Академический Документы
Профессиональный Документы
Культура Документы
FOR
Prepared by:
Job No: PE101
Date: 26th JUNE 2020
CONTENTS
Page 2
1.0 EXECUTIVE SUMMARY
This report is produced based on conducted site visit on 18th and 22nd June
2020. There have been several reports by the occupant regarding the wet floor and/or
water ponding issues in . Previous
report/assessment on the B3 floor recommend the occupant turn on the ventilation
fans in order to reduce the stagnation of air and eliminate the moisture. The reports
suggest that by turning on all the ventilation fans will reduce the wet floor and/or
water ponding issues. As Mechanical & Electrical Professional consultants, we are
called to re-evaluate the overall ventilation system that being installed in the B3 floors
and for what purpose it is supposed to be.
Throughout our studies, our findings show that there was no design fault on
the ventilation design for B3 car park. 4 dual speed fans installed are for mechanical
ventilation and smoke extraction purpose whereas 2 single speed fans installed are for
smoke extraction purpose.
2.0 INTRODUCTION
This report intended to verify the usage of the installed mechanical ventilation
fans in Basement 3 floor. Calculation that’s follow the Malaysian guideline will be
demonstrated in this report to support the verification.
Whilst these documents and drawings may not be immediately useful, they
will be required in the future either for reference, resubmission for approval due to
renovation, or related purposes.
Page 3
4.0 AS-BUILT DRAWINGS
6.0 FINDINGS
Based on our findings, there were a lot of wet floor and/or water ponding
sighted covering most of the B3 floor surfaces. There are 6 numbers of unoperated
fans sighted and 1 stretch of wall located at left wing of the floor layout that opened to
the outside. Another two wall that opened to the outside also founded and it is used as
the carpark entrance and exit located at the right wing of the B3 floor. The walls and
openings were designed to induce the cross ventilation in this B3 floor.
Page 4
TABLE 1: BASEMENT 3 FINDINGS AND DESCRIPTION
Picture Description:
Basement 3 condition, the wet and
dry floor sight.
Picture 1.1
Basement 3 condition, the wet and
dry floor sight.
Picture 1.2
Basement 3 condition, some of the
carpark box have been closed for
some time to prevent the vehicle
bring in the water.
Picture 1.3
Basement 3 condition, water ponding
and dry floor sight.
Picture 1.4
Page 5
7.0 EXISTING VENTILATION SYSTEM
Fans specification:
Fan Tag Fan Speed [cmh] Fan Mode
MV-B1-C-01 44,550 / 68,000 Dual Speed
MV-B1-C-02 44,550 / 68,000 Dual Speed
MV-B1-C-03 44,550 / 68,000 Dual Speed
MV-B1-C-04 44,550 / 68,000 Dual Speed
SFAF-B3-01 34,000 Single Speed
SFAF-B3-02 34,000 Single Speed
Page 6
Picture 7.2 – Exhaust fan (dual speed) specification found on fan body.
4 dual speed fans shall serve as ventilation fans on normal daily routine (low-
speed mode) and serve as Smoke Spill system during the fire mode condition (high-
speed mode).
Another 2 fans are designed for the smoke spill system purposes. Where in fire
mode situation, these fans will operate to pump in the fresh air while the other 4 fans
are extracting the air/smoke out.
Picture 7.3 – Blower (makeup air fans) specification found on fan body.
Page 7
8.0 VENTILATION REQUIREMENT AND CALCULATION
Hence,
The perimeter of wall open to outside is only 90.24 meter, which is 21% of the
total wall perimeter. There are 2 or more sides opened to the outside but the opening
which required at least 50% is not achieved.
Shown from the calculation in sub section 8.1 in this report, this car park opening is
only 21% of total wall perimeter, thus it does not qualify as an open structure car
park, mechanical ventilation is required for ventilation purpose.
With reference to UBBL 1984, Third Schedule (By-Law 41), 7.2 Mechanical
Ventilation system in basement areas. Says that “Basement or underground car parks
shall be provided with mechanical ventilation such that the air exhausted to the external
atmosphere should constitute not less than six air change per hour (6ach).”
This provided exhaust capacity in the development by the 4 fans that found in the
O&M equipment list (Picture 7.1) with 2 mode of fan rate (MV-B1-C-01 to 04).
Page 8
9.0 SMOKE SPILL SYSTEM REQUIREMENT
Since the total parking floor area in this basement is 8730m2 which more than
1000m2, it is required to have smoke purging/dilution system with a rate of 10air
change per hour
Hence, the installed fans with dual mode system sufficient to be used during fire
mode situation.
