Motorized change-over

Change-over switches switches


OTM_F_C_

Installation instruction
34OTM_F_C_ / 1SCC303009M0201
Installation instruction, OTM_F_C_

Contents
Mounting and dimensional drawings............................................................................................................ 4
Mounting positions........................................................................................................................................ 5
Control circuit................................................................................................................................................ 5
Manual operation: Local................................................................................................................................ 6
Electrical operation: Remote......................................................................................................................... 6
Automatic operation...................................................................................................................................... 7
Impulse control.............................................................................................................................................. 8
Continuous control........................................................................................................................................ 8
Locking.......................................................................................................................................................... 9
Locking state information.............................................................................................................................. 9
Technical data............................................................................................................................................. 10
Terminal clamp sets: OZX_......................................................................................................................... 11
Bridging bars: OMZC_................................................................................................................................ 11
Terminal shrouds: OTS_.............................................................................................................................. 12
Auxiliary contact blocks: OA_..................................................................................................................... 13
Handle storage: OTVS0............................................................................................................................... 13
Fourth pole: OTP_....................................................................................................................................... 14

II
OTM
I

I II
O OFF

I ON II ON

O OFF

I ON II ON

O OFF

I ON II ON
A06080

3
1SCC303009M0201, rev. A
Installation instruction, OTM_F_C_ Mounting and dimensional drawings: OTM30-125F_C_

OTM40 OTM63-125
2,5...25mm2 / 2 x 2,5 -16mm2 10...70mm2
12 56 14...4 AWG  / 2 x 14 - 6 AWG 8...2/0 AWG
M4 80
3Nm 56 12
Note:
26.6 lb.in.
Use protection against direct contact.
ø 4,5 For example:
DIA0.18

II
II
OTM OTM

I I 1
90

4 mm
0,16 in
6 Nm
55 lb.-in.

Remove
1
II

II
OTM
I 0
OFF

ON
I
OTM

I 3
OTM

35

A06077
I

1,38 Fuse Reset


II

EN 50022 2

OTM30-125F_C_ 116
115 99
33,5 108 83
M00352/OTM30-125F_C_M A
52
7 22,5 26 75
40 Ø4,5
10
11 14

EN50022
OTM

45 60 35
90
100 65

6,5 44
56 80 56 74,5 35
26,5 12 12

14 65

12

16
230 ( 3-pole ) 12
283 ( 4-pole )

4
1SCC303009M0201, rev. A
Mounting positions, Control circuit Installation instruction, OTM_F_C_

Mounting positions

II

II
OTM
I I

A06078
Control Circuit

Only an authorised electrician may perform the electrical installation and maintenance
of motorized switch. Do not attempt any installation or maintenance actions when a
motorized switch is connected to the electrical mains. Before starting work, make sure
that the switch is de-energised.

3
4

3 I II 4
II
OTM
I
F2

1 PE N
L
2 C II
I 0

A B C
A06079

2
1

1. Terminal for motor operator voltage supply


2. Control terminal for push buttons
3. Terminal for state information (also used with the automatic control unit)
4. Control terminal for automatic control unit (If used OMD controller)

Do not couple power for the control terminal. See the correct terminal for the power
supply.

5
1SCC303009M0201, rev. A
Installation instruction, OTM_F_C_ Manual operation: Local, Electrical operation: Remote

Manual operation: Local

A06081
II
OTM

II I
OTM
I

 !
ICK
1 CL 2

Electrical operation is prevented when the handle is attached to the switch panel.

Electrical operation: Remote

Never open any covers on the product. There may be dangerous external control
voltages inside the motorized switch even if the voltage is turned off.

Never handle control cables when the voltage of the motorized switch or external
control circuits are connected.

Exercise sufficient caution when handling the unit.


OTM
OTM
1 3 4
OTM
OTM OTM
I
I I
Fuse Reset
II
Fuse Reset
II Fuse Reset
II
A06082

Fuse Re
II Fuse Re
OTM set

set

2
I

6
1SCC303009M0201, rev. A
Electrical operation: Automatic operation Installation instruction, OTM_F_C_

Automatic operation
OTM

X
31

X
21
4
I ON

II
OTM

3
Fuse Res
2 et
A06084

See detailed installation instructions for OMD controllers from OMD user manuals.

Resetting Fuse

Fuse Re
set
2
II 2
Fuse Re
set
A06083

7
1SCC303009M0201, rev. A
Installation instruction, OTM_F_C_ Impulse control, Continuous control

Impulse control

I II 0

>100 ms >100 ms >100 ms

I - command II - command 0 - command

I - position

0 - position

A06085
II -position

Continuous control

0 - command

I - command II - command 0 - command

I - position

0 - position
A06086

II - position

If a new command is given before the switch has reached the position of the
previous command, the internal protection may operate.

8
1SCC303009M0201, rev. A
Locking, Locking state information Installation instruction, OTM_F_C_

Locking
Prevent manual and electrical operation.

Locking possible at any position. Check position before locking.

