Moulded case circuit
breakers (MCCB)
202 Chassis
—
For more detailed product information, please refer to the Technical Catalogue:
• Tmax XT – 1SDC210033D0204
• Tmax T – 1SDC210015D0208
178 A B B E L E C T R I F I C AT I O N P R O D U C T S A U S T R A L I A A N D N E W Z E A L A N D
—
Technical data
Moulded case circuit breakers XT
XT1
Size [A] 160
Poles [No.] 3, 4
Rated service voltage, Ue (AC) 50-60Hz [V] 690
(DC) [V] 500
Rated insulation voltage, Ui [V] 800
Rated impulse withstand voltage, Uimp [kV] 8
Versions Fixed, Plug-in(2)
Breaking capacities according to IEC 60947-2 B C N S H
Rated ultimate short-circuit breaking capacity, Icu
Icu @ 220-230-240V 50-60Hz (AC) [kA] 25 40 65 85 100
Icu @ 380V 50-60Hz (AC) [kA] 18 25 36 50 70
Icu @ 415V 50-60Hz (AC) [kA] 18 25 36 50 70
Icu @ 440V 50-60Hz (AC) [kA] 15 25 36 50 65
Icu @ 500V 50-60Hz (AC) [kA] 8 18 30 36 50
Icu @ 525V 50-60Hz (AC) [kA] 6 8 22 35 35
Icu @ 690V 50-60Hz (AC) [kA] 3 4 6 8 10
Icu @ 250V (DC) 2 poles in series [kA] 18 25 36 50 70
Icu @ 500V (DC) 2 poles in series [kA] – – – – –
Icu @ 500V (DC) 3 poles in series(3) [kA] 18 25 36 50 70
Rated service short-circuit breaking capacity, Ics
Ics @ 220-230-240V 50-60Hz (AC) [kA] 100% 100% 75% (50) 75% 75%
Ics @ 380V 50-60Hz (AC) [kA] 100% 100% 100% 100% 75%
Ics @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 75% 50% (37.5)
Ics @ 440V 50-60Hz (AC) [kA] 75% 50% 50% 50% 50%
Ics @ 500V 50-60Hz (AC) [kA] 100% 50% 50% 50% 50%
Ics @ 525V 50-60Hz (AC) [kA] 100% 100% 50% 50% 50%
Ics @ 690V 50-60Hz (AC) [kA] 100% 100% 75% 50% 50%
Ics @ 250V (DC) 2 poles in series [kA] 100% 100% 100% 100% 75%
Ics @ 500V (DC) 2 poles in series [kA] – – – – –
Ics @ 500V (DC) 3 poles in series(3) [kA] 100% 100% 100% 100% 75%
Rated short-circuit making capacity, Icm
Icm @ 220-230-240V 50-60Hz (AC) [kA] 52.5 84 143 187 220
Icm @ 380V 50-60Hz (AC) [kA] 36 52.5 75.6 105 154
Icm @ 415V 50-60Hz (AC) [kA] 36 52.5 75.6 105 154
Icm @ 440V 50-60Hz (AC) [kA] 30 52.5 75.6 105 143
Icm @ 500V 50-60Hz (AC) [kA] 13.6 36 63 75,6 105
Icm @ 525V 50-60Hz (AC) [kA] 9.18 13.6 46.2 73.5 73.5
Icm @ 690V 50-60Hz (AC) [kA] 4.26 5.88 9.18 13.6 17
Breaking capacities according to NEMA-AB1
@ 240V 50-60Hz (AC) [kA] 25 40 65 85 100
@ 480V 50-60Hz (AC) [kA] 8 18 30 36 65
Utilisation Category (IEC 60947-2) A
Reference Standard IEC 60947-2
Isolation behaviour ✔
Mounted on DIN rail DIN EN 50022
Mechanical life [No. Operations] 25000
[No. Hourly operations] 240
Electrical life @ 415 V (AC) [No. Operations] 8000
[No. Hourly operations] 120
3 poles [mm] 76.2 x 70 x 130
Dimensions - Fixed H
(Width x Depth x Height)
4 poles [mm] 101.6 x 70 x 130
D W
1) 90kA@690V only for XT4 160. 2) XT1 plug-in In max=125A 3) XT1 500V DC 4 poles in series 4) XT4 750V DC please ask
Available shortly, please ask ABB ABB for availability
POWER DISTRIBUTION MOULDED C A SE CIRCUIT BRE AKERS 179
100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% (27) 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% (27) 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
100% 100% 100% 100% 75% 75% 50% 100% 100% 100% 100% 75% (20)
100% 100% 100% 100% 100% 100% 75% 100% 100% 100% 100% 100%
– – – – – – – 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 100% 75% 100% 100% 100% 100% 100%
143 187 220 330 440 105 187 143 187 220 330 440
75.6 105 154 264 330 75.6 105 75.6 105 154 264 330
75.6 105 154 264 330 75.6 105 75.6 105 154 264 330
75.6 105 143 220 330 52.5 84 75.6 105 143 220 330
63 75.6 105 132 154 40 63 63 75.6 105 132 154
40 52.5 63 75.6 105 26 40 40 52.5 94.5 105 105
17 24 30 36 40 7.65 13.6 17 24 30 40 52.5
15 15 15
15 15 15
■ ■
■
■ ■
■ ■
■ ■
■ ■
■
■ ■ ■
■
▲ ▲
▲ ▲
■ ■
▲ ▲
