Академический Документы
Профессиональный Документы
Культура Документы
The science of the motions and properties of air. It has been adopted by
engineers to as the branch of physics that deals with the pressure, elasticity, weight,
and other mechanical properties of air and other gases. The English word pneumatic
and its associate noun pneumatics are derived from the Greek root pneuma meaning
“breath “.
Compressed air is one of the oldest forms of energy known to man. However it
is not until the last century that the fundamentals of pneumatics were researched
systematically. While this energy can be used in many facets of industry, the true and
worldwide introduction of pneumatics in industry, commenced only when the need for
automation and rationalization of operational sequences continued to increase
Some of the important reasons for the wide use of compressed air in industry
are as follows:
Availability
Air is available practically everywhere for compression, in unlimited quantities.
Storage
It is easily stored in large volumes if required.
Environmentally clean
It is clean and with proper exhaust air treatment, can be installed to clean room
standards.
Resistance to Environment
It is largely unaffected in the high temperature, dusty and corrosive atmospheres in
which other system may fail.
Overload Safe
Pneumatic tools and operating components can be overloaded to the point of stopping
and they are therefore overloading safe.
6
6
4
3
2
1. Compressor
Air taken in at atmospheric pressure is compressed and delivered at a higher
pressure to the pneumatic system. It thus transforms mechanical energy into
pneumatic energy.
2. Electric Motor
Supplies the mechanical power to the compressor. It transforms electrical energy
into mechanical energy.
3. Pressure Switch
Controls the electric motor by sensing the pressure in the tank. It is set to a
maximum pressure at which it stops the motor, and a minimum pressure at
which it restarts it.
4. Check Valve
Lets the compressed air from the compressor into the tank and prevents it
leaking back when the compressor is stopped.
5. Tank
Stores the compressed air. Its size is defined by the capacity of the compressor.
The larger the volume, the longer the intervals between compressor runs.
6. Pressure Gauge
Indicates the Tank Pressure.
wtandingan 2sem2014 page 2
7. Auto Drain
Drains all the water condensing in the tank without supervision.
8. Safety Valve
Blows compressed air off if the pressure in the tank should rise above the
allowed pressure.
1. Air Take-off
For consumers air is taken off from the top of the main pipe to allow occasional
condensate to stay in the main pipe, when it reaches a low point a water take off
from beneath the pipe will flow into an Automatic Drain and the condensate will
be removed.
2. Auto Drain
Every descending tube should have a drain at its low end. The most efficient
method is an Auto Drain which prevents water remaining in the tube should
manual be neglected.
4. Directional Valve
Alternately pressurizes and exhausts the two cylinder connection to control the
direction of movement
5. Actuator
Transforms the potential energy of the compressed air into mechanical work.
Shown is a linear cylinder, it can also be a rotary actuator or an air tool etc.
6. Speed Controllers
Allow an easy and step less speed adjustment of the actuator movement.
Reciprocating piston The piston draws air in through the suction valve during
the downward stroke; compressor compresses it during
the upward stroke and pushes it out through the
pressure valve.
Screw compressor The air drawn in through the suction nozzle is moved
axially through two impellers at high speed to the
pressure side.
Radial flow compressor Through rapidly rotating blades, the air is accelerated
radially. The kinetic energy of the air is converted into
pressure energy.
The symbol is represented with the advance motion to the right in the system circuit
diagram
Linear Actuators
Single-acting cylinder
Double-acting cylinder
Rotary Drives
Advantages: • Reusability
• Simplification of inventory keeping
• Cost savings
The piston rod of a single acting cylinder is operated by the input of compressed air
at the back end position. When the compressed air is shut off, the piston returns to
its starting position via a return spring.
Operation:
The piston rod of a double acting cylinder is operated by the reciprocal input of
compressed air at the front and back of the cylinder. The end position damping is
adjustable via two regular screws.
operation:
(The cylinder retains its last position after the compressed air is removed.)
Operation:
The check valve is closed. The air The check valve is open. The air
passes through the throttle. The passes through the check valve. The
flow can be regulated. flow cannot be regulated.
The compressed air passes from connection 1 to connection 2. If the pressure should
decrease at connection 1, then the compressed air from connection 1 will escape to
the outside via the installed silencer.
Operation:
When pressure is applied in 1, the steel ball When back pressure is applied in connection
will move to the right and closes the 2, the steel ball will move to the left and
exhaust port 3. The compressed air then closes input 1. The compressed air passes
passes thru connection 2. thru the exhaust port 3.
