Академический Документы
Профессиональный Документы
Культура Документы
net/publication/225150147
CITATIONS READS
31 308
5 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Yong C Wang on 20 June 2014.
Guo-Qiang Li and Guo-Biao Lou, Sate Key Laboratory for Disaster Reduction
in Civil Engineering, 1239 Siping Road, Shanghai, China
Chao Zhang* and Ling-Ling Wang, College of Civil Engineering, Tongji
University, 1239 Siping Road, Shanghai 200092, China
Yong-Chang Wang, School of Mechanical, Aerospace and Civil Engineering,
The University of Manchester, PO Box 88, Manchester M60 1QD, UK
Abstract. Intumescent coatings are now the dominant passive fire protection materi-
als used for steel construction. Intumescent coatings will react at high temperatures
and the thermal properties of intumescent coatings can not be measured directly by
the current standard test methods which are originally designed for the traditional
inert fireproofing materials. This paper proposed a simple procedure to assess the fire
resistance of intumescent coatings by using the concept of equivalent constant ther-
mal resistance. The procedure is based on the approximate formula for predicting the
limiting temperatures of protected steel members subjected to the standard fire. Test
data from investigations on both small-scale samples and full-scale steel members are
used to calculate the equivalent constant thermal resistance. Using the equivalent
constant thermal resistance of intumescent coatings, the calculated steel temperatures
agree well with the test data in the range of the limiting temperatures from 400°C to
600°C. The procedure needs no complex computation and is recommended for prac-
tical usage. The equivalent constant thermal resistance could be used to quantify the
insulation capacity of intumescent coatings.
1. Introduction
Intumescent coatings, by their advantages like attractive appearance, potential for
off-site application and practically taking no space, are now the dominant passive
fire protection materials used in industrial and public buildings [1]. The coatings,
which usually are composed of inorganic components contained in a polymer
matrix, are inert at low temperatures and will expand and degrade to provide a
charred layer of low conductivity materials at temperatures of approximately
280°C to 350°C [2, 3]. The charred layer, which acts as thermal barrier, will pre-
vent heat transfer to underlying substrate.
In current codes, the fire resistance of a coating is measured using standard fire
tests for rating the materials [4, 5]. In such tests, a large steel member (in Chinese
code, the tested sample is a 0.5 m length steel I beam [6]) is coated with the fire-
proofing material then inserted in a furnace that is heated following the standard
temperature–time curve. The time for the steel member to exceed any of the end-
point failure criteria confers the rating of the coating. The widely used endpoint
failure criteria is that the maximum mean steel temperature must be lower than
the critical temperature which is the temperature that causes structure collapse in
fire situation, often taken as 550°C. Such tests are expensive and time-consuming,
with a large number of tests required to cover the range of steel configurations
and protection thicknesses typically required in construction.
Alternatively, if thermal resistance of the coating can be derived, calculation
methods are available and efficient to assess the fire resistance. Unlike the conven-
tional fireproofing materials (e.g. concrete, gypsum, SFRMs) whose thermal prop-
erties are temperature-dependent only, the performance of intumescent coatings
are complex that they will behave differently according to the applied heating con-
dition, coating thickness, and protected structures [7–10]. As a result, the tradi-
tional standard test methods (like ASTM C518-04 [11], GB/T 10294-2008 [12]) are
not applicable to measure the thermal properties of intumescent coatings [13].
Till now, several models have been developed to study the heat transfer of intu-
mescent coatings under heating [2, 7, 13–15]. These models are primarily one-
dimensional, and concentrated on the effects of swelling on the thermal properties
of coatings. The structure of chars is always simply assumed to be constituted of
vapor and solid materials, or to be a porous media, and the thermal conductivity
of chars, kc, is determined by ksol, kvap and fv [2, 13, 15]. (In Refs. [7, 14], the
effect of thermal radiation in bubbles on kc have also been considered.) Here, kc,
ksol and kvap are thermal conductivities of char, solid and vapor, respectively; and
fv is the void fraction of the char. In intumescing or swelling process, the structure
of coatings is divided into two layers, virgin coating and char [7, 13, 15]. (In Refs.
[9, 14], a transforming swelling layer is included between the virgin and char
layers.) In [8], the thermal conductivity of a commercial intumescent coating is mea-
sured using the relationship between thermal conductivity and thermal diffusion,
where thermal diffusivity is measured by a designed laser flash diffusivity system.
