Академический Документы
Профессиональный Документы
Культура Документы
And
Spare Parts List
And
MODELS
ANL/AVL-100 AVL-120 AVL-140
AVR-100 AVR-120 AVR-140
50 Hz
INTRODUCTION
This Service Manual provides comprehensive technical documentation for SKY split air
conditioners, models ANL-100, AVL-100 and AVL-120.
This information contained in the manual is useful for application engineers, architects, designers
and various level service and installation personnel.
The manual also contains information about the optional features offered by the SKY series, as
well as helpful information for service personnel on split air-conditioners, electrical wiring
diagrams, refrigeration cycle diagrams and cooling & heating capacity curves for the various
models.
Product specifications are subject to change without notice.
1. GENERAL DESCRIPTION
Options
Model
H C
ANL 100 ٧ ٧
AVL 100
AVL 120 ٧ ٧
AVL 140
AVR 100
AVR 120 ٧ ٧
AVR 140
-3-
CAPACITY BTU/H Cooling and heating capacity in BTU/Hr. according to ISO 5151 standard.
CAPACITY W Cooling and heating capacity in Watts according to ISO 5151 standard.
SERIAL NO. Unit serial number. If blank – serial number is printed on Bar Code label.
-4-
ANL-100 AVL-100
Model 50Hz
R22 R407C R22 R407C
Btu/h 96700 95000 96700 95000
Cooling capacity Kcal/h 24409 23940 24409 23940
Watt 28341 27842 28341 27842
Btu/h 97300 95540 97300 95540
Heating capacity Kcal/h 24560 24076 24560 24076
Watt 28517 28000 28517 28000
Power Consumption cooling Watt 11500 11300 11500 11300
Power Consumption Heating Watt 11000 11100 11000 11100
Operating Current cooling Amp 19.3 19.1 19.3 19.1
Operating Current Heating Amp 18.5 18.6 18.5 18.6
E.E.R-Energy Efficiency Ratio Cool 8.4 8.4 8.4 8.4
C.O.P-Coefficient Of Performance Heat 2.6 2.52 2.6 2.52
Moisture Removal Lit/h 11.7 11.7 11.7 11.7
Power Supply Volt/Hz/ph 380/415V, 50Hz, 3ph 380/415V, 50Hz, 3ph
Condensate Lines - Drain Ф - mm (in) 28.5 (1 1/8") 28.5 (1 1/8")
Liquid/Gas Lines Ф - inch 1/2" ; 7/8" (insulated) 1/2" ; 7/8" (insulated)
Maximum Piping Length m. 30 30
Maximum Height Difference m. 12 12
Time Delay Fuse Amp. 3x32 3x32
Control Mode I.R. Remote Control / Auto I.R. Remote Control / Auto
Temperature Control Microcomputer Microcomputer
A/C Options: C/H HDE option is under development C/H HDE option is under development
Indoor Unit 50Hz ANL-100 AVL-100
Front Panel Color RAL 7032 RAL 7032
Air Filter 1 Removable/Washable 1 Removable/Washable
Air Direction Control Air Ducts Air Ducts
Dimensions (LxDxH) mm 1300x580x800 1500x480x700
3
m /h 4760/3400/2890 5440/4420/2890
Air Flow (Turbo/High/Low)
cfm 2800/2000/1700 3200/2600/1700
Noise Level (Turbo/High/Low) dba 37/33/30 36/32/30
Net Static Pressure mm H2O 20 10
Net Weight Kg. 120 117
Indoor Fan Motor: HP 0.75 2x0.5
Speed (Turbo/High/Low) R.P.M 900/820/750 900/800/700
Full Load Amperage Amp. 4.6 2x2.6
Motor Capacitor µF/Volt 15/400 2x8/400
Blower Wheel Type Centrifugal Centrifugal
