Академический Документы
Профессиональный Документы
Культура Документы
1215
3 where the threshold ξ is set to 0.4, based on extensive tests.
Te pPM isq (2)
2 Considering the FLC with the shared leg “b” connected to
the machine and grid phases (Fig. 1 (b)), if Δisd and Δisq are
On the other side, considering that the dq-axes rotating at less than Δigd and ξ, respectively, the priority is assigned to the
the grid voltage frequency and the q-axis is aligned with the control of the GSC. Regarding the MSC, further
grid voltage space vector, then the GSC voltages are given by improvements can also be introduced by applying the zero-
sequence signal only when Sb and SB are different. For
digd
ucd R f igd L f g L f igq instance, if Sabc and SABC are {101} and {001}, respectively,
dt the formulated switching state S’abcAC is {10101}, where S’b
(3)
digq corresponds to the switching state common to both converter
ucq R f igq L f g L f igd u gq sides. Let us consider now that SABC is {011}. The zero voltage
dt
vector for the MSC will be realized using {111} instead of
Vector control strategies are implemented based on the {000}, meaning that S’abcAC is {11101}. The same rationale
machine and grid models. The rotor field oriented control can be applied for the equivalent FLC-SL hardware
strategy is combined with the S-PWM technique and applied connections for the other fault cases.
to the MSC. A voltage oriented control based on S-PWM
C. Converter Design Considerations and Post-Fault
technique is implemented on the GSC. The block diagram of
Operating Limits
the fault-tolerant S-PWM control strategies is shown in Fig. 2.
As it is observed, the machine and grid currents are indirectly The converter operation at rated power during the post-fault
controlled resorting to voltages uabc and u ABC , respectively. The period requires the oversizing of voltage and current ratings of
* the power converters. On the other hand, the operation under
reference voltages uabc and u *ABC are usually generated through
derated mode allows the drive to operate in a limited range
proportional-integral (PI) controllers, properly tuned in order without oversizing the ratings of the converters components.
to achieve high performance of the PMSG drive. The In comparison with the standard SLC, the FLC-SL topology
switching states Sabc and SABC are then determined by has a smaller output voltage capability. The linear modulation
comparing the reference voltages with a high-frequency
range can be defined as follows
triangular carrier. The relationship between the converter
output voltages and the switching states is given by udc
u s uc (6)
3
ua , A 2 1 1 S a , A
u
u dc 1 2 1 S (4) where us and uc are the amplitudes of the fundamental
,
,
b B b B
u 3 phase-to-neutral voltages of the MSC and GSC, respectively,
1 1 2 Sc ,C
c ,C and udc is the dc bus voltage.
Taking into account that the required MSC output voltage
B. PWM Control of the FLC-SL depends on the machine speed, and considering that the grid
Under converter post-fault operation, software voltage is constant, the increase of the dc-link voltage and/or
modifications are required in order to adapt the post-fault the decrease of the machine speed are the two available
control strategy to the new converter topology. Therefore, all options, in order to maintain the converter operation within the
switching states are formulated based on Δisd, Δisq and Δigd, linear modulation region (6).
which stand for the absolute values of the reference current Considering three different operating conditions (case (a):
errors isd * isd , isq* isq and igd * igd , respectively. us=uc, case (b): us=0.5uc, case (c): uc=0.5us), the FLC-SL
voltage capability is reduced by approximately 29%, 39%,
The value of Δisd is compared to Δigd, aiming to assign the 39%, respectively, with respect to the voltage capability of the
control priority to one of the converters: an appropriate standard SLC, which is 58 % of the dc link voltage. Therefore,
voltage vector is chosen for the converter with priority, while in the cases (b) and (c) the dc-link voltage must be increased
the other converter is subjected to a zero vector, using the
by 50%, while in case (a) it must be increased by 100%.
switching states {000} or {111}.
