FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Calibration Recommendations . . . . . . . . . . . . . 20
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Auto Calibration Procedure . . . . . . . . . . . . . . . . 24
Manual Calibration Procedure . . . . . . . . . . . . . . 26
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Calibration Procedure for Infiniti with C7065E
Oxygen Sensor . . . . . . . . . . . . . . . . . . . . . . 26
IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . . 4
CGS Sensor Replacement . . . . . . . . . . . . . . . . 27
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . 29
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . 4 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Typical System Wiring . . . . . . . . . . . . . . . . . . . . . 4
Sensor and Hydrophobic Filter Replacement . . 31
Controller/Signal Receiver Options . . . . . . . . . . . 9
Sensor Separation . . . . . . . . . . . . . . . . . . . . . . . . 9 SPARE PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . 15
APPENDIX B — CSA APPROVAL . . . . . . . . . . . . . . B-1
INSTALLATION CHECKLIST . . . . . . . . . . . . . . . . . . 19
APPENDIX C — ATEX APPROVAL . . . . . . . . . . . . C-1
STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . . 19
APPENDIX D — IECEx APPROVAL . . . . . . . . . . . . D-1
Note: For information regarding MOS H2S please refer to form: 95-8532
INSTRUCTIONS
APPLICATION
The Infiniti® Gas Transmitter Model U9500 is designed for
use with Detector Electronics Corporation’s (Det-Tronics)
gas sensors for detection of hazardous gases.
10.2
10.2 ©Detector Electronics Corporation 2016 1 Rev: 4/12 95-8444
Table 1—Power Consumption with Sensor
WIRING—
Power: 18 AWG (0.75 mm2) minimum is recommended
for power wiring to the transmitter. Larger diameter wire
may be required to maintain a minimum of 16 Vdc at the
transmitter for all operating conditions for all sensors
except PointWatch. A minimum of 18 Vdc is required
at the transmitter for all operating conditions for the
PointWatch sensor. Maximum wire size for terminals is 12
AWG (4 mm2).
10.2 2 95-8444
5.86
(14.9)
5.2
(13.2)
2.7
(6.9)
6.57
(16.7)
4.7
(11.9)
3.46
(8.8)
1.28
(3.3)
B2307
10.2 3 95-8444
Important safety notes INSTALLATION
WARNING WIRING REQUIREMENTS
Do not apply power to the system with the • Install per local installation practices and in
enclosure cover removed unless the area has accordance with local authority having jurisdiction.
been de-classified. Do not open the enclosure in a
hazardous area when power is applied. • See Figures 2 and 3 for wiring size and maximum
distance from the power supply to the transmitter.
CAUTION
The wiring procedures in this manual are IMPORTANT
intended to ensure proper functioning of the Proper installation practices must be followed
device under normal conditions. However, to ensure that condensation does not enter the
because of the many variations in wiring junction box and interfere with the electronic
codes and regulations, total compliance to circuitry. Refer to local installation codes.
these ordinances cannot be guaranteed. Be
certain that all wiring complies with applicable WIRING PROCEDURE
regulations that relate to the installation of
electrical equipment in a hazardous area. If in The following procedure should be used for installing
doubt, consult a qualified official before wiring and wiring the Infiniti Transmitter.
the system.
Refer to these figures and table when installing and
The Infiniti contains semiconductor devices wiring the Infiniti:
that are susceptible to damage by electrostatic
d i s c h a rg e . A n e l e c t ro s ta t i c c h a rg e c a n Figure 1 — Infiniti Transmitter Mounting Dimensions
build up on the skin and discharge when
an object is touched. Therefore, use caution Figure 2 — Transmitter Wiring Requirements for
when handling the device, taking care not to Toxic and Oxygen Models with Relays
touch the terminals or electronic components. Figure 3 — Transmitter Wiring Requirements for
Observe the normal precautions for handling Combustible Models with Relays
electrostatic sensitive devices. Figure 4 — Field Wiring Terminal with Relay Option
Figure 5 — Field Wiring Terminal without Relay
To minimize the risk of damage, handle the Option
transmitter module by the edges only. Do
not touch the circuit board, or electronic Figure 6 — Transient Suppression for Inductive
components. Loads
Table 2 — Wiring Size and Maximum Distance from
The fault detection circuitry does not monitor Transmitter to Sensor (for applications
the operation of external response equipment where a sensor termination box is used)
or the external wiring to these devices. It is
important that these devices be checked TYPICAL SYSTEM WIRING
periodically to ensure that they are operational.
Refer to these typical system wiring diagrams for
Exercise caution if an over-range reading is guidance when installing and wiring the Infiniti:
indicated, since a dangerous condition could
exist. Figure 7 -— A Typical System, Infiniti Transmitter with
a Combustible Gas Sensor, Isolated
Current Output and Relay Outputs
Figure 8 — A Typical System, Infiniti Transmitter
with a Toxic Gas/Oxygen Sensor, Non-
Isolated Current Output and Relay
Outputs
Figure 9 — A Typical System, Infiniti Transmitter with
a PointWatch Detector and Non-Isolated
Current Output
Figure 10 — A Typical System, Infiniti Transmitter with
a PIRECL PointWatch Eclipse Detector
and Non-Isolated Current Output
10.2 4 95-8444
12 AWG 14 AWG 16 AWG 18 AWG 12 AWG 14 AWG 16 AWG 18 AWG
32 32
30 30
28 28
26 26
24 24
22 22
20 20
18 18
16 16
14 14
0 2000 4000 6000 8000 10000 0 2000 4000 6000 8000 10000
A1672
DISTANCE (FEET) A1673 DISTANCE (FEET)
1. Install the unit in a location that is best suited to cover 4. Connect the transmitter enclosure to the field
the area to be protected. Whenever practical, the wiring conduit. The enclosure should be electrically
Infiniti should be placed where it is easily accessible connected to earth ground.
for calibration. For proper operation, sensors should 5. Attach the sensor to the proper entry on the transmitter
be pointing down, except for PointWatch, which must enclosure. It is recommended that a layer of teflon
be mounted horizontally. See Figure 1 for mounting tape be applied to the sensor threading. Route the
dimensions. wires through the entry, and tighten the sensor to the
NOTE enclosure to ensure an explosion-proof installation.
