TPR6 series Gas Insulated RMUs D

D 6.6 U1 / U3 type
Bus Coupling Unit with 630 A Disconnector
It is used with the RMU units in medium voltage open or
closed ring distribution structures' medium voltage
distribution centers for the purpose of connecting two
different busbars with Disconnector and Load Break Switch.
Earthing disconnector option is supplied by U3 type switchgear.

The U1 type RMU can be selected to permit expansion to the


right or left. Furthermore, cable and busbar connection
from the top is also possible.

U1 U3 Switchgear Equipment Standard Options


Pressure Gage x
Capacitive Voltage Indicator Set x
LT Type Operating Mechanism x
Opening Disconnector Coil (for 3D Type) x
0 0 Disconnector auxiliary contacts x
+ + Earthing Disconnector x
Earthing Disconnector auxiliary contacts x
K K motor for Disconnector spring Charging: x
(for type 3D)
Disconnector Interlock (Open) x
Earthing Disconnector Interlock (Open) x
Earthing Disconnector Interlock (Close) x
Disconnector Key Lock x
Earthing Disconnector Key Lock x
LV Control Panel x
Short Circuit Lamp Indicator x
Earthing Fault Lamp Indicator x
* The alternative mechanism for LT type Disconnector mechanism can be used in case
a 3D type mechanism is used.

Switchgear Dimensions (for 630 A)


Rated Voltage (kV) Width (mm) Depth (mm) Height (mm)
1 - 24 450** 717 1200 / 1500*
36 - 40.5 625 912 1830
Avaiable Options
* Height of the unit is 1500mm when used together with a C Type module:
Not expandable to the right or left 0 * In case an expansion will not be made, the width is 350 mm.:
Expandable +
Side Cable Entry and Outlet I
Busbar or cable entry-outlet from the top K

75
a Friem & Aktif Group Company
D TPR6 series Gas Insulated RMUs

D 6.7 U2 type
Bus Coupling Unit with 630 A Circuit Breaker
It is used with the RMU units in medium voltage open or
closed ring distribution structures' medium voltage
distribution centers for the purpose of connecting two
different busbars with Disconnector or Load Break Switch
and Circuit Breaker contains secondary protection function.

The U2 type RMU can be selected to permit expansion to the


right or left. Furthermore, cable and busbar connection
from the top is also possible.

Switchgear Equipment Standard Options


Pressure Gage x
Capacitive Voltage Indicator Set x
LT + TCB Type Operating Mechanism x
630A/1250A Vacuum Breaker x
0 0 Breaker Opening Relay x
Breaker auxiliary contacts x
+ +
Breaker central Interlock system* x
K K Disconnector auxiliary contacts x
Earthing Disconnector auxiliary contacts x
Disconnector Interlock (Open) x
Earthing Disconnector Interlock (Open) x
Earthing Disconnector Interlock (Close) x
Disconnector Key Lock x
Earthing Disconnector Key Lock x
Secondary protection relay x
Low Voltage relay x
Breaker Engine for setting the spring: x
Breaker Closing Relay x
LV Control Panel x
Short Circuit Lamp Indicator x
Earthing Fault Lamp Indicator x
* when the Disconnector is off and breaker is on, lock key can be moved.

Switchgear Dimensions (for 630 A)


Rated Voltage (kV) Width (mm) Depth (mm) Height (mm)
1 - 24 450 717 1200 / 1500
36 - 40.5 750 912 1830
Avaiable Options
* Height of the unit is 1500 mm when used together with a C Type module
Not expandable to the right or left 0
Expandable +
Side Cable Entry and Outlet I Switchgear Dimensions (for 1250 A) **
Busbar or cable entry-outlet from the top K Rated Voltage (kV) Width (mm) Depth (mm) Height (mm)
1 - 24 600 717 / 1000 1500 / 2250 *
** K type upper expansion option can only be possible by use of a bar.

76
a Friem & Aktif Group Company
TPR6 series Gas Insulated RMUs D

D 6.8 UCB type


Bus Coupling Unit with 630 A Circuit Breaker
It is used with the RMU units in medium voltage open or
closed ring distribution structures' medium voltage
distribution centers for the purpose of connecting two
different busbars with Circuit Breaker and secondary
protection relay.

The UCB type RMU can be selected to permit expansion to


the right or left. Furthermore, cable and busbar connection
from the top is also possible.

Switchgear Equipment Standard Options


Pressure Gage x
Capacitive Voltage Indicator Set x
CB6 Type Operating Mechanism x
630A/1250A Vacuum Breaker x
0 0 Breaker Opening Relay x
Breaker auxiliary contacts x
+ +
Breaker central Interlock system* x
K K Secondary protection relay x
Low Voltage relay x
motor for C.B spring Charging x
Breaker Closing Relay x
LV Control Panel x
Short Circuit Lamp Indicator x
Earthing Fault Lamp Indicator x
* when the breaker is on, lock key can be moved.