In case (a), the required dc link voltage can be reduced by
It is important to emphasize that, according to (1) and (2),
the zero voltage vectors applied to the MSC may lead to limiting the generator speed. Therefore, the maximum speed is
undesirable electromagnetic torque oscillations, because the limited by the maximum amplitude of the MSC converter
permanent magnets are always rotating, and the rotor flux output voltage, given by
keeps moving towards the fixed stator flux. Accordingly, the 1
interaction between the stator voltage and the rotor magnets us , max udc , max uc , max (7)
must be taken into account. In order to reduce the zero voltage 3
sequences in the MSC, the absolute value of the reference where udc,max is the maximum dc bus voltage and uc,max is the
current error Δisq is also compared to a fixed threshold ξ. The maximum amplitude of the GSC converter output voltage.
priority is assigned as follows: Considering that the maximum dc bus voltage is one and a
GSC control , if isd < igd and isq <
half times the rated value (udc,max=1.5 udc,n), the maximum
priority
(5) speed should be limited to 50% of the rated speed. Therefore,
MSC control , otherwise
the fault-tolerant converter requires power semiconductors and
1216
a capacitor bank with one and a half times the voltage rating. AC Load Encoder Torque Sensor PMSM
Machine
In comparison to the topologies proposed in [5], [7]-[10],
which require an increase of 100% of the dc-link voltage,
independently of the system operating point, the proposed
topology has an improved voltage capability.
The current rating of the switches in both MSC and GSC
are the same as in the SLC, except for the shared leg. The
current rating for the common leg is equal to the sum of the Grid-Side PMSM-Side
Converter Converter
machine phase current and the grid phase current. Considering
that the generator and grid rated RMS currents are equal, and
in order to avoid the oversizing of the converter current
ratings, the load torque should be limited to 50 % of the rated
torque. If the rated torque is intended to be reached, the shared Voltage & Current Protection
leg has to be designed to withstand a rated current two times Filter Sensors Boards Relay
as high. The proposed topology has an improved current Fig. 3. General view of the power stages.
capability in comparison to the FLC-SL topologies based on
the machine/transformer neutral point connection [14], where
the current in the shared leg has to be designed to withstand a
10
rated current four times as high. iA iB iC
1217
TABLE I: PMSG PARAMETERS.
Power P 2.2 kW 5 iA iB iC
of the GSC. 0
In Fig. 4, the fault is introduced at t = 0.7 s under a load
-5
torque equivalent to 42 % of the machine rated load torque,
triggering the remedial procedures after the fault detection. -10
Leg “B” command signals are forced to zero, and TRIAC 0.3 0.4 0.5 0.6 0.7 0.8 0.9
TRb is then turned on, while the switching state is Time (s)
reformulated and the reference dc-bus voltage is increased to 600
Mechanical Speed (rpm)
1218
control techniques, requiring a lower increment of the dc-bus [14] N. M. A. Freire and A. J. M. Cardoso, “Fault-tolerant PMSG drive with
reduced dc-link ratings for wind turbine applications,” IEEE J. Emerg.
voltage to maintain the drive operation with satisfactory Sel. Topics Power Electron., vol. 2, no. 1, pp. 26-34, Mar. 2014.
performance. Simulations and experimental results were [15] I. Jlassi, J.O. Estima, S. Khojet El Khil, N. Mrabet Bellaaj and A. J. M.
presented, demonstrating the feasibility of the proposed fault- Cardoso, “Multiple open-circuit faults diagnosis in back-to-back
tolerant PMSG drive. converters of pmsg drives for wind turbine systems,” IEEE Trans.
Power Electron., vol. 30,no. 5, pp. 2689-2702, May 2015.
ACKNOWLEDGMENT
This work was supported in part by Santander Totta under
fellowship BIPD/ICI-FE-Santander Universidades-UBI/2016.