When used with the PointWatch infrared Do not overtighten.
hydrocarbon gas detector, a 1/4 inch spacer
is required between the enclosure and the IMPORTANT
mounting sur face to allow adequate room To ease maintenance, periodically apply a
for the detector and calibration windshield, if generous amount of Lubriplate grease (p/n
required. 102868-001) to the internal threads on the
junction box cover using an application tool. Do
2. Remove the transmitter from its packing material and not use any silicon based products, since some
note the location of the field wiring terminals and (on materials can cause irreversible damage to the
the catalytic sensor transmitters only) the location of sensing element in the gas sensor.
a small sensor connection plug on the side opposite
the field wiring terminals. 6. Slide the transmitter module into the bracket,
3. Remove the cover from the enclosure. The transmitter being careful to route field and sensor wires to the
module slides into the mounting bracket within the appropriate location within the enclosure for easy
enclosure and all field and sensor wiring connects connection to the transmitter module. Ensure that the
to this module. transmitter display and pushbuttons (at the top) are
oriented correctly.
–– For catalytic combustible gas transmitters, the
sensor connects to a small plug on one side of the
transmitter and all field wiring connects to terminals CAUTION
on the other side. Wires can become pinched between the cover
–– For all other gas transmitters, the sensor and field and base if they are not properly tucked down
wiring all connect to the terminal block on one side inside the enclosure.
of the transmitter module.
10.2 5 95-8444
7. Fasten the transmitter module to the mounting External relays, solenoids, motors, or other devices
bracket with the two captive screws located inside that can cause inductive transients should be transient
the notch on either side of the top of the transmitter. suppressed. Place a diode across the coil for dc devices.
Remove the wire clip and set it aside. See Figure 6.
8. See Figures 4 and 5 for field wiring terminal
designation. 11. An external reset switch can be wired as shown in
Figures 7, 8, 9, and 10. The use of shielded wire is
9. Connect the power and current output leadwires to recommended for wiring the switch.
the screw terminals on the plug that is provided. See
Figures 7, 8, 9, and 10 for examples of transmitter 12. Check all field wiring to ensure that the proper
wiring. Connect the shield to earth ground at the connections have been made. Refer to local codes
power supply. The panel or field end of the shield to be sure wiring and conduit seals are installed
should not be grounded at the transmitter. Contact properly.
the factory for further assistance.
10. For Relay models, refer to Figures 7 and 8 when Warning
connecting external loads to the relay outputs. For When in non-latching mode, the control device
models without relays, proceed to step 11. must latch the alarm output.
CAUTION
IMPORTANT Wires can become pinched between the cover
Direct connection of 120/240 vac to the relay and base if they are not properly tucked down
terminals inside the transmitter enclosure is inside the enclosure. The wire clip will prevent this
not permitted, since switching relay contacts problem when installed correctly.
can induce electrical noise into the electronic
circuitry, possibly resulting in a false alarm or other 13. Replace the wire clip and place the cover back on
system malfunction. If the application requires the transmitter enclosure.
that ac powered equipment be controlled by the
transmitter, the use of externally located relays is
required.
HIGH RELAY
COMMON
+
RESET
AUX RELAY
OUTPUT SIGNAL
PW
+
OUTPUT SIGNAL
–
*SPARE
S
*SPARE ** POWER
POWER
–
S
COMMON
POWER ** POWER
+
POWER
–
24 VDC +
RESET
POWER
{ }
24 VDC + RELAY EXTERNAL 120 VOLT – V13OLA10A
+
OUTPUT SIGNAL
PW
+
– 4 TO 20 MILLIAMPERE 4 TO 20 MILLIAMPERE
IN
10.2 6 95-8444
FAULT RELAY CONTACTS
SEE NOTES 2, 3
NC COM NO
NO COM NC
FLT RELAY
HIGH RELAY
HIGH ALARM RELAY CONTACTS
EXTERNAL SEE NOTES 2, 4
RESET
NC COM NO
LOW RELAY
S
POWER
LOW ALARM RELAY CONTACTS
–
S
SEE NOTES 2, 4, 5
POWER
–
+
24 VDC +
RESET
SEE NOTE 6
+
NC COM NO
AUX RELAY
AUXILIARY ALARM RELAY CONTACTS
CAL
PW
+
+
OUT
24 VDC + SEE NOTES 2, 4, 5
–
IN
–
– +
WARNING: WHEN IN NON-LATCHING MODE, THE CONTROL DEVICE MUST LATCH THE ALARM OUTPUT.
Figure 7—A Typical System - Infiniti Transmitter with Combustible Gas Sensor, Isolated Current Output and Relay Outputs
SEE NOTE 6
POWER
SEE NOTES 2, 4, 5
POWER
–
–
24 VDC +
RESET
+
+
NC COM NO
AUX RELAY
RED
OUT
SEE NOTES 2, 4, 5
– + BLACK
IN
–
GREEN
4 TO 20 MA SEE NOTE 1
NOTE 1 CONNECT THE GREEN SENSOR LEAD TO THE CHASSIS GROUND LUG
ON THE INSIDE BOTTOM OF THE INFINITI ENCLOSURE.
