Technical Catalogue

R134a
HFO
1234ze Water Cooled Centrifugal Chillers
Nominal cooling capacity: 270-3900kW | 200-2340kW
“Some things can’t be
mass-produced.”

2 www.euroklimat.it
ZEUS
Index
ZEUS 4

Capacity range – R134a & R513a Models 6

Capacity range – Hfo1234ze Models 12

Features & Benefits 15

Operating costs and technical solutions 16

Water temperature control and required water content 16

Main component 17

Unit’s frame 17

Compressors 18

Evaporator 19

Condenser 20

Economizer 21

Refrigerant equipment & instruments 22

Controls 24

Electrical equipment 26

Main options 27

Machine nomenclature 30

Machine selection & part load performances 31

Technical data - R134a 32

Technical data - Hfo1234ze 41

Operating limits 46

Drawings 47

Quotes – R134a 48

Quotes – Hfo1234ze 50

Standards 66

www.euroklimat.it 3
ZEUS
ZEUS is a wide range of oil-free water cooled chillers equipped with centrifugal high-speed compressors with magnetic bearings.
These chillers grant astonishing energy performances and extremely low maintenance costs.

Thanks to it, ZEUS chillers are an optimal solution for a wide range of applications, such as:
•  Comfort cooling: retail buildings, hotels, office buildings, hospitals, theatres, district cooling
•  Process cooling: industrial facilities
•  IT cooling: data centers

ZEUS chillers can be provided in heat pump version (reversibility on hydraulic circuit) for hot water production up to 52°C.
In all cases, end users will easily appreciate the benefits of these machines in terms of operating costs and respect of the environment.

COMPRESSORS

1÷6 high speed centrifugal type,


oil free (magnetic bearings).

CONTROLS

Two PLCs, one for generic


chiller function, and a dedicated
controller for compressor’s
management. Integrated driver
for electronic expansion valves.

CONDENSER

Shell & tubes, 2 or 4 passes.


Marine version available on
request.
Max condenser water
temperature: depending from
models (see Technical Data).

4 www.euroklimat.it
ZEUS
ZEUS units are available with two refrigerants:
•  R134a, for a nominal capacity 270 ÷ 3900kW
•  HFO1234ze, 200-2340kW
R134a machines are available in two series:
•  BUSINESS version, optimized for comfort cooling applications
•  PREMIUM version, designed for process & IT cooling applications
Note:
R134a can be replaced with lower GWP refrigerant R513A, with negligible differences in terms of capacity and efficiency.

No. OF CIRCUITS

1÷2 (depending on models).

Note: Double circuit version


is always obtained by dividing
evaporator and condenser shells in
two portions of equal volumes. For
this reason, double circuit is version
is available only for units having
even number of compressors.

EVAPORATOR

Flooded, 2 or 4 passes, with


patented “spray” system for
low refrigerant charge
Water leaving temperature:
4÷20°C.

ECONOMIZERS

High efficiency brazed plate


heat exchangers (some models).

www.euroklimat.it 5
Capacity range
Capacity range - R134a & R513A - models 270÷1640
For each model: min capacity at min evaporator leaving temperature, and max capacity at max evaporator leaving temperature. For all
models: condenser outlet water temperature assumed as 35°C.

Indicative capacity range [kW] for evaporator leaving temperature range 4÷10°C *

Models suitable for high condensing temperature

* For a precise estimation in accordance to design conditions, refer to Zeus Selection Software.

6 www.euroklimat.it
Capacity range
Capacity range - R134a & R513A - models 1770÷3900
For each model: min capacity at min evaporator leaving temperature, and max capacity at max evaporator leaving temperature. For all
models: condenser outlet water temperature assumed as 35°C.

Indicative capacity range [kW] for evaporator leaving temperature range 4÷10°C *

Models suitable for high condensing temperature

* For a precise estimation in accordance to design conditions, refer to Zeus Selection Software.

www.euroklimat.it 7
Capacity range
Capacity range - R134a & R513A - models 270÷1640
For each model: min capacity at min evaporator leaving temperature, and max capacity at max evaporator leaving temperature. For all
models: condenser outlet water temperature assumed as 35°C.

Indicative capacity range [kW] for evaporator leaving temperature range 10÷15°C *

Models suitable for high condensing temperature

* For a precise estimation in accordance to design conditions, refer to Zeus Selection Software.

8 www.euroklimat.it
Capacity range
Capacity range - R134a & R513A - models 1770÷3900
For each model: min capacity at min evaporator leaving temperature, and max capacity at max evaporator leaving temperature. For all
models: condenser outlet water temperature assumed as 35°C.

Indicative capacity range [kW] for evaporator leaving temperature range 10÷15°C *

Models suitable for high condensing temperature

* For a precise estimation in accordance to design conditions, refer to Zeus Selection Software.

www.euroklimat.it 9
Capacity range
Capacity range - R134a & R513A - models 270÷1640
For each model: min capacity at min evaporator leaving temperature, and max capacity at max evaporator leaving temperature. For all
models: condenser outlet water temperature assumed as 35°C.

Indicative capacity range [kW] for evaporator leaving temperature range 15÷20°C *

Models suitable for high condensing temperature

* For a precise estimation in accordance to design conditions, refer to Zeus Selection Software.

10 www.euroklimat.it
Capacity range
Capacity range - R134a & R513A - models 1770÷3900
For each model: min capacity at min evaporator leaving temperature, and max capacity at max evaporator leaving temperature. For all
models: condenser outlet water temperature assumed as 35°C.

Indicative capacity range [kW] for evaporator leaving temperature range 15÷20°C *

Models suitable for high condensing temperature

* For a precise estimation in accordance to design conditions, refer to Zeus Selection Software.

www.euroklimat.it 11
Capacity range
Capacity range - HFO1234ze - all models
For each model: min capacity at min evaporator leaving temperature, and max capacity at max evaporator leaving temperature. For all
models: condenser outlet water temperature assumed as 35°C.

Indicative capacity range [kW] for evaporator leaving temperature range 4÷10°C *

Models suitable for high condensing temperature

* For a precise estimation in accordance to design conditions, refer to Zeus Selection Software.

12 www.euroklimat.it
Capacity range
Capacity range - HFO1234ze - all models
For each model: min capacity at min evaporator leaving temperature, and max capacity at max evaporator leaving temperature. For all
models: condenser outlet water temperature assumed as 35°C.

Indicative capacity range [kW] for evaporator leaving temperature range 10÷15°C *

Models suitable for high condensing temperature

* For a precise estimation in accordance to design conditions, refer to Zeus Selection Software.

www.euroklimat.it 13
Capacity range
Capacity range - HFO1234ze - all models
For each model: min capacity at min evaporator leaving temperature, and max capacity at max evaporator leaving temperature. For all
models: condenser outlet water temperature assumed as 35°C.

Indicative capacity range [kW] for evaporator leaving temperature range 15÷20°C *

Models suitable for high condensing temperature

* For a precise estimation in accordance to design conditions, refer to Zeus Selection Software.

14 www.euroklimat.it
Features & Benefits
Energy Efficiency Levels

Fig. 1 Typical COP trend

Energy efficiencies are extremely high, especially at partial load, as shown in Fig. 1.
To evaluate energy efficiency levels at various operating conditions, refer to ZEUS Selection Software: performance tables generated by
this tool accurately represent machine’s behavior at constant plant side temperature and variable source temperature.

Part Load 150RT turbo (1 compressor) 300RT turbo (two compressors) typical screw chiller (two compressors)
100% 5,58 5,63 5,45
75% 7,97 8,05 6,78
50% 11,77 11,88 5,80
25% 11,73 13,56 5,60

ESEER (EN14511-3:2013): 8.10÷9.70


IPLV (AHRI 550-590:2011): 9.65÷10.50
(see General Data for the exact values of each chiller model)

Overall energy efficiency can be emphasized by the adoption of variable


flow (VPF): in addition to it, chiller controller is able to manage water flow
autonomously, in order to optimize the potential savings connected to VPF
systems and to simplify plant management.

www.euroklimat.it 15
Operating costs
and technical solutions
ZEUS units are designed to offer great energy performances with lower maintenance costs.
To achieve this target, all ZEUS units are equipped with DANFOSS TURBOCOR compressors, oil-free centrifugal twin stage compressors
with magnetic bearings, and high performances shell & tubes exchangers.
Frictionless high speed centrifugal compressors allow significant reduction in maintenance operations due to the total elimination of
oil: with respect to standard chiller with screw compressors, maintenance costs are expected to be reduced by 80%.
The combination of extremely low maintenance costs and outstanding levels of energy performances strongly reduces operating costs
of ZEUS units: since operating costs represent the greatest portion of machine’s life cycle costs, ZEUS units usually grant interesting
pay-back periods.

HFO
1234ze

ZEUS machines are not only a good investment for the business, but also a great contribution
to the respect of the environment: lowest indirect emissions associated to great COP levels are R513A
associated to lowest direct emissions obtained by the usage of poor refrigerant content and by the
adoption of refrigerants with low GWP (in particular, HFO1234ze has a GWP100<1).
HFC
134a

As a general rule, PREMIUM chillers are optimized for process cooling and IT cooling: heat exchangers are sized to cover all operating
range of the machine with high performance levels. Higher initial costs can be usually recovered by energy savings in a short period.
On the other hand, BUSINESS chillers are optimized for comfort cooling, and lower water temperature in general. These models usually
offer the best solution in terms of Life Cycle Cost when operating hours per annum is below 2000.
Anyway, the best choice for any specific application can be easily adopted starting from ZEUS Selection Software: this tool automatically
selects the best heat exchanger configuration in terms of no. of passes in order to grant the max of benefits also in terms of water
pumping costs.
Performance tables cover all possible operating conditions, thus EER/COP values here reported can be used to estimate the overall
energy costs for any building load profile.

EUROKLIMAT can provide customized machines: contact the factory for feasibility and quotation.

Water temperature control and required water content


Thanks to infinite modulation associated to full inverter equipment, ZEUS machines grant a very precise control temperature. Please
refer to the following table to determine the minimum water content of the hydronic circuit in relationship to design capacity:

Minimum water content [lt/kW]


Application
Minimum water content [lt/kW] Unit with multiple compressors
Comfort cooling 3.2÷3.5 2.2÷2.5
Process cooling 5.6÷6.1 3.9÷4.4
Variable Primary Flow (VPF) 6.4÷7.0 4.4÷5.0

In VPF systems, water flow can be reduced with a maximum ratio of 15% each minute.

16 www.euroklimat.it
Main component
Unit’s frame
Components
ZEUS chiller frame is consisting into five main
4a elements:

1 1. Self-supporting evaporator (square plates with


3 lifting holes)
4a 2. Self-supporting condenser (square plates with
lifting holes)
3. Coupling frames (bolded to heat exchangers
square plates)
4. Welded shelves, for
a. Compressors
b. Electrical panels
c. Filters (not visible)
5 d. BPHE economizers (not visible)
5. Mounting brackets for isolators

For units having three compressors or more, an


4b additional beam joins the two coupling frames,
and it is used as main support for eventual BPHE
4b 5 economizers.

3 Evaporator is in upper position. Its placing optimizes


2
the suction line and general layout of the piping,
5 with a positive impact on refrigerant pressure drops
and accessibility of all components.
Handling and lifting is possible by using dedicated lifting holes located on heat exchangers square plates; in some cases, wood base is
available and useful to handle the unit by using a forklift.
Always refer to Instruction & Operation Manual and general documentation of the unit for detailed handling & lifting procedures.

