THE OFFICIAL PUBLICATION OF THE SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS | AUGUST
wattnow 2020| 1
| August 2020
F EAT UR E
BY | CHANDIMA GOMES
CENTER OF EXCELLENCE ON HIGH
VOLTAGE ENGINEERING
FACULTY OF ENGINEERING AND THE
BUILT ENVIRONMENT
UNIVERSITY OF THE
WITWATERSRAND
The situation is not very different in damage attract not only genuine products which are not recommended
other neighbouring countries in the Lightning Protection (LP) providers either by International (IEC) or national
sub-Saharan region. Similar to many but many fraudulent and products, standards. For an example - by the
lightning dense countries in the world erroneous techniques, unethical time the Malaysian government
such as Malaysia, India, Bangladesh, and unscrupulous vendors and issued regulations on installing LPSs,
Colombia, Brazil, Venezuela etc., in incompetent designers, consultants, only that are recommended by the
South Africa as well some highly advisers etc. as well. Such a situation Malaysian Standards (MS IEC 62305-
populated and vastly industrialised leads the general public not only to 2011), almost 75% of the LPSs in the
areas are located in lightning red zones. spend their money superfluously but country were beyond the scopes of
These areas are exposing both living also to place them at utter danger due recommendations given by the national
beings and man-made systems into to a false sense of safety. The failure of standards. Malaysia dearly paid for this
utmost danger and high level of risk of the timely intervening of governments, delay with a large number of buildings
being affected by lightning. statutory bodies and experts in being damaged by lightning despite
educating the public and imposing having these unscientific systems.
The high lightning density, human strict regulations on LP measures, The damaged properties include a
and livestock casualties, and property caused the flooding of unscientific lightning-caused fire at a major hospital
50 | wattnow | August 2020
in the country (Putrajaya hospital) which are the most comprehensive early streamer emission (ESE) devices.
and several other critical installations. such standard in the continent, do Thus in this article, we look into this
However, Malaysia remains one of the not recommend such unscrupulous technology within a critical frame of
few (if it is not the ONLY) countries that technologies and the majority of the view.
have taken the bold step of banning scientific community also strongly
these non-standard systems being condemn such. Thus, it is the high time THE LIGHTNING THREAT
implemented in the country. to educate the relevant policymakers Lightning impulse current lasts for a
and public to be vigilant on adopting few hundred microseconds. However,
The lessons learned by the scientific Lightning Protection Systems (LPSs) due to the immense peak value, very
community in Malaysia and many other only that are recommended by the short rise time and the long continuing
countries demand timely steps and national standards. currents that frequently follows the
precautionary measures to be taken impulse component of lightning
in Africa, which is mostly unfiltered Although there are several types of currents could bring various adverse
by these scientifically unacceptable non-conventional (not recommended effects to the structure through which
products at the moment. The South by IEC Standards or SANS) LPS, the the current flows.
African standards (SANS 62305- 2011) most commonly used of them are the
wattnow | August 2020 | 51
F EAT UR E c ont inues fro m p a g e 5 1
Peak voltage and time derivative of the conductor, this potential gradient, due reached the structure in the absence
current (rate of rising of current) gives to the resistive component, reduces of the LPS. In other words, a properly
rise to the potential gradient along with to few Volts per meter. However, due designed LPS would not increase the
the structure of the current passage, to the path inductance, the potential number of lightning strikes that reach
which may cause side flashes and gradient may still rise to a few tens of the building during a given period.
touch potential hazard. A massive kilovolts per meter.
poetical difference between the upper Due to the potential gradient of the
parts of the current path and any Similarly, when lightning current enters current passage due to the path
nearby conducting object connected a bad conductor, the energy dissipation inductance and current derivative,
to the ground directly or indirectly may may be in the order of tens of Giga it is prescribed in the standards to
give rise to an arcing from the former Joules per meter. In contrast, for a have several down conductors in a
to the latter. The temperature rise of good conductor, it may be a few tens given LPS design. The number of
the surrounding due to a few meter of Joules per meter. down conductors increases with the
arc could be several thousand Celsius. perimeter of the building and the level
Thus it may trigger fire and explosions. of protection (which takes the height
A person touching a higher point of THE THEORY OF PROTECTING of the building into account).