B1669 NOTE 5 LOW, AUXILIARY AND HIGH ALARM RELAYS ARE PROGRAMMABLE
AS A GROUP FOR LATCHING OR NON-LATCHING OPERATION.
WARNING: WHEN IN NON-LATCHING MODE, THE CONTROL DEVICE MUST LATCH THE ALARM OUTPUT.
Figure 8—A Typical System - Infiniti Transmitter with a Toxic Gas / Oxygen Sensor, Non-Isolated Current Output and Relay Outputs
10.2 7 95-8444
HIGH RELAY
NC COM NO
NO COM NC
FLT RELAY
EXTERNAL
RESET
LOW RELAY
NC COM NO
S
POWER
–
S
POWER
–
+
24 VDC +
RESET
+
NC COM NO
AUX RELAY
CAL
PW
+
OUT
– +
IN
–
4 TO 20 MA
BLACK
RED
YELLOW
WHITE
GREEN
CONNECT THE GREEN SENSOR LEAD TO THE CHASSIS GROUND LUG
B1670 POINTWATCH DETECTOR ON THE INSIDE BOTTOM OF THE INFINITI ENCLOSURE
Figure 9—A Typical System - Infiniti Transmitter with a PointWatch Detector and Non-Isolated Current Output
NC COM NO
NO COM NC
FLT RELAY
HIGH RELAY
EXTERNAL
RESET
NC COM NO
LOW RELAY
S
POWER
–
S
POWER
–
+
RESET
+
NC COM NO
AUX RELAY
CAL
PW
+
OUT
– +
IN
–
4 TO 20 MA
+
24 VDC +
–
24 VDC– 1
24 VDC+ 2
CALIBRATE 3
24 VDC– 4
24 VDC+ 5 1
+ 4-20 MA 6
– 4-20 MA 7
RS-485 B 8
RS-485 A 9
Figure 10—A Typical System, Infiniti Transmitter with a PIRECL PointWatch Eclipse Detector and Non-Isolated Current Output
10.2 8 95-8444
CONTROLLER/SIGNAL RECEIVER OPTIONS SENSOR SEPARATION
All Model U9500 Series transmitters offer an analog 4–20 Det-Tronics sensor termination boxes (STBs) enable
mA output, which is configurable for electrically isolated the installation of the sensor separately from the Infiniti
or non-isolated operation. The analog signal is capable transmitter module. Three conductor shielded cable must
of driving a maximum 600 ohm resistance load. Typical be used to prevent possible nuisance EMI/RFI. Contact
controllers used with the U9500 Series include the family the factory for ordering information. (See Appendix C for
of R8471 Controllers, or the Model 8000 eight channel ATEX rating details.) Refer to these typical system wiring
controller for % LFL flammable gas monitoring. It is diagrams for guidance:
also acceptable to use the U9500 with other devices or
systems capable of accepting 4–20 mA signal inputs. The Table 2 — Wiring Size and Maximum Distance from
following illustrations provide examples of recommended Transmitter to Sensor
interconnecting wiring between the U9500 and analog Figure 14 — Sensor Separation with Combustible Gas
signal receivers: Sensor and Infiniti Transmitter
Figure 15 — Sensor Separation with PointWatch and
Figure 11 — A Typical System, Infiniti Transmitter with
Infiniti Transmitter
PointWatch Wired to R8471 Controller,
Non-Isolated Current Output Figure 16 — Sensor Separation with Toxic and
Oxygen Gas Sensors and Infiniti
Figure 12 — A Typical System, Infiniti Transmitter
Transmitter
with PointWatch Wired to a Model 8000
Controller, Isolated Current Output Figure 17 — Sensor Separation with Chlorine Gas
Sensor, Intrinsically Safe barrier and
Figure 13 — A Typical System, Infiniti Transmitter
Infiniti Transmitter
used with PLC Analog Input Module,
Isolated/Non-Isolated Current Output
R8471 CONTROLLER
24 VDC
– 1
ISOLATED OUTPUT
CURRENT LOOP + –
+ 2 * 4-20 MA
CHASSIS GROUND 3
18 TO 32VDC + 4
POWER
HIGH RELAY
NC COM NO
NO COM NC
FLT RELAY
GROUND – 5
POWER + 6 *
SENSOR
SIGNAL – 7
LOW RELAY
NC COM NO
S
POWER
– +
EXTERNAL RESET 8
S
RESET
POWER
–
HIGH ALARM 9
RESET
+
NC COM NO
AUX RELAY
ALARM
PW
+
OUT
AUX. ALARM 11
IN
–
FAULT / OC 16 FAULT
*NO CONNECTION
Figure 11—A Typical System, Infiniti Transmitter with PointWatch Wired to R8471 Controller, Non-Isolated Current Output
10.2 9 95-8444
MODEL 8000 CONTROLLER
TB 1 TB 2
1
CONNECTION 2
NOT RECOMMENDED U9500 TRANSMITTER NO. 1
3
4 HIGH ALARM
HIGH RELAY
NO COM NC
FLT RELAY
NC COM NO
LOW ALARM
–
TROUBLE
24 VDC
LOW RELAY
TB 3 TB 4 TB 5
NC COM NO
BATTERY
S
+
POWER
– +
S
–
POWER
–
24 VDC +
RESET
– ** +
NC COM NO
AUX RELAY
FLOAT
TYPE
CAL
3 CTR 6 3– 6 3+ 6
PW
+
CHARGER
OUT
+
2 CTR 7 2– 7 2+ 7
IN
–
1 CTR 8 1– 8 1+ 8
BLACK
RED
YELLOW
WHITE
GREEN
POINTWATCH DETECTOR
NO. 2* NO. 3*
B2035
* IDENTICAL TO TRANSMITTER NO. 1 WIRING.
