Вы находитесь на странице: 1из 2

Customer : PT DEWATA WIBAWA

Date : 2/10/2020

Project : Four Seasons Residence Rev.01

NO DESCRIPTION PRODUCT SPECIFICATION AND DATA


FIRE SPRINKLER SYSTEM

Item / Equipment : Valve


Utilization / System : Sprinkler System
Manufacturer : Viking / Reliable
Type : Alarm Check Valve
Model : Model J-1 / Model E3
Inlet Size : 80 mm / 100 mm /150 mm / 200 mm
Outlet Size : 80 mm / 100 mm /150 mm / 200 mm
Inlet Connection : Groove
Outlet Connection : Groove
Location : Outdoor
Working Pressure : 300 psi (20.7 bar)
Test Pressure 600 psi (41.4 bar)
Nature of Fluid : Water
Material : Ductile Iron
Weight : 9 kg (80 mm)
: 12 kg (100 mm)
23 kg (150 mm)
48 kg (200 mm)
Approval : FM Approved / UL Listed

Item / Equipment : Sprinkler Head


Utilization / System : Sprinkler System
Manufacturer : Viking / Reliable
Type : Quick Response Upright / Upright / Pendent / Side Wall
Model : VK 300 / VK301 /VK310 / F1FR56
Size : 15 mm
Connection Type : Threaded
Bulb Type & Size : Glass / Nominal 3 mm diameter
Bulb Colour : Red
Temperature Rating : 155 °F / 68 °C
Location : Indoor
Working Pressure : 7 psi (0.5 bar) to 175 psi (12 bar)
Test Pressure : 500 psi (34.5 bar)
K-factor : 5.6 (80)
Nature of Fluid : Water
Material : Brass / Chrome
Length : ~ 56 mm
Concealed / Deflector Plate Provided : Yes / No

Page 1 of 2
Customer : PT DEWATA WIBAWA
Date : 2/10/2020

Project : Four Seasons Residence Rev.01

NO DESCRIPTION PRODUCT SPECIFICATION AND DATA


Approval : FM Approved / UL Listed

Page 2 of 2