▲ ▲
✔ ✔
1.2 / 1.6 1.7 / 2.1 2.5 / 3.5
2.54 / 3.27 3.24 / 4.1 4.19 / 5.52
3.32 / 4.04 5 / 6.76
■ Complete circuit-breaker
▲ Loose trip unit
180 A B B E L E C T R I F I C AT I O N P R O D U C T S A U S T R A L I A A N D N E W Z E A L A N D
—
Circuit breakers for power distribution
Electrical characteristics
Tmax T4 Tmax T5
Rated uninterrupted current [A] 320 400/630
Poles [No.] 3/4 3/4
Rated service voltage, Ue (AC) 50-60 Hz [V] 690 690
(DC) [V] 750 750
Rated impulse withstand voltage, Uimp [kV] 8 8
Rated insulation voltage, Ui [V] 1000 1000
Test voltage at industrial frequency for 1 min. [V] 3500 3500
Rated ultimate short-circuit breaking capacity,
N S H L V N S H L V
Icu
(AC) 50-60 Hz 220/230 V [kA] 70 85 100 200 200 70 85 100 200 200
(AC) 50-60 Hz 380/400/415 V [kA] 36 50 70 120 200 36 50 70 120 200
(AC) 50-60 Hz 440 V [kA] 30 40 65 100 180 30 40 65 100 180
(AC) 50-60 Hz 500 V [kA] 25 30 50 85 150 25 30 50 85 150
(AC) 50-60 Hz 690 V [kA] 20 25 40 70 80 20 25 40 70 80
(DC) 250 V - 2 poles in series [kA] 36 50 70 100 150 36 50 70 100 150
(DC) 250 V - 3 poles in series [kA] – – – – – – – – – –
(DC) 500 V - 2 poles in series [kA] 25 36 50 70 100 25 36 50 70 100
(DC) 500 V - 3 poles in series [kA] – – – – – – – – – –
(DC) 750 V - 3 poles in series [kA] 16 25 36 50 70 16 25 36 50 70
Rated service short-circuit breaking capacity, Ics
(AC) 50-60 Hz 220/230 V [%Icu] 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
(AC) 50-60 Hz 380/400/415 V [%Icu] 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
(AC) 50-60 Hz 440 V [%Icu] 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
(AC) 50-60 Hz 500 V [%Icu] 100% 100% 100% 100% 100% 100% 100% 100% 100% (1) 100%(2)
(AC) 50-60 Hz 690 V [%Icu] 100% 100% 100% 100% 100% 100% 100% 100%(1) 100% (2) 100%(2)
Rated short-circuit making capacity, Icm
(AC) 50-60 Hz 220/230 V [kA] 154 187 220 440 660 154 187 220 440 660
(AC) 50-60 Hz 380/400/415 V [kA] 75.6 105 154 264 440 75.6 105 154 264 440
(AC) 50-60 Hz 440 V [kA] 63 84 143 220 396 63 84 143 220 396
(AC) 50-60 Hz 500 V [kA] 52.5 63 105 187 330 52.5 63 105 187 330
(AC) 50-60 Hz 690 V [kA] 40 52.5 84 154 176 40 52.5 84 154 176
Opening time (415 V) [ms] 5 5 5 5 5 6 6 6 6 6
Utilisation category (IEC 60947-2) A B (400 A)(3) - A (630 A)
Reference Standard IEC 60947-2 IEC 60947-2
Isolation behaviour ■ ■
Trip units: thermomagnetic
T fixed, M fixed TMF – –
T adjustable, M adjustable (5…10 x In) TMA – ■ (up to 500 A)
T adjustable, M fixed (3 x In) TMG – –
T adjustable, M adjustable (2.5…5 x In) TMG – ■ (up to 500 A)
magnetic only MA ■ –
electronic PR221DS ■ ■
PR221GP/PR221MP – –
PR222DS ■ ■
PR223DS ■ ■
PR231/P – –
PR232/P – –
PR331/P – –
PR332/P – –
Interchangeability ■ ■
Versions F-P-W F-P-W
Terminals fixed F-FC Cu-FC CuAl-EF-ES-R-MC F-FC CuAl-EF-ES-R-RC
plug-in EF-ES-HR-VR-FC Cu-FC CuAl EF-ES-HR-VR-FC Cu-FC CuAl
withdrawable EF-ES-HR-VR-FC Cu-FC CuAl EF-ES-HR-VR-FC Cu-FC CuAl
Fixing on DIN rail – –
Mechanical life [No. operations] 20000 20000
[No. Hourly operations] 240 120
Electrical life @ 415 V AC [No. operations] 6000 (320 A) 7000 (400 A) - 5000 (630 A)
Terminal Caption
Tmax T6(9) Tmax T7(10) Tmax T8 F: Front
630/800/1000 800/1000/1250/1600 2000/2500/3200 EF: Front extended
3/4 3/4 3/4 ES: Front extended spread
690 690 690 FC Cu: Front for copper cables
FC CuAl: Front for copper-aluminium
750 – –
cables
8 8 12 R: Rear orientated
1000 1000 1000 HR: Rear flat horizontal
3500 3500 3500 VR: Rear flat vertical
HR/VR: Rear flat orientated
N S H L S H L V(6) L V MC: Multicable
F: Fixed circuit-breakers
70 85 100 200 85 100 200 200 85 130 P: Plug-in circuit-breakers
36 50 70 100 50 70 120 150 85 130 W: Withdrawable circuit-