Number of ports
Number of switching positions
2
1 3
4 2
4 2
4 2
5/3-way valve, (mid-position closed)
5 1 3
Types of Actuation
The symbols for the types of actuation are drawn directly on the valve symbols.
Selection: (Depending upon system requirements)
Manually actuated
Electrically actuated
Mechanically actuated
Pneumatically actuated
Combined types of actuation
MANUAL ACTUATION
General
Lever operated
Roller actuated
only in one direction
Spring actuated
Spring centered
PNEUMATIC ACTUATION
ELECTRICAL ACTUATION
Switch with normally open contacts Switch with Normally close contacts
(non automatically reset/latching) (non automatically reset/latching)
ELECTRICAL RELAY
Lamp = S1•S2•S3
S2
+24V
● Switches S1 & S2 are connected in parallel and any
of the switches or both must be close to operate the
lamp. The Boolean expression of the lamp is S1 or
S1 S2
S2.
• Lamp = S1 + S2
S1 Lamp
S2
Lamp
For several inputs logic OR function, switches are
+0V connected in parallel.
●
Lamp = S1
Lamp
S1 Lamp
+0V
●
+24V 1 2
● ● Relays and switch contacts can be use to hold
solenoid valves, relay and lamps active for extended
S1 K periods without the need to apply additional signals.
This is called the memory function.
• A parallel path (2), which latches the output
permanently, forms a simple memory circuit.
1 2
+24V
● ● The relay remains active until its power cut
from the line. In actual application, additional switch
is use to cut the power supply of relay K1.
S1 K
+0V
●
4 2 4 2
Y14 12 Y14 12
5 1 3 5 1 3
Pb1 Pb1
24V ● 24V ●
● ●
0V 0V
A single solenoid 5/2 way valve is When Pb1 is pressed, electrical
also known as mono stable valve. It supply lines (24V) energized the
always has initial position. solenoid Y14. The solenoid then
pushes the second position of the
valve in line with supply port and
compressing the spring.
4 2
Y14 12
5 1 3
Pb1
24V ●
●
0V
4 2 4 2
14 12 14 12
5 1 3 5 1 3
Pb1 Pb2 Pb1 Pb2
24V ● ● 24V ● ●
● ● ● ●
0V 0V
4 2 4 2
14 12 14 12
5 1 3 5 1 3
Pb1 Pb2 Pb1 Pb2
24V ● ● 24V ● ●
● ● ● ●
0V 0V
24V 24V
Pb Pb
Lamp A Lamp A
0 0
Fig. 1 Fig. 2
Initially the switch is open. There is no current in the circuit (Fig. 1). When push button
Pb is pressed, the current from the 24V source will pass through the Pb switch, the lamp
A then to the 0V line. The current in the switch is the same as the current that energized
the lamp. This is a direct control of the lamp (Fig. 2).
24V 24V
K K
Pb Pb
Ik IL
K K
Lamp A Lamp A
0 0
When push button Pb is pressed, the relay K coil will be energized through the Pb switch,
then the contact K of the relay will close the second circuit. The lamp will be energized
through the relay contact K. The current in the control switch Pb is not the same as the
current that energized the lamp. This is indirect control of the lamp using relay.
+24V
● ●
S2 a normally close contact connected in
series with the latching contact (K).
S1 K
Pressing S2 alone breaks the current path to
relay K coil and the circuit is unlatched. If S1 held
S2 actuated whilst pressing S2, relay K is active.
Therefore, the setting current path is dominant.
•
+0V
●
Dominant set
+24V
● ●
S2 a normally close contact connected in
S1 K series with S1.
+0V
●
Latching circuit is a current path that shorted the momentary input signal (NO pushbutton)
to keep the supply current to the coil/solenoid continues. It is very useful when controlling
a single solenoid valve with set and reset switches.
Exercise 1
The problem:
A double acting cylinder is to extend when a pushbutton is operated. Upon release of the
pushbutton the cylinder is to retract. The cylinder is of small bore (25 mm diameter)
requiring a small flow rate to operate at the correct speed
1.0
Set-up diagram
Draw the circuit diagram for the problem. Designate the pneumatic and electrical
components and indicate the numbering system for the valve ports and electrical
connections.
Questions
1. Adjust the flow control valve nearly close. What happen to the cylinder if the switch is
press for a very short period, and then release?
__________________________________________________________________________
______________________________________________________________________
2. Adjust the flow control valve to almost open. What happen to the cylinder if the switch
is press for a very short period and then release?