This work was also supported by the European Regional
Development Fund (ERDF) through the Operational
Programme for Competitiveness and Internationalization
(COMPETE 2020), under Project POCI-01-0145-FEDER-
029494; and by National Funds through the FCT - Portuguese
Foundation for Science and Technology, under Projects
PTDC/EEI-EEE/29494/2017, UID/EEA/004131/2013, and
SFRH/BD/131002/2017.
REFERENCES
[1] F. Spinato, P. J. Tavner, G. J. W. V. Bussel and E. Koutoulakos,
"Reliability of wind turbine subassemblies," IET Renew. Power Gener.,
vol. 3, no. 4, pp. 387–401, Dec. 2009.
[2] W. Qiao and D. Lu, “A survey on wind turbine condition monitoring and
fault diagnosis-part I: components and subsystems,” IEEE Trans. Ind.
Electron., vol. 62, no. 10, pp. 6536–6545, Oct. 2015.
[3] U. M. Choi, F. Blaabjerg, and K. B. Lee, “Study and handling methods
of power igbt module failures in power electronic converter systems,”
IEEE Trans. Power Electron., vol. 30, no. 5, pp. 2517–2533, May 2015.
[4] W. Sae-Kok, D. M. Grant, and B. W. Williams, “System reconfiguration
under open-switch faults in a doubly fed induction machine,” IET
Renew. Power Gener., vol. 4, no. 5, pp. 458–470, Sep. 2010.
[5] N. M. A. Freire and A. J. M. Cardoso, “A fault-tolerant direct controlled
pmsg drive for wind energy conversion systems,” IEEE Trans. Ind.
Electron., vol. 61, no. 2, pp. 821–834, Feb. 2014.
[6] N. M. A. Freire and A. J. M. Cardoso, “A fault-tolerant PMSG drive for
wind turbine applications with minimal increase of the hardware
requirements,” IEEE Trans. Ind. Appl., vol. 50, no. 3, pp. 2039–2049,
May/Jun. 2014.
[7] D. Zhou, J. Zhao, and Y. Liu, “Independent control scheme for
nonredundant two-leg fault-tolerant back-to-back converter-fed
induction motor drives,” IEEE Trans. Ind. Electron., vol. 63, no. 11,
pp. 6790–6800, Nov. 2016.
[8] C. B. Jacobina, I. S de Farias, E. R. C. da Silva, A. M. N. Lima, and R.
L. de A Ribeiro, “Reduced switch count dc-link ac–ac five-leg
converter,” IEEE Trans. Power Electron., vol. 21, no. 5, pp. 1301–1310,
Sep. 2006.
[9] C. B. Jacobina, R. L. de A Ribeiro, A. M. N. Lima and E. R. C. da Silva,
“Fault-tolerant reversible ac motor drive system,” IEEE Trans. Ind.
Appl., vol. 39, no. 4, pp. 1077-1084, Jul./Aug. 2003.
[10] M. Jones, S. Vukosavic, D. Dujic, E. Levi, and P. Wright, “Five-leg
inverter pwm technique for reduced switch count two-motor constant
power applications,” IET Electric Power Appl., vol. 2, no. 5, pp. 275–
287, Sep. 2008.
[11] C. S. Lim, E. Levi, M. Jones, N. A. Rahim and W. P. Hew, “A
comparative study of synchronous current control schemes based on
fcs-mpc and pi-pwm for a two-motor three-phase drive,” IEEE Trans.
Ind. Electron., vol. 61, no. 8, pp. 3867-3878, Aug. 2014.
[12] C. S. Lim, E. Levi, M. Jones, N. A. Rahim and W. P. Hew, “A
fault-tolerant two-motor drive with fcs-mp-based flux and torque
control,” IEEE Trans. Ind. Electron., vol. 61, no. 12, pp. 6603-6614,
Dec. 2014.
[13] D. Zhou, J. Zhao and Y. Li, "Model-predictive control scheme of
five-leg ac–dc–ac converter-fed induction motor drive," IEEE Trans.
Ind. Electron., vol. 63, no. 7, pp. 4517-4526, Jul. 2016.
1219