Machine’s foundation
ZEUS chiller can be supported by continuous elastomeric pads in correspondence to the frame base (these pads are NOT supplied
with the unit).
In some cases, dependent from building structure, it is recommended to use rubber-metal dampers to reduce the transmission into
foundations of some vibration frequencies generated by frequency converter(s).
Refer to Instruction & Operation Manual for more details and to general documentation of machine for operating weights and
drawings.

www.euroklimat.it 17
Compressors

Maximum pressure ratio depending on model. Inter-stage port available for economizer.
Centrifugal (twin stage),
Mounted on anti-vibration supports made of Neoprene Duro Meter 50. End bell insulated
high-speed direct drive
by polystyrene cap. Low noise component (Lw(A)<82dB(A)at 250kW of capacity).
compressor
Soundproofing box available as option.

Magnetic type (two radials, one axial) for a total oil-free operation. Automatically driven by
Bearings
PWM driver acting at a frequency of 20kHz.

Motor starter Electronic Softstart (negligible inrush current, <5A per compressor).

Infinite variation, typically 25-100% per compressor (without the practice of hot-gas
bypass). Multiple compressor configuration allows wider range of modulation, down to 5%
of chiller’s nominal capacity.
Capacity modulation
Methods of capacity modulation (in sequence): continuous variation of compressor speed,
Inlet Guide Vanes opening, progressive activation/deactivation of compressors (for chillers
with multiple compressors), Hot-gas bypass (on the last compressor running).

Synchronous permanent magnets motor, driven by IGBT inverter. Automatic switch into
Motor and frequency drive generator mode to stop the shaft in a safely manner in case of power outage.
Motor and power electronics cooled by refrigerant.

Compressor CPU transfers all information about compressor’s operating condition to a


dedicated controller, totally focused on compressors management. This concept allows
Controls
the widest exploitation of compressor’s operating range, and the achievement of the best
performances in terms of energy savings and reliability.

Compressor is virtually maintenance-free, thanks to its frictionless, oil-free operation.


Compressor is a hot-spare component: suction shut-off butterfly valve and check valve
Maintenance allows to replace compressors even with unit in function.
Compressor weight is depending from model (always less than 150kg).
As option, standard discharge check valve can be replaced with a stop & check valve.

18 www.euroklimat.it
Evaporator

Flooded evaporator is protected


from the risk of freezing in
multiple ways:
•  water temperature
•  refrigerant pressure
•  DP switch
as standard, and
•  mechanical flow switch
•  electric heaters
as option.

Flooded, with patented “spray” system conceived to distribute small size drops of liquid
refrigerant over the tubes, thus allowing a significant reduction of the refrigerant charge.
A further step in the respect of the environment, in addition to the usage of low GWP
Type and performances refrigerants and the great efficiency levels.
A design approach of 1K (or even less for some models) is used to ensure the best overall
efficiency of the chiller. Approach trend at partial loads is similar to the one of conventional
flooded evaporator.

Two as standard. Four passes are automatically selected by ZEUS Selection Software in case
No. of passes of higher design water delta-temperature or in case of lower nominal water flow (close to
laminar flow or not compatible with the required level of water flow modulation).

Shell (refrigerant side) Carbon steel

Water tubes (water side)


High efficiency copper tubes, size ¾” or 1” depending on models. Two types of tubes
(GEWA B6 or GEWA B4-HSL) are used for different models depending on nominal water
flow, design efficiency and water velocity at full load.
Water filter are mandatory (NOT supplied with the unit and NOT included into
accessories): refer to Instruction and Operation Manual for details.

Water box available as option

Design pressure (water side): 10 barg as standard (16 or 25 available upon request)

depending on model and application (see Technical Data Sheet provided by ZEUS Selection
Min / Max water flow
Software)

Water flow rate of change max 15% each minute

Insulation Embossed PEN/PEAL 19mm (λ ≤ 0.038W/m/K)

www.euroklimat.it 19
Condenser

Shell & tubes, with integrated subcooler. High efficiency, with a design approach of around
1.5K (or even less for some models).
Type and performances
Marine version is available upon request, based on: CuNi 9010 tubes, tube sheets and water
box coated with BELZONA® 1331, sacrificial anodes.
Two as standard. Four passes are automatically selected by ZEUS Selection Software in
No. of passes
case of higher design water delta-temperature.

Shell (refrigerant side) Carbon steel

Water tubes (water side)


High efficiency copper tubes, size ¾” or 1” depending on models.
Standard tubes type: C5
Other tube types available on request for specific applications (contact the factory)

Water box available as option

Design pressure (water side): 10 bar as standard (16 or 25 available upon request)

depending on model and application (see Technical Data Sheet provided by ZEUS Selection
Min / Max water flow
Software)
Insulation (heat pump version
Embossed PEN/PEAL 19mm (λ ≤ 0.038W/m/K)
only)

20 www.euroklimat.it
Economizer

Economizers are available for various models (see general data). They are of closed circuit type, consisting in high efficiency BPHE with
low pressure drop.

BPHE economizer increases the cooling capacity by reducing the liquid temperature: quality of refrigerant at EXV inlet is modified and
the delta-enthalpy available for evaporating process is raised-up.

Even if the advantages granted from economizers in terms of COP are higher when the pressure ratio increases, the usage of BPHE
are justified also for water cooled machines: in facts, an overall improvement of 5÷8% of EER is obtainable in standard operating
conditions.

With the scope to maximize the potential advantages of BPHE economizer, refrigerant flow is controlled through an electronic
expansion valve, with a superheat setpoint compensated with the actual pressure ratio.

In ZEUS chillers, compressors and economizers are coupled in a 1-to-1 configuration, for an optimized combination of compressor
and BPHE sized, to get always the maximum of performance.

www.euroklimat.it 21
Refrigerant equipment
& instruments
Detail of refrigerant and water circuits
All units have a single refrigerant circuit as standard. For units with even number of compressors, double circuit version is available as
option.
Each refrigerant circuit includes:

•  Electronic expansion valve(s)


•  Capacitive sensor mounted on condenser side for liquid level control
•  Drier filter(s)
•  Pressure switch with manual reset on HP side
•  Pressure gauges on LP / HP sides
•  4-20mA pressure transducer
•  Refrigerant liquid temperature at condenser outlet (for measurement of subcooling)
•  Single or double relief valve on LP/HP side with protected seal shut-off valve (optional changeover switch)
Water circuit have:

•  DP pressure switch on evaporator


•  Evaporator inlet & outlet temperature probes (NTC 10kOhm at 25°C)
•  Condenser inlet & outlet temperature probes (NTC 10kOhm at 25°C)

22 www.euroklimat.it
Refrigerant equipment
& instruments
Sample of P&ID for chiller with single circuit and two compressor

01 Flooded evaporator 21 Two passes shell & tubes condenser 43 Compressor cooling liquid drier filter
02 Evaporator vent valve 22 Condenser vent valve 44 Compr. cooling sight glass
03 Evaporator drain valve 23 Cond. drain valve 45 Compr. cooling liquid service valve
04 Chilled water inlet temp. probe 24 Cond. inlet temp. probe 54 Liquid line service valve - upstream
05 Chilled water outlet temp. probe 25 Cond. outlet temp. probe 55 Drier filter
06 Evaporator diff. pressure switch 27 Pressure relief valve - HP side 56 Sight glass
07 Pressure relief valve - LP side 28 High pressure transducer 57 Refrigerant liquid temp. probe
08 Low pressure transducer 29 High pressure gauge 60 Economizer BPHE
09 Low pressure gauge 30 High pressure switch 61 EXV - economizer
10 Centrifugal compressor 31 Cond. liquid level canister 62 Pressure transducer - economizer
11 Suction service valve 32 Cond. liquid level transducer 63 Temperature probe - economizer
12 Discharge stop & check valve 33 Cond. liquid level service valves 64 Main EXV
13 Compr. hot gas bypass 41 Compr. cooling liquid collector 65 Liquid line service valve
16 Compressor econ. service valve 42 Compr. cooling liquid service valve 70 Refrigerant charge connection
71 Pressure test point

www.euroklimat.it 23
Controls
Control system layout

Hardware Based on c.pCO CAREL controllers. System is composed by:


• Main controller: for generic chiller function and control of ancillary devices (pumps, valves,
dry/hybrid coolers, cooling towers)
• Additional controller: dedicated to compressors interface and management
• Integrated driver(s) for electronic expansion valves: perform PID algorithms for liquid flow
control, switching from transient to steady operation phases according to main controller
signals

Software Proprietary software, conceived to integrate generic chiller functions with specific features of
centrifugal oil-free compressors

Cycle time <500ms

UPS standard (power supply of controllers and auxiliaries)

Human Machine Interface touch screen display 7” (additional remote display available as option)

Datalogger integrated

Password levels 3

24 www.euroklimat.it
Controls
Opto-isolated boards for BMS as option, according to user’s selected protocol.
interface Available standards: Modbus RTU RS485, BACnet MS/TP, BACnet TCP/IP, LonWorks
Remote control (via web): optional, see Main Option

Fast restart function available as standard (<3’ to recover the full cooling capacity)

Software main functions • Temperature control selectable on evaporator inlet or outlet


• Same options for condenser temperature in case of heat pump version
• Self-adjusting condensing control loop
• Compressor hot-gas bypass for temperature control at extremely low loads
• Water set point compensation based on external analog signal or external air temperature
• Real-time energy performance measurement (option)
• Refrigerant flow control based on liquid level measured on condenser with a backup
control based on refrigerant subcooling. Set points compensated on the basis of actual
capacity.
• Advanced management of transient situations (unit’s start, staging of subsequent com-
pressor, compressor shutdown at high pressure ratio)
• Self-adjusting procedures for start of machine under harsh conditions
• Self-adjusting economizer control based on actual pressure ratio and no. of compressors
in operation
• High & Low pressure prevent automatic procedures
• Redundant evaporator anti-freeze protection
• Demand limit based on max no. of compressors or actual reading of electrical power input
(option)
• Refrigerant leakage detection (option)
• Advanced menu for periodic and predictive maintenance
• Multi-machine control (for multiple units in parallel)
• Management of external devices, such as:
o Fixed speed or VFD pumps (with various options for management of variable water
flow)
• Two pumps on evaporator side
• Two pumps on condenser side
o Dedicated signals for condensing control devices, such as fixed speed or VFD pumps,
motorized valves, dry/hybrid coolers, cooling towers.

Standard user’s hard-wired INPUT


interface • Remote START/STOP
• Remote serious alarm (for unit STOP)
• Chilled water interlock signal (for external flow switch)
• Condenser flow switch interlock (standard only for heat pump version, optional for chillers)
• Set point change
• Winter/summer selector (heat pump only)
• Remote 0-10V signal for set point compensation
• Water pumps thermal protection (on request)
OUTPUT
• Major fault (volt-free contact & lamp)
• Generic fault (volt free contact & lamp)
• Machine’s run indicator (lamp)
• Power supply alarm (lamp)
• Single or double condensing control signal (0-10V)
• Water pumps start/stop signals (on request)
• VPF pumps speed signal (0-10V, on request)

www.euroklimat.it 25
Electrical equipment
Electrical cabinet is divided in three sections:
1  Power section
2  Control section
3  Line reactor panels

A fourth section is provided in case of Active Harmonic Filters.


Electrical cabinets degree of protection: IP54.
Max ambient temperature: 45°C (for higher ambient temperature, contact the factory).
Control section is completely separated from power section.
Main switch: manual switch disconnector (max cable section indicated in technical data sheet).

