Revision F:
• MXZ-3A54VA- E5 and
MXZ-4A71VA- E5 have been added.
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Please void OB377 REVISED EDITION-E.
OUTDOOR UNIT
HFC No. OB377
SERVICE MANUAL utilized
R410A
REVISED EDITION-F
MXZ-3A54VA - E1
MXZ-3A54VA - E2
CONTENTS
Revision A :
• MXZ-3A54VA- E2 and MXZ-4A71VA- E2 have been added.
Quick clean kit has been removed.(Refer to 2.)
• MXZ-2A40VA- E1 and MXZ-2A52VA- E1 have been added.
Revision B :
• MXZ-2A30VA- E1 and MXZ-2A40VA- E2 have been added.
• “Check of HPS” has been corrected.
• RoHS PARTS LIST has been added.
Revision C :
• MXZ-2A52VA- E2 , MXZ-3A54VA- E3 , MXZ-4A71VA- E3 , MXZ-4A80VA- E2 and MXZ-5A100VA- E1 have been added.
Revision D:
• MXZ-3A54VA- E4 , and MXZ-4A71VA- E4 have been added.
• The content of pre-heat control (12-3) has been corrected.
• 5. SPECIFICATION has been corrected.
Revision E:
• MXZ-2A30VA- E2 has been added.
• 4. INDOOR UNITS COMBINATION of MXZ-5A100VA- E1 has been changed.
Revision F:
• MXZ-3A54VA- E5 and MXZ-4A71VA- E5 have been added.
1 TECHNICAL CHANGES
MXZ-A26WV - E1 ➔ MXZ-3A54VA - E1
1. Indication of capacity has been changed. (BTU➔kW)
2. Capacity specification has been changed. (Cooling capacity 7.1kW➔5.4kW)
3. Dimensions of unit have been changed. (W900oH900oD320➔W840oH710oD330)
4. Combinations of connectable indoor units have been changed.
5. Capacity class of connectable indoor units has been changed.
6. Communication system has been changed.
7. Power supply way has been changed(change to supply to outdoor unit).
8. Compressor has been changed. (TNB220FMCH➔SNB130FLDH1)
9. High-pressure switch has been removed.
10.Outdoor fan motor has been changed. (PM8H60-UA➔RC0J60-AA)
11.Evaporation temperature thermistor has been removed.
12.Ambient temperature thermistor has been added.
13.New dip switch has been added to the controller board for "Locking the operation "mode
and "Lowering the operating noise "mode.
14.A Quick Clean Kit has been added.
MXZ-A32WV - E1 ➔ MXZ-4A71VA - E1
1. Indication of capacity has been changed. (BTU➔kW)
2. Capacity specification has been changed. (Cooling capacity 8.0kW➔7.1kW)
3. Dimensions of unit have been changed. (W900oH900oD320➔W840oH710oD330)
4. Combinations of connectable indoor units have been changed.
5. Capacity class of connectable indoor units has been changed.
6. Communication system has been changed.
7. Power supply way has been changed(change to supply to outdoor unit).
8. Compressor has been changed. (TNB220FMCH➔SNB130FLDH1)
9. High-pressure switch has been removed.
10. Outdoor fan motor has been changed. (PM8H60-UA➔RC0J60-AA)
11. Evaporation temperature thermistor has been removed.
12. Ambient temperature thermistor has been added.
13. New dip switch has been added to the controller board for "Locking the operation "mode
and "Lowering the operating noise "mode.
14. A Quick Clean Kit has been added.
2
OB377F--1.qxp 07.11.22 10:27 AM Page 3
MXZ-A32WV - E1 ➔ MXZ-4A80VA - E1
1. Indication of capacity has been changed. (BTU➔kW)
2. Communication system has been changed.
3. Power supply way has been changed (change to supply to outdoor unit).
4. Evaporation temperature thermistor has been removed.
5. Ambient temperature thermistor has been added.
6. New dip switch has been added to the controller board for "Locking the operation "mode
and "Lowering the operating noise "mode.
7. A Quick Clean Kit has been added.
MXZ-A14WV - E2 ➔ MXZ-2A40VA - E1
1. Indication of capacity has been changed. (BTU➔kW)
2. Dimensions of unit have been changed. (W840oH640oD330➔W800oH550oD285)
3. Communication system has been changed.
4. Power supply way has been changed(change to supply to outdoor unit).
5. Compressor has been changed. (SNV092FJYH➔SNB130FKCH)
6. Outdoor fan motor has been changed. (RA6V49➔RC0J50-CF)
7. Evaporation temperature thermistor has been removed.
8. Gas pipe temperature thermistor has been removed.
9. Ambient temperature thermistor has been added.
MXZ-A18WV - E2 ➔ MXZ-2A52VA - E1
1. Indication of capacity has been changed. (BTU➔kW)
2. Cooling capacity specification has been changed. (5.4kW➔5.2kW)
3. Heating capacity specification has been changed. (6.6kW➔6.4kW)
4. Dimensions of unit have been changed. (W840oH640oD330➔W800oH550oD285)
5. Communication system has been changed.
6. Power supply way has been changed(change to supply to outdoor unit).
7. Compressor has been changed. (SNV092FJYH➔SNB130FKCH)
8. Outdoor fan motor has been changed. (RA6V49➔RC0J50-CF)
9. Evaporation temperature thermistor has been removed.
10.Gas pipe temperature thermistor has been removed.
11. Ambient temperature thermistor has been added.
MXZ-3A54VA - E1 ➔ MXZ-3A54VA - E2
MXZ-4A71VA - E1 ➔ MXZ-4A71VA - E2
1. Quick clean kit has been removed.
MXZ-2A30VA - E1
1. New model
MXZ-2A40VA - E1 ➔ MXZ-2A40VA - E2
1. Compressor has been changed. (SNB130FKCH➔KNB092FEDH)
2. Outdoor heat exchanger has been changed.
MXZ-2A52VA - E1 ➔ MXZ-2A52VA - E2
1. Compressor has been changed. (SNB130FKCH➔SNB130FKMH)
2. Inverter P.C. board has been changed.
MXZ-3A54VA - E2 ➔ MXZ-3A54VA - E3
1. Compressor has been changed. (SNB130FLDH1➔SNB130FLEH1)
2. Electronic control P.C. board has been changed.
MXZ-4A71VA - E2 ➔ MXZ-4A71VA - E3
1. Compressor has been changed. (SNB130FLDH1➔SNB130FLEH1)
2. Electronic control P.C. board has been changed.
3
OB377F--1.qxp 07.11.22 10:27 AM Page 4
MXZ-4A80VA - E1 ➔ MXZ-4A80VA - E2
1. Ball valve has been changed to stop valve.
2. Gas pipe temperature thermistor has been removed.
3. Pre-heat control has been added.
4. Auto line correcting function has been added.
5. Noise filter P.C. board has been changed.
6. Electronic control P.C. board has been changed.
7. Weight has been changed. (70kg ➔ 67kg)
MXZ-5A100VA - E1
1. New model
MXZ-3A54VA - E3 ➔ MXZ-3A54VA - E4
1. Compressor has been changed. (SNB130FLEH1 ➔ SNB130FGBH1)
2. Electronic control P.C. board has been changed.
3. Gas pipe temperature thermistor has been removed.
4. Pre-heat control has been added.
5. Power board has been changed.
MXZ-4A71VA - E3 ➔ MXZ-4A71VA - E4
1. Compressor has been changed. (SNB130FLEH1 ➔ SNB130FGBH1)
2. Electronic control P.C. board has been changed.
3. Gas pipe temperature thermistor has been removed.
4. Pre-heat control has been added.
5. Power board has been changed.
MXZ-2A30VA - E1 ➔ MXZ-2A30VA - E2
1. Compressor has been changed. (KNB092FEDH ➔ KNB073FGDH)
2. Inverter P.C. board has been changed.
MXZ-3A54VA - E4 ➔ MXZ-3A54VA - E5
1. Electronic control P.C. board has been changed.
2. Noise filter P.C. board has been changed.
3. Ball valve has been changed to stop valve.
4. Sub panel has been added.
MXZ-4A71VA - E4 ➔ MXZ-4A71VA - E5
1. Electronic control P.C. board has been changed.
2. Noise filter P.C. board has been changed.
3. Ball valve has been changed to stop valve.
4. Sub panel has been added.
4
OB377F--1.qxp 07.11.22 10:27 AM Page 5
5
OB377F--1.qxp 07.11.22 10:27 AM Page 6
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f
3.5
R410A
Saturated liquid pressure
3.0 R22
2.5
2.0
1.5
1.0 NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
0.5
f [Gauge])
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f
0.0
-0.5
-30 -20 -10 0 10 20 30 40 50 60 (:)
6
OB377F--1.qxp 07.11.22 10:27 AM Page 7
2. Refrigerant piping
1 Specifications
Use the copper or copper-alloy seamless pipe for refrigerant that meet the following specifications.
Outside diameter
Wall thickness Insulation material
mm
6.35 0.8 mm
9.52 0.8 mm Heat resisting foam plastic
12.7 0.8 mm Specific gravity 0.045 Thickness 8 mm
15.88 1.0 mm
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe.
For details of flaring work, refer to Installation manual “FLARING WORK”.
mm R410A R22
6.35 17 17
9.52 22 22
12.7 26 24
15.88 29 27
3. Refrigeration oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4. Air purge
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5. Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the
outdoor unit. In this case, ability of the refrigeration cycle decreases or normal operation can be impossible. However,
charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Union
Stop valve
Indoor unit
Liquid pipe
Gas pipe Outdoor unit
Refrigerant gas
cylinder
operating valve Service port
Gauge manifold
valve (for R410A)
Charge hose (for R410A)
Refrigerant (liquid)
Electronic scale for refrigerant charging
7
OB377F--1.qxp 07.11.22 10:27 AM Page 8
MXZ-2A30VA MXZ-3A54VA- E1 , E2 , E3 , E4
MXZ-2A40VA MXZ-4A71VA- E1 , E2 , E3 , E4
MXZ-2A52VA
Drain hose
Air outlet
Air outlet
Drain outlet
Drain outlet
MXZ-3A54VA- E5
MXZ-4A71VA- E5
Air inlet
(Back and side)
Air outlet
Drain outlet
8
OB377F--1.qxp 07.11.22 10:27 AM Page 9
MXZ-4A80VA- E1 MXZ-4A80VA- E2
MXZ-5A100VA
ACCESSORIES
MXZ-3A54VA - E2 , E3 , E4 , E5
MXZ-2A30VA
MXZ-3A54VA - E1 MXZ-4A71VA - E2 , E3 , E4 , E5
MXZ-2A40VA
MXZ-4A71VA - E1 MXZ-4A80VA
MXZ-2A52VA
MXZ-5A100VA
1 Drain socket 1 1 1
2 Drain cap − 2 2
3 Quick Clean kit − 1 −
9
OB377F--1.qxp 07.11.22 10:27 AM Page 10
10
OB377F--1.qxp 07.11.22 10:27 AM Page 11
11
OB377F--1.qxp 07.11.22 10:27 AM Page 12
12
OB377F--1.qxp 07.11.22 10:27 AM Page 13
13
OB377F--1.qxp 07.11.22 10:27 AM Page 14
14
OB377F--1.qxp 07.11.22 10:27 AM Page 15
15
OB377F--1.qxp 07.11.22 10:27 AM Page 16
16
OB377F--1.qxp 07.11.22 10:27 AM Page 17
17
OB377F--1.qxp 07.11.22 10:27 AM Page 18
18
OB377F--1.qxp 07.11.22 10:27 AM Page 19
19
OB377F--1.qxp 07.11.22 10:27 AM Page 20
20
OB377F--1.qxp 07.11.22 10:27 AM Page 21
21
OB377F--1.qxp 07.11.22 10:27 AM Page 22
22
OB377F--1.qxp 07.11.22 10:27 AM Page 23
23
OB377F--1.qxp 07.11.22 10:27 AM Page 24
24
OB377F--1.qxp 07.11.22 10:27 AM Page 25
25
OB377F--1.qxp 07.11.22 10:27 AM Page 26
26
OB377F--1.qxp 07.11.22 10:27 AM Page 27
27
OB377F--1.qxp 07.11.22 10:28 AM Page 28
28
OB377F--1.qxp 07.11.22 10:28 AM Page 29
29
OB377F--1.qxp 07.11.22 10:28 AM Page 30
30
OB377F--2.qxp 07.11.22 10:31 AM Page 31
31
OB377F--2.qxp 07.11.22 10:31 AM Page 32
32
OB377F--2.qxp 07.11.22 10:31 AM Page 33
33
OB377F--2.qxp 07.11.22 10:31 AM Page 34
34
OB377F--2.qxp 07.11.22 10:31 AM Page 35
35
OB377F--2.qxp 07.11.22 10:31 AM Page 36
36
OB377F--2.qxp 07.11.22 10:31 AM Page 37
5 SPECIFICATION
Max. 20
Connecting pipe length m Max. 15
Height difference (Indoor ~ Outdoor) m Refer to 9
Height difference (Indoor ~ Indoor) m Refer to 9
Function Cooling Heating
Capacity
Capacity [Rated (Min.-Max.) Hz]✽1 kW 3.0 (1.1 - 4.0) 4.0 (1.0 - 4.5)
Dehumidification R/h — —
Outdoor air flow K /h 1,950 1,950
Power outlet A 10
Running current ✽1 A 2.87 3.6
✽2 Electrical
Power factor ✽1 % 90
Starting current ✽1 A 3.60
Compressor motor current A 2.67 3.40
Fan motor current A 0.2
Coefficient of performance(C.O.P) ✽2 5.04 5.37
E1 KNB092FEDH
Model
Compressor
E2 KNB073FGDH
Output W 750
Winding U-V 1.70
"
resistance(at 20:) V-W 1.70 W-U 1.70
Model RC0J50-CF
motor
Fan
37
OB377F--2.qxp 07.11.22 10:31 AM Page 38
Max. 30
Connecting pipe length m Max. 20 Max. 20
Height difference (Indoor ~ Outdoor) m Refer to 9 Refer to 9
Height difference (Indoor ~ Indoor) m Refer to 9 Refer to 9
Function Cooling Heating Cooling Heating
Capacity
Capacity [Rated (Min.-Max.) Hz]✽1 kW 4.0 (1.1 - 4.5) 4.5 (1.0 - 5.0) 4.0 (1.1 - 4.5) 4.5 (1.0 - 5.0)
Dehumidification R/h — — — —
Outdoor air flow K /h 1,860 1,860 1,950 1,950
Power outlet A 15 15
Running current ✽1 A 4.78 4.32 4.78 4.32
✽2 Electrical
Power factor ✽1 % 95 95
Starting current ✽1 A 4.78 4.78
Compressor motor current A 4.58 4.12 4.58 4.12
Fan motor current A 0.2 0.2
Coefficient of performance(C.O.P) ✽2 3.83 4.76 3.83 4.76
Model SNB130FKCH KNB092FEDH
Compressor
38
OB377F--2.qxp 07.11.22 10:31 AM Page 39
Capacity [Rated (Min.-Max.) Hz]✽1 kW 5.2 (1.1 - 6.0) 6.4 (1.0 - 7.2) 5.4 (2.9-6.8) 6.8 (2.6-9.0)
Dehumidification R/h — — — —
Outdoor air flow K /h 1,860 1,860 2,525 2,470
Power outlet A 15 25
Running current ✽1 A 6.75 7.64 5.69 6.39
✽2 Electrical
Power factor ✽1 % 97 99
Starting current ✽1 A 7.64 6.39
Compressor motor current A 6.55 7.44 5.49 6.19
Fan motor current A 0.2 0.2
Coefficient of performance(C.O.P) ✽2 3.46 3.75 4.17 4.67
E1 , E2 SNB130FLDH1
E1 SNB130FKCH
Model E3 SNB130FLEH1
E2 SNB130FKMH E4 , E5 SNB130FGBH1
Compressor
39
OB377F--2.qxp 07.11.22 10:31 AM Page 40
Capacity [Rated (Min.-Max.) Hz]✽1 kW 7.1 (3.7-8.8) 8.6 (3.4-9.0) 8.0 (3.7-9.2) 9.4 (3.4-11.6)
Dehumidification R/h — — — —
Outdoor air flow K /h 2,525 2,790 2,530 2,630
Power outlet A 25 25
Running current ✽1 A 8.48 8.56 9.62 8.48
✽2 Electrical
Power factor ✽1 % 99 99
Starting current ✽1 A 8.56 9.62
Compressor motor current A 8.28 8.36 9.42 8.28
Fan motor current A 0.2 0.2
Coefficient of performance(C.O.P) ✽2 3.68 4.41 3.65 4.87
E1 , E2 SNB130FLDH1
Model E3 SNB130FLEH1 TNB220FMCH
E4 , E5 SNB130FGBH1
Compressor
Winding
"
resistance(at 20:) WHT-RED 15.2 RED-BLK 15.2 WHT-RED 15.2 RED-BLK 15.2
Dimensions WOHOD mm 840o710o330 900o900o320
E1 70
Weight kg 58
E2 67
Sound level (High/Low) ✽3 dB 48/45 50/48 46/44 48/46
Fan speed (High/Low) ✽3 rpm 650/510 700/510 560/400 590/400
remarks
2 2
Refrigerant filling kg 2.7 3.5
capacity(R410A)
E1 , E2 , E3 600 (NEO22)
Refrigeration oil (Model) cc 870 (NEO22)
E4 , E5 700 (NEO22)
NOTE: •Test conditions are based on ISO 5151. (Refrigerant piping length (one way) :5m)
•Refer to 3 “INDOOR/OUTDOOR CORRESPONDENCE TABLE” for the combination.