** INSTALL 250 OHM, 12 WATT RESISTOR ACROSS (+) AND (–) TERMINALS FOR ALL CHANNELS SELECTED FOR SERVICE.
THIS RESISTOR WILL SATISFY POWER MONITORING REQUIREMENTS (ONLY CHANNEL 3 SHOWN FOR CLARITY).
Figure 12—A Typical System, Infiniti Transmitter with PointWatch Wired to a Model 8000 Controller, Isolated Current Output
NC COM NO
AUX RELAY
IN
OUT
–
PW
CAL
24 VDC
+
RESET
OUTPUT
POWER
+
POWER
LOW RELAY
NC COM NO
–
+
S
–
INPUT
S
+
FLT RELAY
24 VDC
RETURN
POWER
–
NC COM NO
AUX RELAY
IN
OUT
–
PW
CAL
24 VDC
+
RESET
OUTPUT
POWER
+
POWER
LOW RELAY
NC COM NO
–
+
S
–
INPUT
S
FLT RELAY
+ – RETURN
24 VDC
A2036 POWER
Figure 13—A Typical System, Infiniti Transmitter used with PLC Analog Input Module, Isolated/Non-Isolated Current Output
10.2 10 95-8444
Table 2—Maximum Sensor Separation Distance
GND
CONNECT TO TRANSMITTER
PIGTAIL CONNECTOR
(PROVIDED IN SENSOR
TERMINATION BOX)
BLK
WHT
RED
BLK
WHT
RED
NOTES
• SHIELDED CABLE REQUIRED.
• GROUND CABLE SHIELD AT TRANSMITTER END ONLY.
2309A
CONNECT CABLE LEADWIRES
FROM SENSOR TERMINATION BOX
Figure 14—Sensor Separation with Combustible Gas Sensor and Infiniti Transmitter
POWER
– +
S
–
POWER
24 VDC +
– + + –
RESET
POWER SUPPLY
+
AUX RELAY
CAL IN
PW
OUT
– +
4 TO 20 MILLIAMPERES INTERNAL
GROUND SCREW
DET-TRONICS JUNCTION BOX
SPARE
CAL CAL GREEN
4 – 20 4 – 20 YELLOW
WHITE
RET RET BLACK
RED
+24 +24
POINTWATCH
DETECTOR
B1907
10.2 11 95-8444
INFINITI TRANSMITTER JUNCTION BOX
FAULT RELAY
NO COM NC
LOW RELAY
S
GROUND SCREW
POWER
– +
S
INFINITI TRANSMITTER OR
POWER OUT
24 VDC + – R8471 CONTROLLER
– + + –
SEE NOTE 1
RESET
POWER SUPPLY
+
AUX RELAY
CAL IN
POWER
PW
– +
S
–
POWER
24 VDC +
– + + –
RESET
POWER SUPPLY
+
AUX RELAY
CAL IN
PW
OUT
– + 4 TO 20 MILLIAMPERES IN SENSOR POWER (+)
4 TO 20 MILLIAMPERES
2 1
SENSOR TERMINATION BOX TWO CONDUCTOR MTL 787S
SHIELDED CABLE I.S. BARRIER
(CONNECT AT THE
TRANSMITTER 4 3
JUNCTION BOX ONLY)
+ SAFE AREA
–
G
D HAZARDOUS AREA
RE SENSOR TERMINATION BOX
+ BL
K * CONNECT THE GREEN
– SENSOR LEAD TO THE
G CHASSIS GROUND LUG
IN THE INSIDE BOTTOM
OF THE JUNCTION BOX. +
–
G
NO CONNECTION RED * CONNECT THE GREEN
+ LK SENSOR LEAD TO THE
GROUND LUG* B CHASSIS GROUND LUG
–
IN THE INSIDE BOTTOM
B2310 TOXIC SENSOR G OF THE JUNCTION BOX.
GROUND LUG*
Figure 16—Sensor Separation with Toxic* and Oxygen Gas Sensors NO CONNECTION
and Infiniti Transmitter C7067E
CHLORINE
* Excluding Chlorine sensor, see Figure 17. SENSOR
NOTES:
1. NEVER EXCEED 25.5 VOLTS DC POWER SUPPLY INPUT VOLTAGE OR
BARRIER DAMAGE WILL RESULT.
2. MAXIMUM TOTAL FIELD WIRING SIGNAL LOOP IMPEDANCE IS
130 OHMS (EXCLUDING BARRIER).
3. INTRINSICALLY SAFE WIRING AND INSTALLATION PRACTICES MUST BE FOLLOWED.
DISPLAY AND CONTROLS, OPTIONS, 4. INTRINSICALLY SAFE BARRIERS ARE NOT COMPATIBLE WITH “GROUND-FAULT”
MONITORED POWER SUPPLIES.
DISPLAY AND CONTROLS Figure 17—Sensor Separation with Chlorine Gas Sensor, Intrinsically
The Infiniti display contains an eight character display Safe Barrier and Infiniti Transmitter
for identifying system status conditions and sensor
input, a magnetic reed switch for resetting the unit and
entering different operating modes, and pushbuttons for PROGRAMMING OPTIONS
programming and calibrating the system. See Figure 18 Operating Range
for the location of indicators and pushbuttons and Tables
The available operating range settings and the
3 and 4 for descriptions.
corresponding default setpoints and calibration gases
are shown in Table 5. Note that not all U9500s support
External Reset
selectable operating range.
The external reset input terminal, when grounded
momentarily, normally initiates a relay/display reset only. IMPORTANT
See Figure 9. However, if the “EXT” “CAL” option is The range setting of the transmitter must match
programmed “YES” during the Infiniti setup procedure, the output range of the sensor being used or
the external reset duplicates the magnetic reed switch the system will fail to operate correctly. For
(Cal Magnet) and can be used to perform calibration. example, if a carbon monoxide (CO) sensor with
a range of 0–500 ppm is being used, the range
setting for the transmitter must be 0–500 ppm.