30 45 50 80 50 65 100 130 85 130 breakers
25 35 50 65 40 50 85 100 65 100 *:The breaking capacity
for settings
20 22 25 30 30 42 50 60 50 80
In = 16 A and
36 50 70 100 – – – – – – In = 20 A is 16 kA
– – – – – – – – – –
20 35 50 65 – – – – – – 1) 75% for T5 630
– – – – – – – – – – 2) 50% for T5 630
3) Icw = 5 kA
16 20 36 50 – – – – – –
4) W version is not available on T6
1000 A
100% 100% 100% 75% 100% 100% 100% 100% 100% 75% 5) Icw = 7.6 kA (630 A) - 10 kA (800 A)
100% 100% 100% 75% 100% 100% 100% 100% 100% 75% 6) Only for T7 800/1000/1250 A
7) Icw = 20 kA (S,H,L versions) – 15 kA
100% 100% 100% 75% 100% 100% 100% 100% 100% 75%
(V version)
100% 100% 100% 75% 100% 100% 75% 100% 100% 75% 8) For availability,
75% 75% 75% 75% 100% 75% 75% 75% 100% 75% please contact ABB
9) For T6V version,
154 187 220 440 187 220 440 440 187 286 please contact ABB
10) For T7V version,
75.6 105 154 220 105 154 264 330 187 286
please contact ABB
63 94.5 105 176 105 143 220 286 187 286 11) On T8 3200 A only VR terminals are
52.5 73.5 105 143 84 105 187 220 143 220 available
40 46 52.5 63 63 88.2 105 132 105 176
Notes:
10 9 8 7 15 10 8 8 30
In the plug-in version T5 630 and in the
B (630A - 800A)(5) - A (1000A) B (7) B (lcw = 40 kA) withdrawable version of T5 630 the
IEC 60947-2 IEC 60947-2 IEC 60947-2 maximum rated current available is
■ ■ ■ derated by 10% at 40 °C
– – –
■ (up to 800 A)(4) – –
– – –
– – –
– – –
■ – –
– – –
■ – –
■ – –
– ■ –
– ■ ■ PR232/P-T8
– ■ ■
– ■ ■
■ ■ ■
F-W(4) F-W F
F-FC CuAl-EF-ES-R-RC F-EF-ES-FC CuAl-HR/VR F-HR/VR-ES-VR(11)
– – –
EF-HR-VR EF-HR/VR-RS-ES –
– – –
20000 10000 15000
120 60 60
4500 (2000A) - 4000
7000 (630A) - 5000 (800A) - 2000 (S, H, L versions) / 3000
(2500A ) -
4000 (1000A) (V version)
3000 (3200A)
60 60 20
210 210 427
280 280 553
103.5 154 (manual) /178 (motorizable) 282
268 268 382
73/95 (2000-2500A) -
9.5/12 9.7/12.5 (manual) - 11/14 (motorizable)
107/140 (3200A)
– – –
12.1/15.1 29.7/39.6 (manual) - 32/42.6 (motorizable) –
182 A B B E L E C T R I F I C AT I O N P R O D U C T S A U S T R A L I A A N D N E W Z E A L A N D
—
Moulded case circuit breakers
Circuit breakers
—
MCCB for power distribution
3 and 4 Poles
Available XT versions fitted with TMD trip unit for In from 1.6A to 12.5A, please contact ABB.
Available versions up to Icu=200kA, please contact ABB.
—
Moulded case circuit breakers
Circuit breakers
T7 circuit breaker
T7S Manual PR232/P LSI 1SDA062995R1 1SDA063003R1
T7S M Motorizable PR231/P LS/I 1SDA063010R1 1SDA063018R1
T7S M Motorizable PR232/P LSI 1SDA063011R1 1SDA063019R1
—
Moulded case circuit breakers
Circuit breakers
—
Moulded case circuit breakers
Circuit breakers
—
MCCB with embedded energy measurement and communication
Available from 0.2 x In in Vaux mode and starting from 0.5 x In in self supply mode; external
current or voltage transformers are not required.
Measuring:
• Currents
-- three phases (L1, L2, L3),
-- neutral (Ne)
XT4 circuit breaker
-- earth fault
-- accuracy: Class 1
• Voltage: phase-phase, phase-neutral
• Power: active, reactive and apparent
• Power factor
• Frequency and peak factor
• Energy: active, reactive, apparent, counter
—
Moulded case switch-disconnectors
3 and 4 Poles
—
Moulded case circuit breakers
Circuit breakers
—
MCCB for motor protection
3 Poles – conventional system
Circuit-breaker A conventional system with three poles a circuit-breaker equipped with a magnetic only
with magnetic trip unit for protection against short-circuits, a thermal relay for protection against
only trip unit
overloads and phase failure or imbalance, and a contactor to operate the motor
Available from 1A to 8A and from 400A to 1600A, please contact ABB.
