Вы находитесь на странице: 1из 5

SURVEY OF DESIGN PRACTICES OF HOSPITAL OPERATING ROOM

AIR CONDITIONING AND VENTILATION SYSTEM


Vinson R. Oviatt, M.P.H., F.A.P.H.A.

Survey questionnaires, similar in many cated that the hospital staff had been
respects to those sent to hospital main- consulted about the design. Others may
tenance engineers, were directed to 287 consult the hospital staff, but at least
individuals and firms identified as being only 23 felt that this item was signifi-
active in the field of hospital air con- cant enough to check on the question-
ditioning and ventilation design. Not naire. This indication can lead to several
only did the survey sheets attempt to conclusions, one of the more important
collect design practice data suitable for being that there appears to be a mini-
tabulation and comparison, but the re- mum of communication between the de-
spondents were encouraged to contribute sign group and the hospital staff who
any original information bearing on de- will use the facilities.
sign practice and theory in the follow- Almost unanimous agreement on two
ing health or safety related areas: design considerations was elicited from
1. Air quality within the operating room the survey returns. The first was that
from a bacteriological point of view. 98 of the 99 respondents replied that
2. Physical comfort of operating room oc- both supply and exhaust ventilation are
cupants. used; one respondent failed to reply to
3. Removal of flammable anesthetic vapors this question. The second was to supply
and odors.
4. Control of electrostatic hazards. clean air to the operating room. It is
significant to note that there were a
The discussion and tabulated material number of requests for information re-
below summarize the information con- ceived in the returned questionnaires
tained in the 99 replies received from as to the degree it is considered neces-
this group. sary to clean the air. Other comments
received advocated stricter standards
Design Standards and the enforcement of standards for
The survey indicated a multiplicity air cleaning.
of sources for design standards, ranging
from original design by the respondent to Air Intake and Exhaust Outlet Location
manufacturers' recommendations. Only
56 of the respondents reported that ele- The numerical preferences for gen-
ments in their designs were based on eral locations for fresh-air intakes and
one or more official or quasi-official exhaust air outlets are summarized in
standards. Whether or not the remain- Table 1(B).
ing 43 consider recognized standards As shown, sidewall locations for fresh-
as being significant enough to use or air intakes are strongly favored. The
mention could not be determined. Of largest number of designers prefer the
the 56 referring to standards, USPHS roof level for exhaust air outlets. Since
("Hill-Burton") standards were listed a variety of potential air pollution
28 times,1 ASHRAE ("Guide") stand- sources occur at grade level, the com-
ards were listed 17 times,2 NFPA Code mittee was gratified to note that grade
56, 17 times,3 and various state codes, level locations for fresh-air intakes are
5 times. rarely used today.
It is of particular interest to note An examination of Table 2(B), which
that only 23 of the respondents indi- summarizes design practice with respect

1902 VOL. 51. NO. 12. A.J.P.H.


OPERATING ROOM AIR CONDITIONING AND VENTILATION SYSTEMS

Table 1 (B)-Location of Fresh Air tamination within enclosed spaces is to


Intake and Exhaust Outlets increase the number of air changes.
It was considered desirable to learn
Supply Exhaust whether air change rates currently being
Location on Air (No. Air (No.
Building Replies) Replies) specified are influenced by this con-
sideration. Generally, from 8 to 12 air
Roof level 25 72 changes per hour are required in United
Sidewall 45 4 States practice for thermal loads in
Grade level 1 2 operating rooms. Table 3(B) is con-
Sidewall and grade structed for comparison with Table 6
level 1 0
Roof level and side- in the preceding survey. In reducing
wall 20 10 survey data to tabular form, the con-
Conditions indicate 5 6 vention was followed of assigning a
No response 2 5 reported range of air change rates,
which extended over more than one
range in the table, to the range em-
to minimum vertical and horizontal dis- bracing its mean.
tances separating fresh-air intakes and From a review of the table it appears
exhaust outlets, shows the wide range that those air change rates reported
of values found in current practice. By are probably based on thermal load re-
their comments, a number of the de- quirements, rather than on air quality
signers showed an awareness of the considerations.
need to achieve the maximum separa-
tion possible. One inference drawn from Temperature and Humidify
the number of returned questionnaires
which did not furnish answers on fresh Table 4(B) which summarizes the
air and exhaust separation is that there prevailing temperature and relative hu-
is a large element of uncertainty or lack midity design practice, shows a close
of understanding in this area of design. adherence on the part of the design
group to published standards for both
Air Cleaning conditions. The extent to which flexi-
As mentioned earlier, the design en-
gineers, as a group, exhibited consid- Table 2(B)-Vertical and Horizontal
erable interest in methods for supplying Distance Between Any Supply Inlet
a bacteriologically clean air. This is and Exhaust Outlet
reflected by the number of combinations
of air cleaning methods reported. In Vertical Horizontal
the face of an absence of standards for (No. (No.
the degree of air cleaning required, the Distance (Ft) Replies) Replies)
availability of project funds appeared 0-10 24 8
in other instances to be the determinant 11-20 19 23
in the selection of surgery air cleaning 21-30 4 12
methods (s) . 31-50 5 12
75 1 1
100 0 1
Other Design Factors with Air "Maximum distance
Quality Implications available" 26 26
"As conditions indi-
One of the simplest design concepts cate" 26 26
which can be used to reduce air con- No response 20 16