Refer to the “Specifications” section for a listing
of available sensors and ranges.
10.2 12 95-8444
Table 3—Display And Controls
Display/Indicator Description
This display is always on and functions as a power indicator.
The display provides a continuous reading of the sensor input in both the Normal and
Calibrate modes.
In the event of a fault, it identifies the nature of the fault with a fault message.
Ex %LFL / ppm In other operating modes it shows the alarm setpoints and programmed calibration
gas concentration.
A negative zero drift condition is indicated by a minus (–) sign in the left hand digit.
In the event of an over-range condition, the display will continue to track the sensor
output as long as the over-range condition exists. Combustible gas transmitters will
latch the display at the highest detected gas concentration.
Asterisk indicates an alarm (any one) has activated since last reset.
Solid black square indicates that the low alarm threshold has been exceeded.
n Low Alarm For relay models, this means that the relay output has activated.
Blank indicates no alarm.
INCREASE
Used to move to next higher setting during system programming.
ms
SETUP
Used to initiate Setup routine, to accept reading displayed, and cycle to the next
m
programming step during Setup (system programming).
ACCEPT
DECREASE
Used to move to next lower setting during system programming.
tm
Used for non-intrusive calibration and transmitter reset.
CAL/RESET
Activated by Cal Magnet from outside the Infiniti enclosure.
Duration of
CAL/RESET Function
Switch Activation
1 Second Resets the Infiniti transmitter
2 - 3 Seconds Enters the Setpoint Display Mode
7 Seconds Enters the Calibration Mode
10.2 13 95-8444
SENSOR INPUT READING ALARM HISTORY INDICATOR
ALARM
}
HI AUX LO
ACCEPT
INCREASE PUSHBUTTON CAL/RESET DECREASE PUSHBUTTON
SETUP/ACCEPT PUSHBUTTON
* Changing the Toxic Measurement Range will reset all alarms and the Cal Gas to the default setting for the selected range.
** For oxygen deficient applications, use the LOW and/or AUX alarms.
For oxygen enrichment applications, use the HIGH and/or AUX alarms.
*** Default settings for all Infiniti relay operation is normally de-energized with non-latching contacts (except fault alarm, which is normally
energized with no faults). Default settings for optional External Reset Pushbutton is “No External Cal” enabled.
Default settings for calibration mode (automatic or manual) is automatic mode. Manual calibration mode is recommended when using the
U9500D chlorine or U9500F Sulfur Dioxide Transmitters.
10.2 14 95-8444
Setpoints External Calibration
The Infiniti Transmitter has three independent alarm Calibration procedures are normally initiated and
outputs (low, high, and auxiliary), with field selectable executed using the Cal Magnet to activate the CAL/
setpoints. For both relay and non-relay models, these RESET switch. Choose “YES EXT CAL” during the setup
setpoints correspond to the HI, AUX, and LO ALARM procedure to allow the additional use of the external reset
indicators on the display. input terminal for initiating and executing a calibration
procedure. See Figure 9 for switch wiring.
Calibration Gas Concentration
The programmed calibration gas concentration is also 4-20 Milliampere Calibration
displayed and adjustable. This known concentration The 4–20 mA current loop is factory calibrated. Perform
(typically one half of the instrument’s full scale detection the “YES 4–20 CAL” function in the Setup procedure if a
range) of the actual gas or vapor that is expected to be recalibration is required. A current meter must be placed
detected should be used to calibrate the system. in the loop to perform this function.
10.2 15 95-8444
Table 6—Infiniti Sensor Compatibility
Output Description
• The linear 4–20 mA output:
– corresponds to the field-programmed gas range.
4–20 Milliamperes (Standard) – can be calibrated in the field for maximum accuracy.
– is user selectable for isolated or non-isolated use.
Refer to the “Setup ” section for programming information.
• The High, Low, and Auxiliary Alarm relays are programmable
as a group for either normally energized or normally de-energized
operation.
4–20 mA with Relays (Optional)
• Option includes a set of four relays: • Low Alarm, Auxiliary Alarm, and High Alarm relays are programmable as
–High Alarm a group for either latching or non-latching operation.
–Low Alarm • Fault relay is normally energized with no faults. Faults are generally
–Auxiliary Alarm non-latching, but faults that occur during calibration and warmup must be
–Fault reset.
• Latching relays are reset using either the Cal magnet or an external reset
switch (field installed, user supplied).
10.2 16 95-8444
Table 8—Infiniti Modes of Operation
10.2 17 95-8444
Table 8—Infiniti Modes of Operation (Continued)
NOTE
If the CAL/RESET switch (or external reset input) is still activated at the end of this cycle, the
transmitter automatically enters the Calibrate mode. If a calibration is not performed, a CAL ABORTED
fault will occur. To exit the Calibrate mode without performing the calibration, cycle power or wait for
the calibration fault message, then reset the unit.
The Setpoint Display mode is used only for displaying the setpoints. Use the “Setup” mode for changing setpoint
and calibration gas values.
Auto calibration is the default setting and the recommended calibration method for all sensors except for Chlorine
(Cl2) and Sulfur Dioxide (SO2). Auto calibration is required for use with PointWatch.
• Auto Cal is an automatic calibration procedure that requires no adjustments by the operator. The Calibrate
mode is entered by holding the Cal magnet to the CAL/RESET magnetic switch until completion of the “Setpoint
Display” sequence described above (approximately 7 seconds). (The external reset input terminal can also be
used to enter the calibrate mode if “YES EXT CAL” was selected during the Setup procedure. Activate the input
until completion of the “Setpoint Display” sequence.)