Switchgear Dimensions (for 630 A)


Rated Voltage (kV) Width (mm) Depth (mm) Height (mm)
1 - 24 450 717 1200 / 1500
36 - 40.5 750 912 1830
Avaiable Options
* Height of the unit is 1500 mm when used together with a C Type module
Not expandable to the right or left 0
Expandable +
Side Cable Entry and Outlet I Switchgear Dimensions (for 1250 A) **
Busbar or cable entry-outlet from the top K Rated Voltage (kV) Width (mm) Depth (mm) Height (mm)
1 - 24 600 717 / 1000 1500 / 2250 *
** K type upper expansion option can only be possible by use of a bar.

77
a Friem & Aktif Group Company
D TPR6 series Gas Insulated RMUs

D 6.9 Q type
Measuring Unit with Circuit Breaker (for 36 kV)
It is used with the RMU units in medium voltage open or
closed ring distribution structures' medium voltage
distribution centers for the purpose of measurement of
electricity consumption at the busbar by entering to the
busbar by a cable or another busbar.

A cable or busbar connection to a Q Type RMU from the top


is possible.

Switchgear Equipment Standard Options


Pressure Gage x
Capacitive Voltage Indicator Set x
K x
LT + TCB Type Operating Mechanism
630A/1250A Vacuum Breaker x
Breaker Opening Relay x
Breaker auxiliary contacts x
Breaker central Interlock system* x
Disconnector auxiliary contacts x
Earthing Disconnector auxiliary contacts x
Disconnector Interlock (Open) x
Earthing Disconnector Interlock (Open) x
Earthing Disconnector Interlock (Close) x
Disconnector Key Lock x
Earthing Disconnector Key Lock x
Secondary protection relay x
Low Voltage relay x
motor for Circuit Breaker spring Charging x
Breaker Closing Relay x
LV Control Panel x
Short Circuit Lamp x
Earthing Fault Lamp Indicator x
Current Transformer Cable Connection x
Current Transformer x
Voltage Transformer x
* when the Disconnector is off and breaker is on, lock key can be moved.

Switchgear Dimensions (for 630 A)


Rated Voltage (kV) Width (mm) Depth (mm) Height (mm)
36 1000 1150 1830 *
Avaiable Options
* Except the upper bar section
Not expandable to the right or left 0
Expandable +
Side Cable Entry and Outlet I
Busbar or cable entry-outlet from the top K

78
a Friem & Aktif Group Company
TPR6 series Gas Insulated RMUs D

D 6.10 M type
Measuring Unit

It is used with the RMU units in medium voltage open or


closed ring distribution structures' medium voltage
distribution centers for the purpose of measurement of
electricity consumption at the busbar.

The M type RMU can be selected to permit expansion to the


right or left. Busbar connection to a M Type RMU from the
top is possible.

Switchgear Equipment Standard Options


Connection Bushings x
Current Transformer Mounting plate x
Voltage Transformer Mounting plate x
1 or 2 piece Electric Connection Kit x
0 0 No 2-3 Current Transformer x
No 2-3 Voltage Transformer x
+ +
LV Control Panel x
K K Fuse and Fuse-Box x

Switchgear Dimensions (for 630A)


Rated Voltage (kV) Width (mm) Depth (mm) Height (mm)
1 - 24 850 717 1200
36 - 40.5 1100 1150 1830
Avaiable Options
Not expandable to the right or left 0
Expandable +
Side Cable Entry and Outlet I
Busbar or cable entry-outlet from the top K

79
a Friem & Aktif Group Company
D TPR6 series Gas Insulated RMUs

D 7 Sample Busbar Design with RMU

0L L L F0 Sample 1 :

A medium voltage busbar with 1 Incoming and 3 Outgoings, not


expanding to the right or left, consisting of L type Incoming unit
with a load separator (not expandable to the right) where
busbar Incoming is made and 2 L type Outgoing units with a F
type unit (no expandable to the right).

With the notation of “0 L”, it is stated that the far most left hand
side L type unit cannot be expanded to the left and similarly
with “F 0”, the far right hand side F type Switchgears will not
expand to the right.
Sample 1

Sample 2 :
+L L F F+
A medium voltage busbar with 1 Incoming and 3 Outgoings,
expandable to the right and left, consisting of L type Incoming
unit with load separator (expendable to the left) where busbar
Incoming is made and 2 F type unit (expendable to the right).

With the notation of “+ L”, it is stated that the far most left hand
side L type unit can be expanded to the left and similarly with
“F +”, the far right hand side F type Switchgears can be
expanded to the right.

Sample 2

Sample 3 :
I F0
A circuit breaker protection solution is derived with an F type
unit that could not expand o the right hand side, by direct cable
connection module for energy feeding.