DECEMBER, 1961 1 903


Table 3 (B) -Rates of Air Change in Surgery

No. of air
changes/hr 0-5 6-10 11-15 16-20 21 Depends No response
on cooling
No. of load
respondents 1 40 34 4 0 5 15

bility in temperature adjustment is being Fresh Air Supply and Exhaust


designed into operating room systems Air Outlet Locations in
to meet individual preferences on the Operating Rooms
part of the surgeons and other members
of the surgical team could not be ascer- A great variety of air supply grilles or
tained from the questionnaires. diffusers and exhaust register designs
are used for operating rooms and a
Type of System systematic study of the rationale for
their selection is complicated by cost
Central air distribution systems of considerations. Sidewall supply grilles
various types were designated by all or diffusers were listed in 69 replies
but five of the respondents as first (28 nonaspirating, 36 aspirating); 72
choice. However, many indicated the replies mentioned ceilingsupplydiffusers
use of room package units with only (14 nonaspirating and 54 aspirating);
one mentioning window-type coolers. while 20 indicated perforated ceiling
This appears to indicate that the selec- panels for the supply.
tion of the type of system is often in- Though aspirating-type air diffusers
fluenced by cost and whether the system complicate any analysis of air flow
is a new or remodeled project. A few patterns, an indication of the designers'
respondents have employed panel cool- intents with regard to air movement is
ing systems. shown in Table 5(B).

Table 4(B)-Temperature and Humidity Design Practice

Temperature Relative Humidity


Winter Summer Winter Summer
(o F) (No.) (No.) (Range-%) (No.) (No.)
68 0 1 30-32 1 0
69 0 0 33-37 0 1
70 7 4 38-42 3 2
71 0 0 43-47 1 3
72 8 6 48-52 38 40
73 2 2 53-57 35 37
74 4 2 58-62 8 8
75 38 34 63-67 0 1
76 7 9 No reply 13 7
77 0 3
78 8 9
79 0 0
80 18 23
No reply 7 6

1 904 VOL. 51. NO. 12. A.J.P.H.


OPERATING ROOM AIR CONDITIONING AND VENTILATION SYSTEMS

Generally, it may be concluded that Table 5(B) - Supply and Exhaust


designers attempt to follow codes which Locations
require low exhausts or low exhausts
in combination with high exhausts. No. of
Location Replies
Interim Recommendations Supply high, exhaust low 37
Supply high, exhaust high and low 41
Following a review and study of the Supply high, exhaust high 9
data in the above surveys, the Com- Supply low, exhaust high 1
mittee on Hospital Facilities of the Not indicated 6
No response 5
APHA Engineering and Sanitation Sec-
tion has issued the following interim
recommendations for certain design
features of hospital operating room air out of the room through the entire area of
conditioning systems. openings under all conditions.
(b) Providing an air lock between the room
A number of the medical, bacterio- and the more contaminated adjacent areas for
logical, and engineering studies of oper- the use of personnel who must leave the op-
ating room air conditioning4-10 have erating room during surgical procedures in
been reported and others are still in the performance of their duties.
progress. Some of these may throw (c) Simultaneous with (a) and (b), pro-
viding the same temperatures in adjoining less
further light on such fundamental issues critical areas as are maintained in the operat-
as the relative amounts of pathogenic ing room to eliminate air movements set up
bacteria disseminated from various by air density currents.
sources or locations within the operating 5. Outdoor air supply inlets properly located
with respect to all forms of exhaust originat-
room.8 Further information upon which ing within the hospital as well as other con-
more specific recommendations can be taminating sources.
made is needed. In consideration of 6. Biological particulate air cleaning devices
these reported studies and the com- placed downstream from all other mechanical
mittee's two surveys, it is recommended elements in the air conditioning system and
located as near as possible to the point of
that the practices in designing operating entry of supply air to the operating room.
room air conditioning systems place 7. Locating devices for the removal of bio-
greater emphasis upon furnishing the logical particulates from exhaust air from
following: highly contaminated sources in the hospital
environs as near as possible to their point of
1. Effective temperatures which will, by pro- origin.
viding the maximum comfort for the surgeon
and the surgical team, help assure optimum ACKNOWLEDGMENTS-The committee wishes
conditions for conducting the surgical pro- to thank all those respondents to its two sur-
cedures. veys for making these reports possible.
2. An air flow pattern designed to displace, Richard G. Bond, professor, School of Pub-
disperse, or accelerate the removal of air- lic Health, and public health engineer, Uni-
borne contamination immediately above the versity Health Service, University of Minne-
operating table in particular and the operating sota, Minneapolis, Minn., and Elmer C.
room in general. Slagle, assistant director, Division of Hospital
3. An air supply free of biological par- Services, Minnesota State Department of
ticulates. Health, were members of Mr. Michaelsen's
4. An absence of backflow of contaminated subcommittee. G. A. Weidemier, American
air into the operating room from less critical Hospital Association, gave valuable assistance
areas, to be achieved, for example, by one or to Mr. Michaelsen in supplying a mailing list
more of the following procedures: of hospital maintenance engineers.
(a) Imbalancing the air supply quantities James C. Barrett, chief of the Ventilation
to the room and the exhaust from the room so Techniques Section, Division of Occupational
as to maintain a positive pressure condition Health, Michigan Department of Health,
within the room sufficient to cause air to move served as a member of Mr. Oviatt's subcom-