• For calibration of the Infiniti with the C7065E O2 sensor, there are two modes of Auto Calibration available:
1. Initial / Sensor Replacement Calibration
2. Routine Calibration
Use Option #1 for new sensor start-up or after replacing a sensor. Use Option #2 for all subsequent calibrations
after Option #1 has been completed.
Auto Calibration • The transmitter performs the Zero adjustments, then signals the operator when to apply and also when to
remove the calibration gas. Upon completion of a successful calibration, the transmitter automatically returns to
the Normal operating mode.
• If the operator fails to complete the calibration procedure, if an error in calibrating occurs, or if a successful
calibration cannot be completed, the transmitter will automatically return to the Normal mode and continue to
use the previous calibration data (after 10 minutes or when the gas level drops below the lowest alarm setpoint).
A fault indication will be displayed until a reset occurs.
• If the microprocessor determines that the sensor cell is approaching the end of its useful life, the message “SEN
AT EOL” will be indicated on the display. A fault indication will be displayed until a reset occurs.
• While in the Calibrate mode, all transmitter outputs are inhibited and the dc current output goes to a preset level
(adjustable from 0 to 20 mA, with a default value of 2.0 mA). See the “Setup” section of this manual for complete
calibration procedure.
10.2 18 95-8444
Table 8—Infiniti Modes of Operation (Continued)
NOTE
When used with PointWatch only 50% LFL gas may be used for span concentration. PointWatch will
not read accurately if other concentrations are used.
10.2 19 95-8444
Table 9—Setpoint Display Cycle
CALIBRATION
CAUTION
Changing the range selection will cause the CALIBRATION RECOMMENDATIONS
alarm setpoints and the calibration gas settings
to default to the setting shown in Table 5. The Infiniti can accommodate automatic or manual
Catalytic combustible, PointWatch infrared, and calibration and for many sensors either of these methods
oxygen sensors have preset ranges that are are effective. Certain sensors, however, require either
automatically selected by the Infiniti and cannot automatic or manual calibration only. The sensors and
be changed. method of calibration required and/or recommended are
listed in Table 11. Refer to this table before proceeding
2. Remove the enclosure cover to access the transmitter with calibration.
display and controls.
Perform Calibration
10.2 20 95-8444
Table 10—Infiniti Setup
10.2 21 95-8444
Table 10—Infiniti Setup (Continued)
10.2 22 95-8444
Table 11—Recommended Sensor Calibration Methods For toxic gas sensor calibration, the calibration gas
type must match the sensor cell type. The calibration
Calibration gas concentration should be one half of the full scale
Sensor Method measurement range of the sensor in use.
Auto Manual
Combustible Catalytic (Ex) X For oxygen sensor calibration, normal ambient air may
H2S X be used for span calibration if it is known to be clean and
not depleted of O2 (21% vol.). Compressed clean air is
CO X
available from Det-Tronics if required. It is not necessary
PointWatch (HC) X only to utilize an O2 free gas such as compressed nitrogen
O2 X only to calibrate the O2 sensor zero level. An electronic zero
Cl2 X only switch is provided within the C7065E sensor housing for
SO2 X only
this function. Refer to the O2 sensor instruction manual
for details.
Sensor Type After 1 Hour Warm-up After 24 Hours After 1 Week Every 90 Days
PointWatch * Opt Opt Opt
Catalytic Req Req Req Req
H2S Electrochemical Req Opt Opt Opt
Chlorine Req Req NR Req
Oxygen Req Opt Opt Opt
Carbon Monoxide Req Opt Opt Opt
Sulfur Dioxide Req Opt Opt Opt
Req = Required
Opt = Optional
NR = Not Recommended
* = Optional for methane. Must be calibrated if gas selection setting other than methane is used.
10.2 23 95-8444
• Inspect the sensor. Loss of sensitivity can be A conversion K-factor must be used in the calibration of
caused by various factors. One common cause is the system whenever detection of gases/vapors other
by clogging of the hydrophobic or sintered filters by than the gas used in the actual calibration process will
dirt, oil, paint, etc. Problems of this nature will not occur. Refer to the “Det-Tronics K-factor Tech Note” for
be detected by the transmitter’s diagnostic circuitry the current list of Det-Tronics K-factors. The K-factor
when used with catalytic or electrochemical sensors. represents the relative sensor response ratio of the
If the filter or the sensor are dirty or plugged, they calibration gas to the detected gas. The K-factor is used
should be replaced. When the transmitter is used within the “K-factor equation” to determine the proper
with the PointWatch Infrared detector, contamination transmitter output level (span setpoint) when the sensor
of its optical surfaces will be annunciated. is exposed to the calibration gas. The K-factor equation
• When calibrating a C7065E O2 Sensor, the initial is as follows:
“zero” calibration requires activation of a switch CxK=S
located inside the sensor housing. Subsequent
calibrations of the sensor do not require switch C = Concentration of the calibration gas in % LFL
activation. Always calibrate the sensor using 20.9% K = Conversion K-factor for the gas to be monitored
O2 if ambient air is less than 20.9% O2. with the given calibration gas
S = Corrected combustible gas transmitter
AUTO CALIBRATION PROCEDURE calibration span output level (span setpoint)
In the Auto Cal mode, all adjustments are made
automatically by the transmitter once calibration has Example: Gas to be detected: Propane
been initiated. Auto Cal mode is recommended for all Calibration gas: 50% LFL Methane in air
sensors except Cl2 and SO2. Refer to Table 13 for the K-factor: 1.39
Automatic Calibration Procedure.