Outdoor Unit 50Hz ANL-100 AVL-100
Casing Color RAL 7030 RAL 7030
Dimensions (LxDxH) mm 1700x830x1000 1700x830x1000
3
m /h 16150/7990 16150/7990
Air flow (High/Low)
cfm 9500/4700 9500/4700
Noise Level (High/Low) dba 75/63 75/63
Net Weight Kg. 250 250
Fittings Type Flare Flare
MT125 MT125
Compressor Thermal Protection Internal
Overload Overload
Full Load Amperage Amp. 3x17 3x17
Locked Rotor Amperage Amp. 3x105 3x105
Capillary Expansion valve Expansion valve
R22 gr. 8100 8100
Refrigerant Charge
R407C gr. 7500 7500
R22 "Bristol" Zerol 150T Zerol 150T
Oil for Compressor
R407C "Bristol" Hatcol 22A Hatcol 22A
Outdoor Fan Motor KW 2x0.66 2x0.66
Speed R.P.M 900 900
Motor Full Load Amperage Amp. 3x1.7 3x1.7
-5-
AVL-120 AVL-140
Model 50Hz
R22 R407C R22 R407C
Btu/h 120300 118000 144000 141000
Cooling capacity Kcal/h 30366 29736
Watt 35258 34583 42204 41324
Btu/h 121500 117700 145400 141600
Heating capacity Kcal/h 30669 29660
Watt 35610 34500 42614 41500
Power Consumption cooling Watt 14000 13100 17000 16700
Power Consumption Heating Watt 13300 13000 16100 15800
Operating Current cooling Amp 23.5 23.2 28.6 28.0
Operating Current Heating Amp 22.3 21.8 27.1 26.5
E.E.R-Energy Efficiency Ratio Cool 8.6 8.55 8.47 8.44
C.O.P-Coefficient Of Performance Heat 2.67 2.65 2.64 2.62
Moisture Removal Lit/h 14.6 14.6 16 16
Power Supply Volt/Hz/ph 380/415V, 50Hz, 3ph 380/415V, 50Hz, 3ph
Condensate Lines - Drain Ф - mm (in) 28.5 (1 1/8") 28.5 (1 1/8")
Liquid/Gas Lines Ф - inch 1/2" ; 7/8" (insulated) 1/2" ; 7/8" (insulated)
Maximum Piping Length m. 30 30
Maximum Height Difference m. 12 12
Time Delay Fuse Amp. 3x40 3x40
Control Mode I.R. Remote Control / Auto I.R. Remote Control / Auto
Temperature Control Microcomputer Microcomputer
A/C Options: C/H HDE option is under development C/H HDE option is under development
Indoor Unit 50Hz AVL-120 AVL-140
Front Panel Color RAL 7032 RAL 7032
Air Filter 1 Removable/Washable 1 Removable/Washable
Air Direction Control Air Ducts Air Ducts
Dimensions (LxDxH) mm 1600x550x800 1600x800x660
3
m /h 6800/5730/5100 8160/6800/5730
Air Flow (Turbo/High/Low)
cfm 4000/3400/3000 4800/4000/3400
Noise Level (Turbo/High/Low) dba 38/34/31 43/38/34
Net Static Pressure mm H2O 17 18
Net Weight Kg. 136 143
Indoor Fan Motor: HP 2x0.75 2x0.75
Speed (Turbo/High/Low) R.P.M 900/820/750 900/820/750
Full Load Amperage Amp. 2x4.6 2x4.6
Motor Capacitor µF/Volt 2x15/400 2x15/400
Blower Wheel Type Centrifugal Centrifugal
Outdoor Unit 50Hz AVL-120 AVL-140
Casing Color RAL 7030 RAL 7030
Dimensions (LxDxH) mm 1700x830x1000 1700x830x1000
3
m /h 16150/7990 16150/7990
Air flow (High/Low)
cfm 9500/4700 9500/4700
Noise Level (High/Low) dba 75/63 75/63
Net Weight Kg. 283 305
Fittings Type Flare Soldering
MT160 MT160
Compressor Thermal Protection Internal
Overload Overload
Full Load Amperage Amp. 3x22 3x22
Locked Rotor Amperage Amp. 3x130 3x130
Capillary Expansion valve Expansion valve
R22 gr. 10000 12000
Refrigerant Charge
R407C gr. 9300 11150