DECEMBER, 1961 1 905


mittee. The American Society of Heating, REFERENCES
Refrigerating and Air Conditioning Engineers 1. Public Health Service Regulations. Part 53 pertain-
kindly gave its permission for the committee ing to the Hospital Survey and Construction Act,
to indicate the society's interest in the survey as amended.
directed to air conditioning engineers and 2. Heating, Ventilating, and Air Conditioning Guide,
design firms. Richard P. Gaulin and his 1960. New York, N. Y.: American Society of Heat-
ing, Refrigerating, and Air Conditioning Engineers.
associates in the Division of Hospital and 3. Code for the Use of Flammable Anesthetics. NFPA
Medical Facilities of the Public Health Serv- Code No. 56. Boston, Mass.: National Fire Protec-
ice, Department of Health, Education, and tion Association (May), 1960.
Welfare, were largely responsible for assem- 4. Blowers, R.; Mason, G. A.; Wallace, K. R.; and
Walton, M. Control of Wound Infection in a
bling the names of the group surveyed by Mr. Thoracic Surgery Unit. Lancet 269:786-794 (Oct. 15),
Oviatt's subcommittee. 1955.
5. Bourdillon, R. B., and Colebrook, L. Air Hygiene
in Dressing-Rooms for Burns or Major Wounds.
Ibid. 250:601-605 (Apr. 27), 1946.
DONALD L. SNOW, M.S., National Insti- 6. Shooter, R. A.; Taylor, Gerard W.; Ellis, George;
tutes of Health, Bethesda 14, Md., and Ross, James Paterson. Postoperative Wound Infec-
tion. Surgery, Gynec. & Obst. 103:257-262 (Sept.),
Chairman, Hospital Facilities Com- 1956.
mittee 7. Greene, V. W.; Bond, R. G.; and Michaelsen, G. S.
Air Handling Systems Must Be Planned to Reduce
JAMES C. BARRETT the Spread of Infection. Mod. Hosp. 95:2,136 (Aug.),
RICHARD G. BOND, M.P.H. 1960.
8. Blowers, Robert, and Crew, Beryl. Ventilation of
RICHARD P. GAULIN Operating-Theatres. J. Hyg. 58,4:427-44 (Dec.),
LAWRENCE B. HALL 1960.
9. Lidwell, 0. M., and Williams, R. E. 0. The Ven-
LOUVA G. LENERT tilation of Operating-Theatres. Ibid. 58,4:449-464
GEORGE S. MICHAELSEN, M.S. (Dec.), 1960.
10. Wolf, Harold W.; Harris, Marvin, M.; and Hall,
VINSON R. OVIATT, M.P.H. Lawrence B. Open Operating Room Doors and
Staphylococcus aureus. Hospitals 35,6:57-64 (Mar.),
ELMER C. SLAGLE, M.P.H. 1961.

Mr. Michaelsen is associate professor and industrial health engineer, School


of Public Health, and University Health Service, University of Minnesota,
Minneapolis, Minn. Mr. Oviatt is Hospital Consultant, Engineering Division,
Michigan Department of Health, Lansing, Mich.
This report was presented before the Conference of Municipal Public Health
Engineers, the National Association of Sanitarians, and the Engineering and
Sanitation Section of the American Public Health Association at the Eighty-
Eighth Annual Meeting in San Francisco, Calif., November 1, 1960.

1 906 VOL. 51, NO. 12, A.J.P.H.

Вам также может понравиться