With the notation of “F O”, it is stated that the left hand side F
type unit cannot be expanded.

Sample 3

80
a Friem & Aktif Group Company
TPR6 series Gas Insulated RMUs D

Sample 4 :
0L L+ M +F F0
Busbar Incoming is performed with L type Incoming unit with
load separator (not expandable to the left) and Outgoing is
realized with 1 L type unit (expandable to the right) and in
addition, one M unit added to the busbar. It is a busbar solution
by addition of an F unit that is extendable to the left on the right
hand side, and addition of 2 F type not extendable units to the
left hand side of the busbar.

With the notation of “0 L”, it is stated that the far most left hand
Sample 4 side L type unit cannot be expanded to the left and similarly
with “L +”, the far right hand side L type Switchgears can be
expanded to the right and with “+ F” notation, it is shown that
the additional unit on the left can be added to the medium
voltage busbar from the far right hand side and with “F 0”
notation it is indicated that the far right hand side Switchgears
can be expanded from its right hand side.

0L LK OF FK OF FK Sample 5 :

This is a sample application of connecting three medium


voltage busbar composed of two units are connected with a
cable or busbar overhead.

In the first busbar “0 L” coded unit describes that the unit with
a load separator cannot be expanded to the left and the unit
with “L K” is an Outgoing unit that can be connected with a
cable or busbar.
Sample 5
The units with the notation of “0 L” on the second and third
busbars indicates these unites that are protected by load
separator circuit breaker are not expandable to the left, and “F
K” notation shows that these load separator circuit breaker
protected transformers can have Outgoing with cable or a
busbar from the top.

Sample 6 :
0L L FO M
In this sample, the energy has been transferred to a busbar by
an L unit which has a load separator and is not expandable to
the right and one Outgoing is secured by an L unit which does
not expand to the right and has a load separator as well as two
Outgoings by an F unit that has a load separator circuit breaker
and does not expand to the right.

In this sample, it is noted that the unit with “0 L” code cannot


expand to the left and has Incoming-Outgoing with a load
separator, “L” denotes Incoming-Outgoing with load separator
with no expandability either to the right or left, whereas the unit
Sample 6 that has "F 0" indicates that it is a Incoming-Outgoing unit with
circuit breaker and load separator and it does not expand to the
right. The unit with an “M” code is a measurement unit that
does not expand to the right or left and the Incoming or
Outgoing is only performed by a cable.

81
a Friem & Aktif Group Company
E 1 Switching Equipment 84
E 1.1 Circuit Breakers 84
E 1.1.1 SVC Series Vacuum Circuit Breakers 84
E 1.1.2 SION/3AH (Siemens) Vacuum Circuit Breakers 86
E 1.1.3 EVOLIS (Schneider) Vacuum Circuit Breakers 86
E 1.1.4 SF1 (Schneider) SF6 Gas Circuit Breakers 86
E 1.1.5 SF2 (Schneider) SF6 Gas Circuit Breakers 86
E 1.2 Vacuum Contactors 87
E 1.3 LBS and Disconnectors 87
E 2 Protection Devices 88
E 2.1 Relays 88
E 2.1.1 M series Digital Protection Relays 88
E 2.1.2 MC series Digital Protection Relays 88
E 2.1.3 ULTRA series Protection Relays 88
E 2.1.4 DTVA series Distance Protection Relays 88
E 2.1.5 ANSI codes Relay Application Table 89
E 2.1.6 Relay Management Software 90
E 2.2 Circuit Breakers 90
E 3 Measuring Devices 91
E 3.1 Capacitive Voltage Indicators 91
E 3.2 Analyzers 92
E 3.2.1 NQM series Energy Analyzers 92
E 3.2.2 NPM series Power Analyzer 92
E 3.2.2 Energy Management Software 92
E 3.3 Power Quality Recorders 93
E 3.3.1 2400d series Power Quality Recorder 93
E 3.3.2 2400ip series Power Quality Recorder 93
E 3.3.3 2400R series Power Quality Recorder 93
E 3.3.4 2400duo series Power Quality Recorder 93
E 3.3.5 2400i series Power Quality Recorder 93
E 3.4 Electricity Meters 94
E 3.4.1 MT860 Electricity meter for Transmission & Production 94
E 3.4.2 MT830 Electricity meter for Distribution & Industry 94
E 3.4.3 MT372 Electricity Meter for Small Size Commercial Subscribers 94
E 3.4.4 MT173 Electricity Meter for Small Size Commercial Subscribers 94
E 4 Measuring Transformers 95
E 4.1 Current Transformers 95
E 4.2 Voltage Transformers 95

82
Auxiliary
Equipment
E 1 Auxiliary Equipment Switching Equipment

E 1 Switching Equipment
E 1.1 Circuit Breakers
Aktif Elektroteknik use followings Vacuum or SF6 gas
insulated circuit breakers in air insulated medium voltage
Switchgears in conformity with IEC 62271-100 standards.