R22 "Bristol" Zerol 150T Zerol 150T
Oil for Compressor
R407C "Bristol" Hatcol 22A Hatcol 22A
Outdoor Fan Motor KW 2x0.66 2x0.66
Speed R.P.M 900 900
Motor Full Load Amperage Amp. 3x1.7 3x1.7
-6-
Evaporator Side
Air Filter 1 Removable/Washable 1 Removable/Washable 1 Removable/Washable
Air Direction Control Air Ducts Air Ducts Air Ducts
3
m /h 5440/4420/2890 6800/5730/5100 8160/6800/5730
Air Flow (Turbo/High/Low)
cfm 3200/2600/1700 4000/3400/3000 4800/4000/3400
Noise Level (Turbo/High/Low) dba 36/32/30 38/34/31 43/38/34
Net Static Pressure mm H2O 10 17 18
Fan Motor: HP 2x0.5 2x0.75 2x0.75
Speed (Turbo/High/Low) R.P.M 900/800/700 900/820/750 900/820/750
Full Load Amperage Amp. 2x2.6 2x4.6 2x4.6
Motor Capacitor µF/Volt 2x8/400 2x15/400 2x15/400
Blower Wheel Type Centrifugal Centrifugal Centrifugal
Condenser Side
3
m /h 16150/7990 16150/7990 16150/7990
Air flow (High/Low)
cfm 9500/4700 9500/4700 9500/4700
Noise Level (High/Low) dba 75/63 75/63 75/63
MT125 MT160 MT160
Compressor Thermal Protection Internal
Overload Overload Overload
Full Load Amperage Amp. 3x17 3x22 3x22
Locked Rotor Amperage Amp. 3x105 3x130 3x130
Capillary Expansion valve Expansion valve Expansion valve
R22 gr. 8100 10000 12000
Refrigerant Charge
R407C gr. 7500 9300 11150
R22 "Bristol" Zerol 150T Zerol 150T Zerol 150T
Oil for Compressor
R407C "Bristol" Hatcol 22A Hatcol 22A Hatcol 22A
Outdoor Fan Motor KW 2x0.66 2x0.66 2x0.66
Speed R.P.M 900/700 900/700 900/700
Motor Full Load Amperage Amp. 3x1.7 3x1.7 3x1.7
-7-
The Cooling and Heating Characteristics curves are mainly intended for use by air conditioning
engineers as an aid in designing systems and in determining the capacity and number of units
required at a given site.
The air conditioner capacities were determined in accordance with ISO 5151 standard operating
conditions:
Design parameters for a given site are often different than the standard conditions. Therefore, the
design engineer should use the capacity charts which follow to calculate the capacity of the air
conditioners under the intended working conditions, in order to optimize the selection of air
conditioner units for use at a particular site.
-8-
*COOLING CAPACITY
30
29.5
29
CAPACITY [KW]
28.5
28
27.5
27
26.5
26
25.5
24 28 32 35 40 44
o
OUTDOOR TEMP [ C]
**HEATING CAPACITY
40
35
30
CAPACITY [KW]
25
20
15
10
5
0
-15 -10 -5 0 5 7 10 15
OUTDOOR TEMP [oC]
-9-
*COOLING CAPACITY
39
38
CAPACITY [KW]
37
36
35
34
33
24 28 32 35 40 44
o
OUTDOOR TEMP [ C]
**HEATING CAPACITY
50
45
40
35
CAPACITY [KW]
30
25
20
15
10
5
0
-15 -10 -5 0 5 7 10 15
OUTDOOR TEMP [ oC]
- 10 -
COOLING CAPACITY
46
45
44
CAPACITY KW
43
42
41
40
39
24 28 32 35 40 44
o
OUTDOOR TEMP C
HEATING CAPACITY
60
50
CAPACITY KW
40
30
20
10
0
-15 -10 -5 0 5 7 10
o
OUTDOOR TEMP C
- 11 -
350 300
PRESSURE [PSI]
300 250
PRESSURE [PSI]
200
250 150
200 100
150 50
0
100
-10 -5 0 5 7 10 15
24 28 32 35 40 44
OUTDOOR TEMP. [ oC]
OUTDOOR TEMP [ oC]
70
76
60
