above the
insulation material and as well for the testing of electric 1.5 kV surge-voltage impulse (1.2/50 µs). This means
and electronic devices. If the residual voltage of an SPD that SPDs with Class I varistors are not capable to protect
stays below the respective max. permissible 1.2/50 µs sensitive electronic devices efficiently.
curve for the device to be protected, then it can be
assumed that the protection effect of the SPD is The residual voltage of a Class I spark gap - in
sufficient. The lower the residual voltage stays below the combination with a Class II varistor - is clearly below the
respective 1.2/50 µs waveshape, the better is the 1.5 kV surge-voltage impulse (1.2/50 µs). This means
protection effect. Therefore the oscillograms shown in low stress and an efficient protection for power supply
fig. 7 + 8, have been superimposed with an 1.5 kV surge- systems and sensitive electronic devices.
voltage impulse of the waveshape 1.2/50 µs.
8 CONCLUSION

The measurements taken with varistor-based and spark-


gap-based Class I SPDs have shown that varistor-based
Class I SPDs don’t provide the same protection against
10/350 µs surge currents compared to modern high-
performance Class I spark gaps. Electronically triggered
Class I spark gaps reach low residual voltages even with
long-duration surge currents.

The combination of a triggered Class I spark gap and a


Fig. 7 – Residual voltages at 25 kA surge-current impulses Class II varistor protects very efficiently power supply
(10/350 µs). Length of feed line: 0.0 m systems and electric and electronic devices. This
combination of SPDs unites in one protection device a
The measurements show that the residual voltage of a real multi-stage protection with a high surge current
Class I varistor-based SPD, exposed to an 25 kA discharge capability, low residual voltages and a very fast
(10/350 µs) surge current, stays for a long time at a about response behavior.
1000 V. This causes a lot of stress for the insulation
material of the power supply system and as well for 9 REFERENCES
devices which are connected with the power supply
system. [1] IEC 62305-1 (2006-01): Protection against lightning -
Part 1: General principles
[2] IEC 62305-4 (2006-01): Protection against lightning -
In real-world applications the length of the feed lines for
Part 4: Electrical and electronic systems within structures
SPDs is always longer than 0.0 m. To show the voltage- [3] IEC 60364-4-44 (2006-11): Low voltage electrical
rising effect which is caused by feed lines the following installations - Part 4-44: Protection for safety - Protection
measurements have been carried out with 0.5 m feed against voltage disturbances and measures against
lines. electromagnetic influences
[4] IEC 60364-5-53 (2002-06): Electrical installations of [8] M. Wetter, J. Wosgien, R. Durth: A new technology of
buildings - Part 5-53: Selection and erection of electrical triggered lightning current arresters; International Confer-
equipment - Isolation, switching and control ence on Lightning Protection (2002-09, Cracow, Poland)
[5] IEC 61643-1 (2005-03): Low-voltage surge protective [9] M. Wetter, J. Schimanski, K. Scheibe: High performance
devices - Part 1: Surge protective devices connected to triggered lightning current arresters; International Confer-
low-voltage power distribution systems - Requirements ence on Lightning Protection (2004-09, Avignon, France)
and tests [10] H. Heckler, J. Schimanski, M. Wetter: Ableitvermögen
[6] IEC 60060-1 (1989-11): High-voltage test techniques - und Ansprechzeit von Blitzstromableitern; etz Heft 8/2005
Part 1: General definitions and test requirements (Germany)
[7] J. Schimanski, K. Scheibe, M. Wetter: Coordination of [11] J. Schimanski: Überspannungsschutz - Theorie und Pra-
varistors; International Conference on Lightning Protec- xis; 2., neu bearbeitete und erweiterte Auflage (2003),
tion (2000-09, Rhodes, Greece) Hüthig Verlag (Heidelberg, Germany)

Вам также может понравиться