✽1 Measured under rated operating frequency.
✽2 Electrical data is for only outdoor unit.
✽3 These specifications are when all indoor units are operating.
TEST CONDITIONS COOLING INDOOR DB27.0°C WB19.0°C
OUTDOOR DB35.0°C WB24.0°C
HEATING INDOOR DB20.0°C
OUTDOOR DB 7.0°C WB 6.0°C
40
OB377F--2.qxp 07.11.22 10:31 AM Page 41
Power factor ✽1 % 99
Starting current ✽1 A 12.88
Compressor motor current A 12.68 12.25
Fan motor current A 0.2
Coefficient of performance(C.O.P) ✽2 3.41 4.23
Model TNB220FMCH
Compressor
Output W 2,700
Winding U-V 1.41
"
resistance(at 20:) V-W 1.41 W-U 1.41
Model PM8H60-UA
motor
Fan
NOTE: •Test conditions are based on ISO 5151. (Refrigerant piping length (one way) :5m)
•Refer to 3 “INDOOR/OUTDOOR CORRESPONDENCE TABLE” for the combination.
✽1 Measured under rated operating frequency.
✽2 Electrical data is for only outdoor unit.
✽3 These specifications are when all indoor units are operating.
TEST CONDITIONS COOLING INDOOR DB27.0°C WB19.0°C
OUTDOOR DB35.0°C WB24.0°C
HEATING INDOOR DB20.0°C
OUTDOOR DB 7.0°C WB 6.0°C
41
OB377F--2.qxp 07.11.22 10:31 AM Page 42
90 90
80 80
70 70
NC-70 NC-70
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 APPROXIMATE 20 APPROXIMATE
THRESHOLD OF THRESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
90 90
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
80 80
70 70 NC-70
NC-70
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 APPROXIMATE 20 APPROXIMATE
THRESHOLD OF THRESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
42
OB377F--2.qxp 07.11.22 10:31 AM Page 43
90 90
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
70 70
NC-70 NC-70
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 APPROXIMATE 20 APPROXIMATE
THRESHOLD OF THRESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz
90 90
1m
MICROPHONE
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR
80 80
70 70
NC-70
60 60
Test conditions
NC-60
Cooling :Dry-bulb temperature 35: Wet-bulb temperature 24:
50 50 Heating :Dry-bulb temperature 7: Wet-bulb temperature 6:
NC-50
40 40
NC-40
30 30
NC-30
20 APPROXIMATE 20
THRESHOLD OF
HEARING FOR NC-20
CONTINUOUS
NOISE
10 10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
43
OB377F--2.qxp 07.11.22 10:31 AM Page 44
MXZ-2A30VA Unit: mm
MXZ-2A40VA
MXZ-2A52VA
REQUIRED SPACE Basically open 100mm or more
without any obstruction in front
and on both sides of the unit.
re
400 r mo
Drainage hole [42 m mo
100 100
mm
or m
ore
44
304 325
344.5
Air in 350
mm
17.5
ore or m
or m ore
200mm
40
Air out Open two sides of left,
right, or rear side.
22.3 2-10x21 Oval hole 23 285 13
handle
550
B unit connection
Gas pipe : [9.52(flared)3/8
251.1
280
302.5 170.4
150 500
800 69
44
OB377F--2.qxp 07.11.22 10:31 AM Page 45
MXZ-3A54VA - E1 E2 E3 E4 Unit: mm
, , ,
500
Open as a rule
63.2 233.1 288 More than 500 mm if
the back, both sides
17.7
396
Air in
Air out
17.7
31
Indoor and
outdoor
connect wiring
840 30 39O27 hole 30 330 13
C unit connection
440
225
360
B unit connection
45
A unit connection
25
84
121 23.1
Liquid pipe
[6.35(flared)1/4
45
OB377F--2.qxp 07.11.22 10:31 AM Page 46
MXZ-3A54VA - E5 Unit: mm
169 500 171
63.2 233.1 288
17.7
31.3
Air in
16.8
20.3
(Bolt Pitch)
360.6
396
Air in
13.3
3-[33 Drain hole
17.7
Air out
27.1
240
66.3
710
C unit connection
440
225
B unit connection
360
45
A unit connection
84
1.Installation space
More than
More than
100
Note : Leave front and both sides
500
clearance fully.
More than
2.Service space
More than
200
More than
clearance fully.
500
350 350
500
46
OB377F--2.qxp 07.11.22 10:31 AM Page 47
MXZ-4A71VA - E1 , E2 , E3 , E4 Unit: mm
500
396
Air in
Air out
17.7
31
Indoor and
outdoor
connect wiring
840 30 39O27 hole 30 330 13
Gas pipe
27.1 66.3 [9.52(flared)3/8(B,C,D unit)
[12.7(flared)1/2(A unit)
710
D unit connection
C unit connection
315
45
440
360
B unit connection
A unit connection
25
84
121 23.1
Liquid pipe
[6.35(flared)1/4
47
OB377F--2.qxp 07.11.22 10:31 AM Page 48
MXZ-4A71VA - E5 Unit: mm
17.7
31.3
Air in
16.8
20.3
(Bolt Pitch)
360.6
396
Air in
13.3
3-[33 Drain hole
17.7
Air out
840 30
200 30 330 13
27.1
Indoor and outdoor 240
connect wiring 66.3 Gas pipe
39o27 hole [9.52(flared)3/8(B,C,D unit)
[12.7(flared)1/2(A unit)
D unit connection
710
C unit connection
315
440
B unit connection
360
45
A unit connection
84
299 23.1
1.Installation space
More than
More than
100
Note : Leave front and both sides
500
clearance fully.
2.Service space
More than
More than
200
More than
100
clearance fully.
350 350
500
48
OB377F--2.qxp 07.11.22 10:31 AM Page 49
MXZ-4A80VA - E1 Unit: mm
(27)
(16)
Air in
35
Veranda
Air in 355 Base
387
74
(16)
40
Air out
Drainage holes 3-[33
2-12O36 Oval hole
Gas pipe
(Base bolt M10) [9.52(flared)3/8(B,C,D unit)
[12.7(flared)1/2(A unit)
900 30 320 10
Indoor and
outdoor
connect wiring 88
26O45 hole
900
D unit connection
50
C unit connection
350
531.3
480.8
460
B unit connection
A unit connection
23
33
317 23
Liquid pipe
[6.35(flared)1/4
1.Installation space
More than
More than
100
Note : Leave front and both sides
500
clearance fully.
More than
2.Service space
More than
200
More than
clearance fully.
500
500 350
500
49
OB377F--2.qxp 07.11.22 10:31 AM Page 50
11 Base
(Bolt pitch)
355
387
Air in
24
16
Air out
2-12 o 36 Oval hole Gas pipe
(Base bolt M10) [9.52(flared)3/8(B,C,D,E(MXZ-5A100VA) unit)
[12.7(flared)1/2(A unit)
900 30 320 10
D unit connection
405
C unit connection
597
460
B unit connection
45
A
A unit connection
132
317 23
Liquid pipe
[6.35(flared)1/4
1.Installation space
More than
More than
100
Note : Leave front and both sides
500
clearance fully.
More than
2.Service space
More than
200
More than
clearance fully.
500
500 350
500
50
OB377F--2.qxp
L64
07.11.22 10:31 AM
BLK
LD69 T801 R62 IPM CT781 C
MXZ-2A30VA MXZ-2A40VA
N
LDE DB65 F901 9
BLU
L65 U 3 5
BLK 1 21S4 TR821
TO INDOOR POWER P.C. 2 P 1
IC801
UNIT No.B 230V~ S1 SSR61 CN912 V MF
GRN
BOARD 1
CONNECTING S2 N 2
CN934 CN933 W
R831 3
7
WIRING DIAGRAM
12-24V S3 TB3
CN937 IC932 CN932
BLK
6
CN938 CN936 CN935 INVERTER P.C. BOARD
BLU
1
ORN 2 CN602 7 CN661 CN663 CN662
3 1 2 3 4 5 6 1 2 1 2 CN791 CN792
BLK
MXZ-2A52VA
TO INDOOR 1 CN601
UNIT No.A 230V~ S1 LED1 LED2 SW1
BLU 2 6 6
51
CONNECTING S2 3 INTERFACE DISPLAY
RED 4 P.C. BOARD P.C. BOARD LEV A LEV B
5 RT61 RT62 RT68 RT65 RT64
12-24V S3 TB2
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CT61,CT761,CT781 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR R61,R62,R831 CURRENT-DETECTING RESISTOR refer to the indoor unit electric wiring
C63A,C63B,C63C SMOOTHING CAPACITOR NF NOISE FILTER R64A,R64B RESISTOR diagram for servicing.
DB61,DB65 DIODE MODULE NR64 VARISTOR TB1,TB2,TB3 TERMINAL BLOCK 2.Use copper conductors only (for field wiring).
F61 FUSE (T20AL250V) RT61 DEFROST THERMISTOR TR821 SWITCHING POWER TRANSISTOR 3.Symbols below indicate.
F64,F801,F901 FUSE (T3.15AL250V) RT62 DISCHARGE TEMPERATURE THERMISTOR T801 SWITCHING TRANS :Terminal block :Connector
IC801 INTELLIGENT POWER DEVICE RT64 FIN TEMPERATURE THERMISTOR X64 RELAY
IPM,IC932 INTELLIGENT POWER MODULE RT65 AMBIENT TEMPERATURE THERMISTOR 21S4 R.V. COIL
L64,L65 REACTOR OUTDOOR HEAT EXCHANGER LEV A,LEV B EXPANSION VALVE
RT68
MC COMPRESSOR TEMPERATURE THERMISTOR SSR61 SOLENOID COIL RELAY
NOISE FILTER PFC POWER BOARD V
P.C. BOARD
OB377F--2.qxp
X64
L
CT1 MC
3 BLK 3 4 R U
RED
TB1 U BLK W
GRN/YLW CB1 CB2 CB3
GROUND F64
PE TAB1
POWER BLK TAB4 WHT 1 2 YLW S
R64A R64B
MXZ-3A54VA -
SUPPLY L BLU N/F
~/N WHT
N TAB2 IPM
E1
230V~ BLK
CIRCUIT V
N
50Hz NR64
1 2
CN5
,
2 1
BREAKER
CN903
CT61 BLK
E2
3 2 1
BLK CT2
07.11.22 10:31 AM
CN61
,
1 2
CN902
RED
RS1 RS3 W
E3
CN2
F911 SSR61
7 6 5 4 3 2 1
CN901 RS2 RS4
BLK
BLU
LDE1 LDE2 1 2 CN912 1 2 3 4 5
BLK
Page 52
CN4
BLK
1 2
CN3
TO INDOOR 1 2
UNIT No.C 12-24V S3 GRN GRN
BLU
BLU
CONNECTING S2 GRN
BLK
BLK
BLK
BLK
YLW 21S4
S1
BLK
BLK
BLK
RED
WHT
BLK
BLK
230V~
BLK
TB4
BLK
BLU
CN603
1 2 3
1 2 3 4 5 1 2 3 4 5 6 7 1 2 1 2 3 CN801
TO INDOOR ORN CN781 CN702 CN701
UNIT No.B 12-24V S3 F801 HC930
CONNECTING CN932
1 2 3
CN602
S2 T801 BLK
RED
52
230V~ S1 WHT
BLU
RED
BLK
TB3 ELECTRONIC CONTROL P.C. BOARD
3 2 1
BLU R937A
CN601
TO INDOOR BLK YLW MF
1 2 3 4 5
(WHT) (RED) (BLU) R937B
UNIT No.A 12-24V S3 CN791 CN792 CN793 CN662 CN661 CN663 CN795 BLU
CONNECTING ORN
S2 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 1 2 3 4 5 6 PNK
230V~ S1 GRY
5 4 3 2 1
TB2
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
BLK
BLK
GRY
GRY
GRY
GRY
RED
BRN
BLU
ORN
YLW
WHT
CN931
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR MC COMPRESSOR RT64 FIN TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
CT1, 2 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR RT65 AMBIENT TEMPERATURE THERMISTOR diagram for servicing.
CT61 CURRENT TRANSFORMER NR64 VARISTOR 2.Use copper conductors only (for field wiring).
FUSE (T2AL250V) RT68 OUTDOOR HEAT EXCHANGER
F64 N/F NOISE FILTER TEMPERATURE THERMISTOR 3.Symbols below indicate.