Available versions up to Icu=200kA, please contact ABB.
Contactor
Icu In Tmax Trip unit Order code
415V A type version
kA 3 poles
Thermal relay
50 20 XT2S MA 1SDA067765R1
52 XT2S MA 1SDA067767R1
100 XT2S MA 1SDA067769R1
200 XT3S MA 1SDA068282R1
250 XT4S Ekip I 1SDA068480R1
Motor
70 320 T4H PR221DS I 1SDA054134R1
400 T5H PR221DS I 1SDA054351R1
Conventional system
—
MCCB for motor protection
3 Poles – advanced protection system
Circuit-breaker An advanced protection system which integrates all the protection and monitoring
with electronic functions and a contractor for operating the motor, in the circuit-breaker itself.
trip unit
Ekip M-LRIU
—
Loose trip units XT2
—
Moulded case circuit breakers
Circuit breakers
—
MCCB for generator protection
—
Loose trip units XT4
These trip units have been designed and made so as to provide a solution for protecting
small generators and distribution networks with very long cables (slight end of line fault
current owing to the high cable impedance).
Generator protection requires a low magnetic threshold, typically about three times circuit-
breaker’s rated current, so as to ‘cut’ the short-circuit current in the ‘transient’ zone of the
decrement curve of the generator fault current.
XT4 circuit breaker
Icu In Tmax Trip unit Order code
415V A type version
kA 3 poles 4 poles
Only trip unit 250 XT4 Ekip G-LS/I 1SDA068042R1 1SDA068047R1
Note:
Several different factors must be considered when choosing and coordinating the protection and operating devices, e.g.:
1) the electrical specifications of the motor (type, power rating, efficiency, cos phi);
2) the starting type and diagram;
3) the fault current and voltage in the part of the network where the motor is installed.
t [s]
10
synchronous
phase
transient
phase
10-1
10-2
sub transient
phase
1SDC21092EF0001
10-3
1 10 10 2
x I1
188 A B B E L E C T R I F I C AT I O N P R O D U C T S A U S T R A L I A A N D N E W Z E A L A N D
—
Moulded case circuit breakers
Conversion kits
—
Plug-in, fixed part
Fixed part supplied with Frontal Extended terminals (EF). Other terminal combinations
available, please contact ABB.
Available 4 pole versions, please contact ABB.
Ê
Tmax fixed circuit breaker
Ê
Conversion kit
—
Moulded case circuit breakers
Conversion kits
—
Withdrawable, fixed part
Fixed part supplied with Frontal Extended terminals (EF). Other terminal combinations
available, please contact ABB.
Ê
Tmax fixed circuit breaker
Ê
Conversion kit
Ê
FLD (Front for lever operating mechanism) or RH_ (Rotary handle) or MOE (Motor)
190 A B B E L E C T R I F I C AT I O N P R O D U C T S A U S T R A L I A A N D N E W Z E A L A N D
—
Moulded case circuit breakers
Conversion kits
—
Withdrawable, fixed part
Ê
Moulded case circuit breaker, fixed version
Ê
Conversion kit
Suitable Order code
type 3 poles 4 poles
T7-T7M 1SDA062162R1 1SDA062163R1
ÊÊ
Sliding contacts
—
Moving part
Standard delivery on fitted accessories.
—
Fixed part
Standard delivery on fitted accessories
—
Which block is necessary for every accessory?
—
Moulded case circuit breakers
Electrical accessories
RC Inst
Trip threshold adjustment: I∆n = 0,03 – 0,1 – 0,3 – 0,5 – 1 – 3A
t = Inst
RC Sel
Trip threshold adjustment: I∆n = 0,03 – 0,05 – 0,1 – 0,3 – 0,5 – 1 – 3 – 5 – 10A
t = 0,1 – 0,2 – 0,3 – 0,5 – 1 – 2 – 3s
RC222
Trip threshold adjustment: I∆n = 0,03 – 0,05 – 0,1 – 0,3 – 0,5 – 1 – 3 – 5 – 10A
t = Inst – 0,1 – 0,2 – 0,3 – 0,5 – 1 – 2 – 3
—
Shunt open release – SOR
Uncabled versions.
—
Shunt closing release – SCR
Uncabled versions.
—
Moulded case circuit breakers
Electrical accessories
—
Undervoltage release – UVR
Uncabled versions.
—
Auxiliary contacts – AUX
Q, open/closed: indication of the position of the circuit-breaker power contacts.
SY, trip: signalling CB opening due to current release tripping (owing to overload or short-
circuit), residual current device, the opening or undervoltage releases, the emergency push
button of the motor, or owing to use of the test button.
Uncabled versions.
—
Auxiliary contact for signaling trip coil release trip – S51
S51, trip unit tripping: indicates that one of the trip unit protection functions has tripped.
Uncabled versions. 250V AC versions.