74 PRESSURE [PSI]
50
72
PRESSURE [PSI]
70 40
68 30
66 20
64 10
62 0
60 -10 -5 0 5 7 10 15
24 28 32 35 40 44
OUTDOOR TEMP. [oC]
OUTDOOR TEMP [ oC]
12.6
25
12.4
12.2 20
12
15
dT [ºC]
11.8
dT [ºC]
11.6 10
11.4
5
11.2
11 0
24 28 32 35 40 44 -10 -5 0 5 7 10 15
- 12 -
300
PRESSURE [PSI]
PRESSURE [PSI]
350
300 250
200
250
150
200 100
150 50
100 0
24 28 32 35 40 44 -10 -5 0 5 7 10 15
o o
OUTDOOR TEMP [ C] OUTDOOR TEMP. [ C]
76 70
74
PRESSURE [PSI]
60
PRESSURE [PSI]
72 50
70
40
68
66 30
64 20
62 10
60 0
24 28 32 35 40 44 -10 -5 0 5 7 10 15
o
OUTDOOR TEMP [ C] OUTDOOR TEMP. [ C]o
12.6 25
12.4
20
12.2
12 15
dT [oC]
dT[oC]
11.8
11.6 10
11.4
5
11.2
11 0
24 28 32 35 40 44 -10 -5 0 5 7 10 15
OUTDOOR TEMP [oC] OUTDOOR TEMP. [oC]
- 13 -
300
PRESSURE [PSI]
PRESSURE [PSI]
350
300 250
200
250
150
200 100
150 50
100 0
24 28 32 35 40 44 -10 -5 0 5 7 10 15
o o
OUTDOOR TEMP [ C] OUTDOOR TEMP. [ C]
76 70
74
PRESSURE [PSI]
60
PRESSURE [PSI]
72 50
70
40
68
66 30
64 20
62 10
60 0
24 28 32 35 40 44 -10 -5 0 5 7 10 15
o
OUTDOOR TEMP [ C] OUTDOOR TEMP. [ C]o
12.6 25
12.4
20
12.2
12 15
dT [oC]
dT[oC]
11.8
11.6 10
11.4
5
11.2
11 0
24 28 32 35 40 44 -10 -5 0 5 7 10 15
OUTDOOR TEMP [oC] OUTDOOR TEMP. [oC]
- 14 -
- 15 -
- 16 -
- 17 -
- 18 -
TURBO
HIGH
Low
6000
5000
4000
Air Flow ANL-100
Q [m /h]
3000
3
2000
1000
0
45
40
35
30
25
20
15
10
P [m m H 2 O ]
- 19 -
P [m m H 2 O ]
10
15
20
25
30
35
0
5
0
1000
2000
4000
5000
6000
Low
HIGH
TURBO
- 20 -
TURBO
HIGH
Low
8000
7000
6000
Air Flow AVL-120
5000
Q [m /h]
4000
3
3000
2000
1000
0
45
40
35
30
25
20
15
10
P [m m H 2 O ]
- 21 -
P [mmH 2O]
10
15
20
25
30
35
0
5
0
2000
Low
high
turbo
- 22 -
TH1 TH2
TH3
FUSE 6A 8
6
blue
green/yellow
INDOOR UNIT
RH
TH3 TH3
RVS RVS
PS
2 1
RH
7
CCF1
COMP
3 yellow
RVS
FAN1
1
black
OF
CCF2
RNV
NV
FAN2
H
white 4 3
2 brown NV CC
R
9 RNV
4 mm
8 4 mm COMP
4 mm
6 blue
N
green/yellow
POWER
GR R S T N
SUPPLY OUTDOOR UNIT
LEGEND:
FC- Indoor fan motors capacitor RVS- 4-way valve coil NV-Phase control
PS- Head pressure control CCF1,CCF2-Outdoor fans contactors RNV-Aux.relay
RH-Cancel high pressure control CC- Compressor contactor H-High pressure control
(heating mode only)
- 23 -
TH1 TH2
TH3
9
connect to point "2"
FUSE 6A 8
6
blue
green/yellow
INDOOR UNIT
RH
TH3 TH3
RVS RVS
PS
2 1
RH
7
CCF1
COMP
3 yellow
RVS
FAN1
1
black
OF
CCF2
RNV
NV
FAN2
H
white 4 3
2 brown NV CC
R
9 RNV
4 mm
8 4 mm COMP
4 mm
6 blue
N
green/yellow
POWER
GR R S T N
SUPPLY OUTDOOR UNIT
LEGEND:
FC- Indoor fan motors capacitor RVS- 4-way valve coil H-High pressure control
PS- Head pressure control CCF1,CCF2-Outdoor fans contactors CT-Turbo speed contactor
RH-Cancel high pressure control CC- Compressor contactor CH-High speed contactor
(heating mode only) NV-Phase control CL-Low speed contactor
RNV-Aux.relay
- 24 -
7.1 General
These instructions are intended as general guidelines. The instructions refer to ANL and AVL
products. The air conditioner must be installed by trained and authorized personnel.