F801 FUSE (T3.15AL250V) PFC POWER FACTOR CONTROLLER SSR61 SOLENOID COIL RELAY :Terminal block :Connector
F911 FUSE (T1AL250V) R64A,B RESISTOR T801 TRANSFORMER
HC930 INTELLIGENT POWER MODULE R937A, B RESISTOR TB1~4 TERMINAL BLOCK
IPM INTELLIGENT POWER MODULE RS1~4 RESISTOR X64 RELAY
L REACTOR RT6A~C GAS PIPE TEMPERATURE THERMISTOR 21S4 R.V. COIL
LEV A~C EXPANSION VALVE RT61 DEFROST THERMISTOR
LEV E EXPANSION VALVE RT62 DISCHARGE TEMPERATURE THERMISTOR
OB377F--2.qxp
MXZ-3A54VA -
E4
07.11.22 10:31 AM
Page 53
53
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR MC COMPRESSOR RT65 AMBIENT TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
CT1, 2 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR diagram for servicing.
RT68 OUTDOOR HEAT EXCHANGER
CT61 CURRENT TRANSFORMER NR64 VARISTOR TEMPERATURE THERMISTOR 2.Use copper conductors only (for field wiring).
F64 FUSE (T2AL250V) N/F NOISE FILTER SSR61 SOLENOID COIL RELAY 3.Symbols below indicate.
F801 FUSE (T3.15AL250V) PFC POWER FACTOR CONTROLLER T801 TRANSFORMER :Terminal block :Connector
F911 FUSE (T1AL250V) R64A,B RESISTOR TB1~4 TERMINAL BLOCK
HC930 INTELLIGENT POWER MODULE R937A, B RESISTOR X64 RELAY
IPM INTELLIGENT POWER MODULE RS1~4 RESISTOR 21S4 R.V. COIL
L REACTOR RT61 DEFROST THERMISTOR
LEV A~C EXPANSION VALVE RT62 DISCHARGE TEMPERATURE THERMISTOR
LEV E EXPANSION VALVE RT64 FIN TEMPERATURE THERMISTOR
OB377F--2.qxp
U NR64 CN902
TB4 BLU 3 1 BLK 1
YLW 2 BLK RS1 RS3 CT2
N/F
12-24V S3 BLK W RED
TO INDOOR BLU 1 CN2
S2 CN61 BLK RS2 RS4
UNIT No.C SSR61 CN3
BLK CN901 BLK CN4
Page 54
CONNECTING S1 BLK 2
230V~ LDE1 CN912 7 LD2 LD1 LD9 1
2 1 1 5 1 2 RT64
BLK
BLK
BLK
BLK
BLK
BLK
BLK
RED
WHT
GRN
21S4
TB3 ORN
S3 YLW 1 5 1 7 1 2 1 3
12-24V 3 CN801
TO INDOOR BLU CN603
S2 CN781 CN702 CN701
UNIT No.B 1 F801
54
CONNECTING BLK HC930 CN932
230V~ S1 T801 1 BLK
ORN 3 R937A WHT
CN602 RED
R937B 3 8
1
ELECTRONIC CONTROL P.C.BOARD 1 YLW
LED3 LED2 LED1 BLU
TB2 RED RED ORN
5 CN931 MS
12-24V S3 PNK
BLU BLU GRY 3~
TO INDOOR S2 CN601 (WHT) (RED) (BLU) 5
UNIT No.A CN791 CN792 CN793 CN661 CN663 CN795 MF
CONNECTING BLK BLK 1
230V~ S1 1 8 1 2
6 6 6 6
NOTES: 1. About the indoor side electric wiring refer to
the indoor unit electric wiring diagram for servicing. M M M RT61 RT68 M
2. Use copper conductors only (For field wiring).
3. Symbols below indicate. LEV A LEV B LEV C RT62 RT65 LEV E
:Terminal block :Connector
SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
CB1~3 SMOOTHING CAPACITOR HC930 INTELLIGENT POWER MODULE MF FAN MOTOR RS1~4 RESISTOR SSR61 SOLENOID COIL RELAY
CT1,2 CURRENT TRANSFORMER IPM INTELLIGENT POWER MODULE NR64 VARISTOR RT61 DEFROST THERMISTOR T801 TRANSFORMER
CT61 CURRENT TRANSFORMER L REACTOR N/F NOISE FILTER RT62 DISCHARGE TEMP.THERMISTOR TB1~4 TERMINAL BLOCK
F64 FUSE(T2AL250V) LEV A~C EXPANSION VALVE PFC POWER FACTOR CONTROLLER RT64 FIN TEMP.THERMISTOR X64 RELAY
F65 FUSE(T6.3AL250V) LEV E EXPANSION VALVE PTC64,65 CIRCUIT PROTECTION RT65 AMBIENT TEMP.THERMISTOR 21S4 REVERSING VALVE SOLENOID COIL
F801 FUSE(T3.15AL250V) MC COMPRESSOR R937A,B RESISTOR RT68 OUTDOOR HEAT EXCHANGER TEMP.THERMISTOR
OB377F--2.qxp
230V~ CIRCUIT V
N
NR64
,
50Hz
1 2
CN5
2 1
BREAKER
CN903
CT61 BLK
E2
3 2 1
,
1 2
CN902
RED
TO INDOOR
BLU
E3
UNIT No.D S3
Page 55
CN2
CONNECTING F911 SSR61
S2
BLK
S1
7 6 5 4 3 2 1
230V~ CN901 RS2 RS4
TB5
BLK
BLU
LDE2 1 2 CN912 1 2 3 4 5
LDE1 BLK
CN4
BLK
1 2
CN3
TO INDOOR BRN
UNIT No.C S3 GRN GRN
BLU
BLU
12-24V
CN604
1 2 3
CONNECTING S2 GRN
BLK
BLK
BLK
BLK
YLW 21S4
S1
BLK
BLK
BLK
RED
WHT
BLK
BLK
230V~
BLK
TB4
BLK
BLU
CN603
1 2 3
1 2 3 4 5 1 2 3 4 5 6 7 1 2 1 2 3 CN801
TO INDOOR ORN CN781 CN702 CN701
UNIT No.B S3 F801 HC930
12-24V
CONNECTING CN932
1 2 3
CN602
S2 T801 BLK
55
S1 RED WHT
230V~
BLK
BLU
TB3 ELECTRONIC CONTROL P.C. BOARD RED
3 2 1
BLU R937A
CN601
TO INDOOR BLK YLW MF
1 2 3 4 5
(WHT) (RED) (BLU) (GRN) R937B
UNIT No.A 12-24V S3 CN791 CN792 CN793 CN794 CN662 CN661 CN663 CN795 BLU
CONNECTING ORN
S2 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 1 2 3 4 5 6 PNK
230V~ S1 GRY
5 4 3 2 1
TB2
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
BLK
BLK
GRY
GRY
GRY
GRY
RED
BRN
BLU
ORN
YLW
WHT
CN931
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR MC COMPRESSOR RT64 FIN TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
CT1, 2 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR RT65 AMBIENT TEMPERATURE THERMISTOR diagram for servicing.
CT61 CURRENT TRANSFORMER NR64 VARISTOR OUTDOOR HEAT EXCHANGER 2.Use copper conductors only (for field wiring).
RT68
F64 FUSE (T2AL250V) N/F NOISE FILTER TEMPERATURE THERMISTOR 3.Symbols below indicate.
F801 FUSE (T3.15AL250V) PFC POWER FACTOR CONTROLLER SSR61 SOLENOID COIL RELAY :Terminal block :Connector
F911 FUSE (T1AL250V) R64A,B RESISTOR T801 TRANSFORMER
HC930 INTELLIGENT POWER MODULE R937A, B RESISTOR TB1~5 TERMINAL BLOCK
IPM INTELLIGENT POWER MODULE RS1~4 RESISTOR X64 RELAY
L REACTOR RT6A~D GAS PIPE TEMPERATURE THERMISTOR 21S4 R.V. COIL
LEV A~D EXPANSION VALVE RT61 DEFROST THERMISTOR
LEV E EXPANSION VALVE RT62 DISCHARGE TEMPERATURE THERMISTOR
OB377F--2.qxp
MXZ-4A71VA -
E4
07.11.22 10:32 AM
Page 56
56
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR MC COMPRESSOR RT65 AMBIENT TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
CT1, 2 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR diagram for servicing.
RT68 OUTDOOR HEAT EXCHANGER
CT61 CURRENT TRANSFORMER NR64 VARISTOR TEMPERATURE THERMISTOR 2.Use copper conductors only (for field wiring).
F64 FUSE (T2AL250V) N/F NOISE FILTER SSR61 SOLENOID COIL RELAY 3.Symbols below indicate.
F801 FUSE (T3.15AL250V) PFC POWER FACTOR CONTROLLER T801 TRANSFORMER :Terminal block :Connector
F911 FUSE (T1AL250V) R64A,B RESISTOR TB1~5 TERMINAL BLOCK
HC930 INTELLIGENT POWER MODULE R937A, B RESISTOR X64 RELAY
IPM INTELLIGENT POWER MODULE RS1~4 RESISTOR 21S4 R.V. COIL
L REACTOR RT61 DEFROST THERMISTOR
LEV A~D EXPANSION VALVE RT62 DISCHARGE TEMPERATURE THERMISTOR
LEV E EXPANSION VALVE RT64 FIN TEMPERATURE THERMISTOR
OB377F--2.qxp
BREAKER V WHT V MS
F65 N/F CN903 CN5
1 BLK 1 3~
TB5 BRN PTC65 2 BLK 2 MC W
12-24V S3 U NR64 CN902
TO INDOOR BLU BLU 3 1 BLK 1
S2 BLK
Page 57
N/F
CONNECTING BLK BLK W RED
230V~ S1 1 CN2
CN61 BLK RS2 RS4
SSR61 CN3
CN901 BLK CN4 2
TB4 LDE1 CN912 BLK 7 LD2 LD1 LD9 1
YLW 2 1 1 5 1 2 RT64
12-24V S3
BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK
RED
WHT
GRN
TO INDOOR S2
UNIT No.C BLK
CONNECTING 21S4
230V~ S1
BRN 3 1 5 1 7 1 2 1 3
CN801
TB3 CN604 CN781 CN702 CN701
ORN 1 F801
57
12-24V S3 YLW 3 HC930 CN932
TO INDOOR BLU T801 1 BLK
UNIT No.B
S2 CN603 R937A WHT
CONNECTING BLK 1 RED
230V~ S1 ORN 3 R937B 3 8
CN602 ELECTRONIC CONTROL P.C.BOARD YLW
1 LED3 LED2 LED1 1 BLU
TB2 RED RED ORN
5 CN931 MS
12-24V S3 PNK
BLU BLU GRY 3~
TO INDOOR S2 CN601 (WHT) (RED) (BLU) (GRN) 5
UNIT No.A CN791 CN792 CN793 CN794 CN661 CN663 CN795 MF
CONNECTING BLK BLK 1
230V~ S1 1 8 1 2
6 6 6 6 6
NOTES: 1. About the indoor side electric wiring refer to
the indoor unit electric wiring diagram for servicing. M M M M RT61 RT68 M
2. Use copper conductors only (For field wiring).
3. Symbols below indicate. LEV A LEV B LEV C LEV D RT62 RT65 LEV E
:Terminal block :Connector
SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
CB1~3 SMOOTHING CAPACITOR HC930 INTELLIGENT POWER MODULE MF FAN MOTOR RS1~4 RESISTOR SSR61 SOLENOID COIL RELAY
CT1,2 CURRENT TRANSFORMER IPM INTELLIGENT POWER MODULE NR64 VARISTOR RT61 DEFROST THERMISTOR T801 TRANSFORMER
CT61 CURRENT TRANSFORMER L REACTOR N/F NOISE FILTER RT62 DISCHARGE TEMP.THERMISTOR TB1~5 TERMINAL BLOCK
F64 FUSE(T2AL250V) LEV A~D EXPANSION VALVE PFC POWER FACTOR CONTROLLER RT64 FIN TEMP.THERMISTOR X64 RELAY
F65 FUSE(T6.3AL250V) LEV E EXPANSION VALVE PTC64,65 CIRCUIT PROTECTION RT65 AMBIENT TEMP.THERMISTOR 21S4 REVERSING VALVE SOLENOID COIL
F801 FUSE(T3.15AL250V) MC COMPRESSOR R937A,B RESISTOR RT68 OUTDOOR HEAT EXCHANGER TEMP.THERMISTOR
OB377F--2.qxp
PE
F64
L BLK TAB1 WHT 3 4 YLW S
R64A R64B TAB4
N BLU N/F
WHT
BLK IPM
07.11.22 10:32 AM
TAB2
NR64 V
N
CIRCUIT BREAKER
2 1
CN5
1 2
CN903
CT61 BLK
3 2 1
TO INDOOR BLK CT2
BLU
1 2
UNIT No.D S3 CN61 RED
CN902
12-24V
BLK
CONNECTING S2 RS1 RS3 W
Page 58
CN2
F911 SSR61
230V~ S1
TB2
7 6 5 4 3 2 1
CN901 RS2 RS4
BLK
BLU
BRN 1 2 CN912 1 2 3 4 5
TO INDOOR LDE1 LDE2
CN4 BLK
UNIT No.C 12-24V S3 BLK
1 2
LD1 LD9
CN3
LD2
CN604
1 2 3
RT64
CONNECTING 1 2
S2
GRN GRN
BLU
BLU
230V~ S1 TB3 YLW
GRN
BLK
BLK
BLK
BLK
21S4
BLK
BLU
BLK
BLK
BLK
RED
WHT
BLK
BLK
CN603
1 2 3
BLK
TO INDOOR
UNIT No.B 12-24V S3 ORN
1 2 3 4 5 1 2 3 4 5 6 7 1 2 1 2 3 CN801
58
CONNECTING S2 CN781 CN702 CN701
1 2 3
CN602
230V~ S1 TB4 F801 HC930
RED CN932
T801 BLK
BLK
BLU
TO INDOOR BLU WHT
ELECTRONIC CONTROL P.C. BOARD RED
3 2 1
CN601
BLK
1 2 3 4 5
CONNECTING S2
230V~ S1 TB5 (WHT) (RED) (BLU) (GRN) R937B YLW MF
CN791 CN792 CN793 CN794 CN681 CN662 CN661 CN663 CN795 BLU
ORN
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 1 2 3 4 5 6 PNK
GRY
5 4 3 2 1
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
BRN
BLU
ORN
YLW
WHT
RED
RED
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
GRY
BLK
BLK
GRY
GRY
GRY
GRY
CN931
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR LEV E EXPANSION VALVE RT62 DISCHARGE TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
CT1, 2 CURRENT TRANSFORMER MC COMPRESSOR RT64 FIN TEMPERATURE THERMISTOR diagram for servicing.
CT61 CURRENT TRANSFORMER MF OUTDOOR FAN MOTOR RT65 AMBIENT TEMPERATURE THERMISTOR 2.Use copper conductors only (for field wiring).
F64 FUSE (T2AL250V) NR64 VARISTOR 3.Symbols below indicate.