—
Moulded case circuit breakers
Mechanical accessories
—
Motor operator – MOD / MOE
Motor is not compatible with 2Q+1SY on XT1, but allows 1Q+1SY.
Motor is not compatible with 3Q+1SY on XT3, but allows 2Q+1SY.
—
Rotary direct handle operating mechanism – RHD
Available for fixed or plug-in versions.
—
Moulded case circuit breakers
Mechanical accessories
—
Rotary transmitted handle operating mechanism - RHE
Available for Fixed or Plug-in versions. T7 part number is available for Withdrawal and Fixed
versions. Shaft length = 500mm.
—
IP54 Protection for transmitted rotary handle (RHE)
—
Transparent protection for buttons
—
IP54 Door protection
—
Padlock lever lock – PLL
PLL for T4…T6 not available.
—
Moulded case circuit breakers
Mechanical accessories
—
Key lock for frontal accessory (FLD) or rotary handle – KLF
—
Front lever operating mechanism – FLD
—
Key lock on the motor – MOL-M
—
Mechanical interlock – MIR
—
Mechanical interlock – MIR
—
Mechanical interlock with cables between T7/T7M and T7/T7M
—
Moulded case circuit breakers
Mechanical accessories
—
Terminals
EF and ES versions include phase barrier separators as standard.
R versions includes LTC terminal shrouds as standard.
To add terminals to both sides of the MCCB, the same part number should be ordered twice.
—
Moulded case circuit breakers
Mechanical accessories
—
Bracket for fixing onto DIN rail
—
Terminal shrouds
Standard supply comes as a pair.
• LTC: Low size terminal shroud
• HTC: High size terminal shroud
—
Phase barriers separators – PB
4 pieces suitable for 3 pole versions.
6 pieces suitable for 4 pole versions.
—
Accessories for electronic trip units
Terminal type Description Order code
XT2 and XT4 For fixed or plug-in circuit breaker 1SDA068661R1
Ekip Com for Withdrawable 1SDA068662R1
For fixed or plug-in circuit breaker 1SDA068660R1
For fixed or plug-in circuit breaker 1SDA068659R1
198 A B B E L E C T R I F I C AT I O N P R O D U C T S A U S T R A L I A A N D N E W Z E A L A N D
—
Moulded case circuit breakers
Mechanical accessories
—
Test and configuration unit
Ekip T&P allows you to perform trip test simulations, configure circuit breaker settings and
download reports with ABB software Ekip Connect.
—
Interface screen on the front of the switchgear – HMI030
—
Connectors for PR222DS or PR223DS trip units – X3/X4
—
Measurement module for PR223DS or PR223EF – VM210
—
Moulded case circuit breakers
Basic transfer switches (BTS)
What is a BTS?
A basic transfer switch (BTS) consists of two circuit breakers assembled on a backplate, which are mechanically interlocked
and equipped with motor operators that allows remote or manual operation.
ÊÊ
Mechanical Interlock
BTS
ÊÊ
Auxiliaries to signal operation
BTS is designed to work as a standard
transfer switch. However, it can also be
FRONT VIEW
BTW is designed to work as a standard transfer switch However, it can also be updated to work as a smart unit capable of
automatically transferring the supply of a load. To do this it is necessary to add an ATS controller and a Loom kit (that
consists of required devices) to operate the BTS.
Automatic BTS
Transfer ÊÊ
ATS controller
Supply ÊÊ
Loom Kit
29 39 1 2 3 4 5 6 7 8 9 10 11 12 13 14 E E
15 16 17 18 19 20 21 22 23 24 25 26 27 28
FRONT VIEW
BTS ATS Controller Loom Kit
—
ATS022 controller
—
Loom kit
—
Moulded case circuit breakers
Basic transfer switches (BTS)
—
Moulded case circuit breakers
Other chassis combinations
—
Chassis codification
Variables C X X X X X X X
Comment
up to 1250 A C 1250 A version: Maximum 24 circuit breakers
up to 1600 A D 1600 A version: Maximum 24 circuit breakers
Number of Circuit One circuit breaker (on T6 1600 A and T5 on 1250 A) L
Breakers
One circuit breaker (on T6 1600 A and T5 on 1250 A) R
Two circuit breakers 2
Three circuit breakers 4
…
Twenty third circuit breakers 22
Twenty forth circuit breakers 24
Circuit Breaker Model Tmax XT1 X1 Suitable for 800 A chassis
Tmax XT2 X2 Suitable for 800 A chassis
Tmax XT3 X3 Comment Suitable for 800 A, 1250 A, 1600 A chassis
Tmax XT4 X4 Suitable for 800 A, 1250 A, 1600 A chassis
Tmax T4 (320 A only) T4 Suitable for 1250 A, 1600 A chassis
Suitable for 1250 A single sided only,
Tmax T5 T5
1600 A single and double sided
Tmax T6 T6 Suitable for 1600 A only single sided (Max. 2 pcs).
Ordering example
For odd combinations of circuit breakers ABB will provide the even sided equivalent and shroud. For instance, the CUC6T4
would be supplied for either 5 x T4 breakers or 6 x T4 breakers.