Equation: C x K = S
O2 Sensor Calibration 50 x 1.39 = 69.5
Initial calibration of the U9500C/C7065E O2 detector
For proper system sensitivity to propane, the Infiniti
requires removal of the C7065E sensor housing for access
transmitter calibration gas concentration setpoint should
to the zero selection switch. Subsequent calibrations of
be adjusted to read 69% LFL. When the sensor is
the sensor will not require removal of the sensor housing,
calibrated with 50% LFL methane in air calibration gas
nor nitrogen purging. The U9500C will automatically set
mixture, the sensor will provide an accurate measurement
the zero cal level even with normal levels of O2 displayed
of propane.
during the zero calibration process. Refer to “Calibration
Procedure for Infiniti with C7065E Oxygen Sensor” for
If more than one calibration gas type and K-factor is
details.
listed for a gas that will be detected, generally the
best calibration gas to use is that which provides a
Catalytic Sensor Calibration
K-factor closest to the value of 1.0 (one). Note that the
Catalytic sensors respond to many combustible gases. presence of Methane gas as a potential detectable gas
While it is highly recommended that a sensor be is an exception. Always use Methane calibration gas if
calibrated to detect a single gas, the fact remains that Methane is expected to be present within the protected
only a few calibration gas types are available. In addition, area.
multiple gas hazards may exist.
If a specific gas/vapor and K-factor is not listed within
A known concentration (typically one half of the full scale the “Det-Tronics K-factor Tech Note,” a K-factor can
detection range of the instrument) of the actual gas or be determined by Det-Tronics Sensor Engineering
vapor type that is expected to be detected should be department. Contact the factory for details.
used to calibrate the system. Det-Tronics calibration
gas should always be used to ensure proper system
calibration performance and accuracy. Calibration gas
should not be used if the Oxygen concentration within
the gas is listed at less than 20% by volume.
10.2 24 95-8444
Table 13—Automatic Calibration Procedure
“GAS”
“ON”
• Remove the calibration gas. When the gas level
falls below the lowest alarm setpoint, and if no faults
are present, the transmitter automatically exits the
Display shows decreasing gas Calibrate mode.
concentration when gas is removed
• A sensitivity reading that can be used to track
and alternating message:
sensor life (except PointWatch) is displayed for
Span calibration complete “CAL” “OK” seven seconds with the “SPAN” reading and prior
then to the transmitter returning to normal operation. Any
“RMV” reading over 100 indicates that the sensor is good.
“GAS”
then, if the calibration is successful:
• At the successful completion of the calibration, all
“XXXX SPAN”
outputs and indicators return to normal operation.
• If faults are present, the unit will exit after the
remainder of 10 minutes.
Display shows alternating messages • If a fault occurs, remove the gas and correct the fault.
indicating the fault, then After the fault has been cleared, begin calibration
Calibration fault indication
“RMV” again. See Table 15 - Fault Messages, Explanations
“GAS” and Corrective Action.
10.2 25 95-8444
MANUAL CALIBRATION PROCEDURE 5. For best results, allow the U9500/C7065E to warm
In the Manual Cal mode, the CAL/RESET switch must be up for one hour before performing the calibration
activated using the Cal magnet to accept a reading as procedure.
a calibration point. (The external reset input can also be
used to accept a reading if “YES EXT CAL” was selected Initial/Replacement Sensor Calibration Procedure
during the Setup procedure.) 1. Remove the C7065E aluminum sensor cover. Leave
the sensor cell plugged in.
The Infiniti must be programmed for manual calibration
prior to initiating the manual calibration procedure (refer 2. Apply the calibration magnet to the U9500 calibration
to the Setup section). Refer to Table 14 for the Manual target location for nine seconds, or until the U9500
Calibration Procedure. display shows “zero-cal.”
3. Move the toggle switch on the electrochemical
IMPORTANT sensor cell to the “zero” position. See Figure 19 for
The Manual Calibration Procedure must be used switch location. This will simulate the “zero” or “no-
for chlorine (Cl2) and sulfur dioxide (SO2) sensors. oxygen” condition necessary to establish a baseline
Use the Auto Calibration Procedure for all other output calibration level. When the U9500 display
sensors. reads “00,” move the toggle switch back to the “on”
position. Place the aluminum sensor cover over the
cell and reinstall.
Calibration Procedure for Infiniti with
C7065E Oxygen Sensor
There are two calibration procedures for the U9500/
C7065E:
10.2 26 95-8444
Routine Calibration Procedure 5. While the Infiniti transmitter display is indicating “Zero
1. Do not remove the C7065E sensor cover. Drift,” simultaneously press and release the Increase
and Decrease switches on the Infiniti faceplate. The
2. Apply the calibration magnet to the U9500 calibration Infiniti will exit the warm up mode and display an
target location for nine seconds, or until the U9500 incorrect gas level reading.
display shows “zero-cal.” The initial zero baseline
output level reading will be referenced. Wait until the 6. Calibrate the U9500A following the “Initial/
U9500 display shows “aply-gas.” Replacement Sensor Calibration” procedure.
3. The transmitter will now begin to record the sensor 7. Replace the Infiniti J-box cover.
output level in response to the ambient oxygen 8. Re-enable any alarming devices triggered by the
concentration. If this is known to be 20.9%, an U9500A Infiniti alarm outputs.
accurate span calculation will result. If the ambient
O2 level is less than 20.9%, it is recommended
Alternate method:
to apply 20.9% oxygen using a Det-Tronics O2
calibration kit. This method can be used in a classified/hazardous area.
4. When span calculations are complete, the U9500 1. Disable any alarming devices triggered by the
display will indicate “cal-OK,” and then “rmv-gas.” U9500A Infiniti transmitter alarm outputs.
If using a Det-Tronics O2 calibration kit, remove the 2. Power up the U9500A with a new or different CGS
calibration cup and close the regulator valve. No sensor installed.
actions are necessary if ambient air O2 is used.