Due to the complexity of intumescing process and the difficulty of measuring
the structure of chars, the thermal conductivity of intumescent coatings can not be
measured directly. In fire engineering, effective thermal conductivity or equivalent
thermal resistance is usually adopted to characterize the thermal insulation
property of intumescent coatings. Anderson et al. [13] developed a procedure
to estimate the effective thermal conductivity of chars of intumescent systems. The
procedure was based on a heat transfer analysis of temperature–time data from
one-dimensionally designed experiments of coated coupons exposed to a fire envi-
ronment typical of aviation-type fuel fires. Bartholmai et al. [10] developed a
simple test method to determine the time dependent thermal conductivity of intu-
mescent coatings. The method consists of temperature measurements using the
Assess the Fire Resistance of Intumescent Coatings 531
1 1 fv fv
¼ þ ð1Þ
kc ks kvap
@ 2 T ðx; tÞ @T ðx; tÞ
ai ¼0 ð2Þ
@x2 @t
where ai = ki/ciqi is the thermal diffusivity; ki is the thermal conductivity; and ciqi
is the volumetric specific heat of the insulation. Equation 2 ignores the energy
generated within the solid, which is valid for the traditional inert fire proofing
materials. For intumescent coatings, the chemical reactions happened in intumesc-
ing process will consume or produce some amount of energy. As has been
Assess the Fire Resistance of Intumescent Coatings 533
mentioned, the intumescing process is complex and explicit molding of the process
is very difficult. In practice, when developing procedures to calculate the effective
thermal conductivity of intumescent coatings, the complex intumescing process is
usually not considered that Equation 2 is used [10, 13, 16].
At the steel–insulation interface, the boundary condition is given by
@T ðdi ; tÞ cs qs @T ðdi ; tÞ
ki ¼ ð3Þ
@x Ai =V @t
where csqs is the volumetric specific heat of the steel; Ai/V is the section factor, in
which Ai is the appropriate area of the fire insulation material per unit length, and
V is the volume of the steel per unit length; and di is the thickness of the insula-
tion.
At the fire–insulation interface, two boundary conditions, namely Neumann and
Dirichlet boundaries, have been used in engineering, which are given by
@T ð0; tÞ
ki ¼ q_ in ð5Þ
@x
and
respectively. Tg(t) and T(0, t) are the temperatures of the fire and the insulation
surface, respectively; q_ in is the incident heat flux, for calculation in most fire
conditions
534 Fire Technology 2012
where r = 5.67 9 10-8 W/(m2 K4) is the Stefan-Boltzmann constant; and e is the
resultant emissivity at the insulation surface, which is dependent on many parame-
ters such as external heat flux, surface temperatures [24, 25]. In practice, constant
value of e is used, e.g. for intumescent coatings e = 0.92 has been used in [24].
di
Ri ¼ ð9Þ
ki
and
1
Rf ¼ : ð10Þ
hc þ hr
Here, Ri, Rf are the thermal resistance of the insulation, and the thermal resis-
tance caused by convection and radiation.
The Neumann boundary is complex and has capacity to represent the real
boundary condition at the fire interface. From Equation 8, we know to get hr,
the value of the surface temperature of the insulation, T(0, t), should be known
beforehand. However, T(0, t) is a unknown variable, and for intumescent coat-
ings in fire the measurement of T(0, t) is very difficult [24]. The Dirichlet
boundary is simple which assumes T(0, t) is equal to the surrounding gas tem-
perature Tg(t). The Dirichlet boundary ignores the heat loss through surface
convection and radiation. This assumption is valid for conditions where
Ri Rf, but will yield conservative results for conditions where insulation is
not effective.
Instead of calculating Rf and Ri directly and separately, using an equivalent
thermal resistor Req, as shown in Figure 2, can represent all thermal energy block-
ing effects caused by convection, radiation, and insulation. For most calculations
using the Dirichlet boundary condition where Rf = 0, the equivalent thermal
resistance Req is equal to Ri. The equivalent thermal resistance is efficient and use-
ful to evaluate the fire resistance of intumescent coatings.
Ignoring the heat absorbed by the insulation materials, by energy balance the
steel temperature can be calculated by [21]
Assess the Fire Resistance of Intumescent Coatings 535
Tg ðtÞ Ts ðtÞ 1 Ai
4Ts ¼ 4t ð11Þ
Req cs qs V
Tg ðtÞ Ts ðtÞ 1 Ai
Req ¼ ð12Þ
4Ts =4t cs qs V
From the equivalent thermal resistance, we can easily get the effective thermal
conductivity of the intumescent coatings by
dio
keff ¼ ð13Þ
Req
here, dio is the initial thickness of the coatings. In DD ENV13381-4:2002 [16], the
following equation is provided for calculating the effective thermal conductivity of
the coatings, thus
dio 1
keff ¼ cs qs ð1 þ /=3Þ ½4Ts þ ðe/=10 1Þ4Ts :
Ai =V ðTg ðtÞ Ts ðtÞÞ4t
ð14Þ
For intumescent coatings, the mass ratio / can be approximated as zero, and
Equation 14 becomes Equation 13.