__________________________________________________________________________
______________________________________________________________________
Y14 12
5 1 3
A1 A1
Pb
A2 A2
24V 1
A2 A2
A1 A1
Pb
A2 A2
0V 0V 0V
Control Valve
Manifold
Y14
12 0 14
0V
Cylinder
1
4 2
24V
1.0
1.0
0V
ELECTRICAL CONTROL CIRCUIT DIAGRAM: (time delay control)
24V
0V
A1 A1
A2 A2
A1 A1
A2 A2
A1 A1
A2 A2
0V 0V 0V
Control Valve
Manifold
12 0 14
Cylinder
Exercise 2
The Problem
The ram of a press is only to extend if the protective guard is closed which actuates switch
S1 and the start button switch S2 is operated. If either of these conditions is not met the
ram is to retract immediately. The cylinder piston rod is operated by a single solenoid valve
with spring return.
S2
S1
Set-up diagram
Complete the circuit diagram for the problem. Designate the electric and pneumatic
components and indicate the numbering system for the connections.
Questions
1. Describe the method of connection of switches to achieve the AND function. Draw the
connection of 3 switches to achieve a 3 input logic AND function.
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
2. Draw the digital symbol of a 3 input AND gate?
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
A1 A1
24V A1 A1
A2 A2
A1 A1
A2 A2
0V 0V 0V
Control Valve
Manifold
12 0 14
0V
Cylinder
Exercise 3
Objectives:
The Problem
Two switches can control a carton ejector from either side of a conveyor track. If switch S1
or S2 is pressed, the double acting cylinder ejects the rejected carton ton from the
conveyor. The ejector piston rod must retract when both switches are released. The
cylinder is to be controlled by a 5/2 way solenoid valve.
Set-up diagram
Complete the circuit diagram for the problem. Designate the electric and pneumatic
components and indicate the numbering system for the connections
Questions
1. Describe the method of connection of switches to achieve the OR function. Draw the
connection of 3 switches to achieve a 3 input logic OR function.
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
A1 A1
ELECTRICAL CONTROL CIRCUIT DIAGRAM:
A2 A2
24V
A1 A1
A2 A2
A1 A1
A2 A2
0V 0V 0V
Control Valve
Manifold
0V 12 0 14
Cylinder
Exercise 4
Objectives:
The Problem
When a pushbutton is pressed the piston rod of a double acting cylinder is to extend. A
roller limit switch is located at the retracted position of the rod. A lamp (L1) is to indicate
that the piston rod is carrying out work and is not home.
L1 S2 1.0
Set-up diagram
Complete the circuit diagram for the problem. Designate the electric and pneumatic
components and indicate the numbering system for the connections
Note: Referring to the circuit diagram, S2 is located at the retracted position of cylinder
1.0 and is indicated by a marker and switch designation. This is the physical location of the
switch. The electrical circuit must also show the correct circuit position of S2 switch.
Question:
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
1.0 S2
24V
0V
A1
A2
A1
A2
A1
A2 0V
0V 0V
Control Valve
Manifold
12 0 14
22 21 24
Cylinder
Exercise 5
Objectives:
1. To use the dominant set circuit to control a double acting cylinder.
The Problem
A stop valve is to be opened and closed by a double acting cylinder. When the switch
marked ‘open’ is pressed the piston rod is to extend and remain extended until the ‘close’
switch is pressed. The switch that opens the valve must override the ‘close’ switch.
Set-up diagram
Complete the circuit diagram for the problem. Designate the electric and pneumatic
components and indicate the numbering system for the connections.
Questions:
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
24V A2 A2
A1 A1
A2 A2
A1 A1
A2 A2
0V 0V 0V
Control Valve
Manifold
0V
12 0 14
SETUP CONNECTION DIAGRAM:
Cylinder
Exercise 6
Objectives:
1. To use the dominant reset circuit to control a double acting cylinder.
2. To connect the control circuit diagram in the trainer board.
The Problem
1.0
Set-up diagram
Complete the circuit. Designate the electric and pneumatic components and indicate the
numbering system for the connections.
Questions:
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
2. If a single acting cylinder replaced the double acting cylinder shown here, what type of
solenoid operated control valve would be required?
__________________________________________________________________________
_______________________________________________________________
__________________________________________________________________________
______________________________________________________________________
PNEUMATICS CIRCUIT DIAGRAM:
A1 A1
A2 A2
A1 A1
A2 A2
A1 A1
A2 A2
0V 0V 0V
0V
Control Valve
Manifold
Cylinder
Exercise 7
Objectives:
1. To use a bistable valve to control a double acting cylinder.
2. To connect the control circuit diagram in the trainer board.
The Problem
Set-up diagram
Complete the circuit diagram for the problem. Designate the electric and pneumatic
components and indicate the numbering system for the connections
Questions:
1. What is the switching status of the bistable memory valve when first fitted to the system
and therefore what position will the cylinder be in?