1.1.1 SVC (Aktif) Vacuum Circuit Breaker (are manufactured


up to the capacities of 40.5 kV, 3150A, 31.5 kA and are used
in the production).
1.1.2 SION/3AH (Siemens) Vacuum Circuit Breakers
1.1.3 EVOLIS (Schneider) Vacuum Circuit Breakers
1.1.4 SF1 type (Schneider) SF6 gas insulated Circuit Breakers
1.1.5 SF2 type (Schneider) SF6 gas insulated Circuit Breakers

E 1.1.1 SVC series Vacuum Breakers

SVC series Vacuum Circuit breakers are designed by Aktif


and their patent is obtained. In this manner the Switchgears
and breakers are supplied from one source.

Three pieces excellent insulated high quality Vacuum


interrupters are used In SVC series Vacuum Circuit breakers
as placed inside a special casing.

4 5 7

A D D
8
1
B
2 9
6

3
C

1. Label
2. Interlock arm
3. Auxiliary carrying support
4. Contacts 3,6kV 7,2kV 12kV 17,5kV 24kV 36kV 40,5kV
5. Mechanism box A 200 200 200 200 200 350 350
6. Push mechanism B 320 320 320 320 320 455 455
7. Busbar shell C 775 775 775 775 775 1150 1150
8. Tube protector D 700 700 700 700 700 930 930
9. 48 pin plug E 640 640 640 640 640 960 960

84

a Friem & Aktif Group Company


Auxiliary Equipment Switching Equipment E 1

The SVC units have compact structures and provide sturdy,


safe mechanical operation.

SVC series Vacuum Circuit Breakers are also designed as


drawer type.

The electrical arc is insulated in the vacuum environment and


extinguished within the vacuum. When an internal arc formed,
the extinguishing process takes place within the vacuum tube;
hence there would not be any release to the outside. The
vacuum tube does not need any maintenance. Due to its
general characteristics its contact structure would not be
deteriorated. Therefore it can be used more efficiently when
compared to similar products.

E 1.1.1.1 Application Areas

SVC units are used in the following application areas:

Overhead transmission lines


Distribution and transformer centers
Cables
Transformers
Motors
Generators
Capacitor banks

E 1.1.1.2 Advantages

Fulfilling committed energy targets


Excellent performance
Excellent Endurance
Long operation life
Low maintenance cost (fast and economic maintenance)

Technical Specifications:
Description Unit Values
Rated Voltage (Ur) kV 3,6 7,2 12 17,5 24 36 40,5
Power frequency 1 minute high frequency withstand voltage (Ud) kV 10 20 28 38 50 70 85
withstand Voltage Lightning impulse withstand voltage (Up) kV 40 60 75 95 125 170 190
Rated Frequency (Fr) Hz 50 / 60
Rated Current (Ir) A 630 - 1250 - 1600 - 2000 - 2500 - 3150
Rated short time withstand current(lk) kA/3s 16 - 25 - 31,5 16 - 25
Rated short time withstand current(lp) kA 40 - 63 - 80 40 - 63
Operational sequence O - 0,3s - CO - 180s - CO
Capacitive load switching current (lc) A 400
Closing time ms 35 - 60
Opening time ms 40 - 50
Process time ms 60
Mechanical Life op. 20.000
Rated control circuit voltage V DC: 24, 110 / AC: 220
Operational temperature C° -5°...+40°

85

a Friem & Aktif Group Company


E 1 Auxiliary Equipment Switching Equipment

E 1.1.2 SION/3AH (Siemens) Vacuum Circuit Breaker


The vacuum breakers are subjected to routine tests during
production and these tests are harder than the
requirements of the standards.
Current measurement data flow
Decisive measurement data
Low power loss
Long term thermal stability
The vacuum circuit breakers do not need maintenance
Under normal operational conditions, 10000 opening and
closing as per IEC 60694 and VDE 0670 part 1000
The performance remains within the limits even in frequent
usage after long term stand-by periods
Environmentally sensitive.

E 1.1.3 EVOLIS (Schneider) Vacuum Circuit Breaker


Evolis vacuum breakers have 3 poles and they are for
internal use. This kind of circuit breaker is used for the
switching and protection purposes in the industry, public
sector and energy distribution.
These types of breakers are suitable for LSC2B type metal
partitioned metal clad sells.
Rated Voltage : up to 24 kV
Rated Current : up to 2500 A
Short Circuit switching Current : up to 40 kA

