Вы находитесь на странице: 1из 5

Water Mist Systems WMS-01- Multi Zone

FPE AS Office Address : Telephone : 51 95 92 92


PO Box 142 Kanalarmen 12, Faximile :51 95 92 91
N-4065 Stavanger N-4033 Stavanger Enterprise No: 981 990 374
Norway QA Certificate no: 2001-OSL-AQ-7140
E-mail: post@fpe.no
Water Mist Systems - WMS- 01 Multi zone rev 00
Water Mist Systems WMS-01- Multi Zone
DESCRIPTION

These systems are single fluid / low pressure type of Water Mist system designed in
accordance with IMO MSC Circ 1165, and is suitable for various fire protection
applications in machinery rooms with a maximum room volume of 3842 m3.

The system design is based on using water mist nozzles which are Certified by DNV, and
by Factory Mutual.
The DNV certificate describes in detail how the nozzles shall be installed:

The nozzles shall have a nozzle pressure of 8 Bar, and will give a flow of 15,84 lpm each
at this pressure.
The nozzles must have a maximum spacing of 3 x 3 metres, and must be installed not
more than 1,5 meter from a wall.
Maximum nozzle installation height is 10 metres.

These water mist systems can be designed as open skids as shown above, or as enclosed
and heated units.

The system consists of the following main components:

 A pump set which is fed by water from an atmospheric water tank reservoir which
could be part of the package supplied by FPE, or it could be connected to an
existing suitable reservoir.
 A piping manifold arrangement
 Automatically released water mist valves ( deluge release valves)
 By-pass and test valve arrangement.
 Necessary instrumentation

PRODUCT DESCRIPTION:

Standard material

Skid : SST AISI 316


Cabinet: SST AISI 316, painted externally
Piping: SST AISI 316
Instrumentation: SST AISI 316
Water Mist valves: Inbal type
Isolation valves: To Client Specification

FPE AS Office Address : Telephone : 51 95 92 92


PO Box 142 Kanalarmen 12, Faximile :51 95 92 91
N-4065 Stavanger N-4033 Stavanger Enterprise No: 981 990 374
Norway QA Certificate no: 2001-OSL-AQ-7140
E-mail: post@fpe.no
Water Mist Systems - WMS- 01 Multi zone rev 00
Water Mist Systems WMS-01- Multi Zone

Nozzle working pressure

Nozzle working pressure: 8 barg

System Logic Drawing

FPE AS Office Address : Telephone : 51 95 92 92


PO Box 142 Kanalarmen 12, Faximile :51 95 92 91
N-4065 Stavanger N-4033 Stavanger Enterprise No: 981 990 374
Norway QA Certificate no: 2001-OSL-AQ-7140
E-mail: post@fpe.no
Water Mist Systems - WMS- 01 Multi zone rev 00
Water Mist Systems WMS-01- Multi Zone

1 Technical description

This type of system is fully designed to Client Specifications. The design shown above
must be seen as an example. The number of protected zones will vary with the Client
Requirement.

As an alternative to the shown example where the water pumps are made part of the
valve skid design, the pumps skid can also be made as a separate unit.

The water supply tank could be a fresh water tank specially made for the purpose, or it
could be an existing fresh water tank used also for other purposes.

The system may be designed with a back-up connection to the firewater system to make
it possible to extend the operation of the system by use of firewater after the fresh water
reservoir has been exhausted.

The water mist nozzles used are VID K6 which are low pressure nozzles which gives a
water mist where minimum 90% of all water mass sprayed has a droplet size < 300
microns.

FWS works by differing combinations of heat absorption, steam generation, oxygen


reduction in the base of the flames, flame destabilisation, liquid and surface cooling. It is
the interaction of the heat from the fire, the water droplets and the ventilation which
create the conditions under which the fires will be extinguished.

Fine Water Spray has several advantages when compared with other agents. The
advantages are:

 it is environmentally benign
 it is safe for personnel
 system testing and accidental releases are inexpensive
 it is easy to maintain
 it is reliable
 it is clean
 it will cause very limited damage

FPE AS Office Address : Telephone : 51 95 92 92


PO Box 142 Kanalarmen 12, Faximile :51 95 92 91
N-4065 Stavanger N-4033 Stavanger Enterprise No: 981 990 374
Norway QA Certificate no: 2001-OSL-AQ-7140
E-mail: post@fpe.no
Water Mist Systems - WMS- 01 Multi zone rev 00
Water Mist Systems WMS-01- Multi Zone

FPE AS Office Address : Telephone : 51 95 92 92


PO Box 142 Kanalarmen 12, Faximile :51 95 92 91
N-4065 Stavanger N-4033 Stavanger Enterprise No: 981 990 374
Norway QA Certificate no: 2001-OSL-AQ-7140
E-mail: post@fpe.no
Water Mist Systems - WMS- 01 Multi zone rev 00

Вам также может понравиться