According to Malaysia UBBL 1984, Third Schedule (By-Law 41), 12. (2) ‘Fresh
air changes’ quote “The minimum scale of fresh air ventilation in conjunction with the
mechanical ventilation system shall be as follow: Basement and garage… … minimum of
6 air changes per hour”.
Hence,
Since the exhaust system is powered exhaust system, while exhaust B3 floor
air, the system will create a negative pressure in the basement, which cause infiltration
of fresh air.
Page 9
Assuming air velocity 0.5m/s and 0.7 of air flow direction diversity, the fresh
air make-up rate for ventilation purpose is as below:
For fresh air intake during fire mode situation, two zones of design are sight in
the B3 as-built drawing. 1st zone is at the left wing side of the as-built drawing and the
2nd zone is at the right wing side of the as-built drawing.
With reference to MS1780:2017 8.2.6 (b) quote “for smoke dilution concept,
replacement air may be introduced at any height but, if powered, shall not be less than
50% and not greater than 75% of the exhaust air volume”
Hence,
Left wing Zone,
Total Purging/Exhuast rate [cmh] = Left wing Volume [m3] x 10ach
= 5180.3m2 x 2.8m (height) x 10ach
= 145,048.4cmh
Assuming air velocity 0.5m/s and 0.7 of air diversity, the fresh air make-up
rate for ventilation purpose is as below:
Page 10
Right wing Zone,
Total Purging/Exhuast rate [cmh] = Left wing Volume [m3] x 10ach
= 3549.7m2 x 2.8m (height) x 10ach
= 99,391.6cmh
Assuming air velocity 0.5m/s and 0.7 of air diversity, the fresh air make-up
rate for ventilation purpose is as below:
Taksifan
Page 11
This section to shows that the blower (make-up fans) which produced sound
level of more than 90dB(A) is advised not to be turned on in daily mode usage. The
fans are located above the parking box where some occupants will park the car under
it and exposed to this level of noise level.
Picture 11.1 – Noise level for the blower (make up fan) running single speed mode (approx. 1m distance
from fan).
Picture 11.2 – Noise level for the blower (make up fan) running single speed mode (approx. 9m distance
from fan).
Meanwhile, the ventilation exhaust fans, in low speed mode condition, the
fans produces about 76dB(A) of noise level, this value considered to be acceptable.
Picture 11.3 – Noise level for the exhaust fan running in Low Speed mode (approx. 1m distance from fan).
Page 12
But in high speed mode, the fans produce 84.5dB(A) of noise level which is
considered as ‘Bising Berlebihan’ as stated in above AKTA KESELAMATAN DAN
KESIHATAN PEKERJAAN 1994. So, it is not advised to turn the high-speed mode
of exhaust fans in daily operation.
Picture 11.4 - Noise level for the exhaust fan running in High Speed mode (approx. 2m distance from fan).
11.0 CONCLUSION
By referring to the
Only 4 numbers of the fans listed below are required be turned on 24 hours
during daily operation at low speed mode:
These fans were tested and it run in noise level of lesser than 82dB(A) during
daily operation not exceeding daily threshold level set in AKTA KESELAMATAN
DAN KESIHATAN PEKERJAAN 1994.
Another 2 blower (makeup fans) shall be operated only in fire mode situation.
These fans had equipped with fire signalling system. These fans will pump in the
fresh air to B3 and at the same time, 4 dual speed fans running in low speed mode will
switch its operation to high-speed mode to in order extract the air/smoke from B3
floor.
These fans running in high speed mode will produce a continuous noise level
of over 82dB(A) which is above the threshold limit set in AKTA KESELAMATAN
DAN KESIHATAN PEKERJAAN 1994. However, this is acceptable in emergency
case.
Page 13
APPENDIXES
Page 14
Appendix 3 : Basement 3 left wing area (strected wall opened to outside)
Page 15
Appendix 5 : Makeup fan specification (sticked on fans body)
Page 16
Appendix 7 : Basement 3 right wing area (entrance & exit ramp staight to outside)
Page 17
Appendix 9 : B3 wet floor condition
Page 18
Appendix 11 : B3 wet floor condition and closed parking boxes
Page 19
Appendix 13 : Exhaust fan located at B1 (blowing air to outside)
Page 20
Appendix 15 : Exhaust fan specification (sticked on fans body)
Page 21
Appendix 16 Legend:
Blower (Makeup Air) Ducting (in Orange) comes with Air Grille (in green)
Exhaust Ducting (in yellow) comes with Air Grille (in pink)