Use 7/8" and 1/2"copper tubing for connecting the outdoor and indoor units:
The installation must be performed in accordance with manufacturer's specifications using only
approved tubing, original cables and original accessories.
Display cable 8m. Insulation for fittings Wall mounted unit (RT)
Fig. 7-1
NOTE: The compressor is equipped with oil heating element. Main circuit breaker and
power supply must therefore always be ON.
If disconnected, make sure that power supply was ON at least 6 hours before starting the
unit.
- 25 -
Fig. 7-2
The indoor and outdoor units should be installed as close to each other as possible. Do not exceed
the tubing length and height differences as shown in the accompanying table. See Fig. 7-3 for
additional information.
Model Maximum Tubing Length Maximum Height Difference Between Units
ANL-100, AVL-100/120/140 30 m 12 m
Fig. 7-3
- 26 -
• Make sure to leave sufficient space around the unit. See figure 6-4 for minimum required
distance between the unit and nearby walls.
• Install the unit in a location with convenient access for service and maintenance purposes.
• Protect the unit from any heat source such as direct sun rays.
• Prevent from any dust or strong wind installation sites.
• Position the unit in such a way to minimize motor noise which reaches the user and
neighbors.
• The unit must be installed at least 5 cm. above a solid surface.
• Make sure that the unit is level.
• Fasten the unit legs to the base. Place the rubber absorbtion cushions (supplied) under the
unit's legs to prevent vibrations.
• For models ANL-100 and AVL-100/120/140 hanging installation is allowed. Install only
on special platform or concrete slab.
• A drainage tube can be connected to the outdoor unit to remove condensation formed
during heating mode operation.
a d
b
c
Fig. 7-4
Distance
Model
a mm b mm c mm d mm
ANL-100 700 600 1000 200
AVL-100 700 600 1000 200
AVL-120 800 700 1000 200
AVL-140 800 700 1000 200
- 27 -
B
B
C C A
A
Fig. 7-5
Dimensions
Model
A mm B mm C mm D mm E mm
ANL-100 1300 580 800 400 345
AVL-100 1500 480 700 970 295
AVL-120 1600 550 800 1190 345
AVL-140 1600 660 800 1190 345
• Allow free access to the service door, air filter and control box.
• Carefully plan the drainage tube path at a minimum slope of 2% avoiding sharp bends or oil
traps.
• The indoor unit may be installed either hanging from the ceiling or resting on hard surface
(i.e. concrete).
• Whenever possible, lead the indoor unit drainage tube to the outdoor unit.
• Stick four rubber absorbtion cushions on the four corners of the base, as shown in Fig. 7-4.
• Select the installation location according to the abovementioned factors and guidelines.
• Select the installation location according to the abovementioned factors and guidelines.
• Mark 4-6 holes on the ceiling, according to the unit's mounting bracket holes.
• If the ceiling is made of concrete, drill holes for the long ceiling anchors.
• Stick four rubber absorbtion cushions on the four corners of the base, as shown in Fig. 7-5.
• Attach the unit to the ceiling using the long anchor screws, as shown in Fig. 7-5.
- 28 -
• To make the connections between the indoor and outdoor units, a 70 mm hole should be
drilled for the refrigerant lines, drainage hose and electrical cable passage, through the wall,
as shown in Fig. 7-6.
• Make sure to drill outwards and downwards, so that the opening in the outside wall is at
least 10 mm lower than the opening on the inside.
• Route the drainage hose at the bottom of the hole.
• Fill in the remaining wall hole gap with an appropriate sealant.
Fig. 7-6
CONCR ETE
CEILING SLEEVE
R UB BER
CUS HION AIR DUCT
DRAIN HO SE
CONNE CTION
2 min
Fig. 7-7
- 29 -
Connect the rubber syphon to the drain hose connection. See Fig. 7-8 for details.
Fig. 7-8
• To connect the refrigerant lines use only "L" type sealed, dehydrated copper refrigerant
tubing. No other type may be used. The use of other types of tubing will void the
manufacturer's warranty.
• Do not open service valves and do not remove protecting caps from tubing ends until all the
connections are made.
• Take care to avoid links or flattening of the tubing.
• Bend tubing with special bending tools to avoid the formation of sharp bends.
• Keep the tubing free of dirt, sand, moisture and other contaminants to avoid damaging the
refrigerant system.