The equation is valid in the range of Tlim from 400°C to 600°C, as shown in
Figure 3. Rearranging Equation 15, we get the expression to calculate the equiva-
lent constant thermal resistance, thus
1=0:77
di t Ai
Rconst ¼ ¼ ð16Þ
ki 2400ðTlim 140Þ V
536 Fire Technology 2012
4. Experimental Investigation
4.1. Test on Small-Scale Samples
4.1.1. Test Approach. A small scale test furnace has been constructed for fire
resistance testing. Figure 4 is a picture of the furnace. The dimensions of the
firebox are 1.0 m (length) 9 1.0 m (width) 9 1.2 m (height). Heating system is
computer controlled, which has capacity of simulating standard ISO834 fire, stan-
dard hydrocarbon fire and user-defined fires. Figure 5 gives the comparison
between the measured furnace temperature–time curve and the standard ISO834
fire curve, which shows good match.
Steel plates with two small holes are used as the test samples (substrates).
Figure 6 shows the dimensions of the plate and the applying of the insulation.
The section factor of the plate is taken as Ai/V = 125 m-1. In tests, samples are
hinged on the supports through holes in the samples, as shown in Figure 7. The
sample is designed to represent the 1D heat transfer model discussed above.
Figure 5. Measured furnace fire curve and the ISO834 standard fire
curve.
4.1.2. Test Data. In another research project [26], which focused on investigating
the effects of aging on thermal properties of intumescent coating for steel ele-
ments, the test approach mentioned above was used for testing. In the project,
accelerated aging and fire tests were conducted on 36 specimens, 18 of which were
applied with 1 mm coating and the other 18 with 2 mm coating. Accelerated aging
tests were conducted by according to the European Code ETAG 018-2 [27]. The
equation given by DD ENV13381-4:2002 [16], or Equation 14, was used to calcu-
late the effective thermal conductivity of the coatings. Figures 8 and 9 give the
results for measured steel temperatures, in which 21 cycles of accelerated aging
was assumed to represent working life of 10 years (and 42 cycles, 20 years, etc.).
same sections 305 9 165 9 40 UB. Numerous thermocouples were used to moni-
tor the temperature distributions at different locations of the steel sections.
4.2.2. Test Data. In Ref. [18], totally 10 tests on joints with different fire-pro-
tection schemes using intumescent coating were conducted. Intumescent coating
540 Fire Technology 2012
Figure 13. Steel column temperatures in [3, 18] (the black bold
lines are measured steel temperatures).
Figure 14. Some results for the calculated Req for test on small-scale
samples. (a) Test 1, 0 cycle, (b) test 1, 2 cycles, (c) test 2, 0 cycles,
and (d) test 2, 2 cycles.
Figure 15. Calculated Req for test on steel members (Rconst = 0.0500
K m2/W).
544 Fire Technology 2012
Table 1
Constant Thermal Resistance Obtained from Small-Scale Tests
(Units in K m2/W)
5. Conclusions
Intumescent coatings are reactive materials at high temperatures. The behavior of
intumescent coatings under heating is very complex and no agreeable model is
available to simulate the behavior. Effective thermal conductivity or equivalent
thermal resistance is usually used to evaluate the fire resistance of intumescent
coatings. However, complex compute simulations are always required to predict
the time/temperature-dependent effective thermal conductivity. This paper pro-
posed a simple procedure to assess the fire resistance of intumescent coatings by
using equivalent constant thermal resistance. The main conclusion of this study is
– The procedure is valid and convenient to assess the fire resistance of intumes-
cent coatings. Using the equivalent constant thermal resistance of intumescent
coatings determined by the procedure, the calculated steel temperatures agree
well with the test data in the range of the concerned limiting temperatures from
400°C to 600°C.
Acknowledgments
The work reported hereinabove is financially supported by the Ministry of Science
and Technology of China through the project SLDRCE08-A-06, and by the
National Natural Science Foundation of China through the contract 50738005.
The support is gratefully acknowledged.