Compressor devices:
• protecting device: switch disconnector with fast-acting fuses NH for busbar assembly
• contactor: provided (AC-1 rating)
• line reactor: 5% (insulation class: F – 155°C, EN IEC 60076-6)
• EMI filter: class B (DIN EN 61000-6-3)

Standard power supply: 400-3-50 (other voltage levels available – see Machine nomenclature and Main Options).
Auxiliary voltage levels: 230Vac (internal trafo) – 24Vdc (with backup batteries).
Max operating current: model dependent (see Technical Data).
Starting current: negligible (less than 5A per compressor), thanks to electronic softstart installed on each compressor.
For electric accessories, see Main Options.

SAMPLE OF ELECTRICAL COMPRESSOR DEVICES

Switch disconnector with fast-acting fuses

Line contactor (AC-1 rating)

EMI filter class B

Ferrite

Line reactor 5%

Shielded power cable

Compressor motor

26 www.euroklimat.it
Main options
Mechanical options
Soundproofing compressor box
ZEUS chillers have low noise levels in their standard configuration. For a further reduction of noise impact, especially at high frequencies
(indicatively above 2.5kHz), soundproofing compressor boxes are available. Refer to technical datasheet of each single unit to estimate
the benefit of this option.

Anti-vibration mounts
ZEUS chiller can be supported by continuous elastomeric pads in correspondence to the frame base (NOT part of
chiller’s supply).

Rubber metal dampers


In some cases, dependent from building structure, it is recommended to use neoprene isolators to reduce the
transmission into foundations of some vibration frequencies generated by frequency converter(s).

Anti-vibration seismic mounts


Alternatively, mounts with anti-seismic structure are available as option.

Note
•  Refer to general documentation and machine’s drawing for details about quantity, models, positioning and static deflection of any
type of isolators.
•  Both types of isolators are mounted on lateral mounting brackets, to minimize the impact on the chiller’s height.

Heat exchanger options


Electric heaters (evaporator only)
Electric heaters can be selected as additional direct protection against the risk of freezing of evaporator, in addition to the compressor
shutdown and to the activation of water pump(s), on the basis of refrigerant pressure and/or water temperature.
Design pressure
Standard water side design pressure is 10barg. Other design pressure levels are available upon request.
Contact the factory for quotation.

Water box
Water box can be selected for both heat exchangers as well as individually.
The installation of water box impacts on the length and on the operating weight of the machine, as indicated in the general
documentation of each unit.

Water connections
Standard water connections depend on the shell diameter, as indicated in the Technical Data machine by machine. Standard connections
are female thread (for shell diameter up to 559mm) and VICTAULIC (for diameter above 559mm).
Flanged connections (with PN depending on the required design vessel pressure) can be selected as option.
VICTAULIC can be required as well for smaller diameter.
Standard orientation of water connection is on the right side of the machine (front side being defined by the positioning of electrical
panel) for both heat exchangers. Different orientation is possible upon request: contact the factory for this purpose.

Mechanical flow switch


As standard, unit is provided with a differential pressure switch on evaporator for chillers.
Mechanical flow switch is part of standard equipment only for unit in heat pump version.

Condenser marine version


Marine version of condenser is based on:
•  Water tubes CuNi 9010
•  Tube sheets and water box coated with BELZONA 1331 or equivalent coating
•  Sacrificial anode
Contact the factory for other configurations, to be evaluated case by case as special versions

www.euroklimat.it 27
Main options
Refrigerant circuit
Compressor discharge shut-off valve
Compressor is normally equipped with low pressure drop check valve. Combined stop & check valve is available as option.

Leakage detection system


Two versions of leak detectors are available for units with R134a or R513A:
1. Semiconductor sensor with two alarm relays
2. Infrared version with analog signal (two alarms threshold configurable by software)
Infrared type is standard for unit with HFO1234ze.

Relief valve with changeover


Standard equipment entails one or two relief valves, each one with shut-off valve with security seal. Double valves with changeover
switch can be selected as option for both exchangers.

Pump on compressor cooling circuit (Low Lift Kit)


Pump on compressor cooling circuit is mandatory in case of continuous operation at low lift (pressure ratio below 1.5), favored by
the availability of low condenser inlet temperatures (example: ground water). Water pump management can be easily configured by
software in combination to an automatic adjustment of condensing pressure control signal curve.

Electrical options
Power supply
Some voltage levels are available, as shown in the tables below. Refer to Technical Data to determine the compressor model for each
machine’s size.
Voltage level [V-ph-Hz] Tag Compressor models Available voltage levels
380-3-50 E TT300-TT400-TG230-TG390 E D H J G F (all voltage levels of previous table)
380-3-60 D TT350-TT700-TG310-TG520 E D H J G (all but 575-3-60)
400-3-50 H
400-3-60 J
460-3-60 G
575-3-60 F
Stainless steel electrical panel
Made of AISI 316L.

SPD Surge Protection Device


Optional SPD are of Class II, DIN-rail mounted, with zinc oxide varistors.
In/Imax (8/20 μs): 15/40kA; Up≤1.5kV
For Class I version, contact the factory for quotation.

Ground Fault Relay


Earth fault definite time residual current relay with single operation threshold. DIN-rail mounted.

3-Phase monitoring relay


Monitoring relay with functions: under-voltage, over-voltage, phase loss, phase sequence. Din-rail mounted. Single SPDT.

Power Network Analyzer


DIN-rail mounted version of optional Power Network Analyzer is connected in Modbus to main controller. Controller provides the
following information (on display and to the supervision):
• Power Factor
• 3-phase current
• Voltage
• Active Power
• THDi
Power Network Analyzer is part of the real-time energy efficiency measurement kit and it is required to implement demand limit
function based on direct reading of electric power input.

28 www.euroklimat.it
Main options
Electrical options
AHF Active Harmonic Filters
Active Harmonic Filters are of wall-mounted type, installed in dedicated cabinets without any impact on the overall dimensions of the
machine. Provided with touch screen display.
AHF limit Total Harmonic Distortion THDi to 5%, for a full compliance with IEEE 519.
With AHF, Power Factor is above 0.98 in all operating conditions.

Automatic Transfer Switch (dual power supply)


ATS is available only in free standing version (external cabinet). UPS for electronic (standard equipment) perfectly matches with ATS,
thus providing a perfect solution for critical applications.

Controls
Opto-isolated BMS card
Available protocols: Modbus RTU RS485, BACnet MS/TP, BACnet TCP/IP, LonWorks

Remote display
Touch screen display 7”, duplicates the one mounted on the electrical panel of the machine.

Remote control (via web)


Based on CAREL Thera solution, provides a full remote control of the unit via web. All anomalies and alarms are recorded; trends of
selected variables and occurrences of specific situations can be easily configured in customized webpages for a comprehensive remote
control of the unit.

Analogue flow meter


Pressure differential transmitter 4-20mA with square root extraction. To be mounted across a calibrated orifice (not part of the supply).
Analogue flow meter is part of the real-time energy efficiency measurement.
Flow meter allows to:
• measure unit capacity in real time
• protect heat exchanger against excessive water flow

Real-time energy efficiency measurement kit


This kit includes:
• Power Network Analyzer, for a direct measure of electric power input
• Analogue flow meter, for a real-time estimation of machine’s capacity
Machine controller, on the basis of the reading of the two instruments above, calculates the energy efficiency and provides a real-time
calculation of unit’s EER (Energy Efficiency Ratio) or COP (Coefficient Of Performances).
A monthly report is also calculated, in order to allow the easiest control of performances and the correct evaluation of pay-back period
of such machines.

Set point compensation


Available in two versions:
1. based on external analog signal 0-10V
2. based on external air temperature
In both cases, user can easily define the magnitude of the compensation in correspondence to the desired interval of input signal:
outside this interval, set point is limited to its min or max value.

Demand limit
User can limit the power absorption of the unit in defined periods of time (function is activated through a volt-free contact).
Limitation can be roughly implemented by limiting the max number of compressors in operation (only for units with multiple
compressors, without any specific option), or by a direct comparison of the power input and the actual threshold: in this second case,
Power Network Analyzer is necessary.

www.euroklimat.it 29
Machine
nomenclature
ZEUS W-P-820-C-1C-2BE-22-H
Heat source
W: water cooled machine

Unit series
B: Business
P: Premium
S: Special unit

Unit size
Nominal capacity [kW]

Refrigerant
C: R134a
F: HFO1234ze
G: R513A

Unit Configuration
No. of circuits
(1 or 2)
Version:
C: chiller
H: heat pump

Compressors equipment
No. of compressors
Compressor model:
A: TT300
B: TT350
C: TT400
D: TT700
H: TG230
I: TG310
J: TG390
K: TG520
BPHE economizer
(1 per compressor)

Heat exchangers configuration


Evaporator no. of passes
Condenser no. of passes

Voltage levels
E: 380-3-50
D: 380-3-60
H: 400-3-50
J: 400-3-60
G: 460-3-60
F: 575-3-60

30 www.euroklimat.it
Machine selection
& part load performances
A dedicated software tool
ZEUS Selection Software is available to select the unit that better fits any specific application.

Technical data reported in the homonym section of this document are referred only to standard conditions (Evaporator: water, 12/7°C,
FF=0.018m2K/kW. Condenser: water, 30/35°C, FF=0. 043m2K/kW): for any other design conditions, refer to ZEUS Selection
Software or contact the Sales representative.

The tool is designed for accurate predictions of unit performances in terms of power consumption and pressure drops: EUROKLIMAT
always maintains this software to ensure the best accuracy, thus technical data are subject to change without prior notice.

Software version is always reported in technical data sheet.


ZEUS Selection Software provides:
• unit performances at design conditions (gross and net capacities, according to EN14511-3:2013)
• automatic selection of evaporator and condenser configuration (best no. of passes)
• compressor envelope with three main operating points:
1. design conditions
2. minimum capacity at minimum condenser inlet temperature
3. maximum capacity at maximum condenser inlet temperature
• compressor map showing capacity range at various source temperature and fixed plant side temperature
(evaporator side for chillers and condenser side for heat pumps)
• NPLV according to AHRI 551-591:2011 (if applicable)
• EUROVENT ESEER according to EN 14511-3:2013
• IPLV according to AHRI 550-590:2011
• Part load performance table (with heat source temperature variable within operating limits)
• Unit description with dimensions and weight
• Noise levels
• Refrigerant content
• Electrical data
• Detail and summary of selected accessories
• Applicable standards

Sample of compressor’s envelope and compressor map available in technical data sheet generated by ZEUS Selection Software. Both
graphs represent compressor operating point at design conditions with a green dot.

