Вы находитесь на странице: 1из 2

The True Threat Of A High Corrosion

Problem To A Fire Sprinkler Line


Wall Loss Equals Rust pipe loss is rarely understood or appreciated
It is a correlation often unrecognized, in real world terms. A corrosion rate of 5
but the presence of rust deposits at a pipe MPY is obviously worse that a 2 MPY rate,
surface define that a wall loss has occurred. but to what degree in terms of pipe service
Likewise, an identified wall loss from an life and volume of deposits produced?
ultrasonic examination, defines that iron A low corrosion rate of 1 MPY at a 10 in.
The most critical piping for any building oxide deposits have been produced. One fire sprinkler main, for example, while it
property or plant operation is unquestionably condition cannot exist without the other. would be viewed as acceptable by most
at the fire sprinkler system. authorities, actually translates to an annual
Exactly how much particulate debris
Corrosion problems at tower water, chill remains within the system is generally physical loss of 11 lbs. of steel for every 100
water, steam, or other HVAC and plumbing dependant upon the piping application and linear feet of pipe. At 10 MPY, approxi-
piping may produce a loss of service, incon- any corrective measures applied. mately 107 lbs. of metal is lost.
venience, property damage, shutdown, and Multiplied by the number of years in
An open tower or condenser water line,
even millions of dollars in monetary losses, service and its overall length, and the true
for example, will produce the same volume
but the failure of a fire sprinkler line always magnitude of pipe corrosion takes on much
of deposits for the same MPY corrosion rate
threatens the loss of human life. greater significance than when reported as
as a closed chill pipe of the same size.
Often considered trouble free, corrosion However, a substantial volume is washed simply 1, 2, or 5 mils per year.
related failures at fire sprinkler lines have out of the system during blowdown, filtration, The below table illustrates just how
greatly increased over the past decade - and through regular maintenance. For open much steel is lost at various corrosion rates
raising not only operating and repair costs, systems, the presence of rust in the tower and for various pipe sizes, and is applicable
but the threat to building inhabitants as well. pans, strainers, and chillers, etc. is often the for any piping system.
No Protection Provided first sign of a corrosion problem.
Deposits The Real Threat
Unlike most HVAC and industrial Closed circulating systems typically
But while even a 5 MPY loss of metal
cooling applications, no chemical corrosion hold their deposits unless regularly flushed,
can be tolerated by many piping systems for
protection is provided to the steel pipe which or unless side stream filtration is provided.
an extended period of time before resulting
carries nearly all fire service water. This is Rarely opened for visual inspection, a loss of
in a leak, it is the deposits created, and their
because traditionally, corrosion problems heat transfer efficiency is often the first clue
eventual deposition and effect, that will
have not been a significant concern. It is that an internal deposit problem exists.
inevitably produce far more serious and long
also due to the virtual impossibility of But fire sprinkler systems provide a flow term secondary problems.
providing effective chemical protection. of water in only one direction to multiple dead
Steel, when corroded back into iron
Up until 10-15 years ago, it was almost end branch lines, and lack the benefit of
oxide, produces a significantly greater
unheard of for fire sprinkler pipe to fail, or to circulation to move either cleaners or debris
volume of less dense material by a factor of
learn of sprinkler pipe in need of replacement laden water to a drain or into a filter for
approximately 18-20 times. Such deposits,
due to corrosion effects. disposal. All iron oxide deposits, therefore,
in turn, ultimately create a substantial loss of
are usually held captive within the piping.
This prior lack of concern has changed in heat transfer efficiency, constricted flow, and
recent years due to the combined use of thin- While flushing a fire sprinkler system under deposit pitting and wall loss.
ner gauge pipe, seemingly more corrosion might show a limited benefit in removing
At a low corrosion rate of 1 MPY for an
susceptible steel, to a higher frequency of some loose rust material over a limited range
office building having 40 floors of 24 in. chill
drain downs, testing, and modifications to fire of piping, it will not likely remove those
water piping, 242 lbs. of steel will be lost for
protection systems, and to greater overall heavier deposits under which the highest
each year of service at just the risers alone.
microbiological activity. corrosion and pitting activity always exists.
In its less dense form of iron oxide, however,
Corrosion rates which once could be The True Meaning Of MPY this same amount of steel is converted into a
expected to range below 0.5 mils per year Minimizing the actual threat of many volume of 10 cubic feet. (See back table)
(MPY) for fire sprinkler lines two decades corrosion problems is the misconception of After 20 years, and where no chemical
ago, are now often measured at 5 mils per exactly what mils per year (MPY) means in cleaning or filtration had been provided, it
year and above. terms of wall loss. Different authorities may would be easily possible to accumulate 200
Numerous Initiating Causes provide recommended acceptable wall loss cubic feet of rust deposits at points within the
estimates in MPY, but the true impact of that system - often at heat transfer surfaces.
Many different factors can lead to a
corrosion problem at a fire sprinkler line.
Absent or improper chemical clean-out prior
to beginning service may leave rust, metal
filings, mill scale, varnishes, iron oxide
particulates, and foreign matter behind to
produce severe problems years later.
The failure to disinfect the pipe of micro
organisms, combined with nutrients from any
remaining organic and particulate debris,
can easily lead to an MIC condition.
A fire sprinkler system bringing in new,
fresh and oxygenated water on a regular
basis is virtually guaranteed to initiate severe
corrosion problems. A frequently running
jockey pump or make-up water meter, or
pipe which is cold and sweating, are two sure
signs of a leak or other flow problem.
per linear foot has now been removed from
the pipe, and placed into its interior in the
form of less dense iron oxide particulates.