__________________________________________________________________________
______________________________________________________________________
2. When the memory valve is initialized air is available at port 2, therefore what position
will the piston rod be in?
__________________________________________________________________________
______________________________________________________________________
3. Describe the operation of the circuit.
__________________________________________________________________________
______________________________________________________________________
4. If the switch that initiates extension is held operated what effect will this have on the
piston rod retraction?
__________________________________________________________________________
______________________________________________________________________
PNEUMATICS CIRCUIT DIAGRAM:
1.0
24V A1 A1
A2 A2
A1 A1
A2 A2
A1 A1
A2 A2
0V 0V 0V
Control Valve
0V Manifold
12 0 14
SETUP CONNECTION DIAGRAM:
Cylinder
22 21 24
Exercise 8
Objectives:
1. To use sensors for confirmation of extension and retraction of a double acting
cylinder.
2. To connect the control circuit diagram in the trainer board.
Set-up diagram
Complete the circuit diagram for the problem. Designate the electric and pneumatic
components and indicate the numbering system for the connections.
Questions:
1. How would you indicate on the circuit diagram, that the reed switch of the retracted
position at the cylinder is actuated initially?
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
2. What are the advantages of using the reed switches?
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
1.0
ELECTRICAL
24V CONTROL CIRCUIT DIAGRAM:
24V 24V
A1 A1
24V
A2 A2
A1 A1
A2 A2
A1 A1
A2 A2
0V 0V 0V
Control Valve
Manifold
0V
12 0 14
SETUP CONNECTION DIAGRAM:
Cylinder
22 21 2
Exercise 9
Objectives:
1. To use the pressure to electrical (PE) converter to control the operation a double
acting cylinder.
2. To connect the control circuit diagram in the trainer board.
1.0
Set-up diagram
Complete the circuit diagram for the problem. Designate the electric and pneumatic
components and indicate the numbering system for the connections.
Questions:
1. The two pushbuttons that initiate movement of the form tool are connected in series.
What logic function does this represent?
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
2. How would you incorporate a limit switch to ensure that the piston rod fully extends
before retraction can occur?
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
1.01
4 2
24V A2 A2
A1 A1
A2 A2
A1 A1
A2 A2
0V 0V 0V
Control Valve
Manifold
0V
12 0 14
Cylinder
PE converter
R Bk Bl
2.97
24V
Counter
Output C
wtandingan 2sem2014 page 49
0
S1 S3
Cycle Sensor Counter Reset
switch switch
Lamp A Lamp B
C RC
C Counter C
RC Reset coil
S1 (Cycle Sensor Switch) serves as the signal input for increment counting.
S3 (Counter Reset Switch) will reset the number of counts made by S1 to zero.
C (Counter output) this will change its state when the setting of the counter is reach. The
close contact will open and the open contact will close.
In this case, each time the S1 switch closes, the counter adds 1. When the count
reaches the preset number, the contact output of the counter change state. Lamp A will
turn off and lamp B will turn on. When S3 is pressed, the counter resets it count back to
zero and the system is ready for the next operation.
Exercise 10
Objectives:
1. To use the electro-mechanical counter to control a double acting cylinder.
2. To connect the control circuit diagram in the trainer board.
1.0
Set-up diagram
Complete the circuit diagram for the problem. Designate the electric and pneumatic
components and indicate the numbering system for the connections.
Questions:
1. Which of the sensors is use to determine the number of cycles the sequence had made?
Why?
__________________________________________________________________________
______________________________________________________________________
______________________________________________________________________
24V
0V
24V
SETUP CONNECTION DIAGRAM: A1
24V A1 24V
A1 R1
A2
R2
A1
0V 0V
Control Valve
Manifold
12 0 14
22 21 24
Cylinder
Displacement-Step Diagram
This is the graph of the cylinder displacement and the steps of the operation. This is
represents the cylinder sequences and their displacements, steps of the operation and the
placement of the sensors in one complete cycle.
Retract position
0
1 2 3 4 5 Steps
0 1 1
2 Cylinder extends
Extend position 0
1 2 3 4 5
0 1 1
3
No displacement
0
1 2 3 4 5
0 1 1
4 Cylinder retracts
0
1 2 3 4 5
1
0 1
5 Cylinder extends
0
1 2 3 4 5
Exercise 11
Objectives:
1. To use the displacement-step diagram in making control circuits of multiple
cylinders in sequential operational.