RT68 OUTDOOR HEAT EXCHANGER
F801 FUSE (T3.15AL250V) N/F NOISE FILTER TEMPERATURE THERMISTOR :Terminal block :Connector
F911 FUSE (T1AL250V) PFC POWER FACTOR CONTROLLER SSR61 SOLENOID COIL RELAY
HC930 INTELLIGENT POWER MODULE R64A,B RESISTOR T801 TRANSFORMER
HPS HIGH PRESSURE SWITCH R937A, B RESISTOR TB1~5 TERMINAL BLOCK
IPM INTELLIGENT POWER MODULE RS1~4 RESISTOR X64 RELAY
L REACTOR RT6A~D GAS PIPE TEMPERATURE THERMISTOR 21S4 R.V. COIL
LEV A~D EXPANSION VALVE RT61 DEFROST THERMISTOR
OB377F--2.qxp
MXZ-4A80VA -
E2
07.11.22 10:32 AM
Page 59
59
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR LEV A~D EXPANSION VALVE RT62 DISCHARGE TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
CT1, 2 CURRENT TRANSFORMER LEV F EXPANSION VALVE RT64 FIN TEMPERATURE THERMISTOR diagram for servicing.
CT61 CURRENT TRANSFORMER MC COMPRESSOR RT65 AMBIENT TEMPERATURE THERMISTOR 2.Use copper conductors only (for field wiring).
F64 FUSE (T2AL250V) MF OUTDOOR FAN MOTOR 3.Symbols below indicate.
RT68 OUTDOOR HEAT EXCHANGER
F65 FUSE (T6.3AL250V) NR64 VARISTOR TEMPERATURE THERMISTOR :Terminal block :Connector
F801 FUSE (T3.15AL250V) N/F NOISE FILTER SSR61 SOLENOID COIL RELAY
F931 FUSE (T3.15AL250V) PFC POWER FACTOR CONTROLLER T801 TRANSFORMER
HC930 INTELLIGENT POWER MODULE R64A,B RESISTOR TB1~5 TERMINAL BLOCK
HPS HIGH PRESSURE SWITCH R930A, B RESISTOR X64 RELAY
IPM INTELLIGENT POWER MODULE RS1~4 RESISTOR 21S4 R.V. COIL
L REACTOR RT61 DEFROST THERMISTOR
OB377F--2.qxp
MXZ-5A100VA
07.11.22 10:32 AM
Page 60
60
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTES: 1.About the indoor side electric wiring
CB1~3 SMOOTHING CAPACITOR LEV A~E EXPANSION VALVE RT62 DISCHARGE TEMPERATURE THERMISTOR refer to the indoor unit electric wiring
CT1, 2 CURRENT TRANSFORMER LEV F EXPANSION VALVE RT64 FIN TEMPERATURE THERMISTOR diagram for servicing.
CT61 CURRENT TRANSFORMER MC COMPRESSOR RT65 AMBIENT TEMPERATURE THERMISTOR 2.Use copper conductors only (for field wiring).
F64 FUSE (T2AL250V) MF OUTDOOR FAN MOTOR 3.Symbols below indicate.
RT68 OUTDOOR HEAT EXCHANGER
F65 FUSE (T6.3AL250V) NR64 VARISTOR TEMPERATURE THERMISTOR :Terminal block :Connector
F801 FUSE (T3.15AL250V) N/F NOISE FILTER SSR61 SOLENOID COIL RELAY
F931 FUSE (T3.15AL250V) PFC POWER FACTOR CONTROLLER T801 TRANSFORMER
HC930 INTELLIGENT POWER MODULE R64A,B RESISTOR TB1~6 TERMINAL BLOCK
HPS HIGH PRESSURE SWITCH R930A, B RESISTOR X64 RELAY
IPM INTELLIGENT POWER MODULE RS1~4 RESISTOR 21S4 R.V. COIL
L REACTOR RT61 DEFROST THERMISTOR
OB377F--3.qxp 07.11.22 10:36 AM Page 61
MXZ-2A30VA Unit:mm
[9.52
Compressor
Discharge
R.V. coil temperature
OFF Refrigerant flow in cooling thermistor RT62
ON Refrigerant flow in heating Muffler
HEX-OUT
Ambient
temperature
Capillary tube thermistor
[3.0✕[2.0✕ 200 RT65
Indoor unit Defrost
A thermistor
[6
Stop valve LEV A RT61
(with strainer #100)
Strainer
#100
[9.52
Capillary tube
[3.0✕[2.0✕ 200
Indoor unit
B [6
Stop valve LEV B
(with strainer #100)
● Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
Unit : mm (inch)
Outdoor unit union diameter
Indoor unit For
Extension pipe diameter
class Pipe diameter Liquid 6.35(1/4)
Liquid 6.35(1/4) Liquid 6.35(1/4) Indoor unit A
22/25 Gas 9.52(3/8)
Gas 9.52(3/8) Gas 9.52(3/8) Liquid 6.35(1/4)
Indoor unit B
Gas 9.52(3/8)
61
OB377F--3.qxp 07.11.22 10:36 AM Page 62
[12 [12
Indoor unit [9.52
A
Stop valve Outdoor heat
(with service port) exchanger
temperature
thermistor
RT68 FAN-OUT
HEX-OUT
Ambient
temperature
thermistor
RT65
Defrost
Capillary tube
thermistor
[3.0✕[2.0✕ 200 RT61
Indoor unit
A Capillary tube
Stop valve LEV A [6 [3.0✕[1.4✕600 (4 pcs)
(with strainer #100)
Strainer
#100 Distributor
[9.52
Capillary tube
[3.0✕[2.0✕ 200
Indoor unit
B [6
Stop valve LEV B
(with strainer #100)
Indoor a
MAX REFRIGERANT PIPING LENGTH units
Piping length each indoor unit (a, b) 20m
Total piping length (a+b) 30m
Bending point for each unit 20 Outdoor
unit 15m
Total bending point 30
❋It does not matter which unit is higher. 15m
ADDITIONAL REFRIGERANT CHARGE
Outdoor unit Refrigerant piping length (one way, 2 unit total)
precharged
(g) 20m 30m 10m
b
1,300 0 200
Unit : mm (inch)
Outdoor unit union diameter
Indoor unit For
Extension pipe diameter
class Pipe diameter Liquid 6.35(1/4)
Liquid 6.35(1/4) Liquid 6.35(1/4) Indoor unit A
22/25/35 Gas 9.52(3/8)
Gas 9.52(3/8) Gas 9.52(3/8) Liquid 6.35(1/4)
Indoor unit B
Gas 9.52(3/8)
62
OB377F--3.qxp 07.11.22 10:36 AM Page 63
MXZ-2A40VA - E2 Unit:mm
[9.52
Compressor
Discharge
R.V. coil temperature
OFF Refrigerant flow in cooling thermistor RT62
ON Refrigerant flow in heating Muffler
[9.52 [9.52
Indoor unit [9.52
A
Stop valve Outdoor heat
(with service port) exchanger
temperature
thermistor FAN-OUT
RT68
HEX-OUT
Ambient
temperature
Capillary tube thermistor
[3.0✕[2.0✕ 200 RT65
Indoor unit Defrost
A thermistor
Stop valve LEV A [6 RT61
(with strainer #100)
Strainer
#100
[9.52
Capillary tube
[3.0✕[2.0✕ 200
Indoor unit
B [6
Stop valve LEV B
(with strainer #100)
1,150 0 200
Unit : mm (inch)
Outdoor unit union diameter
Indoor unit For
Extension pipe diameter
class Pipe diameter Liquid 6.35(1/4)
Liquid 6.35(1/4) Liquid 6.35(1/4) Indoor unit A
22/25/35 Gas 9.52(3/8)
Gas 9.52(3/8) Gas 9.52(3/8) Liquid 6.35(1/4)
Indoor unit B
Gas 9.52(3/8)
63
OB377F--3.qxp 07.11.22 10:36 AM Page 64
HEX-OUT
Ambient
temperature
thermistor
RT65
Defrost
Capillary tube
thermistor
[4.0✕[2.8✕ 100 RT61
Indoor unit
A Capillary tube
Strainer LEV A [6.35 [3.6✕[2.4✕500 (8 pcs)
#100 Ball valve
Capillary tube
Strainer Strainer
[4.0✕[2.8✕ 100 #100 LEV E #100 Distributor
Indoor unit
Power
B [6.35 receiver [9.52
Strainer LEV B
#100
Capillary tube
[4.0✕[2.8✕ 100
Indoor unit
C [6.35
Strainer LEV C
#100
w Except MXZ-3A54VA - E4 .
● Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
● When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, see 17-1.
Unit : mm (inch)
Indoor unit Outdoor unit union diameter
Extension pipe diameter For
class Pipe diameter
Liquid 6.35(1/4) Liquid 6.35(1/4) Liquid 6.35(1/4)
22/25/35 Indoor unit A
Gas 9.52(3/8) Gas 9.52(3/8) Gas 9.52(3/8)
Liquid 6.35(1/4) Liquid 6.35(1/4) Liquid 6.35(1/4)
50 Indoor unit B
Gas 12.7(1/2) Gas 12.7(1/2) Gas 9.52(3/8)
Liquid 6.35(1/4)
Indoor unit C
Gas 9.52(3/8)
64
OB377F--3.qxp 07.11.22 10:36 AM Page 65
MXZ-3A54VA - E5 Unit:mm
[16
Compressor
Discharge
R.V. coil temperature
OFF Refrigerant flow in cooling thermistor RT62
ON Refrigerant flow in heating Oil separator
Capillary tube
[2.5✕[0.6✕1000
Indoor unit [9.52 Stop valve with
C service port 4-way valve
HEX-OUT
Ambient
temperature
thermistor
RT65
Defrost
Capillary tube
thermistor
[4.0✕[2.8✕ 100 RT61
Indoor unit
A Capillary tube
Strainer LEV A [6.35 [3.6✕[2.4✕500 (8 pcs)
#100
Capillary tube
Strainer Stop valve Strainer
[4.0✕[2.8✕ 100 #100 LEV E #100 Distributor
Indoor unit
Power
B [6.35 receiver [9.52
Strainer LEV B
#100
Capillary tube
[4.0✕[2.8✕ 100
Indoor unit
C [6.35
Strainer LEV C
#100
● Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
● When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, see 17-1.
Unit : mm (inch)
Indoor unit Outdoor unit union diameter
Extension pipe diameter For
class Pipe diameter
Liquid 6.35(1/4) Liquid 6.35(1/4) Liquid 6.35(1/4)
22/25/35 Indoor unit A
Gas 9.52(3/8) Gas 9.52(3/8) Gas 9.52(3/8)
Liquid 6.35(1/4) Liquid 6.35(1/4) Liquid 6.35(1/4)
50 Indoor unit B
Gas 12.7(1/2) Gas 12.7(1/2) Gas 9.52(3/8)
Liquid 6.35(1/4)
Indoor unit C
Gas 9.52(3/8)
65
OB377F--3.qxp 07.11.22 10:36 AM Page 66
MXZ-4A71VA - E1 E2 E3 E4 Unit:mm
, , ,
[16
Compressor
Discharge
R.V. coil temperature
OFF Refrigerant flow in cooling thermistor RT62
ON Refrigerant flow in heating Oil separator
Unit D gas pipe
temperature thermistor w Capillary tube
Indoor unit [9.52 [2.5✕[0.6✕1000
Ball valve with
D Unit C gas pipe
temperature thermistor w service port
4-way valve
Indoor unit [9.52
C Unit B gas pipe [16
temperature thermistor w
Indoor unit [9.52
[12 Muffler [16
B Unit A gas pipe
temperature thermistor w [12
Indoor unit [12.7 Outdoor heat
A exchanger
temperature FAN-OUT
thermistor
RT68
HEX-OUT
Ambient
temperature
thermistor
RT65
66
OB377F--3.qxp 07.11.22 10:36 AM Page 67
MXZ-4A71VA - E5 Unit:mm
[16
Compressor
Discharge
R.V. coil temperature
OFF Refrigerant flow in cooling thermistor RT62
ON Refrigerant flow in heating Oil separator
Capillary tube
Indoor unit [9.52 [2.5✕[0.6✕1000
D Stop valve with
[9.52 service port 4-way valve
Indoor unit
C [16
HEX-OUT
Ambient
temperature
thermistor
RT65
67
OB377F--3.qxp 07.11.22 10:36 AM Page 68
MXZ-4A80VA - E1 Unit:mm
[16
Compressor
High-pressure Discharge
R.V. coil temperature
Refrigerant flow in cooling switch
OFF thermistor RT62
ON Refrigerant flow in heating Oil separator
[16
Capillary tube
Unit D gas pipe
Ball valve with [2.5✕[0.6✕1000
temperature thermistor
Indoor unit [9.52 service port
4-way valve
D Unit C gas pipe
temperature thermistor [16
Indoor unit [9.52
C Unit B gas pipe [16 Muffler [16
temperature thermistor
Indoor unit [9.52
B Unit A gas pipe
temperature thermistor
Indoor unit [12.7
A Outdoor Ambient
heat temperature
exchanger thermistor
Outdoor heat RT65
exchanger
temperature
thermistor
RT68
Capillary tube
[4.0✕[2.8✕ 90 Defrost
Indoor unit thermistor
RT61
A
Strainer LEV A [6.35
#100 Capillary tube
Indoor unit Ball valve Strainer Strainer [4.0✕[2.4✕400
B [6.35 #100 LEV E #100 Distributor
Strainer LEV B
#100 Power
receiver [9.52
Indoor unit
C Strainer [6.35
LEV C Distributor
#100
Indoor unit
D [6.35
Strainer LEV D
#100
68
OB377F--3.qxp 07.11.22 10:36 AM Page 69
MXZ-4A80VA - E2 Unit:mm
[16
High-pressure Compressor
switch Discharge
R.V. coil temperature
OFF Refrigerant flow in cooling thermistor RT62
ON Refrigerant flow in heating Oil separator
Capillary tube
Indoor unit [9.52
[2.5✕[0.6✕1000
D Stop valve
[9.52 (with service port) 4-way valve
Indoor unit
C [16
Outdoor Ambient
heat temperature
exchanger thermistor
Outdoor heat RT65
exchanger
temperature
thermistor
RT68
Capillary tube
[4.0✕[2.8✕ 100 Defrost
Indoor unit thermistor
RT61
A
Strainer LEV A [6.35
#100 Capillary tube
Indoor unit Stop valve Strainer Strainer [3.0✕[2.0✕300
B [6.35 #100 LEV F #100 Distributor
Strainer LEV B
#100 Power
receiver [8
Indoor unit
C Strainer [6.35
LEV C
#100
Indoor unit
D [6.35
Strainer LEV D
#100
Indoor a
MAX REFRIGERANT PIPING LENGTH units
Piping length each indoor unit (a, b, c, d) 25m
Total piping length (a+b+c+d) 70m
Bending point for each unit 25 b Outdoor
unit 15m
Total bending point 70
❋It does not matter which unit is higher. 15m
ADDITIONAL REFRIGERANT CHARGE c
69
OB377F--3.qxp 07.11.22 10:36 AM Page 70
MXZ-5A100VA Unit:mm
[16
Compressor
High-pressure
Discharge
R.V. coil switch
temperature
OFF Refrigerant flow in cooling thermistor RT62
ON Refrigerant flow in heating Oil separator
Capillary tube
Indoor unit [9.52
[2.5✕[0.6✕1000
E Stop valve
[9.52 (with service port) 4-way valve
Indoor unit
D [16
10 PERFORMANCE CURVES
The standard specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed, the following information has been pro-
vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198~264V 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :
(2) Indoor outlet air wet-bulb temperature :
(3) Outdoor intake air dry-bulb temperature :
(4) Total input:
°CWB
°CWB
°CDB
W
} Cooling
Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL
(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
71
OB377F--3.qxp 07.11.22 10:36 AM Page 72
25 class
35 class
25 class
35 class
MXZ-3A54VA
MXZ-4A71VA
8.5 9.3 10.6 13.1 13.7
25 class
35 class
50 class
60 class
25 class
35 class
50 class
60 class
72
OB377F--3.qxp 07.11.22 10:36 AM Page 73
MXZ-4A80VA
25 class
35 class
50 class
60 class
71 class
25 class
35 class
50 class
60 class
71 class
MXZ-5A100VA
25 class
35 class
50 class
60 class
71 class
25 class
35 class
50 class
60 class
71 class
73
OB377F--3.qxp 07.11.22 10:36 AM Page 74
(OUTDOOR UNIT:MXZ-2A40VA - E2 )
3. 35-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
1.5 1.5 1.5 1.5
74
OB377F--3.qxp 07.11.22 10:36 AM Page 75
75
OB377F--3.qxp 07.11.22 10:37 AM Page 76
(OUTDOOR UNIT:MXZ-3A54VA)
1. 22-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
1.5 1.5 1.5 1.5
76
OB377F--3.qxp 07.11.22 10:37 AM Page 77
(OUTDOOR UNIT:MXZ-4A71VA)
1. 22-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
1.5 1.5 1.5 1.5
77
OB377F--3.qxp 07.11.22 10:37 AM Page 78
(OUTDOOR UNIT:MXZ-4A80VA)
1. 22-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
1.5 1.5 1.5 1.5
78
OB377F--3.qxp 07.11.22 10:37 AM Page 79
(OUTDOOR UNIT:MXZ-5A100VA)
1. 22-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
1.5 1.5 1.5 1.5
79
OB377F--3.qxp 07.11.22 10:37 AM Page 80
80
OB377F--3.qxp 07.11.22 10:37 AM Page 81
10-4. Outdoor low pressure and outdoor unit current (single operation)
NOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).
