Electronic Position Transducer
Supplement operating instructions for DREHMO actuators with electronic position transducer

T.-Nr. 167725
Installation instructions Revision 1.04
Operating instructions Date: 20.07.2012
Service instructions
For electronic position transducer

NOTE
This instruction is part of the supply and should be kept for future use.

DREHMO GmbH
Zum Eichstruck 10
57482 Wenden / Germany
Tel.: +49 2762 9850-206
Fax: +49 2762 9850-210
Internet: www.drehmo.com
eMail: Drehmo@drehmo.com

Electronic Position Transducer - Instructions Page 1 of 9


Application Versions

The EM 5.004 / EM 5.005 electronic measuring amplifier Two versions of the electronic position transducer are
converts – with the aid of a precision potentiometer with available:
protection IP 65 as pick-up – the mechanical dimension of • Normal version type EM 5.004
distance or angle of rotation linearly into an impressed DC • Explosion-proof version type EM 5.005
signal.
Thus the distances travelled or positions reached by The amplifying potentiometer allows setting of the 20
DREHMO actuators can be displayed directly, even over mA current signal corresponding to travel distance in the
long lines, as an appropriate current value on an indicating range from 45 %...100 %.
instrument.
Additionally, they can be evaluated by a computer. The current-distance characteristic can be reversed by
exchanging connections 1 and 2 with type EM 5.004 and
connections 1 and 3 with type EM 5.005.

When using the explosion-proof version (type EM 5.005) of


the electronic position transducer, the current valid
standards for the installation of intrinsically safe circuits
must be followed without fail (DIN EN 60079-14 / VDE 0165
Teil1).

Normal version type EM 5.004 Explosion-proof version type EM 5.005

Electronic Position Transducer - Instructions Page 2 of 9


Connection details

Normal version type EM5.004 Explosion-proof version type EM5.005

Explosion-proof type EM5.005: Ex ib IIC T4 to T6


applicable for zone 1.

2-wire-systems

3- wire-systems

4- wire-systems

Power pack or supply unit on special order.

Electronic Position Transducer - Instructions Page 3 of 9


Notes for application Electrical connection
1
To set up the electronic position transducer, remove the Actuators with wiring diagram KD 102 are connected as
DREHMO actuator limit switch compartment cover. follow (e.g. EM5.004 with 24V supply):
The reduction gear or pick-off gear resp. has to be set to
suit the valve stroke.
(See installation instructions for DREHMO actuators.)
4-wire-system
2
Normal version type EM 5.004
Connect the power pack and indicating instrument as
shown in the connection diagram below. Connect
terminals 7 and 8.

3-wire-system

Explosion-proof type EM 5.005


Connect the intrinsically safe supply unit and intrinsically
safe indicating instrument as shown in the connection 2-wire-system
diagram below.

3
Connect electronic position transducer according to wanted
operating mode (2-, 3- or 4-wire systems).
If the 4…20 mA signal is required for 3- and 4-wire systems,
terminals 3 and 4 have to be connected. (See schematic
diagrams of current flow, page 5).

4 Actuators with wiring diagram KD 102 are connected as


The indication instrument has to indicate 3,95…4,0 mA at follow (e.g. EM5.005 max. 22.5V with intrinsically safe
valve end position CLOSED and connected terminals 3 and supply):
4, otherwise it has to indicate 0 mA.

5 2-wire-system
Release the turning detend at value end position CLOSED
according to the installation instructions for DREHMO
actuators.

6
In the fully OPEN position of the valve fine-tune the final
current value on the fine adjustment potentiometer.
2-wire connection:
final current value 20 mA (I1)
3- and 4- wire connection:
final current value 24 mA (I1) or 20 mA (I2)

Electronic Position Transducer - Instructions Page 4 of 9


Schematic Diagrams of Current Flow

2-wire-system

3-wire-system

4-wire-system

Electronic Position Transducer - Instructions Page 5 of 9


Technical Data

Type EM 5.004 Type EM 5.005


2-wire-system 3-wire-system 4-wire-system 2-wire-system only
Ignition enclosure type -- -- -- Ex ib IIC T4 to T6
Temperature range -25 °C…+80 °C -25 °C…+80 °C -25 °C…+80 °C -25 °C…+60 °C
Transducer
Precision potentiometer
Precious metal, Precious metal, Precious metal, Precious metal,
Slider
fully rotating fully rotating fully rotating fully rotating
6 6 6 6
Approx. 50 x 10 Approx. 50 x 10 Approx. 50 x 10 Approx. 50 x 10
Mechanical life
shaft movements shaft movements shaft movements shaft movements
Linearity ± 0.3% ± 0.3% ± 0.3% ± 0.3%
Resolution error < 0.01° < 0.01° < 0.01° < 0.01°
Measuring range 293° 293° 293° 293°
Electronic section
(pulse-proof to IEC 1,2 kV/50 µs)
Output current 4…20 mA 0,1…20 mA/4…20 mA 0,1…20 mA/4…20 mA 4…20 mA
Operating voltage*
+17…+30 V +17…+30 V +17…+30 V +12…+22,5 V
(Terminals 5 and 6)
Max. input current when
standard distance setting
29 mA ± 2.5 mA 29 mA ± 2.5 mA 29 mA ± 2.5 mA 23 mA ± 1.5 mA
is exceeded (Terminals 5
and 6)
Permissible load 17 V/ 0 Ω 12 V/ 0 Ω
24 V/ 350 Ω 17 V/ 250 Ω
30 V/ 650 Ω 17 V/ 400 Ω 17 V /400 Ω 22,5 V/ 525 Ω
24 V/ 680 Ω 24 V /680 Ω
UBetrieb – 17V 30 V/ 920 Ω 30 V /920 Ω UBetrieb – 12V
Rbürde = Rbürde =
0.02 A 0.02 A

Max. line resistance


between voltage source -- 80 Ω --
and terminal 5 --
External
-- -- --
Capacitance <0.1 nF
-- -- --
Inductance <0.1 nH

Temperature drift** 0.2 % / 10 k 0.2 % / 10 k 0.2 % / 10 k 0.2 % / 10 k


Linearity deviation 1‰ 1‰ 1‰ 1‰

Effect of altering O.6 ‰ / V O.1 ‰ / V O.1 ‰ / V O.6 ‰ / V


operating voltage**
typ. 0.1%/100 Ω typ. 0.1%/100 Ω typ. 0.1%/100 Ω typ. 0.1%/100 Ω
Effect of altering voltage**

* For 2-wire-systems it is recommended that the smoothing is better than 1.5 Vpp.
**referred to Imax = 20 mA