INSTALLATION, OPERATION AND MAINTENANCE MANUAL
The downconductor has been ground rod using the ground rod clamp, or
specifically designed to cope with alternatively, it can simply be connected to
extremely high impulse voltages the ground rod using only the ground rod
and currents. Due to the nature of the clamp.
downconductor construction, and its
Refer to Figure 1 for the following
working environment, it is Very Important
instructions (1 to 10).
that each step be followed and carried
out exactly as per the following 1. With the hacksaw (or appropriate
instructions. cutters), cut the downconductor cable to
length, leaving enough cable to be able to
The downconductor can be lugged (as
easily and directly route it to the ground
detailed overleaf) and then connected to the
termination.
1. Sharp Knife
2. Tape Measure
3. Flat Blade Screwdriver
4. Hacksaw
5. 150mm (6in.) Adjustable Spanner/Wrench
6. Roll Spring - (supplied with Upper Termination Kit)
7. Insulation Cutting Tool - (supplied with Upper Termination Kit)
8. Crimper (90mm2) (only required if the cable lug is to be used)
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
2. At a distance of 100mm (4 in.) from the end of the outer insulation over the
the end of the cable, carefully cut a shallow exposed copper tape (roll spring supplied
notch into the black outer insulation, no with upper termination kit).
deeper than 1mm, ( 3/64 in.). Using the
insulation cutting tool, cut around the 6. Remove the copper tape up to the roll
circumference of the black outer insulation spring (exposing black triple extrusion layers)
until the copper screen underneath is by unrolling, then tearing the tape up and
exposed. back over the edge of the roll spring at about
a 45º angle. If necessary, cut about 6mm ( 1/4
Important! The insulation cutting in.) of the copper tape up against the roll
tool uses friction to cut into the spring with a knife and then tear over the
sheath and is less likely to spring.
damage the layers underneath than using
a knife. 7. Wrap one end of the 2.5mm2 x 105mm
(12AWG x 41/8 in.) bare copper wire (supplied
3. Use a knife to carefully cut along with the kit) around the hose clamp, then fix
the 100mm (4 in.) length of black outer the hose clamp over the exposed copper
insulation to a depth of no more than 1mm. screen of the downconductor and tighten
( 3/64 in.). Be careful not to cut too deeply so with a screwdriver.
that the copper layer underneath is not
exposed or damaged. Starting from the end 8. At 85mm (33/8 in.) from the end of the
of the cable, carefully remove the outer cable, carefully cut around the circumference
insulation and discard. of the black triple extrusion layers with a
knife, then, from the first cut, along the
4. Carefully clean up the insulation friction length of the insulation to the end of the
cut, removing any burrs for a neat finish. cable. Remove the layers and discard.
5. Fit the roll spring 15mm ( 5/8 in.) from
2
2.5mm Copper Wire Hose Clamp
85mm (33/8 in.) 15mm (5/8 in.)
Compression Lug
Copper Strands Copper Tape Black Copper Strands and Copper Tape Black
and Double Tape Layer Outer Sheath Double Tape Layer Outer Sheath
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
9. Lay back all of the copper strands and the 2.5mm2 (12AWG) bare copper wire from
tape cut off the filler core with a hacksaw or the hose clamp is bonded with the final
knife as close to the strands and tape as grounding connection and all of the other
possible without damaging them. Lay the downconductor copper strands and tape.
copper strands and tape neatly and uniformly Then securely tighten the whole connection.
back in place.
Note: The ground rod clamp supplied in
10. If using the compression lug, combine this kit must be tightened to 44Nm (32lbf.ft.).
the end of the 2.5mm2 (12 AWG) bare
copper wire from the hose clamp with the 13. Make sure the lower termination is
downconductors’ copper strands and then fit free of moisture. Using rubber gloves, shape
ALL conductors into the 90mm2 lug supplied the waterproofing mastic (supplied) around
with the kit. Make sure that it is fitted all of the exposed areas of the lower
correctly before crimping with an termination.
appropriate crimper.
Note: Depending on the environment of
11. Securely connect the lugged the lower termination, it may be necessary to
downconductor to the grounding system. wrap a sealing tape or mastic around the
waterproofing mastic to stop it from drying
12. If the ‘U’ bolt ground rod clamp (or
out over time.
other method) is to be used, then ensure that
ERICORE
ERICORE
System 3000
LEC IV
Hose Clamp
Copper Tape
2.5mm
(12 awg) Entire lower
Copper Wire termination
to be bound
in waterproofing
Compression mastic Rod Clamp
Lug
Copper
Bus Bar
Ground Rod
To Grounding System
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Ground Pit
Downconductor
lower termination
bound in
waterproofing
mastic