Вы находитесь на странице: 1из 9

Protection Relays Test Report

Ref. no.: Location: Aqaba-Jordan


Circuit ID: +Y105 Date: 26-Nov-2019

Client:

Prepared Ahmed Rabaa Sign.:


by: Testing & Protection Engineer
Checked by: Sign.:
Table of Contents
7SR11 Protection Relay Test.............................................................................................................3
Over-Current Function Test (51/50).................................................................................................4
Earth Fault Protection Function Test (51N/50N)..............................................................................8
Test Assessment...............................................................................................................................9
7SR11 Protection Relay Test
Test Object - Device Settings
Substation/Bay:
Substation: New Substation-ACT Substation address: Aqaba
Bay: Crane 1 Bay address: +Y105
. . .
Device:
Name/description: O.C & E/F Protection Relay Manufacturer: SEIMENS

Device type: 7SR11 Device address: F01

Serial/model number: 103610701/015 Additional info 1:

Hardware Configuration
Test Equipment
Type Serial Number
CMC356 KD579T

Hardware Check
Performed At Result
11/11/2019 11:51:54 AM Passed
Over-Current Function Test (51/50)
Test Object - Overcurrent Parameters
General - Values:
Time Tol. Abs.: 0.04 s Current Tol. Abs.: 0.05 Iref
Time Tol. Rel.: 5.00 % Current Tol. Rel.: 5.00 %
Directional: No

Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I #1 Phase IEC Normal Inverse 2.5 Iref 0.30 0.95 Non Directional

Test Module
Name: OMICRON Overcurrent Version: 4.00
Test Start: 11-Nov-2019 11:54:38 Test End: 11-Nov-2019 12:00:19
Testing Engineer: Ahmed Rabaa Company: ID-Technical

Test Settings:
Shot Test Results:

Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 I #1 Phase 880.0 m 2.200 A n/a No trip No trip n/a No Passed
L1-L2 I #1 Phase 1.280 3.200 A n/a 8.486 s 8.453 s -0.3931 % No Passed
L1-L2 I #1 Phase 1.480 3.700 A n/a 5.336 s 5.324 s -0.2248 % No Passed
L1-L2 I #1 Phase 1.680 4.200 A n/a 4.027 s 4.023 s -0.08910 % No Passed
L1-L2 I #1 Phase 1.880 4.700 A n/a 3.306 s 3.300 s -0.1773 % No Passed
L1-L2 I #1 Phase 2.080 5.200 A n/a 2.847 s 2.845 s -0.04790 % No Passed
L1-L2 I #1 Phase 2.280 5.700 A n/a 2.527 s 2.521 s -0.2318 % No Passed
L2-L3 I #1 Phase 880.0 m 2.200 A n/a No trip No trip n/a No Passed
L2-L3 I #1 Phase 1.280 3.200 A n/a 8.486 s 8.452 s -0.3990 % No Passed
L2-L3 I #1 Phase 1.480 3.700 A n/a 5.336 s 5.326 s -0.1761 % No Passed
L2-L3 I #1 Phase 1.680 4.200 A n/a 4.027 s 4.026 s -0.01960 % No Passed
L2-L3 I #1 Phase 1.880 4.700 A n/a 3.306 s 3.304 s -0.05630 % No Passed
L2-L3 I #1 Phase 2.080 5.200 A n/a 2.847 s 2.845 s -0.05840 % No Passed
L2-L3 I #1 Phase 2.280 5.700 A n/a 2.527 s 2.535 s 0.3063 % No Passed
L3-L1 I #1 Phase 880.0 m 2.200 A n/a No trip No trip n/a No Passed
L3-L1 I #1 Phase 1.280 3.200 A n/a 8.486 s 8.448 s -0.4462 % No Passed
L3-L1 I #1 Phase 1.480 3.700 A n/a 5.336 s 5.321 s -0.2829 % No Passed
L3-L1 I #1 Phase 1.680 4.200 A n/a 4.027 s 4.021 s -0.1561 % No Passed
L3-L1 I #1 Phase 1.880 4.700 A n/a 3.306 s 3.308 s 0.07070 % No Passed
L3-L1 I #1 Phase 2.080 5.200 A n/a 2.847 s 2.845 s -0.04790 % No Passed
L3-L1 I #1 Phase 2.280 5.700 A n/a 2.527 s 2.526 s -0.04980 % No Passed
L1-L2-L3 I #1 Phase 880.0 m 2.200 A n/a No trip No trip n/a No Passed
L1-L2-L3 I #1 Phase 1.280 3.200 A n/a 8.486 s 8.449 s -0.4344 % No Passed
L1-L2-L3 I #1 Phase 1.480 3.700 A n/a 5.336 s 5.319 s -0.3110 % No Passed
L1-L2-L3 I #1 Phase 1.680 4.200 A n/a 4.027 s 4.022 s -0.1239 % No Passed
L1-L2-L3 I #1 Phase 1.880 4.700 A n/a 3.306 s 3.298 s -0.2288 % No Passed
L1-L2-L3 I #1 Phase 2.080 5.200 A n/a 2.847 s 2.849 s 0.07860 % No Passed
L1-L2-L3 I #1 Phase 2.280 5.700 A n/a 2.527 s 2.523 s -0.1646 % No Passed
L1 I #1 Phase 880.0 m 2.200 A n/a No trip No trip n/a No Passed
L1 I #1 Phase 1.280 3.200 A n/a 8.486 s 8.457 s -0.3448 % No Passed
L1 I #1 Phase 1.480 3.700 A n/a 5.336 s 5.317 s -0.3410 % No Passed
L1 I #1 Phase 1.680 4.200 A n/a 4.027 s 4.020 s -0.1686 % No Passed
L1 I #1 Phase 1.880 4.700 A n/a 3.306 s 3.305 s -0.01100 % No Passed
L1 I #1 Phase 2.080 5.200 A n/a 2.847 s 2.853 s 0.2121 % No Passed
L1 I #1 Phase 2.280 5.700 A n/a 2.527 s 2.527 s -0.02210 % No Passed
L2 I #1 Phase 880.0 m 2.200 A n/a No trip No trip n/a No Passed
L2 I #1 Phase 1.280 3.200 A n/a 8.486 s 8.454 s -0.3707 % No Passed
L2 I #1 Phase 1.480 3.700 A n/a 5.336 s 5.322 s -0.2604 % No Passed
L2 I #1 Phase 1.680 4.200 A n/a 4.027 s 4.026 s -0.02950 % No Passed
L2 I #1 Phase 1.880 4.700 A n/a 3.306 s 3.307 s 0.02530 % No Passed
L2 I #1 Phase 2.080 5.200 A n/a 2.847 s 2.853 s 0.2332 % No Passed
L2 I #1 Phase 2.280 5.700 A n/a 2.527 s 2.528 s 0.03330 % No Passed
L3 I #1 Phase 880.0 m 2.200 A n/a No trip No trip n/a No Passed
L3 I #1 Phase 1.280 3.200 A n/a 8.486 s 8.457 s -0.3460 % No Passed
L3 I #1 Phase 1.480 3.700 A n/a 5.336 s 5.318 s -0.3260 % No Passed
L3 I #1 Phase 1.680 4.200 A n/a 4.027 s 4.021 s -0.1512 % No Passed
L3 I #1 Phase 1.880 4.700 A n/a 3.306 s 3.306 s -0.004900 % No Passed
L3 I #1 Phase 2.080 5.200 A n/a 2.847 s 2.850 s 0.1348 % No Passed
L3 I #1 Phase 2.280 5.700 A n/a 2.527 s 2.528 s 0.04910 % No Passed

Charts for Fault Types:


Type Angle
L1-L2 n/a
t/s

101010101.0Angle
Charts for Fault Types:
Type
3 5 7 1I/A
0 20 30
L2-L3 n/a
t/s

101010101.0Angle
Charts for Fault Types:
Type
3 5 7 1I/A
0 20 30
L3-L1 n/a
t/s

101010101.0Angle
Charts for Fault Types:
Type
3 5 7 1I/A
0 20 30
L1-L2-L3 n/a
t/s

101010101.0Angle
Charts for Fault Types:
Type
3 5 7 1I/A
0 20 30
L1 n/a
t/s

101010101.0Angle
Charts for Fault Types:
Type
3 5 7 1I/A
0 20 30
L2 n/a
t/s

101010101.0 3 5 7 1I/A
0 20 30

Charts for Fault Types:


Type Angle
L3 n/a
t/s

101010101.0
State: 3 5 7 1I/A
0 20 30
49 out of 49 points tested.
49 points passed.
0 points failed.

General Assessment: Test passed!


Earth Fault Protection Function Test (51N/50N)
Test Object - Overcurrent Parameters
General - Values:
Time Tol. Abs.: 0.04 s Current Tol. Abs.: 0.05 Iref
Time Tol. Rel.: 5.00 % Current Tol. Rel.: 5.00 %
Directional: No

Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I #1 Residual IEC Normal Inverse 0.20 Iref 0.20 0.95 Non Directional

Test Module
Name: OMICRON Overcurrent Version: 4.00
Test Start: 11-Nov-2019 12:07:14 Test End: 11-Nov-2019 12:08:13
Testing Engineer: Ahmed Rabaa Company: ID-Technical

Test Settings:
Shot Test Results:

Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-E I #1 Residual 500.0 m 100.0 m A n/a No trip No trip n/a No Passed
L1-E I #1 Residual 1.500 300.0 m A n/a 3.439 s 3.454 s 0.4436 % No Passed
L1-E I #1 Residual 2.500 500.0 m A n/a 1.514 s 1.534 s 1.299 % No Passed
L1-E I #1 Residual 3.500 700.0 m A n/a 1.104 s 1.129 s 2.266 % No Passed
L1-E I #1 Residual 4.500 900.0 m A n/a 916.9 ms 935.4 ms 2.021 % No Passed
L2-E I #1 Residual 500.0 m 100.0 m A n/a No trip No trip n/a No Passed
L2-E I #1 Residual 1.500 300.0 m A n/a 3.439 s 3.454 s 0.4466 % No Passed
L2-E I #1 Residual 2.500 500.0 m A n/a 1.514 s 1.533 s 1.265 % No Passed
L2-E I #1 Residual 3.500 700.0 m A n/a 1.104 s 1.123 s 1.786 % No Passed
L2-E I #1 Residual 4.500 900.0 m A n/a 916.9 ms 935.4 ms 2.021 % No Passed
L3-E I #1 Residual 500.0 m 100.0 m A n/a No trip No trip n/a No Passed
L3-E I #1 Residual 1.500 300.0 m A n/a 3.439 s 3.455 s 0.4698 % No Passed
L3-E I #1 Residual 2.500 500.0 m A n/a 1.514 s 1.539 s 1.682 % No Passed
L3-E I #1 Residual 3.500 700.0 m A n/a 1.104 s 1.128 s 2.176 % No Passed
L3-E I #1 Residual 4.500 900.0 m A n/a 916.9 ms 938.1 ms 2.315 % No Passed

Charts for Fault Types:


Type Angle
L1-E n/a
t/s

101010101.0
State: .10 0.20 0.50 1.00 2.0
I/A
0 5.00 10.00 20.00
15 out of 15 points tested.
15 points passed.
0 points failed.

General Assessment: Test passed!

Test Assessment
All functions were tested successfully and the results were satisfactory and within the
function’s tolerances limits.

Relay test is passed.