f[Gauge])
The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/f
(1) COOL operation
Dry-bulb temperature(:) Relative humidity(%)
1 Both indoor and outdoor unit are under the
same temperature/humidity condition. 20 50
2 Operation : TEST RUN OPERATION (refer to 10-3.) 25 60
30 70
MXZ-2A30VA MXZ-2A40VA - E2
42Hz 42Hz
Outdoor low pressure
Outdoor low pressure
13 1.3 13 1.3
12 1.2 12 1.2
3 3
11 1.1 42Hz 11 1.1 42Hz
10 1.0 10 1.0
2 2
9 0.9 9 0.9
8 0.8 8 0.8
7 1 7 0.7 1
0.7
15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
MXZ-2A40VA- E2
35-class unit
(kgf/F[Gauge]) (MPa[Gauge])
14
1.4 4
Outdoor unit current (A)
42Hz
Outdoor low pressure
13 1.3
12 1.2
3
11 1.1 42Hz
10 1.0
2
9 0.9
8 0.8
7 0.7 1
15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%)
81
OB377F--3.qxp 07.11.22 10:37 AM Page 82
MXZ-2A40VA - E1 MXZ-2A52VA
22-class unit 25-class unit
(kgf/F[Gauge]) (MPa[Gauge]) (kgf/F[Gauge])(MPa[Gauge])
1.4 4 14
1.4 4
14
13 1.3 13
12 1.2 12 1.2
3 3
30Hz 30Hz
11 1.1 11 1.1
10 1.0 10 1.0
2 2
9 0.9 9 0.9
8 8 0.8
0.8
7 7 0.7 1
0.7 1
15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
35-class unit
(kgf/F[Gauge])(MPa[Gauge])
14
1.4 4
Outdoor unit current (A)
30Hz
Outdoor low pressure
13 1.3
12 1.2
3
30Hz
11 1.1
10 1.0
2
9 0.9
8 0.8
7 0.7 1
15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%)
MXZ-3A54VA MXZ-4A71VA
22-class unit 25-class unit
(kgf/F[Gauge]) (MPa[Gauge]) (kgf/F[Gauge]) (MPa[Gauge])
12
1.2 5 1.2 5
Outdoor unit current (A)
12
Outdoor unit current (A)
40Hz
40Hz
Outdoor low pressure
11 1.1 1.1
11
4 4
10 1.0 40Hz
10 1.0 40Hz
9 0.9 3 0.9 3
9
8 0.8 8 0.8
2 2
7 0.7 7 0.7
6 0.6 1 6 0.6 1
15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%) (%) (%)
50 60 70 50 60 70
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
40Hz
Outdoor unit current (A)
40Hz
Outdoor low pressure
12 1.2 12 1.2
4 4
11 1.1 40Hz 1.1 40Hz
11
10 1.0 3 10 1.0 3
9 0.9 9 0.9
2 2
8 0.8 8 0.8
7 0.7 1 7 1
0.7
15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
82
OB377F--3.qxp 07.11.22 10:37 AM Page 83
MXZ-4A71VA
60-class unit
(kgf/F[Gauge]) (MPa[Gauge])
14
1.4 5
13 1.3
4
12 1.2 40Hz
11 1.1 3
10 1.0
2
9 0.9
8 0.8 1
15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%)
MXZ-4A80VA
22-class unit 25-class unit
(kgf/F[Gauge]) (MPa[Gauge]) (kgf/F[Gauge]) (MPa[Gauge])
1.2 5 12
1.2 5
12
24Hz 24Hz
Outdoor low pressure
Outdoor low pressure
11 1.1 11 1.1
4 4
10 1.0 24Hz 10 1.0 24Hz
9 0.9 3 9 0.9 3
8 0.8 8 0.8
2 2
7 0.7 7 0.7
6 1 6 0.6 1
0.6
15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
24Hz
Outdoor low pressure
Outdoor low pressure
12 1.2 12 1.2
4 4
1.1 24Hz 11 1.1 24Hz
11
10 1.0 3 10 1.0 3
9 0.9 9 0.9
2 2
8 0.8 8 0.8
7 0.7 1 7 0.7 1
15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
14
Outdoor unit current (A)
24Hz
Outdoor low pressure
24Hz
1.3
Outdoor low pressure
13
13 1.3
4
4
12 1.2 24Hz
12 1.2 24Hz
11 1.1 3
11 1.1 3
10 1.0
10 1.0
2
2
9 0.9
9 0.9
8 0.8 1 8 0.8 1
15 20 25 30 35 (:) 15 20 25 30 35 (:)
(%) (%) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 50 60 70 (%) (%)
50 60 70 50 60 70
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
83
OB377F--3.qxp 07.11.22 10:37 AM Page 84
MXZ-5A100VA
22-class unit 25-class unit
(kgf/F[Gauge]) (MPa[Gauge]) (kgf/F[Gauge]) (MPa[Gauge])
1.2 5 12
1.2 5
12
11 1.1 11 1.1
4 4
10 1.0 24Hz 10 1.0 24Hz
9 0.9 3 9 0.9 3
8 0.8 8 0.8
2 2
7 0.7 7 0.7
6 1 6 0.6 1
0.6
15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
24Hz
Outdoor low pressure
Outdoor low pressure
12 1.2 12 1.2
4 4
1.1 24Hz 11 1.1 24Hz
11
10 1.0 3 10 1.0 3
9 0.9 9 0.9
2 2
8 0.8 8 0.8
7 0.7 1 7 0.7 1
15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 (%) 50 60 70 (%) 50 60 70 (%) 50 60 70 (%)
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
14
Outdoor unit current (A)
24Hz
Outdoor low pressure
24Hz
1.3
Outdoor low pressure
13
13 1.3
4
4
12 1.2 24Hz
12 1.2 24Hz
11 1.1 3
11 1.1 3
10 1.0
10 1.0
2
2
9 0.9
9 0.9
8 0.8 1 8 0.8 1
15 20 25 30 35 (:) 15 20 25 30 35 (:)
(%) (%) 15 20 25 30 35 (:) 15 20 25 30 35 (:)
50 60 70 50 60 70 (%) (%)
50 60 70 50 60 70
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
Ambient humidity(%) Ambient humidity(%) Ambient humidity(%) Ambient humidity(%)
84
OB377F--3.qxp 07.11.22 10:37 AM Page 85
HEAT operation
1 Condition :
Indoor Outdoor
Dry bulb temperature (°C) 20.0 2 7 15 20.0
Wet bulb temperature (°C) 14.5 1 6 12 14.5
2 2 2
1 1 1
5 10 15 20 25 5 10 15 20 25 5 10 15 20 25
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
MXZ-2A40VA- E1 MXZ-2A52VA
22-class unit 25-class unit 35-class unit
4 4 4
Outdoor unit current (A)
2 2 2
1 1 1
5 10 15 20 25 5 10 15 20 25 5 10 15 25
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
MXZ-3A54VA MXZ-4A71VA
22-class unit 25-class unit 35-class unit 50-class unit
7 7 7 7
Outdoor unit current (A)
Outdoor unit current (A)
6 6 6 6
48Hz 48Hz
48Hz
5 5 5 5
48Hz
4 4 4 4
3 3 3 3
2 2 2 2
5 10 15 20 25 5 10 15 20 25 5 10 15 20 25 5 10 15 20 25
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
MXZ-4A71VA
60-class unit
7
Outdoor unit current (A)
5
48Hz
2
5 10 15 20 25
Ambient temperature(:)
85
OB377F--3.qxp 07.11.22 10:37 AM Page 86
MXZ-4A80VA
22-class unit 25-class unit 35-class unit 50-class unit
7 7 7 7
4 4 4 4
3 3 3 3
2 2 2 2
5 10 15 20 25 5 10 15 20 25 5 10 15 20 25 5 10 15 20 25
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
6 6
5 5
32Hz 32Hz
4 4
3 3
2 2
5 10 15 20 25 5 10 15 20 25
Ambient temperature(:) Ambient temperature(:)
MXZ-5A100VA
22-class unit 25-class unit 35-class unit 50-class unit
7 7 7 7
Outdoor unit current (A)
Outdoor unit current (A)
6 6 6 6
32Hz 32Hz
32Hz
5 5 5 5
32Hz
4 4 4 4
3 3 3 3
2 2 2 2
5 10 15 20 25 5 10 15 20 25 5 10 15 20 25 5 10 15 20 25
Ambient temperature(:) Ambient temperature(:) Ambient temperature(:) Ambient temperature(:)
6 6
5 5
32Hz 32Hz
4 4
3 3
2 2
5 10 15 20 25 5 10 15 20 25
Ambient temperature(:) Ambient temperature(:)
86
OB377F--3.qxp 07.11.22 10:37 AM Page 87
11 ACTUATOR CONTROL
Actuator
Sensor Purpose Outdoor Reversing
Compressor LEV
fan motor valve
Discharge temperature thermistor Protection
Indoor coil thermistor Defrosting Protection
Defrost thermistor Defrosting
Gas pipe temperature thermistor
(MXZ-3A54VA- E1 , E2 , E3
Control
MXZ-4A71VA- E1 , E2 , E3
MXZ-4A80VA- E1 )
Fin temperature thermistor Protection
Ambient temperature thermistor Control
Outdoor heat exchanger temperature Protection
Capacity code Control
87
OB377F--3.qxp 07.11.22 10:37 AM Page 88
12 SERVICE FUNCTIONS
ON ON
MXZ-4A80VA- E2
MXZ-5A100VA
MXZ-4A80VA- E2
12-2. Lowering the operating noise of the outdoor unit MXZ-5A100VA
SW871
SW2 SW1
ON ON
JK
JK
1 2 3 4 5 6 1 2 3 4
MXZ-3A54VA- E4 , E5 MXZ-4A80VA- E2
MXZ-4A80VA- E2 MXZ-5A100VA
MXZ-5A100VA MXZ-4A71VA- E4 , E5
MXZ-2A
<MXZ-2A>
Improper wiring or piping can be automatically detected when one
indoor unit is operated in COOL mode for 30 minutes. When improper
wiring or piping is detected, wiring lines are corrected (A to B/ B to A) with the software.
NOTE:
This function may not work due to the condition or environment of the
unit, such as the following:
- gas leak, closed stop valve
- unit failure such as defective LEV
- indoor/outdoor temperature
<Correct line>
Refrigerant piping
Indoor/outdoor
connecting wire
A
B INDOOR UNIT A
<Incorrect wiring>
B INDOOR UNIT A
<Incorrect piping>
B INDOOR UNIT A
89
OB377F--3.qxp 07.11.22 10:37 AM Page 90
The record of auto line correcting can be confirmed in the following way:
1 Turn OFF the power supply.
2 Turn ON the 4th Dip Switch of SW1 on the display P.C. board.
3 Turn ON the power supply. SW1
ON
4 Confirm the correction by the blinking of LED.
Number of blinks
Wiring line
LED1(Red) LED2(Yellow) MXZ-2A
Once Once Not corrected
3 times 3 times Corrected
5 Turn OFF the power supply after the confirmation, and turn OFF the 4th Dip Switch of SW1 on the display P.C. board.
6 Turn ON the power supply.
NOTE: This function does not work when the jumper wire JGO on the inverter P.C. board is cut.
<MXZ-4A80VA- E2 , MXZ-5A100VA>
Improper wiring or piping can be automatically detected by pressing the piping/wiring correction switch (SW871).
When improper wiring or piping is detected, wiring lines are corrected.
This will be completed in about 10 to 15 min.
90
OB377F--4.qxp 07.11.22 11:04 AM Page 91
The record of auto line correcting can be confirmed in the following way:
Press the switch for more than 5 sec.
LED will show the record of auto correcting for about 30 sec. as shown in the table below:
Number of blinks
Wiring line
LED1(Red) LED2(Yellow) LED3(Green)
Once Once Lighting Not corrected
3 times 3 times Lighting Corrected
NOTE: Activate this function to confirm the correct wiring after replacing the electronic control P.C. board.
(Previous records are deleted when the electronic control P.C. board is replaced.)
The record cannot be shown if auto line correcting is not canceled (Refer to "How to activate this function").
12-5. Increasing maximum compressor operational frequency and fan speed of the outdoor unit
<MXZ-4A80VA- E2 , MXZ-5A100VA>
Compressor operational frequency and fan speed can be increased.
Capacity of the unit can be improved with this function.
NOTE:
Compressor operational frequency may not be increased under primary current restriction or high pressure protection.
Compressor operational frequency will not be increased when 1 or 2 indoor units are operating.
This function doesn't work when the function which lowers the operating noise of the outdoor unit is activated.
Noise level of the outdoor unit will increase (You may need to explain this to your customers.)
1 Turn OFF the power supply for the air conditioner before making the setting.
2 Set the 3rd Dip Switch of SW2 on the outdoor electronic control P.C. board to ON to enable this function.
3 Turn ON the power supply for the air conditioner.
SW2
ON
1 2 3 4 5 6
1 Turn OFF the power supply for the air conditioner before making the setting.
2 Set the 1st Dip Switch of SW2 on the outdoor electronic control P.C. board to ON to enable this function.
3 Turn ON the power supply for the air conditioner. SW2
ON
1 2 3 4 5 6
13 TROUBLESHOOTING
Refer to the service manual of indoor unit for how to recall the failure mode and the details of indoor unit failure mode.