For a 600 ft. main sprinkler feed, it is
easy to estimate that 2,500 lbs. of rust would
now exists in some proportion of hardened
deposits or tubercles attached to the pipe’s
interior wall, and the rest as loose sediment
and mud along the bottom.
This material accumulates with time,
ultimately to the point where the pipe wall
finally fails and brings attention to the prob-
lem, or to when a fire occurs.
In a very possible worse case scenario,
this loose rust and mud will be dislodged by
the shocking action of the fire pump starting
up in response to a fire call. With perhaps
dards. For higher pressure applications thousands of pounds of loose material
Key Factors For Failure suddenly rushing downstream toward the
having a higher minimum acceptable thick-
It is important to recognize that all fire’s location, the potential to block closed
ness limit, schedule 10 pipe will provide
carbon steel pipe will corrode to some any control or preaction valves, reducers,
service only assuming that virtually no corro-
degree. Even when chemically protected, tees, small diameter distribution lines, or fire
sion will take place - a known impossibility.
pipe corrosion can only be minimized, never sprinkler heads is tremendous.
stopped. Threat Varies Per Application Such an actual event, whereby the fire
With the application of chemical corro- The ultimate impact of internal deposits, sprinkler lines have been found totally
sion inhibitors generally not feasible for fire similar to wall loss itself, is greatly dependent clogged with rust and mud in a fire emergen-
sprinkler service, the rate of its inevitable upon the piping system involved. Deposits cy, has actually occurred in previous
deterioration becomes generally dependent produced at an open piping system will be instances - leaving those involved without
upon certain fixed parameters. observed quickly and be likely addressed, the fire protection they believed existed.
Of first importance is the amount of while a closed system will instead conceal is
fresh water entering the pipe - with highest problem until a heat transfer loss, leak, or MIC And Other Causes
corrosion rates consistently found where some other operating problem is realized. Such severe corrosion problems have
water flow is the greatest, such as at the inlet. But corrosion at a fire sprinkler system been commonly attributed to microbiologi-
A second critical factor is pipe schedule. is often totally concealed from view, and may cally influenced corrosion, or MIC. But while
At any given corrosion rate, the service life of remain unrecognized for years. No external MIC may exist as the foremost cause, the end
a pipe before failure is directly dependant signs or indicators normally exist to suggest product of MIC and the source of sprinkler
upon its initial wall thickness. a corrosion problem prior to a leak occurring failures, rust deposits, can be produced by
- at which time the major damage, often various other corrosion mechanisms.
For this reason alone, far more sprinkler
failures occur today due to the common use irrevocable, has already taken place. Common to all problems, however, is the
of thin wall schedule 10 pipe. Schedule 10 Ultrasound, which is unquestionably the infiltration of fresh water into the system. If
offers savings on material, time, and installa- most cost-effective nondestructive technol- filled and left stagnant, a small amount of
tion costs, but at the trade-off of severely ogy available to detect a corrosion problem rusting occurs, the oxygen content is deplet-
reduced service life. in pipe, is rarely used as a preventative tool ed, and corrosion almost ceases.
in evaluating fire sprinkler systems.
Whereas extra strong schedule 80 In contrast, the constant renovation and
would have been typically installed 50-75 In most cases, the concern raised due upgrading of newer properties itself pro-
years ago for fire service, lighter schedule 40 to a leak at fire sprinkler pipe is more motes fire sprinkler problems - as every
has been used since around the mid 1960's. directed to the potential for water damage or draining and refilling introduces into the pipe
cost of replacement, rather than whether the new oxygen, biological sources, as well as
Over the past 20 years, this thin wall
pipe will provide the necessary water flow the nutrients they need to thrive.
schedule 40 fire pipe has been frequently
during a fire emergency. And yet the latter,
replaced with even thinner schedule 10 - Ironically, one of the root causes of the
by far, presents the greatest threat.
leaving very little available pipe wall to greater fire sprinkler problems seen today is
corrode before reaching minimum accept- Potential System Failure mandated procedures to ensure their proper
able thickness limits and inevitable failure. In fact, years of corrosion activity can operation in the first place. Each required test
The below comparison of 8 in. ASTM easily produce thousands of pounds of of a fire protection system introduces new
A53 black pipe shows the representative debris capable of being dislodged from the fresh water to produce further deterioration.
amount of available wall thickness that shock of a fire pump kicking in, and then With so many forces acting against mod-
would be available to corrode at a sprinkler forced downstream into the critical actuating ern fire sprinkler systems, and few protective
line installed decades ago using schedule valves, and ultimately - the sprinkler heads. measures available, better corrosion moni-
80, as opposed to most new installations At that point, all the fire fighting equip- toring becomes the only means to ensure that
today using schedule 10. ment, command and controls, sensing, plan- water will be available when a fire emergency
Schedule 80 Schedule 40 Schedule 10 ning, inspection, and emergency training exists.
suddenly becomes worthless if water cannot
be supplied to the source of the fire.
0.188 in. The potential for such a catastrophe is
0.322 in. easily demonstrated.
A 25% wall loss at an 8 in. schedule 10 CorrView International, LLC
0.500 in. P.O. Box 8513 * Landing, NJ 07850
sprinkler main, for example, is still not likely
Under the clearly greater overall corro- to produce any notice in the form of a leak or Tel: 973.770.7764
sion threat which exists today, only 0.088 in. failure. Yet, that same 25% loss of steel from Bill Duncan, CVI
exists to corrode before this schedule 10 www.CorrView.com
pipe which weighed a factory new 17 lbs. per
Info@CorrView.com
pipe will reach minimum acceptable stan- linear foot, also means that 4.25 lbs. of steel

Вам также может понравиться