SW version 2.6.0
1 General information 2
2 Changes in the version 2.6.0 3
3 Changes in the version 2.5.0 4
4 Changes in the version 2.4.0 5
5 Changes in the version 2.3.1 10
6 Changes in the version 2.3.0 11
7 Related information 16
8 Notes 18
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
D+ Treshold
Setpoint group Engine Params Range [units] 0 .. 100 [%]
Default value 80 % Step 1%
Position Under D+ Function Related applications AMF, MRS
Description
This setpoint adjusts threshold level for D+ function.
D+ Delay
Setpoint group Engine Params Range [units] 0 .. 255 [s]
Default value 1s Step 1s
Position Under D+ Treshold Related applications AMF, MRS
Description
This setpoint adjusts delay for D+ function. This delay is used for:
alarm Wrn Charging Alternator Fail
for engine running condition - disengagement of binary output STARTER
ChokeIncrement
Setpoint group Basic Settings Range [units] 0,00 .. 20,00 [s/°C]
Default value 0,00 s/°C Step 0,01 s/°C
Position Related applications AMF, MRS
Description
This setpoint adjust the maximal time of activation of binary output Choke which depends on engine
temperature. Setpoint adjust curve which will be used for counting of actual Choke Time.
Choke Voltage
Setpoint group Basic Settings Range [units] 0 .. 600 [V]
Default value 0V Step 1V
Position Related applications AMF, MRS
Description
This setpoint adjust threshold level for deactivation of logical binary output CHOKE. When generator voltage
is bigger than this level, then logical binary output CHOKE is deactivated.
Choke Lead
Setpoint group Basic Settings Range [units] 0 .. Prestart Time [s]
Default value 0s Step 1s
Position Related applications AMF, MRS
Description
This setpoint adjust the lead of logical binary output CHOKE. CHOKE is activated before logical binary output
STARTER.
Choke Inhibit
Description
Logical binary input CHOKE INHIBIT prevent Choke functionality when CHOKE is activated. If CHOKE INHIBIT is
activated when CHOKE LBO is active, CHOKE LBO is deactivated immediately and vice versa if LBI CHOKE
INHIBIT is deactivated and LBO CHOKE should be active then is activated.
6.2 Repairs
Missing symbols of Ukrainian language
Symbols added in Cyrilic code page
Missing values of kWh and kVArh when Chinesse language selected
Added values to:
AMF25 - Genset kWh, Genset kVARrh, Mains kWh, Mains kVArh
AMF8, 9, 20 - Genset kWh, Genset kVARrh - added new screen
MRS15, 16 - Genset kWh, Genset kVARrh
MRS3, 4, 10, 11 - Genset kWh, Genset kVARrh - added new screen
When LBO1 is configured as Not Used, it is permanently acivated
Repaired, when LBO1 isconfigured as Not Used, it is deactivated
Wrong Fls Oil Pressure evaluation
Engine is able to start even Oil pressure sensor is disconnected
When Oil Pressure analog input Direction was set to UnderLimit+Fls, sensor was disconnected and
thenFault Reset was pressed. It was possible to start engine manualy. Gen-set Red and Green LED
Archives (*.ail)
For: IL-NT AMF(8,9,20,25), MRS(3,4,10,11,15,16,19)
IL-NT-AMF(8,9,20,25), MRS(3,4,10,11,15,16,19)-2.6.0.ail