The outdoor unit failure mode is indicated by the operation indicator lamp on the indoor unit and the LED of outdoor unit.
See "13-2.2.Outdoor unit failure mode table".
92
OB377F--4.qxp 07.11.22 11:04 AM Page 93
3-time flash Discharge temperature Lighting Once Thermistor shorts or opens during • Refer to 13-6.F "Check
thermistor compressor running. of outdoor thermistors".
Defrost thermistor Lighting Once
Ambient temperature thermistor Lighting Twice
Fin temperature thermistor Lighting 3 times
P.C. board temperature Lighting 4 times • Replace the outdoor
thermistor electronic control
P.C. board.
Outdoor heat exchanger Lighting 9 times • Refer to 13-6.F "Check
temperature thermistor of outdoor thermistors".
4-time flash Overcurrent Once Goes out 23A(MXZ-2A30VA- E1 , MXZ-2A40VA, • Reconnect compressor
MXZ-2A52VA)/ 14A(MXZ-2A30VA- E2 ) connector.
current flows into intelligent power • Refer to 13-6.E "How
module. to check inverter/
compressor".
• Check the stop valve.
Compressor Twice The possibility of intercepting the • Check the connection of
Goes
overcurrent by the compressor lock is the compressor
out
high. connecting wire.
• Refer to 13-6.E "How to
9 times Goes The compressor doesn't synchronize check inverter/
out with the operating power. compressor".
5-time flash Discharge temperature Lighting Lighting Discharge temperature exceeds 116: • Check refrigerant circuit
during operation. and refrigerant amount.
Compressor can restart if discharge • Refer to 13-6.D "Check
temperature thermistor reads 100: or of LEV".
less 3 minutes later.
6-time flash High pressure Lighting Lighting The outdoor heat exchanger • Check refrigerant circuit
temperature exceeds 70: during and refrigerant amount.
cooling or the indoor gas pipe • Check the stop valve.
temperature exceeds 70: during
heating.
7-time flash Fin temperature 3 times Goes The fin temperature exceeds 90: • Check around outdoor
out during operation. unit.
• Check outdoor unit air
P.C. board temperature 4 times Goes The P.C. board temperature exceeds passage.
out 78: during operation. • Refer to 13-6.G "Check
of outdoor fan motor".
8-time flash Outdoor fan motor Lighting Lighting Failure occurs continuously three • Refer to 13-6.G "Check
times within 30 seconds after of outdoor fan motor".
the fan gets started.
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (13-4).
93
OB377F--4.qxp 07.11.22 11:04 AM Page 94
15-time flash LEV for drain Lighting Lighting The indoor unit detects any • Refer to 13-6.D "Check
abnormalities in the LEV for drain. of LEV".
• Check the drain pump of
the indoor unit.
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (13-4).
94
OB377F--4.qxp 07.11.22 11:04 AM Page 95
MXZ-3A/4A/5A
Upper or left lamp of LED indication Indoor/outdoor
OPERATION INDICATOR Abnormal point Condition Correspondence
(Outdoor P.C. board) unit failure mode
lamp (Indoor unit) (Failure mode / protection) recall function
LED 1 LED 2
OFF None (Normal) - -
2-time flash Outdoor power system Lighting Lighting Overcurrent protection stop is • Check the connection
continuously performed three times of the compressor
within 1 minute after the compressor connecting wire.
gets started, or converter protection • Refer to 13-6.E
stop or bus-bar voltage protection "How to check
stop is continuously performed inverter/ compressor".
three times within 3 minutes after • Check the stop valve.
start-up.
3-time flash Discharge temperature Lighting Once Thermistor shorts or opens during • Refer to 13-6.F "Check
thermistor compressor running. of outdoor thermistors".
Defrost thermistor Lighting Once
Ambient temperature thermistor Lighting Twice
Fin temperature thermistor Lighting 3 times
P.C. board temperature Lighting 4 times • Replace the outdoor
thermistor electronic control
P.C. board.
Outdoor heat exchanger Lighting 9 times • Refer to 13-6.F "Check
temperature thermistor
of outdoor thermistors".
Gas pipe temperature Lighting 10 times A short or open circuit is detected in
thermistor A the thermistor during cooling.
Gas pipe temperature Lighting 11 times (A,B,C : MXZ-3A54VA- E1 , E2 , E3
thermistor B MXZ-4A71VA- E1 , E2 , E3
Gas pipe temperature Lighting 12 times MXZ-4A80VA- E1 )
thermistor C (D : MXZ-4A71VA- E1 , E2 , E3
Gas pipe temperature Lighting 13 times MXZ-4A80VA- E1 )
thermistor D
4-time flash Overcurrent Once Goes out 28A current flows into intelligent power • Reconnect compressor
module. connector.
• Refer to 13-6.E "How to
check inverter/
compressor".
• Check the stop valve.
5-time flash Discharge temperature Lighting Lighting Discharge temperature exceeds 116: • Check refrigerant circuit
during operation. and refrigerant amount.
Compressor can restart if discharge • Refer to 13-6.D "Check
temperature thermistor reads 100: or of LEV".
less 3 minutes later.
6-time flash High pressure Lighting Lighting High-pressure is detected with the • Check refrigerant circuit
high-pressure switch (HPS) and refrigerant amount.
during operation. • Check the stop valve.
(MXZ-4A80VA, MXZ-5A100VA)
The outdoor heat exchanger
temperature exceeds 70: during
cooling or the indoor gas pipe
temperature exceeds 70: during
heating.
Fin temperature 3 times Goes The fin temperature exceeds 89: • Check around outdoor
7-time flash
out during operation. unit.
P.C. board temperature 4 times Goes The P.C. board temperature exceeds • Check outdoor unit air
out 73:(MXZ-3A54VA, MXZ-4A71VA)/ passage.
87:(MXZ-4A80VA, MXZ-5A100VA) • Refer to 13-6.G "Check
during operation. of outdoor fan motor".
8-time flash Outdoor fan motor Lighting Lighting Failure occurs continuously three • Refer to 13-6.G "Check
times within 30 seconds after the of outdoor fan motor".
fan gets started.
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (13-4).
95
OB377F--4.qxp 07.11.22 11:04 AM Page 96
Current sensor Lighting 7 times A short or open circuit is detected in • Replace the power
the current sensor during compressor board.
operating.
Current sensor protection stop is
continuously performed twice.
Zero cross detecting circuit 5 times Goes Zero cross signal cannot be detected • Check the connecting
out while the compressor is operating. wire among electronic
control P.C. board,
The protection stop of the zero cross noise filter P.C. board
detecting circuit is continuously and power board.
performed 10 times.
Converter 5 times Goes A failure is detected in the operation • Replace the power
out of the converter during operation. board.
15-time flash LEV for drain Lighting Lighting The indoor unit detects any • Refer to 13-6.D "Check
abnormalities in the LEV for drain. of LEV".
• Check the drain pump of
the indoor unit.
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (13-4).
Operation start
• Indoor unit • COOL or • When cooling, heat • When cooling, • When heating, • When cooling,
serial signal HEAT exchanger of dew drops in the room does not get room does not
error operation only non-operating indoor non-operating warm. cool.
Refer to 13-6. Refer to 13-6. unit frosts. indoor unit. Refer to 13-6.E Refer to 13-6.E
B "How to C "Check of •When heating, non- Check of "How to check of "How to check
check R.V. coil". operating indoor unit mispiping inverter/ compressor". of inverter/
miswiring and gets warm. Check mispiping, compressor".
serial signal Refer to 13-6. shortage of capacity
error". D "Check of LEV".
96
OB377F--4.qxp 07.11.22 11:04 AM Page 97
6 Lighting 7 times Nonvolatile memory data The nonvolatile memory data cannot be read properly. • Replace the outdoor electronic control P.C. board.
Bus-bar voltage The bus-bar voltage exceeds 430V or falls to 50V or below during • Replace the power board.
12 9 times Goes out compressor operating.
protection
Failure occurs continuously three times within 30 seconds after the fan
13 13 times Goes out Outdoor fan motor • Refer to 13-6.G "Check of outdoor fan motor".
gets started.
Current sensor A short or open circuit is detected in the current sensor during
14 8 times Goes out protection • Replace the power board.
compressor operating.
The discharge temperature exceeds 100: during operation. • Check refrigerant circuit and refrigerant amount.
Discharge temperature
18 3 times Lighting • Refer to 13-6.D "Check of LEV".
protection
• Refer to 13-6.F "Check of outdoor thermistors".
The frequency of the compressor is kept 80Hz or more and the discharge
Low discharge temperature is kept under 50:(COOL mode)/40:(HEAT mode) for • Refer to 13-6.D "Check of LEV".
19 4 times Lighting temperature protection more than 40 minutes. • Check refrigerant circuit and refrigerant amount.
97
OB377F--4.qxp 07.11.22 11:04 AM Page 98
Indication
No. Symptom Abnormal point / Condition Condition Correspondence
LED1(Red) LED2(Yellow)
Outdoor unit
operates. This symptom does not mean any abnormality of the
Cooling high-pressure product, but check the following points.
20 5 times Lighting protection The outdoor heat exchanger temperature exceeds 58: during operation. • Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
Outdoor unit
21 operates 9 times Lighting Inverter check mode The unit is operated with emergency operation switch. -
normally.
ON
2.5-second OFF 2.5-second OFF
OFF
98
OB377F--4.qxp 07.11.22 11:04 AM Page 99
MXZ-3A/4A/5A
Indication
No. Symptom Abnormal point / Condition Condition Correspondence
LED1(Red) LED2(Yellow)
Outdoor unit • Refer to 13-6.D "Check of LEV".
does not Lighting Once LEV for drain The indoor unit detects any abnormality in the LEV for drain.
1 operate. • Check the drain pump of the indoor unit.
Overcurrent protection stop is continuously performed three times • Check the connection of the compressor connecting
within 1 minute after the compressor gets started, or converter protection wire.
2 Lighting Twice Outdoor power system
stop or bus-bar voltage protection stop is continuously performed three • Refer to 13-6.E "How to check inverter/compressor".
times within 3 minutes after start-up. • Check the stop valve.
A short circuit is detected in the thermistor during operation, or an open
3 Discharge temperature • Refer to 13-6.F "Check of outdoor thermistors".
Lighting 3 times circuit is detected in the thermistor after 10 minutes of compressor start-up.
thermistor
Fin temperature
• Refer to 13-6.F "Check of outdoor thermistors".
thermistor
4 Lighting 4 times A short or open circuit is detected in the thermistor during operation.
P.C board temperature
• Replace the outdoor electronic control P.C. board.
thermistor
Ambient temperature A short or open circuit is detected in the thermistor during operation.
thermistor
A short circuit is detected in the thermistor during operation, or an open
Outdoor heat exchanger
circuit is detected in the thermistor after 5 minutes (in cooling) and 10
temperature thermistor
5
minutes (in heating) of compressor start-up. • Refer to 13-6.F "Check of outdoor thermistors".
Lighting 5 times
A short circuit is detected in the thermistor during operation, or an open
Defrost thermistor
circuit is detected in the thermistor after 5 minutes of compressor start-up.
6 Lighting 7 times Nonvolatile memory data The nonvolatile memory data cannot be read properly. • Replace the outdoor electronic control P.C. board.
7 Lighting 8 times Current sensor Current sensor protection stop is continuously performed twice. • Replace the power board.
Gas pipe temperature
thermistor A A short or open circuit is detected in the thermistor during cooling.
(A,B,C : MXZ-3A54VA- E1 , E2 , E3 , MXZ-4A71VA- E1 , E2 , E3
Gas pipe temperature
MXZ-4A80VA- E1 ) • Refer to 13-6.F "Check of outdoor thermistors".
8 thermistor B
Lighting 10 times (D : MXZ-4A71VA- E1 , E2 , E3 , MXZ-4A80VA- E1 )
Gas pipe temperature
thermistor C
Gas pipe temperature
thermistor D
Communication error Communication error occurs twice between the outdoor electronic control • Check the connecting wire between outdoor electronic control
9 Lighting 11 times
between P.C. boards P.C. board and power board for more than 10 seconds. P.C. board and power board.
Zero cross detecting The protection stop of the zero cross detecting circuit is continuously • Check the connecting wire among outdoor electronic control
10 Lighting 12 times
circuit performed 10 times. P.C. board, noise filter P.C. board and power board.
'Outdoor unit Overcurrent is detected after 30 minutes of compressor start-up. • Reconnect compressor connector.
stops and IPM protection
restarts 3 Twice Goes out • Refer to 13-6.E "How to check inverter/compressor".
11
minutes Overcurrent is detected within 30 minutes of compressor start-up • Check the stop valve.
later' is Lock protection
• Check the power module (PAM module).
repeated.
Discharge temperature Discharge temperature exceeds 116: during operation. Compressor can • Check the amount of gas and refrigerant circuit.
12 3 times Goes out protection restart if discharge temperature thermistor reads 100: or less 3 minutes • Refer to 13-6.D "Check of LEV".
later.
Fin temperature
The fin temperature exceeds 89: during operation. •Check refrigerant circuit and refrigerant amount.
protection
13 4 times Goes out •Refer to 13-6.G "Check of outdoor fan motor".
P.C. board temperature The P.C. board temperature exceeds 73:(MXZ-3A54VA, MXZ-4A71VA)/
protection 87:(MXZ-4A80VA, MXZ-5A100VA) during operation.
High-pressure High-pressure is detected with the high-pressure switch (HPS) during • Check the amount of gas and the refrigerant circuit.
protection operation. (MXZ-4A80VA, MXZ-5A100VA) • Check the stop valve.
14 5 times Goes out
The outdoor heat exchanger temperature exceeds 70: during cooling
or indoor gas pipe temperature exceeds 70: during heating.
Converter protection A failure is detected in the operation of the converter during operation.
15 8 times Goes out • Replace the power board.
Bus-bar voltage The bus-bar voltage exceeds 400V or falls to 200V or below during
protection (1) compressor operating.
16 • Replace the power board.
9 times Goes out Bus-bar voltage The bus-bar voltage exceeds 400V(MXZ-3A54VA, MXZ-4A71VA)/
protection (2) 430V(MXZ-4A80VA, MXZ-5A100VA) or falls to 50V or below during
compressor operating.
Failure occurs continuously three times within 30 seconds after the fan
17 13 times Goes out Outdoor fan motor • Refer to 13-6.G "Check of outdoor fan motor".
gets started.
Current sensor A short or open circuit is detected in the current sensor during compressor
18 Lighting 8 times • Replace the power board.
protection operating.
Communication protection Communication error occurs between the outdoor electronic control P.C. • Check the connecting wire between outdoor electronic control
19 Lighting 11 times
between P.C. boards board and power board for more than 10 seconds. P.C. board and power board.
Zero cross detecting circuit • Check the connecting wire among outdoor electronic control
20 Lighting 12 times Zero cross signal cannot be detected while the compressor is operating.
protection P.C. board, noise filter P.C. board and power board.
99
OB377F--4.qxp 07.11.22 11:04 AM Page 100
Indication
No. Symptom Abnormal point / Condition Condition Correspondence
LED1(Red) LED2(Yellow)
Outdoor unit The input current exceeds 15A(MXZ-3A54VA, MXZ-4A71VA)/ These symptoms do not mean any abnormality of the
operates. Primary current protection
17A(MXZ-4A80VA)/ 18A(MXZ-5A100VA). product, but check the following points.