1600A Chassis
R W B
T6
T5 T5
1600A Chassis
R W B XT4 XT4
1250A Chassis 1600A Chassis
R W B R W B T6 XT4 XT4
1250A Chassis
R W B T5 T5 T5 T5 T5 XT4 XT4
800A Chassis
R W B T4 T4 XT4 XT4 XT4 T5 T5 XT4 XT4
—
Moulded case circuit breakers
Chassis
—
Chassis range
—
Moulded case circuit breakers
Chassis
DIM A - BAR LENGTH
DIM A - BAR LENGTH
154
154 TO UNDERSIDE
55 DIM B - TRAY LENGTH 55 TO UNDERSIDE
55 DIM B - TRAY LENGTH 55 OF ESCUTCHEON
OF ESCUTCHEON
DIM ADIM
- BAR
A LENGTH
- BAR LENGTH
45 76.2 PITCH 45
45 76.2 PITCH 45 6.35
154 154 6.35 (MAIN BAR)
55 55 DIM BDIM
- TRAY
B - LENGTH
TRAY LENGTH 55 55 TO UNDERSIDE(MAIN BAR)
TO UNDERSIDE
OF ESCUTCHEON
OF ESCUTCHEON
25
25
45 45 76.2 PITCH
76.2 PITCH 45 45 6.35 6.35
(MAIN(MAIN
BAR) BAR)
25 25
20 20 11
20 20 11
20 20 11
154 20 20 11
55 DIM B - TRAY LENGTH 55 TO UNDERSIDE
OF ESCUTCHEON
41
45 76.2 PITCH 45
6.35
41
(MAIN BAR) 5
25
B B B 41 41 B 50
(MAIN
(M
BA
BAR)
50 50
B B B B (MAIN(MAIN
BAR) BAR)
70
70
TOP
20 11
TOP
70208 70
208 357 PAPER
W W W W151 151
TOP
TOP
70 41
70
50
70 70
B (MAIN
BAR)
R R R R
R R R R
41
41
41 41
W 151 380
R
41 8 8 8
8
B B B
B
A A A 75 75 75
A 75
12 12
DIM D - PAPER LENGTH 12 12 49
76
12
12 12 DIM E
12 15 15 TO LAST
20 15 15 14 14 CUT-OUT
15
9 DETAIL A 15A DETAIL B
DETAIL B15
DETAIL 14 SCALESCALE
1:1 1:1
15 SCALESCALE
1 : 1 1 : 14
1
DETAIL A DETAIL B
DETAIL A DETAIL B SCALE 1 : 1
SCALE 1 : 1 SCALE 1 : 1
SCALE 1 : 1
SCALE 1 : 4
12
—
15
15 XT1
14 800 A
DETAIL A DETAIL B
SCALE 1 : 1 Range SCALE 1 : 1
Base Plate Number Order code
of poles
A B C D E
Bar length Tray length Mounting holes Paper length Last cut out
(mm) (mm) (m) (mm) (mm)
XT1 302.2 191.7 161.7 391.7 125.2 12 CUB4X1
800 A
378.4 267.9 237.9 467.9 201.4 18 CUB6X1
454.6 344.1 314.1 544.1 277.6 24 CUB8X1
607.0 496.5 466.5 696.5 430.0 36 CUB12X1
759.4 648.9 618.9 848.9 582.4 48 CUB16X1
911.8 801.3 771.3 1001.3 734.8 60 CUB20X1
1064.2 953.7 923.7 1153.7 887.2 72 CUB24X1
204 A B B E L E C T R I F I C AT I O N P R O D U C T S A U S T R A L I A A N D N E W Z E A L A N D
—
Moulded case circuit breakers
Chassis
DIM A - BAR LENGTH
DIM A - BAR LENGTH
154
154 TO UNDERSIDE
53 DIM B - TRAY LENGTH 53 TO UNDERSIDE
53 DIM B - TRAY LENGTH 53 OF ESCUTCHEON
OF ESCUTCHEON
50 50 90.0 PITCH
90.0 PITCH 50 50
6.35 6.35
(MAIN BAR)
(MAIN BAR)
30 30
20 20 11
20 20 11
20 20 154
TO UNDERSIDE 20 20 11 11
53 DIM B - TRAY LENGTH 53
OF ESCUTCHEON
41
41
50 90.0 PITCH 50
6.35
(MAIN BAR) 50
30
B B B 41 41
B 50
(MAIN
(MAIN
BAR)
BAR)
50 50
70
B70 B B B (MAIN (MAIN
BAR) BAR)
TOP
20 20 11
TOP
208
208 357
357 PAPER
70
PAPER
W
WIDTH
70
W W 160 W 160
380
380
TOP
TOP
WIDTH
208 208
357 357
PAPER PAPER
WIDTH WIDTH W W 41
W W160 160 380 380
70
70
50
70 70 B (MAIN
R R
BAR)
R R
R R R R
41
41
W 160 380 41 41
R
8
ES
41 8
B 8 8
B B B
A 62
A A A 62 62 62
DIMDD --PAPER
DIM
PAPER DIM D -LENGTH
D -LENGTH
PAPER PAPER LENGTH
DIM LENGTH 49 49
90 90
ESCUTCHEON CUT-OUT 90
20 20 20 8
20
B
A 9 9 62 9 46 157 46
9
9 9
9
100 DIM C - MOUNTING HOLES 9 100
15
15 — 14
XT2 800 A
DETAIL A DETAIL B
SCALE 1 : 1 SCALE 1 : 1
—
Moulded case circuit breakers
Chassis
DIM A - BAR LENGTH
DIM A - BAR LENGTH
154
154 TO UNDERSIDE
53 DIM B - TRAY LENGTH 53 TO UNDERSIDE
53 DIM B - TRAY LENGTH 53 OF ESCUTCHEON
OF ESCUTCHEON
55 DIMDIM
A -A
BAR
- BAR
LENGTH
105.0 LENGTH
PITCH 55
55 105.0 PITCH 55 6.35
6.35 (MAIN BAR)
154154(MAIN BAR)