Chiller: modulation of compressor evaporator capacity


at fixed evaporating temperature and variable
condensing temperature

www.euroklimat.it 31
ZEUS R134a

270 410

Technical data R134a


ZEUS 270 270 310 310 380 380 410 410
Series (P=Premium, B=business) P B P B P B P B

Gross cooling nominal capacity (1) [kW] 270.0 270.0 310.0 310.0 380.0 380.0 410.0 410.0
Net cooling capacity (EN14511) [kW] 269.4 269.3 309.3 309.1 379.4 379.2 409.2 409.0

Unit engaged power input [kW] 50.0 52.0 56.7 59.1 69.2 71.8 71.1 73.7
Unit engaged current [kW] 73.7 76.6 83.5 87.0 101.9 105.8 104.7 108.6
Evaporator (1)
Water flow [m3/h] 46.4 46.4 53.3 53.3 65.3 65.3 70.5 70.5
Pressure drop [kPa] 17 23 23 30 15 23 18 26
Water volume [dm3] 58 49 58 49 87 66 87 66
Condenser (1)
Water flow [m3/h] 55.0 55.4 63.1 63.5 77.2 77.7 82.7 83.2
Pressure drop [kPa] 15 27 20 36 16 26 19 30
Water volume [dm3] 56 41 56 41 77 59 77 59
Energy efficiency indexes
EER 5.27 5.03 5.32 5.06 5.37 5.15 5.63 5.39
ESEER - EN 14511-3:2013 7.07 6.71 7.23 6.93 8.28 7.90 8.45 8.03
IPLV - AHRI 550-590:2011 9.32 9.16 9.59 9.43 9.81 9.57 10.03 9.77
NPLV - AHRI 551-591:2011 9.29 9.29 9.67 9.65 9.55 9.32 9.82 9.56
Compressors
Number 1 1 1 1 1 1 1 1
Model TT300 TT300 TT300 TT300 TT350 TT350 TT350 TT350
Economizer(s) n.a. n.a. BPHE BPHE n.a. n.a. BPHE BPHE
Refrigerant
Type R134a R134a R134a R134a R134a R134a R134a R134a
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 44 112 46 114 68 94 72 98
Electrical data [400-3-50]
Unit max operating current [A] 137 137 137 137 212 212 212 212
Sound levels (2)
Sound power Lw(A) [dB(A)] 87.5 87.5 87.5 87.5 88.0 88.0 88.0 88.0
Sound pressure Lp(A) at 1m [dB(A)] 70.1 70.1 70.1 70.1 70.3 70.6 70.3 70.6
Dimensions
Length [mm] 2543 2493 2543 2493 2595 2543 2595 2543
Width [mm] 1197 1197 1197 1197 1342 1197 1342 1197
Height [mm] 1710 1710 1710 1710 1910 1710 1910 1710
Weight - operating [kg] 1834 1614 1850 1630 2035 1869 2056 1889
Water connections (3)
Evaporator [DN] 125 125 125 125 150 125 150 125
Condenser [DN] 125 100 125 100 150 125 150 125

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

32 www.euroklimat.it
R134a

ZEUS
460 590

Technical data R134a


ZEUS 460 460 510 510 540 540 590 590
Series (P=Premium, B=business) P B P B P B P B

Gross cooling nominal capacity (1) [kW] 460.0 460.0 510.0 510.0 540.0 540.0 590.0 590.0
Net cooling capacity (EN14511) [kW] 459.2 459.0 509.0 508.7 539.1 539.0 589.1 588.7

Unit engaged power input [kW] 82.1 86.1 87.6 91.9 100.0 103.2 105.7 106.3
Unit engaged current [kW] 120.9 126.8 129.0 135.4 147.3 152.0 155.6 156.5
Evaporator (1)
Water flow [m3/h] 79.1 79.1 87.7 87.7 92.9 92.9 101.5 101.5
Pressure drop [kPa] 18 24 22 29 18 22 16 26
Water volume [dm3] 97 81 97 81 118 96 130 96
Condenser (1)
Water flow [m3/h] 93.2 93.9 102.8 103.5 110.1 110.6 119.6 119.7
Pressure drop [kPa] 15 31 19 37 14 24 17 25
Water volume [dm3] 93 66 93 66 113 90 113 94
Energy efficiency indexes
EER 5.48 5.19 5.68 5.36 5.29 5.11 5.47 5.40
ESEER - EN 14511-3:2013 7.96 7.70 8.34 7.93 8.72 8.36 8.15 7.83
IPLV - AHRI 550-590:2011 10.28 9.94 10.48 10.11 10.11 9.89 10.00 9.86
NPLV - AHRI 551-591:2011 10.01 9.69 10.24 9.89 9.90 9.69 9.73 9.59
Compressors
Number 1 1 1 1 2 2 1 1
Model TT400 TT400 TT400 TT400 TT300 TT300 TT700 TT700
Economizer(s) n.a. n.a. BPHE BPHE n.a. n.a. n.a. n.a.
Refrigerant
Type R134a R134a R134a R134a R134a R134a R134a R134a
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 65 63 70 68 91 65 87 65
Electrical data [400-3-50]
Unit max operating current [A] 172 172 172 172 272 272 198 198
Sound levels (2)
Sound power Lw(A) [dB(A)] 89.0 89.0 89.0 89.0 90.5 90.5 90.0 90.0
Sound pressure Lp(A) at 1m [dB(A)] 71.3 71.3 71.3 71.3 72.6 72.8 72.1 72.3
Dimensions
Length [mm] 2595 2583 2595 2583 2540 2585 2540 2595
Width [mm] 1342 1289 1342 1289 1456 1456 1456 1342
Height [mm] 1910 1860 1910 1860 1938 1938 1934 1910
Weight - operating [kg] 2118 1973 2160 2016 2647 2321 2467 2122
Water connections (3)
Evaporator [DN] 150 150 150 150 200 150 200 150
Condenser [DN] 150 125 150 125 150 150 150 150

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

www.euroklimat.it 33
ZEUS R134a

620 820

Technical data R134a


ZEUS 620 620 650 650 760 760 820 820
Series (P=Premium, B=business) P B P B P B P B

Gross cooling nominal capacity (1) [kW] 620.0 620.0 650.0 650.0 760.0 760.0 820.0 820.0
Net cooling capacity (EN14511) [kW] 618.7 618.5 648.9 648.3 758.3 758.5 818.0 818.1

Unit engaged power input [kW] 113.3 117.2 112.4 112.8 139.8 144.7 143.7 148.5
Unit engaged current [kW] 166.9 172.7 165.5 166.1 205.9 213.1 211.6 218.8
Evaporator (1)
Water flow [m3/h] 106.6 106.6 111.8 111.8 130.7 130.7 141.0 141.0
Pressure drop [kPa] 24 29 20 32 27 25 32 29
Water volume [dm3] 118 96 130 96 130 128 130 128
Condenser (1)
Water flow [m3/h] 126.1 126.8 131.1 131.2 154.7 155.6 165.7 166.6
Pressure drop [kPa] 19 31 21 30 17 29 20 33
Water volume [dm3] 113 90 113 94 147 113 147 113
Energy efficiency indexes
EER 5.34 5.13 5.65 5.58 5.31 5.12 5.55 5.35
ESEER - EN 14511-3:2013 8.73 7.68 8.30 7.92 8.50 8.21 8.60 8.29
IPLV - AHRI 550-590:2011 10.20 9.96 10.24 10.09 9.96 9.73 10.16 9.92
NPLV - AHRI 551-591:2011 10.01 9.77 9.97 9.82 9.73 9.52 9.95 9.72
Compressors
Number 2 2 1 1 2 2 2 2
Model TT300 TT300 TT700 TT700 TT350 TT350 TT350 TT350
Economizer(s) BPHE BPHE BPHE BPHE n.a. n.a. BPHE BPHE
Refrigerant
Type R134a R134a R134a R134a R134a R134a R134a R134a
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 96 70 93 71 91 87 98 93
Electrical data [400-3-50]
Unit max operating current [A] 272 272 198 198 422 422 422 422
Sound levels (2)
Sound power Lw(A) [dB(A)] 90.5 90.5 90.0 90.0 91.0 91.0 91.0 91.0
Sound pressure Lp(A) at 1m [dB(A)] 72.6 72.8 72.1 72.3 73.1 73.1 73.1 73.1
Dimensions
Length [mm] 2540 2585 2540 2595 2100 2540 2408 2540
Width [mm] 1456 1456 1456 1342 1540 1456 1540 1456
Height [mm] 1938 1938 1934 1910 1938 1938 1938 1938
Weight - operating [kg] 2679 2353 2514 2169 2882 2675 2924 2716
Water connections (3)
Evaporator [DN] 200 150 200 150 200 200 200 200
Condenser [DN] 150 150 150 150 150 150 150 150

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

34 www.euroklimat.it
R134a

ZEUS
920 1140

Technical data R134a


ZEUS 920 920 1020 1020 1080 1080 1140 1140
Series (P=Premium, B=business) P B P B P B P B

Gross cooling nominal capacity (1) [kW] 920.0 920.0 1020.0 1020.0 1080.0 1080.0 1140.0 1140.0
Net cooling capacity (EN14511) [kW] 918.7 917.3 1018.3 1016.5 1077.0 1077.1 1138.3 1137.0

Unit engaged power input [kW] 164.2 170.1 175.2 182.1 199.0 201.9 208.0 214.2
Unit engaged current [kW] 241.8 250.6 258.0 268.2 293.1 297.3 306.3 315.5
Evaporator (1)
Water flow [m3/h] 158.2 158.2 175.4 175.4 185.7 185.7 196.0 196.0
Pressure drop [kPa] 17 40 21 49 38 37 19 37
Water volume [dm3] 194 130 194 130 264 264 280 198
Condenser (1)
Water flow [m3/h] 186.4 187.5 205.5 206.7 220.0 220.4 231.8 232.9
Pressure drop [kPa] 15 25 19 30 51 68 18 29
Water volume [dm3] 185 146 185 146 262 224 301 241
Energy efficiency indexes
EER 5.50 5.24 5.70 5.40 5.22 5.12 5.38 5.16
ESEER - EN 14511-3:2013 9.03 8.38 9.14 8.38 7.32 7.15 8.63 8.11
IPLV - AHRI 550-590:2011 10.48 10.24 10.69 10.41 9.66 9.58 9.94 9.74
NPLV - AHRI 551-591:2011 10.23 10.00 10.45 10.18 9.87 9.76 9.72 9.52
Compressors
Number 2 2 2 2 4 4 3 3
Model TT400 TT400 TT400 TT400 TT300 TT300 TT350 TT350
Economizer(s) n.a. n.a. BPHE BPHE n.a. n.a. n.a. n.a.
Refrigerant
Type R134a R134a R134a R134a R134a R134a R134a R134a
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 117 91 128 102 202 171 176 149
Electrical data [400-3-50]
Unit max operating current [A] 342 342 342 342 542 542 632 632
Sound levels (2)
Sound power Lw(A) [dB(A)] 92.0 92.0 92.0 92.0 93.5 93.5 93.0 93.0
Sound pressure Lp(A) at 1m [dB(A)] 73.8 74.1 73.8 74.1 74.3 74.4 74.2 74.4
Dimensions
Length [mm] 2437 2408 2437 2408 4508 4640 3447 3418
Width [mm] 1715 1540 1715 1540 1540 1456 1715 1540
Height [mm] 2054 1938 2054 1938 2005 1933 2054 2005
Weight - operating [kg] 3611 2883 3697 2969 4485 4073 4440 3772
Water connections (3)
Evaporator [DN] 200 200 200 200 200 200 200 200
Condenser [DN] 200 150 200 150 200 150 200 200

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

www.euroklimat.it 35
ZEUS R134a

1180 1300

Technical data R134a


ZEUS 1180 1180 1230 1230 1240 1240 1300 1300
Series (P=Premium, B=business) P B P B P B P B

Gross cooling nominal capacity (1) [kW] 1180.0 1180.0 1230.0 1230.0 1240.0 1240.0 1300.0 1300.0
Net cooling capacity (EN14511) [kW] 1178.2 1176.7 1227.9 1226.3 1235.7 1235.8 1297.6 1295.7