E 1.1.4 SF1 type (Schneider) SF6 Gas insulated Circuit Breaker


SF1 with 3 poles is for medium voltage internal usage. Between
1 kV and 40.5 kV, this kind of circuit breaker is used for the
switching and protection purposes in the industry, public sector
and commercial distribution. The SF1 breaker equipped with
automated compression technique and uses SF6 gas during
current cutting phase. There are 3 types of SF1:
Horizontal type suitable for metal enclosed LSC2A
Switchgears
Rated Voltage : up to 40.5 kV
Rated Current : up to 1250 A
Short Circuit switching Current : up to 25 kA

E 1.1.5 SF2 type (Schneider) SF6 Gas insulated Circuit Breaker


SF2 with 3 poles is for medium voltage internal usage. Between
24 kV and 38 kV, this kind of circuit breaker is used for the
switching and protection purposes in the industry, public sector
and commercial energy distribution. These types of breakers
are suitable for LSC2B metal clad Switchgears.
Rated Voltage : up to 40.5 kV
Rated Current : up to 2500 A
Short Circuit switching Current : up to 31.5 kA

86

a Friem & Aktif Group Company


Auxiliary Equipment Switching Equipment E 1

E 1.2 Vacuum Contactors


The vacuum contactors have 3 poles and have cycle capacity
of over 1 million in the medium voltage facilities with their high
electromagnetic characteristics.

The vacuum contactors are also performed for alternative


current facilities for the below given purposes:

Motor start-up
Switching of transformers
Switching of reactors
Switching of big resistive loads similar to those in electric
furnaces
Switching of capacitor banks

E 1.3 Load Break Switches


SLB series Load Break Switches used are in conformanity with
IEC 60295-1 and 62271-102 standards and load break switches
are able to switch the circuit on load. The rated current is up to
630 A and the short circuit withstand is up to 20 kA.

The Load Break Switch has SF6 gas and it switches on load.
It has 3 poles and 3 modes (open - close - earthed). The
Earthing Disconnector is located in Load Break Switch
structure.

E 1.4 Disconnectors
In close position In open position Grounding
E 1.4.1 SF6 gas insulated Disconnectors

SGD series SF6 gas insulated Disconnectors are used in


conformity with IEC 60295-1 and 62271-102 standards. The
rated current is up to 1250 A and the short circuit withstand
is up to 25 kA.

Furthermore, it has SF6 gas and it has opening and closing


feature without load. It has 3 poles and 3 modes (open -
close - earthed). The Earthing Disconnector is located in
Load Break Switch structure.

E 1.4.2 Air insulated Rotary Switches

SRS series Air Insulated Rotary Switches have rated current


of up o 1250 A and short circuit withstand current of up to 25
kV and are used in Metal Enclosed Switchgears.

E 1.5 Earthing Disconnectors


SES series earthing switches are manufactured and
produced with 3 second withstand up to 31.5 kA and 1
second withstand up to 50 kA.

87

a Friem & Aktif Group Company


E 2 Auxiliary Equipment Protection Devices

E 2 Protection Devices
E 2.1 Relays
Microelettrica Scientifica secondary protection relays are used
in our products. These relays are digital and able to provide
protection in different applications and functions. These relays
have Modbus RTU, IEC 60870-103 or IEC 61850 communication
protocols; are classified as M series, MC series, Ultra series
and DTVA series. The protection functions that can be done
with these relays are;
Current & Voltage protection
Feeder, Line and Busbar protection
Transformer protection
Motor and Generator protection
Capacitor feeder protection
In addition to these protection functions, trip and event recording
can also be obtained. These relays provide easy to use feature with
their draw-out execution. Relays can communicate with MSCom2,
Actwin RM and any Scada software.

E 2.1.1 M series
These relays are microprocessor based and are used in high
and medium voltage systems.
They have Modbus RTU communication protocol and R485
serial communication port at the back.

E 2.1.2 MC series
Different protection features are combined in these relays
due to its compact structure.
They have one R485 serial communication port at the back
and there is one RS232 serial communication port on the
front panel.

E 2.1.3 ULTRA series


These relays can be used in any application in transmission,
distribution and industrial plants.
It combines protection, measurement and control features.
In addition to R485 serial communication port at the back
and one RS232 serial communication port on the front panel,
Modbus RTU/IEC60870-5-103/IEC61850/TCP-IP
communication protocols are also presented.

E 2.1.4 DTVA series


These relays make distance protection in 3 phase, phase to
phase and phase to ground faults.
These relays are distance protection relays that have auto
reclosing function.
The communication can be done by RS232 from the front panel
and by fiber optic connection from the rear of the equipment.
These relays have the functions of remote testing by a
computer,collecting the measured values and setting.