I
1 3 4
OTM II
II Position
I - 0 - II

ONI
I

ONI I
OTM

I
5
4...5mm
2 OTM II

A06088
ONI I
State information
OTM OTM OTM
I
II
II OTM II OTM
OTM I
I
ON
II

4 4 4
4
1 2 3

1 1 1

Fuse Res
II Fuse Res
II
et Fuse Res
et et

I II

2 3 2 3 2 3
O I II
OFF ON ON
A06095

1 1 1 1 1 1

9
1SCC303009M0201, rev. A
Installation instruction, OTM_F_C_ Technical data

Technical data

Motor operator, control circuit Value Cabling/Rating

Rated operational voltage U [V] 110-240 Vac/dc 50-60Hz


24 Vdc
Operating voltage range 0.85... 1.1 x U
Operating angle 90° 0-I, I-0, 0-II, II-0; 180° I-0-II
Operating time See Table 2
Protection degree IP 20, front panel
Rated impulse withstand voltage Uimp 4 kV
Voltage supply PE N L 1,5 -2,5mm2
F2 Max. MCB 16A
Control terminal for the push-buttons C II I 0 1,5 -2,5mm2
Maximum cable length 100 m
Terminal for state information 1 2 3 4 1,5mm2
Also used with the automatic control unit
I II 3A AC-1/250V
Common, voltage supply 1
Position of change-over switch I 2
Position of change-over switch II 3
Handle attached or motor operator locked 4
SCPD Max. MCB C2A
Control terminal for automatic control unit 1,5-2,5mm2
If used OMD_ controller
1 2 3
Common, voltage supply from motor operator 1 24VDC
Close switch I or open switch II 2 24VDC 500mW
Close switch II or open switch I 3 24VDC 500mW
Operating temperature -25... +55 °C
Transportation and storage temperature -40... +70 °C
Altitude Max. 2000m

Table 1 General technical data of motor operators

Type Voltage Nominal Current Operating Operating OFF-time


Ue current a) Inrush a) time a) transfer when
In I-0, 0-I, time a) operating a)
0-II, II-0 I-II or II-I I-II or II-I
[V] [A] [A] [s] [s] [s]
OTM140...125_C 110-240 Vac/dc 0,2 - 0,5 1,5 - 3,0 0,5 - 1,0 1,2 - 1,5 0,4 - 0,8
OTM40...125_C
24 Vdc
a) Under nominal conditions

Table 2 Specified technical data of motor operators

10
1SCC303009M0201, rev. A
Terminal clamp sets OZX_, Bridging bars OMZC_ Installation instruction, OTM_F_C_

OZX_

1 OTM63-125F_C
2
OZXL1 OZXT3
10...70 mm OZXL1 OZXT3 OZXT4
8...2/0 AWG OZXT4

OZXT6 OZXT1
3
OZXT1 OZXT6
A06089

II
OTM

OMZC_
2
OTM
ON
100 I

OTM I
ON
I

I 3
Fuse Reset
II
Fuse Reset
II 125
53

1
OMZC03, OMZC04 OMZC003, OMZC004
4mm 6Nm 10...70mm2 2,5...25mm2
0,16in 55lb.-in. 8...2/0AWG 14...4 AWG
2x2,5...16mm2
2x14... 6 AWG

OTM
ON
I

OTM40-125F_C   OMZC03
I
OTM40F_C OMZC003
Fuse Reset
II

OTM40-125F_C   OMZC04
A06090

OTM40F_C    OMZC004

11
1SCC303009M0201, rev. A
Installation instruction, OTM_F_C_ Terminal shrouds OTS_

OTS_

OTS125T3 3
2

IIII
II OTM
I
OTM
0
OFF
1
ON
I

OTS125T1

2 3

I IIII
1 I
OTM

OTM
ON
I

I
OMZC03, OMZC003 II
OTS125T3
Fuse Rese
t

OMZC04, OMZC004
OTS125T3 + OTS125T1
A06091

OTS125T1 OTS125T3 OMZC_

12
1SCC303009M0201, rev. A
Auxiliary contact blocks OA_, Handle storage OTVS0 Installation instruction, OTM_F_C_

OA_
NO NC NO NC
I max 2
II max 2
OA 1G10 OA 8G01
I
OA 7G10 OA 1G01
1 I
0 0
II II II

OTM 13
I 14
13 11
14 12
11
12
23 36
21
2x0,75...2,5mm2 54 OA2G11
2x18...14AWG 37

2 0,8 Nm
7 lb.-in. 11
8,75
13
POZIDRIVE

A06092
M3,5 Form 2
max 2
3 OA1G10
II OA8G10
OA2G11
max 2 I
OTM

OA1G01 OA2G11
OA7G01 For 3-pole only
OA2G11

OTVS0
6
230
1 A B

5800
3
365
1

2
II
OTM

I
A06093

13
1SCC303009M0201, rev. A
Installation instruction, OTM_F_C_ Fourth pole OTP_

OTP_

1 OTPD60FP
OTP_
OTPD125FP
C II I
OTM
2
A I O 1

N
OFF
B O
N
N

OTM40 OTPS60FP OTPL60FP OTPN60FP OTPE60FP N


OTM63-125 OTPS125FP OTPL125FP OTPN125FP OTPE125FP N

(N)7 L4 N N PE N

(N)8 T4 N N PE

OTM63-125
10...70mm2
8...2/0 AWG

2 3 OTM40
2,5...25mm2
14...4 AWG
2 x 2,5 -16mm2
2 x 14...6 AWG
IIII OTM

OTM
I
I
A06094

6 Nm
55 lb.-in.

4 mm
0,16 in

14
1SCC303009M0201, rev. A
Printed by: Waasa Graphics Oy, Vaasa Finland
Producted by: GRAFIMER, Vaasa, Finland

ABB Oy The technical data and dimensions are valid


at the time of printing. We reserve the right to
Low Voltage Switches subsequent alterations.
P.O Box 622
FI-65101 VAASA, Finland
Telephone +358 10 22 11
Telefax +358 10 22 45708
www.abb.com