21 Once Lighting
The current of the compressor exceeds 12A(MXZ-3A54VA, MXZ-4A71VA)/ • Check if indoor filters are clogged.
Secondary current protection 10A(MXZ-4A80VA, MXZ-5A100VA). • Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
High-pressure protection The indoor gas pipe temperature exceeds 45: during heating.
Twice Lighting
22
Defrosting in cooling The indoor gas pipe temperature falls 3: or below during cooling.
The frequency of the compressor is kept 80Hz or more and the discharge
Low discharge • Refer to 13-6.D "Check of LEV".
24 4 times Lighting temperature protection temperature is kept under 50:(COOL mode) /40:(HEAT mode) for
• Check refrigerant circuit and refrigerant amount.
more than 40 minutes.
Outdoor unit
26 operates 9 times Lighting Inverter check mode The unit is operated with emergency operation switch. -
normally.
NOTE 1. The location of LED is illustrated at the right figure. Refer to 13-7.2. Outdoor electronic control P.C. board(Parts side)
2. LED is lighted during normal operation.
MXZ-3A54VA, MXZ-4A71VA, MXZ-4A80VA- E1
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. LED2 LED1
(Example) When the flashing frequency is “2”.
Lighting
0.5-second ON 0.5-second ON
MXZ-4A80VA- E2 , MXZ-5A100VA
LED1 LED2
ON
2.5-second OFF 2.5-second OFF Lighting
OFF
100
OB377F--4.qxp 07.11.22 11:04 AM Page 101
Fin temperature Refer to 13-7. “Test point diagram and voltage”,1. “Inverter P.C.board” or 2. “Outdoor
thermistor (RT64) electronic control P.C. board”, the chart of thermistor.
Outdoor fan motor Measure the resistance between lead wires using a tester.
(Part temperature : -10°C ~ 40°C)
Linear expansion valve Measure the resistance using a tester.(Part temperature : -10°C ~ 40°C)
WHT Color of lead wire Normal
RED LEV WHT - RED
ORN RED - ORN
37.4Ω ~ 53.9Ω
YLW - BRN
BRN - BLU
YLW BRN BLU
101
OB377F--4.qxp 07.11.22 11:04 AM Page 102
MXZ-2A30/2A40/2A52
Yes
Replace the inverter P.C. board.
MXZ-3A54/4A71/4A80/5A100
Yes
Replace the outdoor electronic control
P.C. board.
102
OB377F--4.qxp 07.11.22 11:04 AM Page 103
• When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.
Indoor unit does not operate.
• When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
Outdoor unit does not operate.
B How to check mis-wiring and serial signal error (when outdoor unit does not work)
LED indication
for communication status
Communication status is indicated Turn OFF the power supply.
by the LED.
Unit status
Blinking: normal communication Is there rated voltage in No Check the power
Lighting: abnormal communication or the power supply? supply.
not connected
Pattern 1 and 2 is repeatedly displayed Yes
alternately. Each pattern is displayed for Turn ON the power supply.
15 seconds.
NOTE: "Lighting" in the table below does not
indicate abnormal communication. Is there rated voltage between No
outdoor terminal block S1 and Check the wiring.
S2?
MXZ-2A52VA Yes
Outdoor display P.C. board
Press EMERGENCY OPERATION switch once.
LED1 LED2
Is there voltage of 230V AC between pin1 and No 1. Turn OFF the power supply of indoor and outdoor unit, and
pin 2 at connector CN912? disconnect the connector CN933 or CN781.
2. 3 minutes after turning ON the power supply, start
Yes EMERGENCY OPERATION in HEAT mode.
Turn OFF the power supply of indoor and outdoor unit.
Yes Yes
Replace the 4-way valve. Replace the power P.C. board or
the noise filter P.C. board.
104
OB377F--4.qxp 07.11.22 11:04 AM Page 105
D Check of LEV
Turn ON the power supply to the outdoor unit after checking LEV coil is mounted
to the LEV body securely.
No
Replace LEV coil.
105
OB377F--4.qxp 07.11.22 11:04 AM Page 106
Disconnect the terminal of the compressor. 3 minutes after turning ON the power supply, start
EMERGENCY OPERATION.
W 1After the outdoor fan starts running, wait for 1 minute
Measure the voltage between each or more before measuring the voltage.
lead wire leading to the compressor. The output voltage values have the tolerance of i20%.
W 2The output differs depending on the capacity or the
U (BLK) - V (WHT)
V (WHT) - W (RED) No number of indoor units to be operated.
W (RED) - U (BLK)
Output voltage
COOL: 150V(48Hz) HEAT: 170V(64Hz)
Is voltage output? W 1, W 2
Yes
(MXZ-2A) Yes No
Is output balanced?
Yes (MXZ-3A/4A/5A)
Is the input voltage to the outdoor electronic No Replace the inverter P.C. board or
control P.C. board 370V or more? the power board.
Yes
106
OB377F--4.qxp 07.11.22 11:04 AM Page 107
Does the unit operate 10 minutes or more without No Replace the inverter P.C. board,
showing thermistor abnormality? the outdoor electronic control P.C. board,
Yes or the outdoor power board.
Normal
MXZ-2A30/2A40/2A52
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN661 pin1 and pin2
Discharge temperature RT62 Between CN661 pin3 and pin4
Outdoor heat exchanger temperature RT68 Between CN661 pin5 and pin6 Inverter P.C. board
Fin temperature RT64 Between CN662 pin1 and pin2
Ambient temperature RT65 Between CN663 pin1 and pin2
MXZ-3A54/4A71/4A80/5A100
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN661 pin1 and pin2
Discharge temperature RT62 Between CN661 pin3 and pin4
Outdoor heat exchanger temperature RT68 Between CN661 pin7 and pin8
Gas pipe temperature (Unit A) w RT6A Between CN662 pin1 and pin2
Outdoor electronic control P.C. board
Gas pipe temperature (Unit B) w RT6B Between CN662 pin3 and pin4
Gas pipe temperature (Unit C) w RT6C Between CN662 pin5 and pin6
Gas pipe temperature (Unit D) w RT6D Between CN662 pin7 and pin8
Ambient temperature RT65 Between CN663 pin1 and pin2
Fin temperature RT64 Between CN3 pin1 and pin2 Outdoor power board
w Except MXZ-3A54VA- E4 , E5 , MXZ-4A71VA- E4 , E5 , MXZ-4A80VA- E2 and MXZ-5A100VA.
107
OB377F--4.qxp 07.11.22 11:04 AM Page 108
• Fan motor does not operate or stops operating shortly after starting the operation.
Rotate the outdoor fan motor manually and measure the voltage of
CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
(Fixed to either 5V or 0V DC) No Does the voltage between each terminal become 5V DC and 0V DC
repeatedly?
Yes
No
Does the outdoor fan motor rotate smoothly?
Yes
Replace the outdoor DC fan motor. Replace the outdoor electronic control P.C. board.
108
OB377F--4.qxp 07.11.22 11:04 AM Page 109
H Check of HPS
MXZ-4A80VA/5A100VA
Normal
109
OB377F--4.qxp 07.11.22 11:04 AM Page 110
JK,JGO
To
interface
P.C.board
Output to
drive
compressor LEV A
(LDW, (CN791)
LDV,
LDU) LEV B
(CN792)
(
12V
GND
Zero cross
X64
R.V.coil
Primary current
To display P.C.board
thermistor/RT64 (CN662)
Fin temperature
pulse wave
5V DC
GND
5V
Output to drive
outdoor fan motor
(CN932)
Front side of unit
(
To fan motor
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger
Fin temperature thermistor(RT64) temperature thermistor(RT68)
200 100
180 90
Resistance(k")
600
120 60
Resistance(k")
50 500
100
80 40 400
60 30 300
40 20 200
20 10 100
0 0 0
-20 -10 0 10 20 30 40 0 10 20 30 40 50 60 70 80 90 100 110 120
0 10 20 30 40 50 60 70 80
Temperature(:) Temperature(:)
Temperature(:)
110
OB377F--4.qxp 07.11.22 11:04 AM Page 111
Resistance (k')
Resistance (k')
500 80
140
400 120 70
100 60
300
CN661
50
200 60
40
100 40
20 30
5V DC pulse wave
(From power board) GND
Signal reception
CN702
5V DC pulse wave
(To power board)
Signal transmission (+)
CN701
12V
0
-20 -10 0 10 20 30 40
Temperature (;)
(
pulse wave
12V DC
CN795
GND (power board)
CN781
(
LEV E
pulse wave
5V DC
CN931 GND
20-90V AC
CN932
(
(
(
15V
15V
(+) (
(–)
5V
(+)
(–)
(–)
(+)
(
(
(
LED 1 CN604
LED 2 Serial signal Room D
12~24V DC
LED 3
SW1
CN603
Serial signal Room C
12~24V DC
CN801
325V DC
~
370V DC CN602
Input
Serial signal Room B
F801 12~24V DC
FUSE
T3.15AL250V
CN601
230V AC
Input
Serial signal
Room A
12~24V DC
CN662
CN681 MXZ-4A80VA
(
(
(
(
(
(
CN794
CN793
CN792
(
CN791
(
(
(–) pulse wave
Gas pipe A thermistor
Gas pipe B thermistor
Gas pipe C thermistor
Gas pipe D thermistor
(+)
(–)
(+)
(–)
(+)
(
(
(
(
B
LEV Room
12V DC
D
pulse wave
12V DC
C
LEV Room
pulse wave
12V DC
A
LEV Room
12V DC
111
OB377F--4.qxp 07.11.22 11:04 AM Page 112
Resistance (k')
Resistance (k')
80
140
Resistance (k')
500 70
120
400 100 60
80
300 50
60
200 40
40
20 30
100
0 20
0 0 10 20 30 40 50 60 70 80
0 10 20 30 40 50 60 70 80 90 100 110 120 Temperature (;) 10
Temperature (;)
thermistor (RT65)
5V DC pulse wave
(From power board)
pulse wave
5V DC
15V DC
5V DC
GND
GND
GND
(+)
(
(
LED 1
LED 2
LED 3
CN641
Serial signal Room E
F931 (MXZ-5A100VA)
FUSE 12~24V DC
T3.15AL250V
CN631
Serial signal Room D
12~24V DC
SW1 CN621
Serial signal Room C
SW2 12~24V DC
SW871
CN611
Serial signal Room B
12~24V DC
CN801 CN601
325 ~ 370 V DC 230V AC
Input
Input
Serial signal
Room A
12~24V DC
F801
FUSE
T3.15AL250V
{( –
CN796
LEV F
12V DC
( +
pulse wave
CN795
LEV Room E (MXZ-5A100VA)
CN794
LEV Room D
CN793
LEV Room C
CN792
LEV Room B
CN791
CN681 LEV Room A
High pressure switch
112
OB377F--4.qxp 07.11.22 11:04 AM Page 113
CN901
To electronic CN902 CN903
control To power To power
P.C. board board board
{
{
230V AC
Input
CN912
R.V. coil
230V AC
{
230V AC
{ 230V AC
Output Output
MXZ-3A54VA - E5 MXZ-4A71VA - E5
CN901
To electronic
control CN903
P.C. board To power CN902
board To power
{
{
board
{
CN912 230V AC
R.V. coil Output
230V AC
230V AC
Output
F65
FUSE
T6.3AL250V
230V AC
F64 Input
FUSE
T2AL250V
113
OB377F--4.qxp 07.11.22 11:04 AM Page 114
MXZ-4A80VA - E2 MXZ-5A100VA
CN901
To electronic CN912
control CN902 CN903 R.V. coil
P.C. board To power To power 230V AC
board board
{
{
{
230V AC
Output
230V AC
Output
F65
F64 FUSE
FUSE T6.3AL250V
T2AL250V
230V AC
Input
230V AC
Input
230V AC
Output
R.V.coil
(CN912)
230V AC
FUSE(F64) 12V R.V.coil Zero cross
T3.15AL250V
GND X64 Primary current
(
To inverter P.C.board(CN934)
114
OB377F--4.qxp 07.11.22 11:04 AM Page 115
CN5
Primary current detection
(Connect to the noise filter)
325-370V DC CN2
Output Connect to the controller board
(Red) (+)1-5(–): Signal transmission
(+) 1 (To electronic control P.C. board)
5V DC pulse wave
(+)2-5(–): Zero cross signal
(–) 3 3-4 : Not used
(White) (+)6-5(–): 15V
(+)7-5(–): 15V
CN3
Fin temperature thermistor RT64
CN5
Primary current detection
(Connect to the noise filter)
115
OB377F--4.qxp 07.11.22 11:04 AM Page 116
5V GND SW1
LED1 LED2
5V GND
Serial signal
room A
116
OB377F--4.qxp 07.11.22 11:05 AM Page 117
14 DISASSEMBLY INSTRUCTIONS
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
Sleeve
14-1. MXZ-2A30VA
MXZ-2A40VA
MXZ-2A52VA
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet Photo 1
(1) Remove the screw fixing the service panel.
Screws Screw of
(2) Pull down the service panel and remove it.
of the the cabinet Screws of
(3) Disconnect the power supply and indoor/outdoor connecting wire.
top panel the top panel
(4) Remove the screws fixing the top panel. Back Screw
(5) Remove the top panel. panel of the
(6) Remove the screws fixing the cabinet.
(7) Remove the cabinet. service
(8) Remove the screws fixing the back panel. panel
(9) Remove the back panel.
Direction to
remove
Hooks
Screws of Service
the cabinet panel
117
OB377F--4.qxp 07.11.22 11:05 AM Page 118
Screw of the
power P.C. board
4. Removing the discharge temperature thermistor, Photo 4 R.V. coil
defrost thermistor and outdoor heat exchanger
temperature thermistor
(1) Remove the top panel, cabinet and service panel (Refer to 1).
(2) Disconnect the power supply and indoor/outdoor connecting
wire and remove the back panel (Refer to 1).
(3) Remove the inverter assembly (Refer to 2).
(4) Pull out the discharge temperature thermistor from its
holder.
(5) Pull out the defrost thermistor from its holder (Photo 5).
(6) Pull out the outdoor heat exchanger temperature thermistor
from its holder (Photo 5).
118
OB377F--4.qxp 07.11.22 11:05 AM Page 119
(5) Detach the welded part of the suction and the discharge pipe Photo 6 Screws of the outdoor fan motor
connected with compressor.
(6) Remove the nuts of compressor legs.
(7) Remove the compressor.
(8) Detach the welded part of pipes connected with 4-way valve
(Photo 7).