88

a Friem & Aktif Group Company


Auxiliary Equipment Protection Devices E 2

E 2.1.5 ANSI codes Application Tables

Sekonder Koruma Röleleri Genel Uygulama Tablosu

IM30-B00

MC30-RG
DTVA-EP

MM30-W
IM30-AB

IM30-SR
IM30-AP

IM30-DT

IM30-SA
IM30-BY

MM30-D
DTMR-3

MD32-G
MC30-R

UM30-A
DM30-S

MD32-T
MD33-T

M-HIB3
M-LIB3
IM30-D

IM30-G
IM30-C

IM30-T

RIA123
SCM21
SPM21
MTR33

UFD14
UFD34
DLMR

MW33
DTMR

MM30
DM33

MC1V
MC3V

MG30
MC20
MC30

MMR
MCM
GMR
FMR

MFP
12 /14 Speed Control
21 Distance protection / Under impedance
24 Volts per Herz
25 Synchronization and/or synchrocheck
27 Under Voltage (AC)
27/59 Under/over Voltage (AC)
27/59d Under/over voltage of positive sequence
32 Directional Power
37 Under current or under power
40 Loss of field
46 Reverse phase or phase balanced current
46N Unbalanced protection for capacitors
47 Phase sequence or phase balance voltage
48 Control of motor starting sequence
49 Thermal protection for machine or trafo
50/51 Instantaneous / time delayed over current
50/51N Instantaneous / time delayed earth fault
50/51V Voltage restrained over current
51BF Breaker failure protection
51LR Locked rotor protection
55 Power factor
59 Over voltage (AC)
59Uo Zero sequence over voltage
60FL Fuse failure
64 Ground fault protection (insulation)
64S Machine stator ground fault
64SEF Sensitive earth fault protection
66 Control of motor starting number
67 AC directional over current relay
67N Directional earth fault relay
68 Blocking output
74 Trip circuit supervision
78 Phase angle or out of step protection
79 Reclosing
81 Frequency
86 Lock-out
87 Differential protection
87/85 Pilot cable differential protection
87B Busbar differential protection
87N Differantial earth fault current
90 Regulating control
df/dt Frequency rate of change
dv/dt Voltage rate of change
I2t Breaker interruption energy
Osi Oscillographic waveform capturing
2xIn Automatic threshold doubling on inrush
2-set Double setting

Note: This table is prepared by taking into consideration of frequently used relays. There are a lot of relays
applicablefor protection functions that are not listed here being used. Please ask for a copy of detailed
product catalogue for other relays and protection functions that are not listed in this table.

89

a Friem & Aktif Group Company


E 2 Auxiliary Equipment Protection Devices

E 2.1.6 Relay Management Software


MSCom2

It communicates with any Microelettrica Scientifica relays.


Real time measurement and all system and function settings
are possible.
It can communicate with up to 250 relays.
Firmware update is available.
Free of charge.
Real time measuring can be performed.

ActWin RM
It is developed for remote monitoring and control of the relays.
GPRS and RS485 communications are available.
All events, alarms and all other operations are recorded.
It provides protection against unauthorized interference with
its three level of authorization scheme.
Monitoring and control over the mobile phones and
computers are available.
Drawing a single line diagram and displaying relay on it, is
provided.

Actwin Mobile

It is the Mobile phone version of ActWin RM.

E 2.2 Fuses
The fuses that are used in our products safely protect the
transformers, cable, capacitor banks against thermal effects
and short circuits between the 6 kV and 36 kV.

Appropriate circuit breaker selection can be made by using


below provided reference table.
Trans-
former Rated Voltage U1N= 17,5 kV U2N = 400V Rated Voltage U1N= 20/24 kV U2N = 400V Rated Voltage U1N= 30/36 kV U2N = 400V
Rated
Power Transformer MV Rated LV Rated Transformer MV Rated LV Rated Transformer MV Rated LV Rated
(KVA) Rated Current Fuse Current Fuse Current Rated Current Fuse Current Fuse Current Rated Current Fuse Current Fuse Current
prim. sec. min. max. min. max. prim. sec. min. max. min. max. prim. sec. min. max. min. max.
(A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
25 1,0 36 4 6,3 31,5 40 0,7 36 4 6,3 31,5 40 0,5 36 2 6,3 31,5 40
50 1,9 72 6,3 10 63 80 1,4 72 6,3 6,3 63 80 1,0 72 4 6,3 63 80
75 2,9 108 10 10 100 125 2,2 108 6,3 6,3 100 125 1,4 108 6,3 6,3 100 125
100 3,8 144 10 16 125 160 2,9 144 10 10 125 160 1,9 144 6,3 6,3 125 160
125 4,8 180 16 20 160 200 3,6 180 10 16 160 200 2,4 180 6,3 10 160 200
160 6,2 231 16 25 200 250 4,6 231 16 20 200 250 3,1 231 10 16 200 250
200 7,7 289 20 25 250 315 5,8 289 16 20 250 315 3,8 289 10 16 250 315
250 9,6 361 25 31,5 315 400 7,2 361 20 25 315 400 4,8 361 16 20 315 400
315 12,1 455 25 31,5 400 500 9,1 455 20 25 400 500 6,1 455 16 25 400 500
400 15,4 577 25 40 500 630 11,5 577 25 40 500 630 7,7 577 16 25 500 630
500 19,2 722 31,5 50 630 720 14,4 722 31,5 50 630 720 9,6 722 25 31,5 630 720
630 24,2 909 40 63 800 900 18,2 909 40 63 800 900 12,1 909 31,5 40 800 900
800 30,8 1155 63 80 1000 1200 23,1 1155 50 63 1000 1200 15,4 1155 40 50 1000 1200
1000 38,5 1443 80 100 1200 - 28,9 1443 63 80 1200 - 19,2 1443 40 50 1200 -
1250 48,1 1804 100 100 - - 36,1 1804 80 80 - - 24,1 1804 50 63 - -
1600 61,6 2309 125 125 - - 46,2 2309 100 100 - - 30,8 2309 63 80 - -
2000 77,0 2887 160 160 - - 57,7 2887 125 125 - - 38,5 2887 2x50 - -