Unit engaged power input [kW] 204.6 211.0 213.8 220.2 226.1 229.3 216.9 224.3
Unit engaged current [kW] 301.3 310.8 314.8 324.3 333.1 337.8 319.4 330.3
Evaporator (1)
Water flow [m3/h] 202.9 202.9 211.5 211.5 213.2 213.2 223.6 223.6
Pressure drop [kPa] 20 40 22 43 50 49 24 48
Water volume [dm3] 280 198 280 198 264 264 280 198
Condenser (1)
Water flow [m3/h] 238.1 239.2 248.3 249.4 252.1 252.7 260.9 262.1
Pressure drop [kPa] 18 27 21 34 67 89 21 32
Water volume [dm3] 313 258 301 241 262 224 313 258
Energy efficiency indexes
EER 5.65 5.42 5.63 5.39 5.22 5.11 5.85 5.58
ESEER - EN 14511-3:2013 8.82 8.23 8.76 8.16 7.36 7.14 8.94 8.26
IPLV - AHRI 550-590:2011 10.54 10.29 10.16 9.93 9.87 9.79 10.81 10.52
NPLV - AHRI 551-591:2011 10.26 10.02 9.94 9.72 9.99 9.88 10.54 10.25
Compressors
Number 2 2 3 3 4 4 2 2
Model TT700 TT700 TT350 TT350 TT300 TT300 TT700 TT700
Economizer(s) n.a. n.a. BPHE BPHE BPHE BPHE BPHE BPHE
Refrigerant
Type R134a R134a R134a R134a R134a R134a R134a R134a
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 176 149 186 159 212 180 188 161
Electrical data [400-3-50]
Unit max operating current [A] 394 394 632 632 542 542 394 394
Sound levels (2)
Sound power Lw(A) [dB(A)] 93.0 93.0 93.0 93.0 93.5 93.5 93.0 93.0
Sound pressure Lp(A) at 1m [dB(A)] 74.2 74.4 74.2 74.4 74.3 74.4 74.2 74.4
Dimensions
Length [mm] 3447 3418 3447 3418 4508 4640 3447 3418
Width [mm] 1715 1540 1715 1540 1540 1456 1715 1540
Height [mm] 2054 2005 2054 2005 2005 1933 2054 2005
Weight - operating [kg] 4265 3610 4503 3835 4549 4138 4359 3704
Water connections (3)
Evaporator [DN] 200 200 200 200 200 200 200 200
Condenser [DN] 200 200 200 200 200 150 200 200

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

36 www.euroklimat.it
R134a

ZEUS
1350 1640

Technical data R134a


ZEUS 1350 1380 1380 1520 1520 1530 1530 1640 1640
Series (P=Premium, B=business) P P B P B P B P B

Gross cooling nominal capacity (1) [kW] 1350.0 1380.0 1380.0 1520.0 1520.0 1530.0 1530.0 1640.0 1640.0
Net cooling capacity (EN14511) [kW] 1345.9 1378.1 1376.2 1515.5 1515.6 1527.5 1525.1 1634.6 1634.7

Unit engaged power input [kW] 254.0 246.2 254.1 276.2 280.7 262.8 271.9 284.4 288.7
Unit engaged current [kW] 374.1 362.6 374.3 406.8 413.4 387.0 400.4 418.9 425.2
Evaporator (1)
Water flow [m3/h] 232.2 237.3 237.3 261.4 261.4 263.1 263.1 282.0 282.0
Pressure drop [kPa] 44 18 39 43 42 22 48 50 49
Water volume [dm3] 308 346 236 348 349 346 236 348 349
Condenser (1)
Water flow [m3/h] 275.8 279.7 281.0 308.9 309.7 308.3 309.9 330.9 331.7
Pressure drop [kPa] 66 19 27 58 77 23 33 66 88
Water volume [dm3] 262 375 298 343 293 375 298 343 293
Energy efficiency indexes
EER 5.08 5.50 5.27 5.27 5.16 5.69 5.43 5.49 5.37
ESEER - EN 14511-3:2013 7.12 8.94 8.38 7.88 7.64 9.04 8.37 7.92 7.65
IPLV - AHRI 550-590:2011 9.56 10.41 10.19 9.96 9.85 10.63 10.37 10.13 10.01
NPLV - AHRI 551-591:2011 9.72 10.17 9.95 9.75 9.64 10.40 10.14 9.92 9.81
Compressors
Number 5 3 3 4 4 3 3 4 4
Model TT300 TT400 TT400 TT350 TT350 TT400 TT400 TT350 TT350
Economizer(s) n.a. n.a. n.a. n.a. n.a. BPHE BPHE BPHE BPHE
Refrigerant
Type R134a R134a R134a R134a R134a R134a R134a R134a R134a
No.of circuits 1 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 263 229 192 249 226 245 208 262 239
Electrical data [400-3-50]
Unit max operating current [A] 677 512 512 842 842 512 512 842 842
Sound levels (2)
Sound power Lw(A) [dB(A)] 94.0 94.0 94.0 94.0 94.0 94.0 94.0 94.0 94.0
Sound pressure Lp(A) at 1m [dB(A)] 74.6 75.0 75.2 74.6 74.7 75.0 75.2 74.6 74.7
Dimensions
Length [mm] 4537 3488 3447 4537 4537 3488 3447 4537 4537
Width [mm] 1715 1862 1715 1715 1656 1862 1715 1715 1656
Height [mm] 2054 2172 2054 2054 2054 2172 2054 2054 2054
Weight - operating [kg] 5177 5245 4332 5281 4950 5374 4460 5364 5034
Water connections (3)
Evaporator [DN] 200 250 200 200 200 250 200 200 200
Condenser [DN] 200 200 200 200 150 200 200 200 150

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

www.euroklimat.it 37
ZEUS R134a

1770 1950

Technical data R134a


ZEUS 1770 1770 1840 1840 1860 1900 1950 1950
Series (P=Premium, B=business) P B P B P P P B

Gross cooling nominal capacity (1) [kW] 1770.0 1770.0 1840.0 1840.0 1860.0 1900.0 1950.0 1950.0
Net cooling capacity (EN14511) [kW] 1765.9 1762.2 1835.0 1835.1 1853.6 1894.8 1944.7 1939.9

Unit engaged power input [kW] 304.7 314.5 327.4 332.8 340.7 345.2 323.3 335.1
Unit engaged current [kW] 448.7 463.2 482.2 490.1 501.8 508.5 476.2 493.5
Evaporator (1)
Water flow [m3/h] 304.4 304.4 316.4 316.4 319.9 326.7 335.3 335.3
Pressure drop [kPa] 34 70 41 40 53 41 41 85
Water volume [dm3] 462 314 434 436 374 446 462 314
Condenser (1)
Water flow [m3/h] 356.8 358.5 372.7 373.7 378.5 386.1 390.9 393.0
Pressure drop [kPa] 53 73 54 72 67 57 64 87
Water volume [dm3] 407 353 423 366 388 427 407 353
Energy efficiency indexes
EER 5.59 5.31 5.40 5.28 5.20 5.29 5.76 5.43
ESEER - EN 14511-3:2013 8.29 7.58 8.21 7.96 7.37 7.92 8.28 7.48
IPLV - AHRI 550-590:2011 10.50 10.24 10.39 10.27 9.85 9.97 10.73 10.43
NPLV - AHRI 551-591:2011 10.26 10.02 10.14 10.03 9.93 9.76 10.46 10.15
Compressors
Number 3 3 4 4 6 5 3 3
Model TT700 TT700 TT400 TT400 TT300 TT350 TT700 TT700
Economizer(s) n.a. n.a. n.a. n.a. BPHE n.a. BPHE BPHE
Refrigerant
Type R134a R134a R134a R134a R134a R134a R134a R134a
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 306 267 316 304 260 311 324 285
Electrical data [400-3-50]
Unit max operating current [A] 590 590 682 682 812 1052 590 590
Sound levels (2)
Sound power Lw(A) [dB(A)] 95.0 95.0 95.0 95.0 95.0 94.5 95.0 95.0
Sound pressure Lp(A) at 1m [dB(A)] 75.4 75.6 75.4 75.5 75.6 74.9 75.4 75.6
Dimensions
Length [mm] 4578 4537 4578 4578 4537 4578 4578 4537
Width [mm] 1832 1715 1832 1803 1715 1832 1832 1715
Height [mm] 2172 2054 2172 2172 2054 2172 2172 2054
Weight - operating [kg] 5851 5019 6040 5776 6027 6297 5992 5160
Water connections (3)
Evaporator [DN] 250 200 250 250 200 250 250 200
Condenser [DN] 200 200 200 150 200 200 200 200

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

38 www.euroklimat.it
R134a

ZEUS
2040 2460

Technical data R134a


ZEUS 2040 2040 2050 2280 2300 2360 2360 2460
Series (P=Premium, B=business) P B P P P P B P

Gross cooling nominal capacity (1) [kW] 2040.0 2040.0 2050.0 2280.0 2300.0 2360.0 2360.0 2460.0
Net cooling capacity (EN14511) [kW] 2033.4 2033.5 2043.6 2271.7 2293.1 2353.8 2352.5 2449.8

Unit engaged power input [kW] 350.3 355.9 355.5 402.5 410.7 407.6 416.7 414.8
Unit engaged current [kW] 516.0 524.2 523.6 592.8 605.0 600.3 613.7 610.9
Evaporator (1)
Water flow [m3/h] 350.8 350.8 352.5 392.1 395.5 405.8 405.8 423.0
Pressure drop [kPa] 50 49 48 58 47 40 50 68
Water volume [dm3] 434 436 446 640 495 556 491 640
Condenser (1)
Water flow [m3/h] 411.1 412.0 413.7 461.3 466.2 475.9 477.5 494.4
Pressure drop [kPa] 66 88 65 86 53 53 73 99
Water volume [dm3] 423 366 427 605 535 545 465 605
Energy efficiency indexes
EER 5.55 5.43 5.50 5.35 5.38 5.57 5.39 5.55
ESEER - EN 14511-3:2013 8.17 7.89 7.97 7.61 8.17 8.16 7.76 7.61
IPLV - AHRI 550-590:2011 10.59 10.46 10.15 10.16 10.36 10.53 10.36 10.35
NPLV - AHRI 551-591:2011 10.36 10.23 9.94 9.94 10.13 10.28 10.11 10.14
Compressors
Number 4 4 5 6 5 4 4 6
Model TT400 TT400 TT350 TT350 TT400 TT700 TT700 TT350
Economizer(s) BPHE BPHE BPHE n.a. n.a. n.a. n.a. BPHE
Refrigerant
Type R134a R134a R134a R134a R134a R134a R134a R134a
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 337 325 328 387 305 387 295 406
Electrical data [400-3-50]
Unit max operating current [A] 682 682 1052 1262 852 786 786 1262
Sound levels (2)
Sound power Lw(A) [dB(A)] 95.0 95.0 94.5 95.5 95.5 96.0 96.0 95.5
Sound pressure Lp(A) at 1m [dB(A)] 75.4 75.5 74.9 75.3 75.9 76.2 76.4 75.3
Dimensions
Length [mm] 4578 4578 4578 5878 4578 4620 4578 5878
Width [mm] 1832 1803 1832 1832 1862 1978 1832 1832
Height [mm] 2172 2172 2172 2172 2172 2288 2172 2172
Weight - operating [kg] 6212 5948 6402 7919 6922 7238 6331 8045
Water connections (3)
Evaporator [DN] 250 250 250 250 250 300 250 250
Condenser [DN] 200 150 200 200 200 200 200 200

