Академический Документы
Профессиональный Документы
Культура Документы
CHAPTER 4
ANALYSIS AND DESIGN OF FLAT SLAB
4.1. General
In this chapter, flat slab design, stair design and choice of opening location in
accordance with ACI 318-14. Slab and stair are designed with concrete compressive
'
strength f c and reinforcing yield strength fy as 3ksi and 50 ksi. Design results and
schedules of slab, and stair are presented in this chapter. Flat slab design are
calculated with manually and insert drop panel and with spandrel beams are used.
The proposed structure is the eight-storeyed reinforced concrete building and located
in seismic zone 4. Flat slab punching shear is checked with SAFE software and slab
deflection is checked with manually. In stair design, landing beam are used. Location
of opening for flat slab in accordance with ACI code and the permitting of opening
size depends upon the location of column strip and middle strip.
20 ft 12 ft 20 ft
4 ft
12 ft FS 2 FS 1 FS 2
14 ft
FS 4 FS 5 FS 4
14 ft
FS 4 FS 5 FS 4
14 ft
FS 4 FS 5 FS 4
16 ft FS 3 FS 3
4 ft
12 ft
14 ft FS 5
60 in
24 in
60 in 24 in
Column
Drop panel
d
shear stress is at a distance from the column faces; hence, the net
2
factored perimetric shear force is,
Concrete cover = 1.5 in
Bar diameter = 0.5
d= 9-1.5-0.5 = 7 in
2
V u= 0.297 x 12 x 14−( 31 )
{ 12 }
= 48.1kips
The perimeter of the critical shear failure surface is ,
b 0 = ( 24 + 7 )
= 116 in
14
β = ratio of longer to shorter side of columns = = 1.2
12
Available nominal shear (the smallest value),
ϕV c = ϕ (2+4/β ) √ f c' b 0 d
ϕV c = 0.75 x (2 + 4/1.2) x √ 3000/1000 x 116 x 7
= 181.08 kips
ϕV c = ϕ ( ∞ s d / b 0+2 ) √ f c ' b0 d
∞ s = 40 (interior panel )
ϕV c = 0.75 x (40 x 7/116+ 2 ) x √ 3000/1000 x 116 x 7
= 147.23 kips
ϕV c = ϕ λ 4 √ f c ' b0 d (for 1ft width strip, λ=1)
= (0.75)x(4) x (1) x √ 3000/1000 x 116 x 7
= 133.43 kips (control ) > V u (OK)
Hence, the floor thickness is adequate.
(c) Calculate the total static moments in the long and short directions.
M ol = W u x l s x l 2n /8
= (0.297 x 12 x 13 x 13) / 8
= 65.86 kips-ft
67
M os= W u x l l x l 2n /8
= (0.297 x 14 x 11 x 11 )/8
= 53.65 kips-ft
h s = 9 (middle)
h s = 7 (column)
Table 4.2. Design Result of Short Direction for FS5
Δ < Δallowable
Therefore, it is satisfied.
For Long-direction,
Modulus of elasticity of slab concrete,
6
Ecs = 3.32×10 psi
Moment of inertia about centroid axis of gross section of slab,
3
bh 14×12×73
I = 12 = 12 =4116 in4
65 .86×124 ×123 ×12
6
Δ = 384×3 .32×10 ×4116 0.022 in
ℓ
Δallowable = 480
12×12
= 480
= 0.3 in
Δ < Δ allowable
Therefore, it is satisfied.
For exterior panel,
20 ft
70
14 ft
FS 4
60 in
24 in
24 in
60 in
Column
vapppanel
Drop Panel
Fig 4.5. Drop Panel and Column Dimensions of FS4 vapppanel
Because the drop panel length is L/3 in each direction, the average q u is,
Average q u = (2/3) x 289+(1/3) x 319
= 299 psf
b 0 =4 ( 24 + 7 )
= 124 in
20
β = ratio of longer to shorter side of columns = 14 = 1.4
Available nominal shear (the smallest value),
ϕV c = ϕ (2+4/β ) √ f c' b 0 d
ϕV c = 0.75 x (2 + 4/1.2) x √ 3000/1000 x 124 x 7
= 171.15 kips
ϕV c = ϕ ( ∞ s d / b 0+2 ) √ f c ' b0 d
∞ s = 40 (interior panel )
ϕV c = 0.75 x (40 x 7/116+ 2 ) x √ 3000/1000 x 116 x 7
= 151.83 kips
ϕV c = ϕ λ 4 √ f c ' b0 d (for 1ft width strip, λ=1)
= (0.75)x(4) x (1) x √ 3000/1000 x 116 x 7
= 142.63 kips (control ) > V u (OK)
= (0.299 x 14 x 19 x 19) / 8
= 169.53 kips-ft
M os= W u x l l x l 2n /8
= (0.299 x 20 x 13 x 13 )/8
= 107.64 kips-ft
For long direction,
column strip= 7 ft
middle strip= 13 ft
Δ < Δallowable
Therefore, it is satisfied.
For Long-direction,
Modulus of elasticity of slab concrete,
14×12
Δallowable = 480
= 0.35 in
Δ < Δ allowable
Therefore, it is satisfied.