90

a Friem & Aktif Group Company


Auxiliary Equipment Measuring Devices E 3

E 3 Measuring Devices

E 3.1 Capacitive voltage indicators


The voltage indicators that we use in our products work on
the principle of measuring of capacitive voltage.

It provides excellent results in displaying the presence of the


voltage without supply.

They are manufactured according to IEC 61243-5 standard.

Technical Specifications

Standards : IEC 61243-5


Display of Phase : No display U<%10 Un
Led light on U>%10 Un
o o
Operational Temperature Range : -25O C … +70O C
o o
Storage Temperature Range : -30O C … +80O C
Protection Class : IP 54

91

a Friem & Aktif Group Company


E 3 Auxiliary Equipment Measuring Devices

E 3.2 Power & Energy Analyzers


Analyzers combine voltmeter, cosphimeter, wattmeter,
var-meter and frequency-meter into single equipment.
Therefore, it is possible to make savings from space, cable
and cost of equipment.
The data read can be transferred to SCADA or energy
Management Software on a computer via communication
ports that on the equipment. Since this data is kept in the
data base of the equipment, it provides simplicity in fault
determination. Furthermore consumption figures for the
past periods can be obtained hence planning towards future
can be made more consistently.
Due to digital outputs provided by the equipment it has
became indispensible part of SCADA systems. Transducer
usage becomes unnecessary by the help of some models
which have analog outputs.
Due to these features, the analyzers become essential part
of any management or automation system.

E 3.2.1 NQM series Energy Analyzers


Large 128 x 128 graphic LCD
Embedded memory for measurements records (with
extendable memory)
Programmable digital outputs (maximum 6)
Digital inputs may be used as a counter (for gas and water
meters) and position monitoring (maximum 8)
Programmable analog outputs (maximum 4)
RS232 and RS485 communication ports
Current and voltage waveform display on the screen
Harmonic analysis
Faulty connection warning

E 3.2.2 NPM series Power Analyzer


RS485 communication port
4 LED screen that can be read remotely
Display of more than 30 electrical parameter

E 3.2.3 Energy Management Software


Actwin Energy Management Software reads all energy
parameters of Asset Power Analyzers and digital Electricity
Meters and records the data with time labels. It supports various
communication interfaces as well as communication protocols.
With different reporting and monitoring screens, various reports
and invoices can be created by the parameters recorded and can
be viewed in different formats in real time.
The most important feature of the software is that the data reading is
possible from multiple ports simultaneously and this increases
communication speed to a maximum level. In this manner, it is possible
to obtain more reading and create much more detailed reports.

92

a Friem & Aktif Group Company


Auxiliary Equipment Measuring Devices E 3

E 3.3 Power Quality Recorders


Energy quality recorders are the necessary equipment for
analyzing the quality of electric networks according to
related standards (EN 50160, IEC 6100-4-7). The various
electrical parameters such as flickers, harmonics,
inter-harmonics, symmetric components, instability and
energy can be monitored simultaneously.

According to EN 50160, IEC 61000-3-6/7 standards, all


statistical data relating to quality of the energy of the
distribution and transmission systems including voltage sag,
swell and interruptions and so on are recorded by IEC
61000-4-30 class A and detailed reporting in conformity with
the standards are made.