- 30 -
Torque
Valve Type Tubing
Kg m
Liquid Small 1/2" 5
When all the fittings are connected, air must be purged as follows:
• Open the service port cap on the suction line valve (large valve).
• Connect the vacuum pump to the service port via the pressure gauge and operate the pump
for 30 minutes.
• Make sure that full vacuum is reached and disconnect the vacuum pump.
• Open the liquid line valve (small valve) with an Allen-Wrench for the purpose.
• Open the suction line valve (large valve) using an Allen-Wrench for the purpose.
• The outdoor unit is supplied with sufficient refrigerant for eight meters tubing. Add
refrigerant and oil according to the table, for each meter of tubing used. If the tubing is
shorter than eight meters, release gas from the system through the service valve into a
recycling device.
• Close the service port caps on the suction line and the liquid valves.
• Make sure that the valves are properly opened. Be careful not to open them more than
required, as this may damage the thread.
• Replace the stem cap. Oil the cap beam and hand tighten the cap, until resistance is met.
Use a suitable wrench to tighten the cap by an additional 1/6 turn.
• Check the system for refrigerant leaks using a leak detector.
- 31 -
• Remove the two units illustrated in Figure 6-10 from their packaging.
• Attach each unit to the wall with two screws. Use the template attached to the packaging to
assist in positioning the screws for the wall mounted unit.
• The two units must be positioned in the same room in such a way that there is an unimpeded
line of sight between them.
Fig. 7-10
10
2 R
6 S
8 T
9 N
GREEN / YELLOW
OUTDOOR SENSOR CABLE (Th3)
Fig. 7-11
- 32 -
MOTORS
HARNESS
CLAMP
FAN MOTOR
FUSE
DISPLAY CABLE (8m)
DISPLAY
SENSOR
CLAMP
INTER-UNIT
WALL MOUNTED UNIT (RT) DISPLAY CLAMP
ELECTRICAL CABLE
Fig. 7-12
Place the control box on the indoor unit service door, or up to 1.5 m. from the unit. The box
should be conveniently located for access by service personnel. Protect both the control box
and the electrical connections from water and high humidity.
• Remove the control box cover. Locate the connectors according to the drawing on the
inside of the box cover.
• Connect the fan motor harness (10-pin connector) to the connector labeled "Indoor Fan"
and secure the clamp.
• Route sensor TH1 to the air feedback area (near the air filter) and connect the outer end to
its appropriate control box location.
• Connect sensor TH2 to its appropriate location.
• Place the wall mounted unit 1 up to 8 meters from the control box; choose a position from
which it is possible to receive commands from anywhere in the room.
• Connect "DISPLAY" cable to the wall mounted unit and connect the other end to the
appropriate place (labeled DP "DISPLAY") in the control box.
• Connect the inter-unit electrical cable to the terminal block 3, using a screw driver to insert
the stripped wire end (8 mm.). Make sure that the wires are connected in accordance with
the wiring diagram in Fig. 7-11.
• Attach the inter-unit electrical cable with the cable clamp located on the control box.
• Attach the sensors cables TH1, TH2, TH3, Display cable and Electrical cable in place and
secure the clamp.
• Close the control box.
- 33 -
P LUG TO CONNE CT
W ITH OUTDOOR
S E NS OR CABLE (Th3)
INTE R -UNIT
E LE CTRICAL CABLE
CLAMP
Fig. 7-13
- 34 -
Explain the following items to the user, with the aid of the User Manual:
• How to turn the air conditioner on and off; selecting cooling, heating and other operating
modes; setting a desired temperature; setting the timer to automatically start and stop air
conditioner operation; and the other features of the remote controller and display panel.
• How to remove the air filter and adjust the air deflectors.
• Present the User Manual and this installation sheet to the customer
- 35 -
4. A/C does not receive 4. Make sure that noting blocking the
transmitted commands. R/C transmission to the A/C display.
2 Only indoor fan 1. The selected mode is on 1. Check if the R/C is on the desired
ventilator works Fan Only, or on Cool when mode. If not, select the correct mode
although cooling or heating is desired. (refer to your User Manual). Also note
heating is desired. that each 15 min. (max), the
compressor will be switch on for 3
min. (at least).
3 Only indoor fan 1. In Heat mode: Head 1. Wait up to 90 seconds. Check air flow
motor and pressure is too high. through indoor evaporator. Eventually
compressor clean filter.
working. Outdoor 2. In Cool mode: system runs
fan motor stopped. while evaporator Anti-Ice
routine takes place. 2. Wait up to 90 seconds until Anti-Ice
routine is completed.