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

www.euroklimat.it 39
ZEUS R134a

2550 3900

Technical data R134a


ZEUS 2550 2600 2600 2760 2950 3060 3250 3540 3900
Series (P=Premium, B=business) P P B P P P P P P

Gross cooling nominal capacity (1) [kW] 2550.0 2600.0 2600.0 2760.0 2950.0 3060.0 3250.0 3540.0 3900.0
Net cooling capacity (EN14511) [kW] 2540.9 2592.0 2590.3 2749.8 2942.3 3046.6 3240.1 3525.4 3881.1

Unit engaged power input [kW] 439.9 432.8 443.2 476.4 510.4 510.3 542.1 591.8 628.2
Unit engaged current [kW] 647.9 637.5 652.8 701.7 751.7 751.5 798.4 871.6 925.2
Evaporator (1)
Water flow [m3/h] 438.5 447.1 447.1 474.6 507.3 526.2 558.9 608.8 670.7
Pressure drop [kPa] 58 49 61 61 41 75 50 71 86
Water volume [dm3] 495 556 491 759 693 759 693 894 894
Condenser (1)
Water flow [m3/h] 514.2 521.6 523.3 556.6 595.1 614.0 652.1 710.5 778.7
Pressure drop [kPa] 64 63 87 85 54 103 64 71 86
Water volume [dm3] 535 545 465 734 673 734 673 1038 1038
Energy efficiency indexes
EER 5.52 5.73 5.53 5.47 5.56 5.60 5.72 5.66 5.81
ESEER - EN 14511-3:2013 8.12 8.17 7.72 7.62 8.11 7.77 8.12 7.83 7.78
IPLV - AHRI 550-590:2011 10.54 10.69 10.50 10.59 10.50 10.79 10.69 10.72 10.95
NPLV - AHRI 551-591:2011 10.31 10.45 10.26 10.35 10.23 10.54 10.43 10.45 10.70
Compressors
Number 5 4 4 6 5 6 5 6 6
Model TT400 TT700 TT700 TT400 TT700 TT400 TT700 TT700 TT700
Economizer(s) BPHE BPHE BPHE n.a. n.a. BPHE BPHE n.a. BPHE
Refrigerant
Type R134a R134a R134a R134a R134a R134a R134a R134a R134a
No.of circuits 1 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 332 412 319 514 478 546 508 670 706
Electrical data [400-3-50]
Unit max operating current [A] 852 786 786 1022 982 1022 982 1178 1178
Sound levels (2)
Sound power Lw(A) [dB(A)] 95.5 96.0 96.0 96.5 96.5 96.5 96.5 97.5 97.5
Sound pressure Lp(A) at 1m [dB(A)] 75.9 76.2 76.4 76.1 76.5 76.1 76.5 76.9 76.9
Dimensions
Length [mm] 4578 4620 4578 5920 4649 5920 4649 5949 5949
Width [mm] 1862 1978 1832 1978 2125 1978 2125 2184 2184
Height [mm] 2172 2288 2172 2288 2405 2288 2405 2405 2405
Weight - operating [kg] 7137 7426 6519 9200 8827 9457 9062 11480 11762
Water connections (3)
Evaporator [DN] 250 300 250 300 300 300 300 300 300
Condenser [DN] 200 200 200 200 200 200 200 250 250

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

40 www.euroklimat.it
ZEUS
HFO
1234ze

200 430

Technical data HFO1234ze


ZEUS 200 230 270 310 350 390 400 430
Series (P=Premium, B=business) P P P P P P P P

Gross cooling nominal capacity (1) [kW] 200.0 230.0 270.0 310.0 350.0 390.0 400.0 430.0
Net cooling capacity (EN14511) [kW] 199.6 229.4 269.4 309.3 349.4 389.2 399.3 429.2

Unit engaged power input [kW] 37.5 42.3 47.4 52.9 64.4 68.7 75.1 75.6
Unit engaged current [kW] 55.3 62.3 69.8 77.9 94.9 101.1 110.5 111.3
Evaporator (1)
Water flow [m3/h] 34.4 39.6 46.4 53.3 60.2 67.1 68.8 73.9
Pressure drop [kPa] 16 21 17 23 16 20 16 18
Water volume [dm3] 46 46 58 58 79 79 89 89
Condenser (1)
Water flow [m3/h] 40.8 46.8 54.6 62.4 71.3 78.9 81.7 86.9
Pressure drop [kPa] 11 14 11 14 11 14 10 11
Water volume [dm3] 50 50 66 66 86 86 102 102
Energy efficiency indexes
EER 5.21 5.29 5.57 5.71 5.33 5.55 5.23 5.58
ESEER - EN 14511-3:2013 7.26 7.63 8.38 8.57 8.59 8.78 8.73 8.92
IPLV - AHRI 550-590:2011 9.54 9.98 9.94 10.25 10.19 10.45 10.06 10.30
NPLV - AHRI 551-591:2011 9.72 9.90 9.71 10.04 9.97 10.23 9.85 10.10
Compressors
Number 1 1 1 1 1 1 2 2
Model TG230 TG230 TG310 TG310 TG390 TG390 TG230 TG230
Economizer(s) n.a. BPHE n.a. BPHE n.a. BPHE n.a. BPHE
Refrigerant
Type R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 48 50 44 47 71 77 67 72
Electrical data [400-3-50]
Unit max operating current [A] 97 97 152 152 125 125 192 192
Sound levels (2)
Sound power Lw(A) [dB(A)] 87.0 87.0 87.5 87.5 88.5 88.5 90.0 90.0
Sound pressure Lp(A) at 1m [dB(A)] 69.6 69.6 70.1 70.1 70.8 70.8 72.3 72.3
Dimensions
Length [mm] 2543 2543 2543 2543 2595 2595 2585 2585
Width [mm] 1197 1197 1197 1197 1342 1342 1456 1456
Height [mm] 1710 1710 1710 1710 1910 1910 1938 1938
Weight - operating [kg] 1783 1800 1864 1886 2046 2089 2345 2377
Water connections (3)
Evaporator [DN] 125 125 125 125 150 150 150 150
Condenser [DN] 125 125 125 125 150 150 150 150

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

www.euroklimat.it 41
ZEUS
HFO
1234ze

460 860

Technical data HFO1234ze


ZEUS 460 540 620 700 780 800 810 860
Series (P=Premium, B=business) P P P P P P P P

Gross cooling nominal capacity (1) [kW] 460.0 540.0 620.0 700.0 780.0 800.0 810.0 860.0
Net cooling capacity (EN14511) [kW] 459.1 538.4 617.7 697.9 777.2 797.9 807.6 857.2

Unit engaged power input [kW] 84.7 93.8 105.0 127.4 136.2 148.7 140.7 140.0
Unit engaged current [kW] 124.7 138.2 154.6 187.6 200.6 219.0 207.2 206.1
Evaporator (1)
Water flow [m3/h] 79.1 92.9 106.6 120.4 134.1 137.6 139.3 147.9
Pressure drop [kPa] 21 37 49 40 49 33 39 44
Water volume [dm3] 89 126 126 159 159 212 183 183
Condenser (1)
Water flow [m3/h] 93.7 109.0 124.7 142.3 157.6 163.1 163.5 172.0
Pressure drop [kPa] 13 38 50 41 50 37 38 42
Water volume [dm3] 102 113 113 140 140 230 165 165
Energy efficiency indexes
EER 5.32 5.53 5.62 5.29 5.46 5.20 5.54 5.88
ESEER - EN 14511-3:2013 8.80 8.26 8.21 8.30 8.29 7.54 8.28 8.35
IPLV - AHRI 550-590:2011 10.19 10.31 10.55 10.51 10.72 10.04 10.24 10.72
NPLV - AHRI 551-591:2011 10.01 10.08 10.33 10.27 10.50 9.84 10.04 10.44
Compressors
Number 2 2 2 2 2 4 3 2
Model TG230 TG310 TG310 TG390 TG390 TG230 TG310 TG520
Economizer(s) BPHE n.a. BPHE n.a. BPHE n.a. n.a. BPHE
Refrigerant
Type R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 72 102 108 140 151 221 131 143
Electrical data [400-3-50]
Unit max operating current [A] 192 302 302 248 248 382 452 286
Sound levels (2)
Sound power Lw(A) [dB(A)] 90.0 90.5 90.5 91.5 91.5 93.0 92.5 92.5
Sound pressure Lp(A) at 1m [dB(A)] 72.3 72.2 72.2 73.0 73.0 73.8 74.0 74.0
Dimensions
Length [mm] 2585 3595 3595 3550 3550 4508 3550 3550
Width [mm] 1456 1456 1456 1456 1456 1540 1456 1456
Height [mm] 1938 1938 1938 1938 1938 2005 1938 1938
Weight - operating [kg] 2378 2664 2708 3073 3160 4270 3433 3330
Water connections (3)
Evaporator [DN] 150 150 150 200 200 200 200 200
Condenser [DN] 150 150 150 150 150 200 150 150

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

42 www.euroklimat.it
ZEUS
HFO
1234ze

920 1290

Technical data HFO1234ze


ZEUS 920 930 1000 1050 1080 1170 1240 1290
Series (P=Premium, B=business) P P P P P P P P

Gross cooling nominal capacity (1) [kW] 920.0 930.0 1000.0 1050.0 1080.0 1170.0 1240.0 1290.0
Net cooling capacity (EN14511) [kW] 917.1 926.6 997.6 1047.2 1077.1 1166.3 1235.8 1285.3

Unit engaged power input [kW] 168.3 157.5 185.9 191.4 187.8 204.7 210.3 214.3
Unit engaged current [kW] 247.9 232.0 273.8 281.9 276.5 301.5 309.7 315.6
Evaporator (1)
Water flow [m3/h] 158.2 159.9 172.0 180.6 185.7 201.2 213.2 221.8
Pressure drop [kPa] 44 52 32 36 37 45 49 53
Water volume [dm3] 212 183 264 264 264 264 264 264
Condenser (1)
Water flow [m3/h] 187.2 187.0 203.9 213.5 218.0 236.4 249.4 258.7
Pressure drop [kPa] 49 50 37 41 38 50 50 54
Water volume [dm3] 230 165 285 285 301 285 301 301
Energy efficiency indexes
EER 5.24 5.63 5.21 5.30 5.55 5.47 5.63 5.73
ESEER - EN 14511-3:2013 7.66 8.18 7.58 8.34 8.30 8.36 8.25 8.08
IPLV - AHRI 550-590:2011 10.19 10.47 10.02 10.43 10.26 10.66 10.41 10.59
NPLV - AHRI 551-591:2011 10.00 10.26 9.82 10.20 10.04 10.44 10.20 10.35
Compressors
Number 4 3 5 3 4 3 4 3
Model TG230 TG310 TG230 TG390 TG310 TG390 TG310 TG520
Economizer(s) BPHE BPHE n.a. n.a. n.a. BPHE BPHE BPHE
Refrigerant
Type R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze
No.of circuits 1 1 1 1 1 1 1 1
No.of circuits / Charge [kg] 231 141 202 202 202 218 215 220
Electrical data [400-3-50]
Unit max operating current [A] 382 452 477 371 602 371 602 428
Sound levels (2)
Sound power Lw(A) [dB(A)] 93.0 92.5 93.5 93.5 93.5 93.5 93.5 94.5
Sound pressure Lp(A) at 1m [dB(A)] 73.8 74.0 74.3 74.3 74.3 74.3 74.3 75.3
Dimensions
Length [mm] 4508 3550 4508 4508 4508 4508 4508 4508
Width [mm] 1540 1456 1593 1540 1540 1540 1540 1540
Height [mm] 2005 1938 1938 2005 2005 2005 2005 2005
Weight - operating [kg] 4336 3499 4778 4330 4591 4460 4679 4534
Water connections (3)
Evaporator [DN] 200 200 200 200 200 200 200 200
Condenser [DN] 200 150 200 200 200 200 200 200