E 3.3.1 2400d Series Power Quality Recorder


DIN rail type, compact structure, suitable for placing in a panel.
Without an external connection, assembled solutions
RS232 and USB connection
GPS and pulse synchronization
Screwed input terminal blocks
Ethernet and website interface
PSTN and GSM/GPRS modem
DC insulated 4 current and 4 voltage measurement inputs in
2444d model
Only 4 voltage measurement inputs in 2440d model

E 3.3.2 2400ip Series Power Quality Recorder


Suitable design for heavy conditions
IP 65 protection class against water, dust and impacts
4 voltage and 4 current measurement inputs
Water proof connections
Wall mounted type structure and flush mounting

E 3.3.3 2400R Series Power Quality Recorder


The best protection and safety level in its own class
Galvanized insulated 4 voltage and 4 current measurement inputs
Screw type connections to the terminal blocks that provides
maximum level of safety
Strengthened battery for 3 hours of operation

E 3.3.4 2400duo Series Power Quality Recorder


Measuring two transformers' parameters simultaneously at
transmission and distribution substations or in industrial plants
DC insulated 8 current and 8 voltage measurement inputs
Screw type connections to the terminal blocks that provides
maximum level of safety

E 3.3.5 2400i Series Power Quality Recorder

4 current and 4 voltage measurement input


High speed communication

93

a Friem & Aktif Group Company


E 3 Auxiliary Equipments Measuring Devices

E 3.4 Electricity Meters


Unless otherwise required, static electric meters are used in
our products and meters with appropriate features and
certifications are chosen for different applications.

E 3.4.1 MT860 Electricity Meter with High Accuracy for


Transmission and Production Plants
Class 0.2S active energy measurement accuracy
Active, reactive and apparent energy/demand measurement
Modular communication and input/output options
Sag/swell and interruption measurements
Leakage detection and recording function
Due to the optic probe, there is no need to energy for reading
Various communication alternatives (RS485, GSM/GPRS,
Ethernet)

E 3.4.2 MT830 Electricity Meter for Distribution and


Industrial plants

Class 0.5s active energy measurement accuracy


Active, reactive and apparent energy/demand measurement
In conformity with the EPDK technical specifications
Energy interruption counter
Harmonic component analysis
Leakage detection and recording function
Various communication alternatives (RS485, GSM/GPRS,
Ethernet)

E 3.4.3 MT 372 Electricity Meter for Small Size Commercial


Subscribers

Class 1 active energy measurement accuracy


Active, reactive and apparent energy/demand measurement
Suitable for pre-paid subscriptions with internal cut-off
device
Internal GPRS modem option
Possibility of reading water and gas meters with MBus output
Various communication alternatives (RS485, GSM/GPRS,
Ethernet, MBus)

E 3.4.4 MT173 Electricity Meter for Small Size Commercial


Subscribers
Class 1 active energy measurement accuracy
Active, reactive and apparent energy/demand measurement
Network/generator tariffs
Different tariffs during the day (Day, night, peak time)
RS485 communication port

94

a Friem & Aktif Group Company


Auxiliary Equipments Measuring Transformers E 4

E 4 Measuring transformers
We use, depending on the requirement, either conventional
type measurement transformers in conformity with IEC
60044-1 and IEC 60044-2 or Rogowski type cast resin
measurement transformers in conformity with IEC 60044-8.

E 4.1 Current transformers


Current/Voltage slope is extremely linear and does not get
saturated
Can work in many different frequencies
Since it does not have iron core, fast current change and
transient response is very well.
Decreases the interaction due to magnetic field.

Rogowski and Conventional type of current transformers


are used in SME series switchgears.

Internal Type - with supports /bushings


Internal Type - with capacitive layers
External Type

Basic Specifications
Operational voltage : up to 40.5 kV
Withstand voltage : up to 85 kV
Short period testing voltage (1.2/50ºs) : up to 185 kV
Rated frequency : 50 / 60 Hz
Rated primer current : up to 4000 A
Secondary coils :1/5A
Short period thermal withstand current (1s) : up to 1000 In
Insulation Class :E

E 4.2 Voltage transformers


The cast resin coated conventional voltage transformers
used in our products are as follow:

Internal type single pole insulated with circuit breaker


Internal type single pole insulated without circuit breaker
Internal type double pole insulated

Basic Specifications
Operational voltage : up to 40.5 kV
Withstand voltage : up to 85 kV
Short period testing voltage (1.2/50ºs) : up to 185 kV
Rated frequency : 50 / 60 Hz
Rated primer current : up to 40.5/√3 kV
Secondary Voltage : 100/√3 V, 110/√3 V,
120/√3 V
Class : 0,2 / 0,5 / 1
Nominal gerilim faktörü : 1,9
Insulation Class :E

95

a Friem & Aktif Group Company


Enerji ve Endüstri Raylı Sistemler

Orta Gerilim Hücreler Enerji Da€›tım Çözümleri

Doc. Nr. AET-SW 1105/C.Eng Owing to periodical improvements of our products the supplied products may differ in some details from the data stated in the prospectus material. Published by Aktif Elektroteknik A.S. Data subject to alteration without notice.
Trafo ve Da€›t›m Kö kleri Depo Alanı Çözümleri

Mobil ‹stasyonlar Araçüstü Ekipmanlar

Dirençler

Enerji Kalitesi

OSOS ve Faturalama

T›bbi Güç Sistemleri

Senkronizasyon Cihazlar›

Sekonder Koruma Röleleri