20 ft
16 ft FS 3
75
60 in
24 in
60 in
Column
Drop panel
Minimum preliminary thickness h from table with edge beam and drop
panels using fy = 50000 psi (l n=¿ clear spacing in long direction)
Drop panel size = L/6 = 16/6= 2.5 ft (extend from center line)
20
(iv) Ratio longer span/shorter span = 16 = 1.25 < 2.0, hence two way
action.
qu = 1.2(132.5)+1.6(100)
= 319 psf
Because the drop panel length is L/3 in each direction, the average q u is,
76
b 0 = 4( 24 + 7 )
= 124 in
ϕV c = ϕ (2+4/β ) √ f c' b 0 d
ϕV c = 0.75 x (2 + 4/1.25) x √ 3000/1000 x 124 x 7
= 185.42 kips
ϕV c = ϕ ( ∞ s d / b 0+2 ) √ f c ' b0 d
∞ s = 40 (interior panel )
ϕV c = 0.75 x (40 x 7/124+ 2 ) x √ 3000/1000 x 124 x 7
= 151.83 kips
(c) Calculate the total static moments in the long and short directions
77
M ol = W u x l s x l 2n /8
= (0.299 x 16 x 19 x 19) / 8
= 193.75 kips-ft
M os= W u x l l x l 2n /8
= (0.299 x 20 x 15 x 15 )/8
= 146.51 kips-ft
20×12
Δallowable = 480
= 0.5 in
Δ < Δallowable
Therefore, it is satisfied.
For Long-direction,
Modulus of elasticity of slab concrete,
16×12
Δallowable = 480
= 0.4 in
Δ < Δ allowable
Therefore, it is satisfied.
Table 4.7. Slab Column Strip Steel Schedule
Column Strip
size Directio
Type Exterior Positive Interior
(in) n
Short #4@12"c/c #4@12"c/c #4@12"c/c
FS1 12x12
Long #4@12"c/c #4@12"c/c #4@12"c/c
Short #4@12"c/c #4@12"c/c #4@6"c/c
FS2 12X20
Long #4@9"c/c #4@6"c/c #5@6"c/c
Short #4@12"c/c #4@12"c/c #4@5"c/c
FS3 16X20
Long #4@12"c/c #4@6"c/c #5@6"c/c
80
Middle Strip
size Directio
Type Exterior Positive Interior
(in) n
Short #4@12"c/c #4@12"c/c #4@12"c/c
FS1 12x12
Long #4@12"c/c #4@12"c/c #4@12"c/c
Short #4@6"c/c #4@6"c/c #4@6"c/c
FS2 12X20
Long #4@6"c/c #4@9"c/c #4@9"c/c
Short #4@12"c/c #4@12"c/c #4@12"c/c
FS3 16X20
Long #4@6"c/c #4@6"c/c #4@12"c/c
Short #4@15"c/c #4@15"c/c #4@15"c/c
FS4 14X20
Long #4@6"c/c #4@10"c/c #4@10"c/c
Short #4@12"c/c #4@12"c/c #4@12"c/c
FS5 12X14
Long #4@12"c/c #4@12"c/c #4@12"c/c
14 ft
#4@ #4@
10"c/c 10"c/c
20 ft
#4@ #4@
6"c/c 6"c/c
Fig (4.4.1 ) shows the first floor punching shear checking for interior column.
This results are analysis by SAFE 2016 software. Because of using spandrel beams,
SAFE software are not calculated punching shear for this columns. N/C means not
calculated.
are sometimes required for stairs and elevators shafts. ACI 318 Code gives guidelines
and limitations for opening location and size. It should be noted that openings cut in
the column strip area could reduce punching shear capacity.
l2 l2 l2
l1
Column
strip
l 1/8
Middle
strip Any size l1
permitted
Column
l 1/16
strip
l 1/16 l 1/16
l1
3 ft wide opening
24 in
24 in
24 in 24 in
#4 bar
3 ft 2 in clear
#4 bar
3 ft
3 in clear
is 3000 psi and reinforcing yield stress f y is 50000 psi. Stair design calculation is
followed by the ACI 318-14. Assuming waist thickness is 6 in. Stair location plan is
shown in Figure 4.9. Design results for stairs are shown in Table 3.3.
For Typical Stair,
Floor height = 9.5 ft
No. of steps = 12 steps
Rise = 5.5 in
Tread =11 in
Assume waist thickness = 6 in
6
Weight of waist = 11 × 1 × 12 × 150 = 825 lb
1 11×5.5
× ×150 ×12
Weight of steps = 2 144 = 378.125 lb
85
50
55.44 = 0.9 × 50×0.0214× 12 × d2 (1- 0.59 ×0.0214× 3 )
d = 2.5 in
h = 2.5+1
= 3.5 in
cover = 1 in
Use h = 6 in, d = 5 in
2Mu
a =d- √ d2−
0 . 765f 'c b
2×55 .44
=5- √ 52 −
0 .765×3×12
86
= 0.42 in
Mu
As = φ f y (d−a/2)
55.44
= 0.9×50( 5−0 .42/2) = 0.257 in2
200
As(min) = ρminbd (ρmin =
fy )
= 0.004 ×12× 5
= 0.24 in2
Use #4@5'' c/c spacing (As = 0.292 in2 > 0.257 in2)
Stair steel schedules are expressed in Table and detail section of stair for typical floor
is shown in Figure .
10 ft
4.75 ft
Figure 4.14. Detail Section of Stair for Typical Floor (9.5' height)