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

www.euroklimat.it 43
ZEUS
HFO
1234ze

1350 1620

Technical data HFO1234ze


ZEUS 1350 1380 1400 1550 1560 1620
Series (P=Premium, B=business) P P P P P P

Gross cooling nominal capacity (1) [kW] 1350.0 1380.0 1400.0 1550.0 1560.0 1620.0
Net cooling capacity (EN14511) [kW] 1346.8 1376.1 1396.5 1545.4 1555.3 1615.4

Unit engaged power input [kW] 234.8 252.5 255.2 262.8 273.0 282.1
Unit engaged current [kW] 345.8 371.9 375.8 387.1 402.0 415.5
Evaporator (1)
Water flow [m3/h] 232.2 237.3 240.8 266.6 268.3 278.6
Pressure drop [kPa] 33 41 36 44 44 41
Water volume [dm3] 353 328 353 353 353 374
Condenser (1)
Water flow [m3/h] 272.5 280.7 284.6 311.8 315.2 327.1
Pressure drop [kPa] 37 49 41 49 50 37
Water volume [dm3] 375 340 375 375 375 449
Energy efficiency indexes
EER 5.56 5.26 5.30 5.66 5.48 5.54
ESEER - EN 14511-3:2013 8.36 7.75 8.39 8.34 8.39 8.25
IPLV - AHRI 550-590:2011 10.24 10.16 10.39 10.42 10.62 10.20
NPLV - AHRI 551-591:2011 10.02 9.97 10.15 10.22 10.40 9.98
Compressors
Number 5 6 4 5 4 6
Model TG310 TG230 TG390 TG310 TG390 TG310
Economizer(s) n.a. BPHE n.a. BPHE BPHE n.a.
Refrigerant
Type R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze
No.of circuits 1 1 1 1 1 1
No.of circuits / Charge [kg] 253 276 253 269 275 246
Electrical data [400-3-50]
Unit max operating current [A] 752 572 494 752 494 902
Sound levels (2)
Sound power Lw(A) [dB(A)] 94.0 94.5 94.5 94.0 94.5 95.0
Sound pressure Lp(A) at 1m [dB(A)] 74.6 75.1 75.1 74.6 75.1 75.6
Dimensions
Length [mm] 4537 4537 4537 4537 4537 4537
Width [mm] 1715 1715 1715 1715 1715 1715
Height [mm] 2054 2054 2054 2054 2054 2054
Weight - operating [kg] 5608 5794 5411 5718 5585 6100
Water connections (3)
Evaporator [DN] 200 200 200 200 200 200
Condenser [DN] 200 200 200 200 200 200

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

44 www.euroklimat.it
ZEUS
HFO
1234ze

1720 2340

Technical data HFO1234ze


ZEUS 1720 1750 1860 1950 2100 2340
Series (P=Premium, B=business) P P P P P P

Gross cooling nominal capacity (1) [kW] 1720.0 1750.0 1860.0 1950.0 2100.0 2340.0
Net cooling capacity (EN14511) [kW] 1715.9 1745.7 1853.4 1944.3 2089.1 2325.5

Unit engaged power input [kW] 278.1 319.0 316.1 341.2 376.9 404.6
Unit engaged current [kW] 409.6 469.8 465.6 502.5 555.1 596.0
Evaporator (1)
Water flow [m3/h] 295.8 300.9 319.9 335.3 361.1 402.4
Pressure drop [kPa] 34 35 55 44 86 107
Water volume [dm3] 443 443 374 443 483 483
Condenser (1)
Water flow [m3/h] 343.6 355.8 374.2 394.0 426.0 472.0
Pressure drop [kPa] 37 40 48 49 79 97
Water volume [dm3] 472 472 449 472 584 584
Energy efficiency indexes
EER 5.98 5.31 5.63 5.49 5.23 5.35
ESEER - EN 14511-3:2013 8.58 8.41 8.22 8.43 7.59 7.47
IPLV - AHRI 550-590:2011 10.80 10.36 10.39 10.59 10.46 10.67
NPLV - AHRI 551-591:2011 10.55 10.14 10.19 10.37 10.24 10.45
Compressors
Number 4 5 6 5 6 6
Model TG520 TG390 TG310 TG390 TG390 TG390
Economizer(s) BPHE n.a. BPHE BPHE n.a. BPHE
Refrigerant
Type R1234ze R1234ze R1234ze R1234ze R1234ze R1234ze
No.of circuits 1 1 1 1 1 1
No.of circuits / Charge [kg] 337 313 265 353 342 374
Electrical data [400-3-50]
Unit max operating current [A] 570 617 902 617 740 740
Sound levels (2)
Sound power Lw(A) [dB(A)] 95.5 95.0 95.0 95.0 96.0 96.0
Sound pressure Lp(A) at 1m [dB(A)] 75.9 75.4 75.6 75.4 76.0 76.0
Dimensions
Length [mm] 4578 4578 4537 4578 5837 5837
Width [mm] 1832 1832 1715 1832 1715 1715
Height [mm] 2172 2172 2054 2172 2054 2054
Weight - operating [kg] 6421 6439 6231 6662 7158 7419
Water connections (3)
Evaporator [DN] 250 250 200 250 200 200
Condenser [DN] 200 200 200 200 200 200

Note:
(1) Std conditions: evap. water 12/7*C, FF=0. 018m2K/kW, cond. water 30/35°C FF=0.043m2K/kW
(2) Average sound pressure for unit in free field on a reflective surface. Non binding values calculated from sound power level.
(3) For standard evaporator and condenser with two passes

www.euroklimat.it 45
Operating limits
Working limits water cooled chillers ZEUS-W

REGIONS
H High condensing temperature, restrictions in chilled water delivery conditions
N Standard operating zone
L Low Lift zone (requires Low Lift Kit), both for models suitable to high either low condensing temperature

LIMITS
α Max pressure ratio
β Min evap. pressure
γ Min pressure ratio
δ Max evaporating pressure
ε Max capacity, Max Electrical Power
ζ Max condensing pressure

46 www.euroklimat.it
Drawings
Generic drawing of ZEUS units

General notes
Standard water connections are on the right side of the unit: for different orientation, consult the factory. In case of opposite
connections for evaporator and condenser, lateral clearance must equal Lt on both sides.

Quotes Xg, Yg, Zg of center of gravity are provided with general documentation of unit.

For detailed handling and lifting procedures, refer to Installation and Operation Manual.

Quotes for all models are reported in form of tables in the following.

Detailed drawings are reported in the following pages (see Column “DWG” to identify the drawing for each model).

Construction drawing can be subjected to changes without prior notice. Always refer to single machine technical documentations for
construction drawing.

Contact the factory for drawing not inserted in this catalogue and for versions with water boxes.

www.euroklimat.it 47
Quotes
Quotes R134a
Referred to picture at page 47. All quotes in [mm]. Detailed DWG in the following pages.

DWG H L W H1 H3 Hc He Hf Lt W1 W13 Wf
P-270 A 1710 2543 1197 300 718 200 221 615 2100 214 461 922
B-270 B 1710 2493 1197 284 718 150 221 574 2100 214 461 922
P-310 A 1710 2543 1197 300 718 200 221 615 2100 214 461 922
B-310 B 1710 2493 1197 284 718 150 221 574 2100 214 461 922
P-380 C 1910 2595 1342 363 791 252 250 814 2100 267 560 1120
B-380 A 1710 2543 1197 300 718 200 221 615 2100 214 461 922
P-410 C 1910 2595 1342 363 791 252 250 814 2100 267 560 1120
B-410 A 1710 2543 1197 300 718 200 221 615 2100 214 461 922
P-460 C 1910 2595 1342 363 791 252 250 814 2100 267 560 1120
B-460 D 1860 2583 1289 338 741 200 250 652 2100 214 507 1014
P-510 C 1910 2595 1342 363 791 252 250 814 2100 267 560 1120
B-510 D 1860 2583 1289 338 741 200 250 652 2100 214 507 1014
P-540 E 1938 2540 1456 363 739 252 292 839 2100 350 617 1317
B-540 F 1938 2585 1456 363 821 252 250 839 2100 350 617 1317
P-590 G 1934 2540 1456 363 739 252 292 839 2100 267 617 1234
B-590 C 1910 2595 1342 363 791 252 250 814 2100 267 560 1120
P-620 E 1938 2540 1456 363 739 252 292 839 2100 350 617 1317
B-620 F 1938 2585 1456 363 821 252 250 839 2100 350 617 1317
P-650 G 1934 2540 1456 363 739 252 292 839 2100 267 617 1234
B-650 C 1910 2595 1342 363 791 252 250 814 2100 267 560 1120
P-760 n.a. 1938 2100 1540 404 769 252 292 862 2100 321 646 1317
B-760 E 1938 2540 1456 363 739 252 292 839 2100 350 617 1317
P-820 n.a. 1938 2408 1540 404 769 252 292 862 2100 321 646 1317
B-820 E 1938 2540 1456 363 739 252 292 839 2100 350 617 1317
P-920 n.a. 2054 2437 1715 404 769 292 350 943 2100 380 764 1552
B-920 n.a. 1938 2408 1540 404 769 252 292 862 2100 321 646 1317
P-1020 n.a. 2054 2437 1715 404 769 292 350 943 2100 380 764 1552
B-1020 n.a. 1938 2408 1540 404 769 252 292 862 2100 321 646 1317
P-1080 H 2005 4508 1540 404 806 292 292 900 4200 350 700 1400
B-1080 I 1933 4640 1456 393 739 252 292 869 4200 268 616 1234
P-1140 n.a. 2054 3447 1715 404 739 292 350 918 3110 353 764 1525
B-1140 J 2005 3418 1540 404 806 292 292 901 3110 348 703 1400
P-1180 n.a. 2054 3447 1715 404 739 292 350 918 3110 353 764 1525
B-1180 K 2005 3418 1540 404 806 292 292 901 3110 348 703 1400
P-1230 n.a. 2054 3447 1715 404 739 292 350 918 3110 353 764 1525
B-1230 J 2005 3418 1540 404 806 292 292 901 3110 348 703 1400
P-1240 H 2005 4508 1540 404 806 292 292 900 4200 350 700 1400

48 www.euroklimat.it
Quotes
Quotes R134a
Referred to picture at page 47. All quotes in [mm]. Detailed DWG in the following pages.