53 53 DIMDIM
B -B - TRAY
TRAY LENGTH
LENGTH 53 53 TO TO
UNDERSIDE
UNDERSIDE
35 OF OF
ESCUTCHEON
ESCUTCHEON
35
55 55 105.0
105.0
PITCH
PITCH 55 55
6.35
6.35
(MAIN
(MAIN
BAR)
BAR)
35 35
20 20 11
20 20 11
154
20 20 20 20 11 11
53 DIM B - TRAY LENGTH 53 TO UNDERSIDE
OF ESCUTCHEON
55 105.0 PITCH 55
6.35 41
(MAIN BAR)
41
50
35
B B B B 50
(MAIN
(MAIN
BAR)
BAR)
41 41
50 50
70
70BB BB (MAIN
(MAIN
BAR)
BAR)
TOP
0 20 11
TOP
208
208 357
357 PAPER
PAPER 70 70
W
WIDTH W W 138 W 138
380
380
TOP
TOP
WIDTH
208208
357357 PAPER
PAPER
WIDTH
WIDTH WW WW 138138 380380
70 41
70
50
70 70 B (MAIN
BAR)
R R R R
RR RR 41
41
41 41
W 138 380
R E
41
8
8 8
8
B
A B B
B 75
A A A 75 75 75
20 20 20 8 46 134 46
20
B
A 9 9 75
9
9
9 9
9
0 DIM C - MOUNTING HOLES 9 100
49
DIM D - PAPER LENGTH 12 12 105
12 12 12 DIM E
12 12
TO LAST
12 CUT-OUT
20 15 15
15 15 14 14 15
9
15 15
14 DETAIL
DETAIL
B B
15 14A A
DETAIL
DETAIL
9 SCALE
SCALE
1 : 11 : 1 SCALE
SCALE
1 : 11 : 1
DETAIL A DETAIL B
DETAIL A DETAIL B SCALE 1 : 1
SCALE 1 : 1 SCALE 1 : 1
SCALE 1 : 1 SCALE 1 : 4
12
15
— 14 15
—
Moulded case circuit breakers
Chassis
DIM A - BAR LENGTH
DIM A - BAR LENGTH
154
154 TO UNDERSIDE
53 DIM B - TRAY LENGTH 53 TO UNDERSIDE
53 DIM B - TRAY LENGTH 53 OF ESCUTCHEON
OF ESCUTCHEON
55 DIM 105.0
DIMAA--BAR
BAR PITCH
LENGTH
LENGTH 55
55 105.0 PITCH 55 6.35
6.35 (MAIN BAR)
154 (MAIN BAR)
154
53
53 DIM
DIMBB--TRAY
TRAYLENGTH
LENGTH 53
53 TO
TOUNDERSIDE
UNDERSIDE
35 OF
OFESCUTCHEON
ESCUTCHEON
35
55
55 105.0
105.0PITCH
PITCH 55
55
6.35
6.35
(MAIN
(MAINBAR)
BAR)
35
35
20 20 11
20 20 11
20
20 154
TO UNDERSIDE 20
20 11
11
53 DIM B - TRAY LENGTH 53
OF ESCUTCHEON
41
41
55 105.0 PITCH 55
6.35
(MAIN BAR) 50
35
B B B 41
41
B 50
(MAIN
(MAIN
BAR)
BAR)
50
50
70
70 BB BB (MAIN
(MAIN
BAR)
BAR)
TOP
20 11
TOP
208
208 357
357 PAPER
PAPER 70
W
WIDTH
70
W W 160 W 160 380
38
TOP
WIDTH
208
208
357
357 PAPER
PAPER
WIDTH
WIDTH W
W 41 W
W 160
160 380
380
70
70
50
70
70 B (MAIN
R R
BAR)
R R
RR RR
41
41
W 160 380 41
41
R
8
41 8
B 88
A B
BB 62
A AA 62
62 62
20
20 20 8 46 156 46
20
B
99 9 62
9
99
9
DIM C - MOUNTING HOLES 9 100
49
DIM D - PAPER LENGTH 12
12 105
12
12 12 DIM E
12 12
12 TO LAST
20 CUT-OUT
15
15
15
15 14
14 15
9 15 15
14 DETAIL
DETAILBB
15 14AA
DETAIL
DETAIL
SCALE
SCALE11: :11 SCALE
SCALE11: :11
DETAIL A DETAIL B
DETAIL A DETAIL B SCALE 1 : 1
SCALE 1 : 1 SCALE 1 : 1
SCALE 1 : 1
SCALE 1 : 4
12
15
15 14
— DETAIL B
DETAIL A
SCALE 1 : 1XT4 800 A SCALE 1 : 1
—
Moulded case circuit breakers
Chassis
128.70
128.70
TOTO
UNDERSIDE
UNDERSIDE
100.00
100.00 38.00
38.00 DimCC
Dim 38.00
38.00 100.00
100.00 OFOF
ESCHUTEON
ESCHUTEON 12.2012.20
GENE
G
50.00
50.00 POLES
POLE
12
128.70 12
TO UNDERSIDE 13.00
137.00 13.00
0 38.00 137.00 Dim C 38.00 100.00 OF ESCHUTEON 12.20
18
18
24
GENERAL DIMENSIONS 24
40.80 30
50.00 40.80 POLES A B C D 30
36
12 152 251 175 451 36
13.00
42
85.00 18 257 356 280 556 42
85.00
48
24 362 461 385 661 48
TOP
TOP
270.00
444.00 40.80 258.00 154.00 30 467 566 490 766
PAPER270.00
WIDTH
444.00 258.00 154.00
PAPER WIDTH
36 572 671 595 871
85.00
85.00 42 677 776 700 976
270.00 40.80
258.00 154.00
PAPER WIDTH 40.80
189.40
189.40
137.00
137.00 ESCUTC
46.00
ESC
40.80
46.00
189.40
35.00
35.00
55.50 105.00 55.50 49.00
ESCUTCHEON CUT-OUT
105.00 - PITCH
55.50 105.00 55.50 49.00
46.00 150.00 105.00 46.00
- PITCH
50.00 Dim B 50.00
Dim D
PAPER LENGTH
SCALE 1 : 4