2. To connect the control circuit diagram in the trainer board.
The Problem
Two cylinders are use to transfer parts from a magazine onto a chute. When a pushbutton
is pressed, cylinder 1.0 extends, pushing the part from the magazine and positions it in
1.0
0
1
2.0
0
1 2 3 4 5=1
Displacement step diagram
Solution
Control of the sequence of actions for this task depends on sensors of the cylinder
displacements. The start conditions for the control are that the last action in the operation
sequence has occurred, that is cylinder 2.0 is retracted and the start button is pressed,
steps in the operating sequence are shown on the displacement step diagram.
Symbols notation:
Y112 S10
1.0
0
1
1 2 3 4 5=1
I. CYLINDER SEQUENCE:
_______________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
4 2 4 2
24V
0V
24V
0V
EXAMPLE 12
1.0
0
1
2.0
1 2 3 4=1
I. CYLINDER SEQUENCE:
_______________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
4 2 4 2
24V
0V
24V
0V
The first Programmable Logic Controller (PLC) was developed by a group of engineers
at General Motors in 1968, when the company was looking for an alternative to replace
complex relay control systems.
• Simple programming
• Program changes without system intervention (no internal rewiring)
• Smaller cheaper and more reliable than corresponding relay control systems
• Simple, low cost maintenance
Rung
Power rails
Fig. 1
Fig. 1 illustrates the basic structure of a current rung. In this example, the status of
the flag F1.5 is directly assigned to Q3.5. Listed below are the most common important
elements of a ladder diagram.
`
Normally closed contact (R) Resetting coil
() Coil
- A normally open contact supplies the value 1 when the corresponding push button switch
is closed.
- A normally closed contact reacts with the value 1, when the corresponding switch or push
button is opened.
- A normal coil, the result (resulting logic operation of the contacts) is copied to the
specified variable.
- The setting coil assumes the value 1, if the result is 1 and remains unchanged even if the
result is 0 in between.
- The resetting coil only assumes the value 0, if the result is 1.
AND function
Fig 1 (a)
OR function
I1.3 Q0.1
( )
The operating resources for the controller (timer, counter, index, inputs, outputs etc.) are
addressed via operands (operating resources of the controller). For each program, the
operating resources can be accessed via:
- Symbolic operands (e.g. label used in the control circuit diagram S10; Pb; K1; Y112 etc.)
- Absolute operands (e.g. I0.1; Q0.1; F0.2; etc.).
Symbolic operands:
You can specify any symbolic name for the operand. If, for instance, output Q0.1
switches a motor on and off, you can define this output in your programs as
"MotorOn".
- A character denoting the operand type (O for output, I for input etc.)
- Where applicable the character W to denote word (for multi-bit operands)
- The address of the operating resources. (0.1, 1.2, etc)
To open the Allocation List, select [View] [Allocation List] in the project window or double-
click on the Allocation List item. The absolute operand, symbolic operand, and a comment
are displayed in columns. The symbols at the start of the line help to differentiate between
the inputs and outputs of internal operands. Table below is an example of Allocation List.
The PLC module has input ports where the shorting devices such as switches,
sensors are connected. The signal flow is from the positive (+) supply of the PLC, shorting
devices then to the input ports of the PLC. The driven devices such are solenoid,
contactors, and high rating relays are connected to the output ports of the PLC. The signal
flow is from the output ports, driven devices then to the ground/0V supply. Fig B8.3 shows
the signal flow connections.
24 V
Pb S1
Input ports
i0.0 i0.1 i0.2 i0.3 i0.4 i0.5 i0.6 i0.7 i1.0 i1.1 i1.2 i1.3
i1.3
PLC MODULE
Output ports
L1 Y114
i0.0 i0.1 i0.2 i0.3 i0.4 i0.5 i0.6 i0.7 i1.0 i1.1 i1.2 i1.3
i1.3
PLC MODULE
0V
There is no need to change the Input / Output connections. Use the address of the ports
where the needed input signals are connected. Modify the operand in the allocation list if
necessary.
i0.0 i0.1 i0.2 i0.3 i0.4 i0.5 i0.6 i0.7 i1.0 i1.1 i1.2 i1.3
i1.3
PLC MODULE
0V
There is no need to change the Input / Output connections. Use the address of the ports
where the needed input signals are connected. Modify the operand in the allocation list if
necessary.
i0.0 i0.1 i0.2 i0.3 i0.4 i0.5 i0.6 i0.7 i1.0 i1.1 i1.2 i1.3
i1.3
PLC MODULE
0V
There is no need to change the Input / Output connections. Use the address of the ports
where the needed input signals are connected. Modify the operand in the allocation list if
necessary.