DWG H L W H1 H3 Hc He Hf Lt W1 W13 Wf
B-1240 I 1933 4640 1456 393 739 252 292 869 4200 268 616 1234
P-1300 n.a. 2054 3447 1715 404 739 300 350 922 3110 353 764 1525
B-1300 K 2005 3418 1540 404 806 292 292 901 3110 348 703 1400
P-1350 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1380 n.a. 2172 3488 1862 404 739 325 400 965 3110 382 852 1701
B-1380 n.a. 2054 3447 1715 404 739 292 350 918 3110 353 764 1525
P-1520 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
B-1520 n.a. 2054 4537 1656 404 739 252 350 837 4200 294 705 1407
P-1530 n.a. 2172 3488 1862 404 739 325 400 965 3110 382 852 1701
B-1530 n.a. 2054 3447 1715 404 739 292 350 918 3110 353 764 1525
P-1640 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
B-1640 n.a. 2054 4537 1656 404 739 252 350 837 4200 294 705 1407
P-1770 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
B-1770 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1840 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
B-1840 n.a. 2172 4578 1803 404 739 292 400 887 4200 323 793 1583
P-1860 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1900 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
P-1950 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
B-1950 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-2040 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
B-2040 n.a. 2172 4578 1803 404 739 292 400 887 4200 323 793 1583
P-2050 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
P-2280 n.a. 2172 5878 1832 404 739 292 400 918 5500 353 823 1642
P-2300 n.a. 2172 4578 1862 404 739 325 400 965 4200 382 852 1701
P-2360 n.a. 2288 4620 1978 404 739 325 450 965 4200 382 911 1818
B-2360 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
P-2460 n.a. 2172 5878 1832 404 739 292 400 918 5500 353 823 1642
P-2550 n.a. 2172 4578 1862 404 739 325 400 965 4200 382 852 1701
P-2600 n.a. 2288 4620 1978 404 739 325 450 965 4200 382 911 1818
B-2600 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
P-2760 n.a. 2288 5920 1978 404 739 325 450 965 5500 382 911 1818
P-2950 n.a. 2405 4649 2125 404 739 350 500 1008 4200 411 999 1993
P-3060 n.a. 2288 5920 1978 404 739 325 450 965 5500 382 911 1818
P-3250 n.a. 2405 4649 2125 404 739 350 500 1008 4200 411 999 1993
P-3540 n.a. 2405 5949 2184 445 739 400 500 1136 5500 470 1058 2111
P-3900 n.a. 2405 5949 2184 445 739 400 500 1136 5500 470 1058 2111

www.euroklimat.it 49
Quotes
Quotes HFO1234ze
Referred to picture at page 47. All quotes in [mm]. Detailed DWG in the following pages.

DWG H L W H1 H3 Hc He Hf Lt W1 W13 Wf
P-200 A 1710 2543 1197 300 718 200 221 615 2100 214 461 922
P-230 A 1710 2543 1197 300 718 200 221 615 2100 214 461 922
P-270 A 1710 2543 1197 300 718 200 221 615 2100 214 461 922
P-310 A 1710 2543 1197 300 718 200 221 615 2100 214 461 922
P-350 C 1910 2595 1342 363 791 252 250 814 2100 267 560 1120
P-390 C 1910 2595 1342 363 791 252 250 814 2100 267 560 1120
P-400 F 1938 2585 1456 363 821 252 250 839 2100 350 617 1317
P-430 F 1938 2585 1456 363 821 252 250 839 2100 350 617 1317
P-460 F 1938 2585 1456 363 821 252 250 839 2100 350 617 1317
P-540 L 1938 3595 1456 393 821 252 250 869 3110 268 616 1234
P-620 L 1938 3595 1456 393 821 252 250 869 3110 268 616 1234
P-700 M 1938 3550 1456 393 739 252 292 869 3110 268 616 1234
P-780 M 1938 3550 1456 393 739 252 292 869 3110 268 616 1234
P-800 H 2005 4508 1540 404 806 292 292 900 4200 350 700 1400
P-810 N 1938 3550 1456 393 739 252 292 869 3110 267 617 1234
P-860 M 1938 3550 1456 393 739 252 292 869 3110 268 616 1234
P-920 H 2005 4508 1540 404 806 292 292 900 4200 350 700 1400
P-930 N 1938 3550 1456 393 739 252 292 869 3110 267 617 1234
P-1000 n.a. 1938 4508 1593 404 739 292 292 918 4200 353 700 1403
P-1050 O 2005 4508 1540 404 806 292 292 900 4200 350 700 1400
P-1080 H 2005 4508 1540 404 806 292 292 900 4200 350 700 1400
P-1170 O 2005 4508 1540 404 806 292 292 900 4200 350 700 1400
P-1240 H 2005 4508 1540 404 806 292 292 900 4200 350 700 1400
P-1290 O 2005 4508 1540 404 806 292 292 900 4200 350 700 1400
P-1350 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1380 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1400 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1550 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1560 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1620 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1720 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
P-1750 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
P-1860 n.a. 2054 4537 1715 404 739 292 350 918 4200 353 764 1525
P-1950 n.a. 2172 4578 1832 404 739 292 400 918 4200 353 823 1642
P-2100 n.a. 2054 5837 1715 404 739 292 350 918 5500 353 764 1525
P-2340 n.a. 2054 5837 1715 404 739 292 350 918 5500 353 764 1525

50 www.euroklimat.it
Technical drawing
DWG “A”
A Evaporator inlet Victaulic DN125 OD141.3
B Evaporator outlet Victaulic DN125 OD141.3
C Condenser inlet Victaulic DN125 OD141.3
D Condenser outlet Victaulic DN125 OD141.3
E Electrical power supply

www.euroklimat.it 51
Technical drawing
DWG “B”
A Evaporator inlet Victaulic DN125 OD141.3
B Evaporator outlet Victaulic DN125 OD141.3
C Condenser inlet Victaulic DN125 OD141.3
D Condenser outlet Victaulic DN125 OD141.3
E Electrical power supply

52 www.euroklimat.it
Technical drawing
DWG “C”
A Evaporator inlet Victaulic DN150 OD168.3
B Evaporator outlet Victaulic DN150 OD168.3
C Condenser inlet Victaulic DN150 OD168.3
D Condenser outlet Victaulic DN150 OD168.3
E Electrical power supply

www.euroklimat.it 53
Technical drawing
DWG “D”
A Evaporator inlet Victaulic DN150 OD168.3
B Evaporator outlet Victaulic DN150 OD168.3
C Condenser inlet Victaulic DN125 OD141.3
D Condenser outlet Victaulic DN125 OD141.3
E Electrical power supply

54 www.euroklimat.it
Technical drawing
DWG “E”
A Evaporator inlet Victaulic DN200 OD216.3
B Evaporator outlet Victaulic DN200 OD216.3
C Condenser inlet Victaulic DN150 OD168.3
D Condenser outlet Victaulic DN150 OD168.3
E Electrical power supply

www.euroklimat.it 55
Technical drawing
DWG “F”
A Evaporator inlet Victaulic DN150 OD168.3
B Evaporator outlet Victaulic DN150 OD168.3
C Condenser inlet Victaulic DN150 OD168.3
D Condenser outlet Victaulic DN150 OD168.3
E Electrical power supply

56 www.euroklimat.it
Technical drawing
DWG “G”
A Evaporator inlet Victaulic DN200 OD216.3
B Evaporator outlet Victaulic DN200 OD216.3
C Condenser inlet Victaulic DN150 OD168.3
D Condenser outlet Victaulic DN150 OD168.3
E Electrical power supply

www.euroklimat.it 57
Technical drawing
DWG “H”
A Evaporator inlet Victaulic DN200 OD216.3
B Evaporator outlet Victaulic DN200 OD216.3
C Condenser inlet Victaulic DN200 OD216.3
D Condenser outlet Victaulic DN200 OD216.3
E Electrical power supply

58 www.euroklimat.it
Technical drawing
DWG “I”
A Evaporator inlet Victaulic DN200 OD216.3
B Evaporator outlet Victaulic DN200 OD216.3
C Condenser inlet Victaulic DN150 OD168.3
D Condenser outlet Victaulic DN150 OD168.3
E Electrical power supply

www.euroklimat.it 59
Technical drawing
DWG “J”
A Evaporator inlet Victaulic DN200 OD216.3
B Evaporator outlet Victaulic DN200 OD216.3
C Condenser inlet Victaulic DN200 OD216.3
D Condenser outlet Victaulic DN200 OD216.3
E Electrical power supply

60 www.euroklimat.it
Technical drawing
DWG “K”
A Evaporator inlet Victaulic DN200 OD216.3
B Evaporator outlet Victaulic DN200 OD216.3
C Condenser inlet Victaulic DN200 OD216.3
D Condenser outlet Victaulic DN200 OD216.3
E Electrical power supply

www.euroklimat.it 61
Technical drawing
DWG “L”
A Evaporator inlet Victaulic DN150 OD168.3
B Evaporator outlet Victaulic DN150 OD168.3
C Condenser inlet Victaulic DN150 OD168.3
D Condenser outlet Victaulic DN150 OD168.3
E Electrical power supply

62 www.euroklimat.it
Technical drawing
DWG “M”
A Evaporator inlet Victaulic DN200 OD216.3
B Evaporator outlet Victaulic DN200 OD216.3
C Condenser inlet Victaulic DN150 OD168.3
D Condenser outlet Victaulic DN150 OD168.3
E Electrical power supply

www.euroklimat.it 63
Technical drawing
DWG “N”
A Evaporator inlet Victaulic DN200 OD216.3
B Evaporator outlet Victaulic DN200 OD216.3
C Condenser inlet Victaulic DN150 OD168.3
D Condenser outlet Victaulic DN150 OD168.3
E Electrical power supply

64 www.euroklimat.it
Technical drawing
DWG “O”
A Evaporator inlet Victaulic DN200 OD216.3
B Evaporator outlet Victaulic DN200 OD216.3
C Condenser inlet Victaulic DN200 OD216.3
D Condenser outlet Victaulic DN200 OD216.3
E Electrical power supply

www.euroklimat.it 65
Standards
Unit
2006/42/CE Machinery Directive
EN ISO 12100 Safety of machinery
EN 378-1 Refrigerating systems and heat pumps. Safety and environmental requirements. Basic requirements, definitions, classification
and selection criteria

Mechanical
2014/68/UE Pressure Equipment Directive

Electrical
2013/35/EU Low Voltage Directive
EN 60204-1 Safety of machinery - Electrical equipment of machines
EN 61439-1 Low-voltage switchgear and controlgear assemblies. General rules

Electromagnetic Compatibility
2014/30/EU EMC Directive
IEC 61000-6-1 Electromagnetic compatibility (EMC) - Immunity for residential, commercial and light industrial environments
IEC 61000-6-2 Electromagnetic compatibility (EMC) - Immunity for industrial environments
IEC 61000-6-3 Electromagnetic compatibility (EMC) – Emission Standard for residential, commercial and light industrial environments
IEC 61000-6-4 Electromagnetic compatibility (EMC) – Emission Standard for industrial environments

Power Quality
EN 50160 Voltage Characteristics of Public Distribution Systems

66 www.euroklimat.it
Notes

www.euroklimat.it 67
The data are indicative and not binding. Euroklimat reserves the right to make changes at any time without notice
99992035 CATALOGO “ZEUS” “ZEUS_12-18_rev0_EN”

EUROKLIMAT SpA Euroklimat Co., Ltd EUROKLIMAT FZCO

Factory Italy Factory China Office Dubai

Via Liguria, 8 Euroklimat Industrial Park, High Bay Office 24, Dubai Silicon Oasis,UAE
27010 Siziano (PV) Italy Huangjiang, Dongguan, Guangdong, China PO Box 28178, Dubai, UAE

T: +39 038 2610282 T +86 0769 8366 0888 ext. 8260 T + 971 4 3423152
E: info@euroklimat.it E: info@euroklimat.it E: info@ek-me.com

www.euroklimat.it www.euroklimat.com.cn www.euroklimatme.com



Вам также может понравиться