—
XT4 1250 A
—
Moulded case circuit breakers
Extended warranty
—
1 year A free of charge one year warranty is included with all ABB circuit breakers. An extensions of this
warranty is available as specified below:
—
2 years Simply by registering your installation site details within 6 months from purchasing, you are entitled
to a free of charge extension of your warranty for one additional year, which will add up the total
number of your warranty to 2 years. The address for online web registration platform:
https://abbextendedwarranty.azurewebsites.net
Note: The system will return the 2 year warranty based on the production date (Factory Warranty). ABB Australia will cover the warranty for the rest
of the time.
—
4 years With a fee. No registration is required.
Note: This option can only be purchased within the first 6 months duration past the original purchase order.
—
5 years Same price as 4 years, simply by registering your installation site details, you are entitled for a
free of charge extension of your warranty for one additional year, which will add up the total
number of our warranty to 5 years. The address for online web registration platform:
https://abbextendedwarranty.azurewebsites.net
Note: This option can only be purchased within the first 6 months duration past the original purchase order.
—
For ‘Existing’ systems and installations
4 years warranty
XT1 1SDA082447R1 Warranty 4 years product already purchased XT1 Stand-alone part without circuit breaker
XT2 1SDA082448R1 Warranty 4 years product already purchased XT2 Stand-alone part without circuit breaker
XT3 1SDA082449R1 Warranty 4 years product already purchased XT3 Stand-alone part without circuit breaker
XT4 1SDA082450R1 Warranty 4 years product already purchased XT4 Stand-alone part without circuit breaker
T4 1SDA082405R1 Warranty 4 years product already purchased Tmax T4 Stand-alone part without circuit breaker
T5 1SDA082433R1 Warranty 4 years product already purchased Tmax T5 Stand-alone part without circuit breaker
T6 1SDA082434R1 Warranty 4 years product already purchased Tmax T6 Stand-alone part without circuit breaker
T7 1SDA082435R1 Warranty 4 years product already purchased Tmax T7 Stand-alone part without circuit breaker
T8 1SDA082436R1 Warranty 4 years product already purchased Tmax T8 Stand-alone part without circuit breaker
5 years warranty
XT1 1SDA082466R1 Warranty 5 years product already purchased XT1 Stand-alone part without circuit breaker
XT2 1SDA082467R1 Warranty 5 years product already purchased XT2 Stand-alone part without circuit breaker
XT3 1SDA082468R1 Warranty 5 years product already purchased XT3 Stand-alone part without circuit breaker
XT4 1SDA082469R1 Warranty 5 years product already purchased XT4 Stand-alone part without circuit breaker
T4 1SDA082451R1 Warranty 5 years product already purchased Tmax T4 Stand-alone part without circuit breaker
T5 1SDA082452R1 Warranty 5 years product already purchased Tmax T5 Stand-alone part without circuit breaker
T6 1SDA082453R1 Warranty 5 years product already purchased Tmax T6 Stand-alone part without circuit breaker
T7 1SDA082454R1 Warranty 5 years product already purchased Tmax T7 Stand-alone part without circuit breaker
T8 1SDA082455R1 Warranty 5 years product already purchased Tmax T8 Stand-alone part without circuit breaker
209
—