Вы находитесь на странице: 1из 1

7772

1000 Long

450
Foundation Bolt

300

100

100
8mm @ 300 C/C

CONTOUR DRG.

300

300
8mm @ 300mm C/C R.C.C. (M-20)
F.L.

1300
12mm @ 300mm C/C
With 300mm L

FROM G.L. OR

SOIL STRATA
UPTO GOOD
10mm @ 300mm C/C

2000 Min
8 # 12mm Tor
With 150mm L (Bothways) Each Column

1600
R.C.C. (M-20)
R.C.C. RAFT (M-20)

600
P.C.C. (M-10) P.C.C. (1:4:8)

100
2000

300
2000
2900
3100

1400 1400

100
SECTIONAL ELEVATION P.C.C. (1:4:8)
1600 1600

7772
SECTIONAL ELEVATION
2670
600 Long (4 - Nos Each)
1000
485 300 430 300 485 300 430 300

225
485
300

300

2000

2900

3100
430

430

2600

2400

2000
1550

1160

1550
300

300
485

3050

225
1400

PLAN 2000 1600


2900
DETAIL OF 66 KV F.C. GANTRY PLAN
3100
DETAIL OF 66 KV BUS'S'

150
ALL DIMENSIONS ARE IN MILIMETERS.

300
ALL R.C.C. WORK TO BE CARRIED-OUT AS PER IS-456(2000)
F.L.
CONC. MIX M-20 GRADE
CEMENT AS PER IS-8112
TMT-STEEL AS PER I.S. 1786 (Fe-415).
CLEAR COVER TO REINFORCEMENT SHALL BE AS FOLLOWS
C.C. (M-20)
1) FOR RAFT / FOOTING = 50 MM
2) FOR COLUMN = 25 MM

1400
THE DEPTH OF FOUNDATION EXCAVATION SHOWN IS FOR NORMAL SOIL FOUNDATIONS
(CONSIDERING SBC 10T/SQ.M.) SHALL NOT REST ON FILLED UP SOIL.
FOR THE HIGHER SBC 15T/SQ.M. AND 20 T/SQ.M. NO MARGINAL CHANGE IN THE DESIGN
IS NOTICED, HENCE SAME DESIGN IS ADOPTED.
IN CASE OF OTHERS SOIL TYPE AS PER SOIL INVESTIGATION REPORT THE EE (CIVIL) WILL
200 450 200

50
EXAMINE AND OBTAIN THE OPINION OF ENGG. SECTION.
NO OUT SIDE CEMENT PLASTER IS TO BE DONE ON SURFACE OF FOUNDATIONS
THE POSITION OF FOUNDATION BOLTS SHALL BE CHECKED WITH RESPECTIVE
EQUIPMENT, STRUCTURE MANUFACTURER DRAWING.
THE WORK IS TO BE CARRIED OUT AS PER SPECIFICATION AND FIELD QUALITY PLAN.
SECTIONAL ELEVATION ISA 25 X 25 X 6 200 THK.
BLOCK/230 THK

150
@ 1200 C/C

400
DEPTH OF EXCAVATION SHALL BE AS PER THE SOIL INVESTIGATION REPORT. BRICK MASO.
1500

75
450 450
P.C.C. (1:4:8)
END WALL 230 MM THK.

100
230

SECTIONAL ELEVATION

SLIT 2.00 X 0.45 X 0.45 M


SINGLE TIER CABLE TRENCH
FOR RAIL GROUTING
2500

2500

PLAN
66 KV TR PLINTH PLAN

OWNER : ------------- DRG. NO. RPSPL/66KV/FDN-2

REVISION R0 DATE 08/06/2011


PROJECT : --------------
PREPARED NJS APPROVED AGD
EPC CONTRACTORE : RAJESH POWER SERVICES PVT. LTD., SIDDHI HOUSE, OFF CG ROAD, AHMEDABAD
SIGNATURE

REV. DESCRIPTION APP. DATE DRAWING : Standard Drawing for 66KV S/S Switch Yard Foundation
SCALE NOT TO SCALE