- 36 -
5 Only indoor fan 1. Overload safety device on 1. Switch Off power and try again after
motor and outdoor compressor is cut out due one hour.
fan motor are to high temperature.
working. No
cooling and/or 2. Compressor run capacitor 2. Replace compressor run capacitor.
heating take place. is burnt.
6 No air supply at 1. Indoor fan motor is blocked 1. Check voltage. Repair wiring if
indoor unit or turns slowly. necessary.
(compressor
operates). 2. Indoor fan motor capacitor 2. Check indoor fan wheel if tight on
is burnt. motor shaft. Tighten if necessary.
8 In Heat mode: only A/C operates in De-Icing cycle. Wait (max.) 10 min. until the A/C resumes
compressor runs, to normal operation.
outdoor and indoor
fan motors are
stopped.
AIR CON indicator
flashes.
- 37 -
10 Water dripping Water drain outlet or the spout Open condenser cover, clean out water
from the condenser is clogged. outlet, and clean the base inside
base (in Heat thoroughly.
mode).
11 R/C fail to active 1. The 3-position slide switch 1. Change the slider position to REMOTE
the on the A/C display is in (RMOT).
prescribed AUTO or OFF position.
functions.
. 2. Faulty R/C settings. 2. A. If R/C symbols respond to the
commands correctly, check the A/C ID
Code (Standard or Alternative). Refer
to "Changing A/C ID Code" and to R/C
DIP switch 3 setting.
B. If Cool commands are OK, but Heat
symbol is skipped on LCD, refer to R/C
DIP switch 7 setting.
C. Replace R/C.
- 38 -
- 39 -
12. Service valves are not 12. Open the valves full.
fully open.
2 Air circulation Air filter is clogged. Clean air filter.
failure.
- 40 -
- 41 -
- 42 -
12 POWER & AIR Normal Operation This is normal operation when the A/C
CON lamps lit, enters the thermostat stop, and the
COMPRES lamp ‘minimal halt period’ (5 min.) is passed.
flashes. This indication will continue until the first
thermostat demand or the ‘maximal halt
period’ (15 min.) will elapse.
- 43 -
- 44 -
29 30 31 32 ONLY
AVL
ONLY
1
AVL
ONLY
2
28
3
4
27 5
6
26
7
8
25
9
10
AVL
ONLY 11
24 12
13
AVL 14
ONLY
15
23
16
ANL
ONLY
22
17
18
21 20 19
- 45 -
- 46 -
18
17
16
3
5
6
15 7
8
14
9
10
13 12 11
- 47 -
- 48 -
13 12 11 10
- 49 -
- 50 -
13
1
12
11
2
10
3
9
5
6
- 51 -
Electrical Components
Part No.
No. Part Description
AVR-100 AVR-120 AVR-140
1b Axial Fan with motor and protector 405Z063 405Z063 405Z063
6 Contactor 1001AB26 1001AB26 1001AB26
7 Contactor 1001AB09 1001AB09 1001AB09
8 Normally Open Relay 1001G7L0 1001G7L0 1001G7L0
9 RST Controller 1001RSTC 1001RSTC 1001RSTC
Assembly Parts
Part No.
No. Part Description Qty.
AVR-100 AVR-120 AVR-140
1 Centrifugal Fan – Right 1 N/A 4021138 4021120
2 Centrifugal Fan – Left 1 N/A 4021138 4021120
3 Centrifugal Fan – Right 4021120 N/A N/A
4 Centrifugal Fan – Left 4021120 N/A N/A
5 Fitting – Flare 1 1106MF12 1106MF58 1106MF78
6 Fitting – Flare 1 1106MF78 N/A N/A
7 Plastic Joint 1 1009SB22 1009SB22 1009SB22
8 Plastic Fastening Screw 4 13010043 13010043 13010043
9 plastic handle 2 15050001 15050001 15050001
10 Duralast filter 1/2" 1 15040050 15040052 15040053
11 Evaporator Heat Exchanger 1 50104C8 5010486 50104E8
12 Fan Connector Cable 1 10050071 10050071 10050071
13 Indoor Unit Coil Sensor Cable 1 1005T002 1005T002 904TS11
- 52 -