References
1. Fire resistance OF steel-framed buildings, 2006 edn. Corus Construction and Industrial
(2006)
2. Bourbigot S, Duquesne S, Leroy JM (1999) Modeling of heat transfer of a polypropyl-
ene-based intumescent system during combustion. J Fire Sci 17:42–56
Assess the Fire Resistance of Intumescent Coatings 545
3. Yuan JF (2009) Intumescent coating performance on steel structures under realistic fire
conditions. PhD thesis, The University of Manchester
4. Standard test methos for fire tests of building construction and materials. ASTM E119-
00a. ASTM International, West Conshohocken, PA (2000)
5. GB/T 9978-1999 (1999) Fire-resistance tests—elements of building construction. Chinese
National Code
6. GB 14907-2002 (2002) Fire resistive coating for steel structure. Chinese National Code
7. Yuan JF, Wang YC (2008) Prediction of intumescent coating performance under cone
calorimeter—a mathematical approach to performance based design. In: Proceedings of
the fifth international conference on structures in fire (SiF’08), Singapore, pp 713–724
8. Koo JH (1998) Thermal characterization of a ceramic intumescent material. Fire
Technol 34:59–71
9. Di Blasi C (2004) Modeling the effects of high radiative heat fluxes on intumescent
material decomposition. J Anal Appl Pyrol 71:721–737
10. Bartholmai M, Schriever R, Schartel B (2003) Influence of external heat flux and coat-
ing thickness on the thermal insulation properties of two different intumescent coatings
using cone calorimeter and numerical analysis. Fire Mater 27:151–162
11. Standard test method for steady-state thermal transmission properties by means of the
heat flow meter apparatus. ASTM C518-04. ASTM International, West Conshohocken,
PA (2003)
12. GB/T 10294-2008 (2008) Thermal insulation—determination of steady-state thermal
resistance and related properties—guarded hot plate apparatus. Chinese National Code
13. Anderson CE, Ketchum DE, Mountain WP (1988) Thermal conductivity of intumes-
cent chars. J Fire Sci 6:390–410
14. Griffin GJ (2009) The modeling of heat transfer across intumescent polymer coatings.
J Fire Sci 00:1–29
15. Gillet M, Autrique L, Perez L (2007) Mathematical model for intumescent coatings
growth: application to fire retardant systems evaluation. J Phys D: Appl Phys 40:883–
899
16. DD ENV 13381-4 (2002) Test methods for determing the contribution to the fire resis-
tance of structural members—part 4: applied protection to steel members. British Stan-
dardrds Institution, London
17. EN 1993-1-2 (2005) Eurocode 3: design of steel structures. Part 1–2. General
rules—structural fire design. British Standard Institution, London
18. Dai XH, Wang YC, Bailey C (2010) A simple method to predict temperatures in steel
joints with partial intumescent coating fire protection. Fire Technol 46:19–35
19. Design manual on the european recommendation for the fire safety of steel structures.
European Commission for Constructional Steelwork, Brussels (1985)
20. China Association for Engineering Construction Standardization (CECS200) (2006)
Technical code for fire safety of steel structure in buildings. China Planning Press, Bei-
jing (in Chinese)
21. Zhang C, Li GQ, Wang YC. Sensitivity study on using different formulae for claculat-
ing the temperature of insulated steel members in natural fires. Fire Technol. doi:
10.1007/s10694-011-0225-x
22. Li GQ, Zhang C (2010) Thermal response to fire of uniformly insulated steel members:
background and verification of the formulation reccomended by chinese code CECS200.
Adv Steel Constr 6(2):788–802
23. EN 1991-1-2 (2002) Eurocode 1: actions on structures. Part 1-2. General actions—ac-
tions on structures exposed to fire. British Standards Institution, London
546 Fire Technology 2012
24. Omrane A, Wang YC, Goransson U, Holmstedt G, Aldn M (2007) Intumescent coat-
ing surface temperature measurement in a cone calorimeter using laser-induced phos-
phorescence. Fire Saf J 42:68–74
25. Staggs JEJ, Phylaktou HN (2008) The effects of emissivity on the performance of steel
in furnace tests. Fire Saf J 43:1–10
26. Wang LL, Wang YC, Li GQ (2010) Experimental study of aging effects on insulative
properties of intumescent coating for steel elements. In: Proceedings of the sixth inter-
national conference on structures in fire, MI, USA, pp 735–742
27. European Organization for Technical Approvals, ETAG018 (2006) Guideline for Euro-
pean Technical Approval of fire protective products. Part 2. Reactive coatings for fire
protection of steel elements