132KV Single line diagram CE/AAAA/NNNA/E/01/01 5 0

Category
SR. Description Dewa Specification/ DEWA Applicable Reference Complied with
Practice/ Guidelines/ Tender
1 Prerequisites documents/ requirements document
1.1 Engineering design drawings shall be submitted to DEWA as per priority highlighted in DDCMS list . Guidelines DDCMS

1.2 Engineering design drawings shall be provided with List of required legends and reference of related drawing. DEWA Practice Nil
1.3 DEWA approved title Blocks only to be used for each drawings. Drawing number and drawing title must be same as indicated in DDCMS. Guidelines DDCMS

1.4 DEWA approval status of reference drawings to be indicated in reference list respectively. DEWA Practice Nil
1.5 Major references drawings to be provided to Dewa engineers in time to avoid delay in approval process. DEWA Practice Nil

1.6 Revision number and date shall be maintained based on revised submission to DEWA only. DEWA Practice Nil

1.7 The GIS manufacturer and type shall be mentioned. DEWA Practice Nil
1.8 Compliance statement for the previous comments if any is enclosed and all the comments are complied. DEWA Practice Nil

1.9 Ensure PDF is directly converted from the soft file of the drawing / document. Guide line TPD Submittal Guidelines

1.10 The name and signature of approved Consultant / Contractor engineer for Design/Engineering review shall be included in the cover sheet of transmittal Guidelines
Note Submittals.
2 Confirmation List

3 Technical detailed Check points


3.1 Engineering

3.1.1 All bus bars shall be marked with normal current 2000A, short time current rating with duration 40KA for 1 sec, at 50 degree & BIL 275/650KV. DEWA Specification 1.5.1.2.2.01 - Clause 6 - Para 7
3.1.2 Provision for future bays as per tender SLD and PPR shall be provided. Tender document Tender SLD and PPR

3.1.3 Current rating for CBs, Disconnectors shall be mentioned (1500A for all feeders , 2000A for bus coupler). Moreover. Actual current rating shall be provided DEWA Specification 1.5.1.2.2.01 - Clause 6 - Para 7
also as per GTP.
3.1.4 Line side earth switches for feeder bays and bus bar earthing switches shall be fault making type. DEWA Specification 1.5.1.2.2.01 - Clause 11
3.1.5 All earthing switches shall have isolating facility for primary injection purpose. DEWA Specification 1.5.1.2.2.01 - Clause 9.2.3 and 4 - Para 69 and
73
3.1.6 Primary injection current and duration shall be indicated in the drawing DEWA Specification 1.5.1.2.2.01 - Clause 9.2.3 and 4 - Para 69
and 73
3.1.7 Location of CTs and VTs shall be as per tender single line diagram Tender document Tender SLD
3.1.8 VT shall be provided without isolator. DEWA Specification Clause 9.4 Para 76
3.1.9 Polarity of CTs are mentioned as per tender SLD DEWA Specification Tender SLD
3.1.10 Provision for future lightening arrestor for each line feeder shall be provided. DEWA Specification 1.5.1.2.2.01 - Clause 9.6 - Para 94
3.1.11 Arrangement of the circuit shall be from left to right when standing between GIS & LCC and looking to GIS. Tender document Tender SLD
3.1.12 Bus bar 1,3,5 shall be located bottom side( starting from left to right). Tender document Tender SLD
3.1.13 Bus bars 2,4,6 shall be located on top side ( starting from left to right). Tender document Tender SLD
3.1.14 Bus bar -1 disconnector shall be shown on left side and bus bar-2 disconnector shall be shown on right side for all feeders. Tender document Tender SLD

All rights reserved © TED 1 CL-Rev.0


Document Title Document Number Issue Rev Date Approval Status
132KV Single line diagram CE/AAAA/NNNA/E/01/01 5 0

Category
SR. Description Applicable Reference Complied with
3.1.15 All feeders, CBs, disconnectors & earth switches shall be marked with SCADA numbers and device number( Q. number). Tender document Tender SLD
3.1.16 All feeders shall be marked with bay number, Scada number and feeder name (with number 1&2 in case of two feeders are connected to same remote Tender document Tender SLD
end substation) as per tender document

3.1.17 Maintenance earth switches shall be provided on both sides of CB and shall have different legend from fault making earth switches legend. Tender document Tender SLD
3.1.18 Following details shall not be indicated on SLD, to be shown only in the respective drawings. Tender document Tender SLD
- Power cables and earthing cables sizing details.
- GIS / Mechanism boxes degree of protection
- Gas barriers and SF6 gas pressures / alarms
- PD couplers

3.1.19 Power transformers with ratings , earthing transformers with ratings and neutral earthing for transformers shall be shown with the required CTs. Tender document Tender SLD
3.1.20 CT/VT characteristics are mentioned as per CT/VT characteristics approved by DEWA in tabular format. DEWA Practice Nil
3.1.21 Symbols and details shall be given in Legend matching with SLD . Tender document Tender SLD
3.1.22 Number of reactors in line feeders, Remote ends etc shall be in line with PPR. Tender document PPR and Substation Layout
3.1.23 Provision of future cable head chamber for future reactor shall be provided for bays around bus coupler E05, E07 Tender document Substation Layout
3.1.24 The adopted CT ratio is not mentioned since the same is not required to be shown in single line diagram Guidelines
3.1.25 Only main protection function like M1FP, etc only shall be mentioned and the other internal functions of main protection like 50BF1, etc is not mentioned Dewa Practice

3.1.26 Ratings and short circuit current shall be as per PPR Tender document PPR
3.1.27 CT/VT characteristics shall be specified exactly as per tender SLD, detailed characteristics like Rct, VK, etc. need not be shown. Tender document Tender SLD

3.2 Inspection

3.3 Construction & Installation

3.4 Testing & Commissioning

3.5 Maintenance

All rights reserved © TED 2 CL-Rev.0


Document Title Document Number Issue Rev Date Approval Status
132KV Single line diagram CE/AAAA/NNNA/E/01/01 5 0

Category
SR. Description Applicable Reference Complied with
Prepared By: Checked By: Approved By:

DEPARTMENT HEAD

All rights reserved © TED 3 CL-Rev.0

Вам также может понравиться