Photo 7
119
OB377F--4.qxp 07.11.22 11:05 AM Page 120
Screws of the
cabinet
120
OB377F--5.qxp 07.11.22 11:20 AM Page 121
Screw of the
back panel
4 way valve
Screws of
LEV coil E the back panel
Expansion valve E
Suction pipe
welded part Screws of
the back panel
Screw of the
Discharge back panel
pipe welded part
Photo 4
Compressor nuts
Screws of
the electrical
parts
Propeller
Sound
proof
felt
Propeller nut
Separator
121
OB377F--5.qxp 07.11.22 11:20 AM Page 122
Welded parts
122
OB377F--5.qxp 07.11.22 11:20 AM Page 123
123
OB377F--5.qxp 07.11.22 11:21 AM Page 124
Screw of the
back panel
4 way valve
Screws of
LEV coil E the back panel
Expansion valve E
Suction pipe
welded part Screws of
the back panel
Screw of the
Discharge back panel
pipe welded part
Photo 4
Compressor nuts
Screws of
the electrical
parts
Sound
Propeller nut proof
Propeller felt
Separator
124
OB377F--5.qxp 07.11.22 11:21 AM Page 125
R.V. coil
Welded parts
Expansion
LEV coils valves
125
OB377F--5.qxp 07.11.22 11:21 AM Page 126
14-4. MXZ-4A80VA - E1
OPERATING PROCEDURE PHOTOS
1. Removing the compressor Photo 1
(1) Remove the screws of the top panel, and remove the top Screws of the top panel
panel.
(2) Remove the screws of the service panel, and remove the
service panel.
(3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge Screws of
shows 0 kg/cm2 (0 MPa). service
panel
(4) Remove the screws of the front panel, and remove the front
panel.
(5) Disconnect the compressor lead wire from terminal of
compressor (U, V, W).
(6) Disconnect the outdoor electronic control P.C. board
connectors:
CN661, CN662 , CN663, CN681, CN791, CN792, CN793,
Screws of the front panel
CN794, CN795, CN931, CN932
Disconnect the noise filter P.C. board connector: Photo 2
CN912
(7) Remove the screws of the electrical parts, and remove the
electrical parts.
(8) Remove the propeller.
(9) Remove the screws of the separator, and remove the
separator.
(10) Remove the sound proof felt. Screws
(11) Detach the welded parts of the compressor suction and of the
electrical
discharge pipes (Photo 3).
parts Electronic
(12) Remove the compressor nuts and remove the compressor.
control
P.C.
board
Photo 3
LEV coil E
Expansion
valve E
Suction
pipe
welded
part
Discharge
pipe
welded
part
Terminal
126
OB377F--5.qxp 07.11.22 11:21 AM Page 127
Propeller
Sound
proof
felt
Separator
Propeller nut Compressor nuts
Welded parts
Expansion
valves
LEV coils
127
OB377F--5.qxp 07.11.22 11:21 AM Page 128
128
OB377F--5.qxp 07.11.22 11:21 AM Page 129
Photo 3
Discharge
pipe
welded
part
129
OB377F--5.qxp 07.11.22 11:21 AM Page 130
Propeller
Propeller nut
Sound
Separator proof felt
Welded parts
LEV coils
Expansion
valves
130
OB377F--5.qxp 07.11.22 11:21 AM Page 131
131
OB377F--5.qxp 07.11.22 11:21 AM Page 132
MXZ-2A40VA - E1 MXZ-2A52VA - E1
18
19
13
1
11
12
3 4 5 6 7 8
2 9
132
OB377F--5.qxp 07.11.22 11:21 AM Page 133
MXZ-2A40VA - E1 MXZ-2A52VA - E1
133
OB377F--5.qxp 07.11.22 11:22 AM Page 134
MXZ-2A40VA - E1 MXZ-2A52VA - E1
15-2. OUTDOOR UNIT ELECTRICAL PARTS
13 12 11
10
1 2 3 4 5
6 7
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
No. Part No. Part Name in Wiring Remarks
Diagram MXZ-2A40VA- E1 MXZ-2A52VA- E1
134
OB377F--5.qxp 07.11.22 11:22 AM Page 135
MXZ-2A40VA - E1 MXZ-2A52VA - E1
Symbol Q'ty/unit
No. Parts No. Parts Name in Wiring Remarks
MXZ-2A40VA- E1 MXZ-2A52VA- E1
Diagram
1 E02 838 704 DRAIN SOCKET 1 1
135
OB377F--5.qxp 07.11.22 11:22 AM Page 136
MXZ-3A54VA - E1 , E2
MXZ-4A71VA - E1 , E2
15-4. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
23 22 21
24
20
19
18
17
16
15
12
2
3 11
4 5 6 7 8 9 10 13 14
136
OB377F--5.qxp 07.11.22 11:22 AM Page 137
MXZ-3A54VA - E1 , E2
MXZ-4A71VA - E1 , E2
15-4. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
No. Parts No. Parts Name in Wiring MXZ-3A54VA- MXZ-4A71VA- Remarks
Diagram E1 E2 E1 E2
137
OB377F--5.qxp 07.11.22 11:22 AM Page 138
MXZ-3A54VA - E1 , E2
MXZ-4A71VA - E1 , E2
15-5. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
12 11 10
1 2 3 4 5 6 7
15-6. ACCESSORY 16 17
138
OB377F--5.qxp 07.11.22 11:22 AM Page 139
MXZ-3A54VA - E1 , E2
MXZ-4A71VA - E1 , E2
15-5. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
No. Parts No. Parts Name in Wiring MXZ-3A54VA- MXZ-4A71VA- Remarks
Diagram E1 E2 E1 E2
15-6. ACCESSORY
Symbol Q'ty/unit
No. Parts No. Parts Name in Wiring MXZ-3A54VA- MXZ-4A71VA- Remarks
Diagram E1 E2 E1 E2
139
OB377F--5.qxp 07.11.22 11:22 AM Page 140
MXZ-4A80VA - E1
15-7. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
25 24 23
22
21
19 18
20
2
14
15
17
16
1
5 13
2 6 12
11
7 8 9 10
140
OB377F--5.qxp 07.11.22 11:22 AM Page 141
MXZ-4A80VA - E1
15-7. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
No. Parts No. Parts Name in Wiring Remarks
MXZ-4A80VA- E1
Diagram
1 M21 TK0 232 FRONT PANEL 1
2 M21 TK0 027 HANDLE ASSEMBLY 2
3 M21 TK5 010 GRILLE 1
4 M21 TK0 245 SERVICE PANEL 1
5 T92 500 801 COMPRESSOR MC 1 TNB220FMCH
6 T2W TK0 505 COMPRESSOR RUBBER SET 3 3RUBBERS SET
R01 E39 401 EXPANSION VALVE 1 D room
7
T2W TK0 654 LEV COIL LEV D 1 D room
R01 E39 401 EXPANSION VALVE 1 C room
8
T2W TK0 653 LEV COIL LEV C 1 C room
R01 E39 401 EXPANSION VALVE 1 B room
9
T2W TK0 652 LEV COIL LEV B 1 B room
R01 E39 401 EXPANSION VALVE 1 A room
10
T2W TK0 651 LEV COIL LEV A 1 A room
11 M21 TK0 290 BASE ASSEMBLY 1
12 M21 42E 644 UNION 1 [12.7,[9.52,[6.35 SET
13 T2W TK0 247 PIPE COVER 1
14 M21 TK5 667 BALL VALVE (LIQUID) 3/8 1 [9.52
15 M21 TK0 667 BALL VALVE (GAS) 5/8 1 [15.88
16 M21 TK0 248 REAR PANEL 1
17 T2W TK0 959 POWER RECEIVER 1
18 M21 G0H 642 4-WAY VALVE 1
19 M21 NT1 646 HIGH PRESSURE SWITCH HPS 1 4.8MPa(48.9kg/cm2)
20 T2W WW8 401 EXPANSION VALVE 1 E
21 T2W TK0 651 LEV COIL LEV E 1
22 M21 TK0 297 TOP PANEL 1
23 T2W E40 523 REAR GUARD 1
24 M21 YH1 630 OUTDOOR HEAT EXCHANGER 1
25 M21 TK0 249 SIDE PANEL 1
26 M21 SJ4 937 CAPILLARY TUBE 2 [4.0O[2.4O400
27 M21 TK0 936 CAPILLARY TUBE 4 [4.0O[2.8O90
28 T2W E59 936 CAPILLARY TUBE 1 [2.5O[0.6O1000
29 T2W YH1 656 OIL SEPARATOR 1
141
OB377F--5.qxp 07.11.22 11:22 AM Page 142
MXZ-4A80VA - E1
15-8. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
12
11
10
1 2 3 4 5 6
15-9. ACCESSORY 16
142
OB377F--5.qxp 07.11.22 11:22 AM Page 143
MXZ-4A80VA - E1
15-8. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
No. Parts No. Parts Name in Wiring Remarks
MXZ-4A80VA- E1
Diagram
1 M21 TK0 501 PROPELLER 1
2 M21 TK0 301 OUTDOOR FAN MOTOR MF 1 PM8H60-
3 T2W YH1 440 POWER BOARD 1 Including heat sink and RT64
4 T2W YH1 451 ELECTRONIC CONTROL P.C. BOARD 1
5 M21 TK0 337 REACTOR L 1 20A 600µH
6 T2W YH1 424 NOISE FILTER P.C. BOARD 1
7 T2W YH1 376 TERMINAL BLOCK TB2~5 4 Indoor unit connecting
8 T2W E64 376 TERMINAL BLOCK TB1 1 Power supply
9 T2W E70 307 GAS PIPE TEMPERATURE THERMISTOR RT6A,B,C,D 1
10 T2W TK0 398 R.V. COIL 21S4 1
DEFROST, DISCHARGE,
11 M21 G0H 308 THERMISTOR SET RT61,62,68 1 OUTDOOR HEAT EXCHANGER
12 M21 90V 309 AMBIENT TEMPERATURE THERMISTOR RT65 1
13 T2W YH1 381 FUSE F801 1 T3.15AL250V
14 T2W YH1 382 FUSE F911 1 T1AL250V
15 T2W E88 313 FUSE&VARISTOR SET F64,NR64 1 T2AL250V
15-9. ACCESSORY
Symbol Q'ty/unit
No. Parts No. Parts Name in Wiring Remarks
MXZ-4A80VA- E1
Diagram
DRAIN SOCKET O1
16 T2W E59 704 DRAIN SOCKET ASSEMBLY 1 DRAIN CAP O2
143
OB377F--5.qxp 07.11.22 11:22 AM Page 144
18
19
13
1
11
12
3 4 5 6 7
2 8 9
144
OB377F--5.qxp 07.11.22 11:22 AM Page 145
Symbol Q'ty/unit
RoHS
No. Part No. Part Name in Wiring MXZ-2A30VA- MXZ-2A40VA- MXZ-2A52VA- Remarks
Diagram E1 E2 E1 E2 E1 E2
145
OB377F--5.qxp 07.11.22 11:22 AM Page 146
1 2 3 4 5
6 7
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS
No. Part No. Part Name in Wiring MXZ-2A30VA- MXZ-2A40VA- MXZ-2A52VA- Remarks
Diagram E1 E2 E1 E2 E1 E2
146
OB377F--5.qxp 07.11.22 11:22 AM Page 147
Symbol Q'ty/unit
RoHS
No. Parts No. Parts Name in Wiring MXZ-2A30VA- MXZ-2A40VA- MXZ-2A52VA- Remarks
Diagram E1 E2 E1 E2 E1 E2
147
OB377F--5.qxp 07.11.22 11:22 AM Page 148
MXZ-3A54VA - E1 , E2 , E3 , E4
MXZ-4A71VA - E1 , E2 , E3 , E4
16-4. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
23 22 21
24
20
19
18
17
16
15
12
2
3 11
4 5 6 7 8 9 10 13 14
148
OB377F--5.qxp 07.11.22 11:22 AM Page 149
MXZ-3A54VA - E1 , E2 , E3 , E4
MXZ-4A71VA - E1 , E2 , E3 , E4
16-4. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS
149
OB377F--5.qxp 07.11.22 11:22 AM Page 150
MXZ-3A54VA - E1 , E2 , E3 , E4
MXZ-4A71VA - E1 , E2 , E3 , E4
16-5. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
12 11 10
1 2 3 4 5 6 7
16-6. ACCESSORY 16 17
150
OB377F--6.qxp 07.11.22 11:25 AM Page 151
MXZ-3A54VA - E1 , E2 , E3 , E4
MXZ-4A71VA - E1 , E2 , E3 , E4
16-5. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS
16-6. ACCESSORY
Symbol Q'ty/unit
RoHS
151
OB377F--6.qxp 07.11.22 2:02 PM Page 152
MXZ-3A54VA - E5
MXZ-4A71VA - E5
16-7. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
23 22 21 20
19
18
1 17
16
13
3
12
4 5 6 7 8 9 10 11 14 15
152
OB377F--6.qxp 07.11.22 11:25 AM Page 153
MXZ-3A54VA - E5
MXZ-4A71VA - E5
16-7. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS
153
OB377F--6.qxp 07.11.22 11:25 AM Page 154
MXZ-3A54VA - E5
MXZ-4A71VA - E5
16-8. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
11 10 9
1 2 3 4 5 6 7
16-9. ACCESSORY 15 16
154
OB377F--6.qxp 07.11.22 11:25 AM Page 155
MXZ-3A54VA - E5
MXZ-4A71VA - E5
16-8. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS
16-9. ACCESSORY
Symbol Q'ty/unit
RoHS
155
OB377F--6.qxp 07.11.22 11:25 AM Page 156
MXZ-4A80VA - E1
16-10. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
25 24 23
22
21
19 18
20
2
14
15
17
16
1
5 13
2 6 12
11
7 8 9 10
156
OB377F--6.qxp 07.11.22 11:25 AM Page 157
MXZ-4A80VA - E1
16-10. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS
157
OB377F--6.qxp 07.11.22 11:26 AM Page 158
MXZ-4A80VA - E1
16-11. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
12
11
10
1 2 3 4 5 6
16
16-12. ACCESSORY
158
OB377F--6.qxp 07.11.22 11:26 AM Page 159
MXZ-4A80VA - E1
16-11. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS
16-12. ACCESSORY
Symbol Q'ty/unit
RoHS
159
OB377F--6.qxp 07.11.22 11:26 AM Page 160
MXZ-4A80VA - E2 MXZ-5A100VA - E1
16-13. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
22 21
23
24 20
19
17
18 16
15
14 2
1
2 5 13
6
7 8 9 10 11 12
160
OB377F--6.qxp 07.11.22 11:26 AM Page 161
MXZ-4A80VA - E2 MXZ-5A100VA - E1
16-13. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS
161
OB377F--6.qxp 07.11.22 11:26 AM Page 162
MXZ-4A80VA - E2 MXZ-5A100VA - E1
16-14. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
11
10
1 2 3 4 5 6
16-15. ACCESSORY 15
162
OB377F--6.qxp 07.11.22 11:26 AM Page 163
MXZ-4A80VA - E2 MXZ-5A100VA - E1
16-14. OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part numbers that are circled are not shown in the illustration.
Symbol Q'ty/unit
RoHS
16-15. ACCESSORY
Symbol Q'ty/unit
RoHS
163
OB377F--6.qxp 07.11.22 11:26 AM Page 164
17 OPTIONAL PARTS
13.7
5-
Z Z-Z
52.
15.7
MXZ-2A30
MXZ-2A40
48
79
10o48(=480)
MXZ-4A80
450.8
MAC-855SG 51H-855
537.2
327
MXZ-5A100
103.1
42.6
Z 71.6
MAC-889SG
610.4 150
534 5 - [6 109.4
29.2
760.8
832
29.2
6.4
386 5 - [6
Punched hole
534
MAC-855SG