the current path while his feet are in STRUCTURES AGAINST
contact with the ground will draw a LIGHTNING The SANS 62305-3 (2011) describes
part of the lightning current through The above information shows that by how to implement the earthing
his body, which is termed - “touch ensuring that lightning current passes system to minimise surface arcing or
potential”. Similarly, as the current is into the earth without any adverse step potential hazards. Typically, each
injected into the ground, a potential effects, it should be driven through down conductor should end up at an
gradient is generated in the vicinity, few parallel metal paths which are earthing component. Interconnection
that could knock-off a person whose well-grounded. Therefore, a structural of all earthing components is strongly
feet are along the poetical gradient. protection system is designed so recommended, although it is not
This is popularly known as “step that the building to be covered with essential. Alternatively, all down
potential”. a certain minimum number of air- conductors could be connected to a
terminations, down conductors and a ring earth which should satisfy certain
The peak current and the duration of comprehensive earthing system. The compulsory conditions.
the current pulse are two determinants SANS 62305-3 (2011) described how
of the energy dissipated in the current to select the number of air-terminations EARLY STREAMER EMISSION (ESE)
passage. The integration of the square and to design the placement of them TECHNOLOGY
of the current with respect to time, to optimise the interception of a In the early 70s, due to the rapid increase
which is termed the “action integral” lightning-stepped leader at a given in copper price prompted several
or “specific energy” provides the level of protection. An air-termination scientists to look for an alternative
amount of energy dissipated per unit is either a vertical rod or a horizontal method of protecting structures that
resistance of the current path. The tape made of a suitable metal such could reduce the amount of metal
continuing current, which has a few as copper, aluminium etc. The vertical used in the LPS. By that time several
hundred amperes of amplitude but rod type air-terminations are usually industries produced an air-termination
several to several tens of milliseconds, termed Franklin rods, to honour its with a piece of radioactive material such
significantly contributes to the total inventor, Benjamin Franklin. However, as Americium (Am-241), Caesium (Cs-
energy dissipation. it is nothing but an ordinary metal rod 137), Polonium (Po-210) etc., placed
of which the dimensions are specified in a small container located at the air
When the lightning current travels in SANS 62305-3 (2011). terminal which claimed to be enhancing
along a bad conductor, such as wood, the emission of the upward streamer
a massive potential gradient, in the It is imperative to understand that that intercept with the stepped leader.
order of few Giga volts per meter is the purpose of an LPS is not to As the streamer inception from these
developed along the current path. If attract lightning but to intercept with radioactive air-termination occurs
the lightning current enters a good any stepped leader that would have earlier than that from an ordinary metal
1.
As per the NF C 17-102 (2011),
the threshold requirements for H,
h1 and h2 in figure-1 is 2 m 1 m, 1
m respectively. Thus, although the
laboratory experiments show the
time advantage of the ESE rod, the
extrapolation of the results to the
natural lightning phenomena which
occurs in many magnitudes larger
scale is highly questionable.
2. There is no scientific evidence to
prove that the upward streamer
speed is 106 m/s. In reality, it may
be a couple of magnitudes less. The
recent experiments done with fast
video camcorders will soon reveal
the validity of this assumption.
3. The NF C 17-102 states that “In
case of an isolated ESE System,
at least one down-conductor is
needed for each ESE air-terminal”.
It is undeniable that vendors always
follow the minimum requirements
Figure 2
outlined in the standards to
propagation begins at a much earlier advantage, in 1995 French Standard maximise the profit. Thus, the above
time. The difference in the two times NF C 17-102 was established. Spain clause enables them to install only a
is called the time advantage (∆T) of the followed soon setting a standard for single down conductor for buildings
ESE rod. ESE technology coded UNE21186. with single ESE terminal, if the
Both standards were updated in 2011. system is not connected to the steel
∆T = TFR – TESE reinforcement (which is the case in
The testing method and consequent a vast majority of ESE installations).
Then this time advantage is multiplied computational guidelines specified in One can show with a simple
by the speed of the upward streamer the above French and Spanish standards calculation that at 20 m height a
(U) to find the height advantage (∆H). enables the ESE manufacturers negative subsequent stroke with
to claim a large protective volume average parameters could generate
∆H = ∆T × U due to the effective height which 1.6 MV in a single copper conductor
may be 100-200 times greater than of cross-section 75 mm2. Such high
The ESE vendors arbitrarily assumed the physical height of the ESE rod. voltages need several meters long
that U = 1 × 106 m/s. gaps to avoid possible arcing.
As a result, the number of air terminations 4. In many countries with a high
Whereas many national and that are required for a building as per the density of lightning ground flash
international standards refused IEC 62305-3 (2010) could be drastically occurrence, statistical data shows
to recommend this so-called new reduced to a minimal value. that there are many failures of ESE
technology, citing that there is no systems, although they are installed
theoretical, experimental or statistical There are few key reasons for the according to the French or Spanish
proof to justify the claimed height committees of IEC and other significant standards. It is a well-known fact