3. Wait for the U9500A Infiniti transmitter to display
5. The U9500 will automatically exit calibration mode “Zero Drift” indication (approximately four minutes
when calibration is complete. The displayed O2 level from power up).
should be 20.9% (17.4 mA current level) if ambient
conditions are normal. 4. Apply calibration gas to the sensor. After
approximately 30 seconds, the U9500A will reset,
go through the startup cycle, and display some
cgs sensor replacement incorrect gas level.
Under certain circumstances, an existing U9500A 5. Apply a calibration magnet and hold it in place until
Infiniti gas transmitter fitted with a replacement CGS the Infiniti transmitter enters the calibration mode.
sensor may not exit “warm up” mode after four minutes The Infiniti display will read a gas indication number
from power up, causing a “Zero Drift” indication to be alternating with “Zero Cal.”
displayed on the U9500A. This uncommon situation can
6. Remove the calibration gas from the sensor.
occur when a CGS pellistor resistance is slightly offset
from the previous CGS pellistor resistance. It does not 7. Allow the Infiniti to zero calibrate to the new or
mean that the sensor or the Infiniti transmitter are bad or different sensor.
out of tolerance. 8. When prompted by the Infiniti, apply the calibration
gas to set the 50% LFL span setting.
There are two simple methods to solve this problem.
9. Once the Infiniti accepts the new span setting, follow
Preferred method: the prompts to exit the calibration mode.
10. From this point, allow the sensor to fully warm up for
This method requires a Hot Work Permit and
one hour minimum, and then calibrate the U9500A
declassification of the work area.
following the normal calibration procedure in the
1. Disable any alarming devices triggered by the instruction manual.
U9500A Infiniti transmitter alarm outputs.
11. Re-enable any alarming devices triggered by the
2. Power up the U9500A with a new or different CGS U9500A Infiniti alarm outputs.
sensor installed.
Contact the factory if you have any questions or
3. Wait for the U9500A Infiniti transmitter to display comments.
“Zero Drift” indication (approximately four minutes
from power up).
4. Remove the cover from the Infiniti transmitter.
10.2 27 95-8444
Table 14—Manual Calibration Procedure
10.2 28 95-8444
TROUBLESHOOTING Prioritized Faults
The faults are prioritized, with the highest fault being the
Automatic Diagnostics and Fault Messages
only one displayed (see Table 15 for a prioritized listing).
The transmitter features self-testing circuitry that If an additional fault exists, it will be displayed after the
continuously checks for problems that could prevent higher priority fault has been cleared.
proper system response. When power is applied, the
microprocessor automatically tests the unit. If a fault is Clearing Faults
detected during this warmup mode, it will be indicated
Generally, faults that occur while in the normal mode are
on the display and must be reset to clear. In the Normal
self-clearing once the fault condition has been corrected.
operating mode, it continuously monitors the input signal
Faults that occur while in the warmup and calibration
from the sensor to ensure proper functioning.
modes require a manual reset to clear (using either an
externally connected reset switch or the Cal magnet).
In the event of a system fault: After the fault condition has been corrected, the fault
• The display identifies the nature of the fault using a relay automatically switches to the normal (energized)
fault message. Refer to Table 15 for an expanded state, the dc current output returns to normal, and the
explanation of the messages. fault message turns off.
10.2 29 95-8444
Table 15—Fault Messages, Explanations And Corrective Action
EEPROM sumcheck failure. Cycle power to clear fault. If fault persists, return the unit to the
Blank Display
factory for repair.
“COMPUTER” RAM or processor failure. Cycle power to clear fault. If fault persists, return the unit to the factory
“FAILURE” for repair.
“WDT” Watchdog timer failure. Cycle power to clear fault. If fault persists, return the unit to the factory
“FAILURE” for repair.
“EEPROM” Activate the Cal/Reset switch using the Cal Magnet, then perform Setup and Calibration
“FAILURE” procedures. If fault persists, return the unit to the factory for repair.
“EXT RSET” External reset button has been activated for 15 seconds or longer. Self-clearing when button is
“PROBLEM” released.
External 24 volt power supply is not in the 15 to 32 volt range. Check and correct input voltage.
“24V P.S.”
During normal operating mode, this fault is self clearing when the fault is corrected. If fault
“FAILURE”
occurs during warmup or calibration modes, activate the Cal/Reset switch using the Cal Magnet.
Internal 5 volt analog power supply is not in the 4.75 to 5.35 volt range. During normal operating
“5V P.S” mode, this fault is self clearing when the fault is corrected. If fault occurs during warmup or
“FAILURE” calibration modes, activate the Cal/Reset switch using the Cal Magnet. If fault persists, return
the unit to the factory for repair.
Sensor input fault. With 4 to 20 mA output sensors, the current output is below 2 mA or above
“SENSOR” 35 mA. In normal operating mode, the unit automatically goes through warmup when this fault
“PROBLEM” clears. If this fault occurs at the end of the warmup period or calibration procedure, recalibrate
the sensor. If fault persists, check sensor condition and wiring.
“PTIR CAL” (PointWatch sensor only). The PointWatch has detected that the calibration line is low (active)
“LINE LOW” during power-up.
“PTIR” (PointWatch sensor only). The PointWatch has detected that its input voltage is below specified
“VOLT LOW” level.
“DIRTY” (PointWatch sensor only). The PointWatch has detected that its optics are dirty. Refer to the
“OPTICS” PointWatch manual for cleaning procedure.
“REPLACE” (In calibration mode) sensor is defective. Replace sensor and perform calibration procedure.
“SENSOR”
“CAL” (Cal Message) Time ran out while waiting for the gas reading to stabilize. Activate the Cal/Reset
“ABORTED” switch using the Cal Magnet.
“SENSOR” (Cal Message) Sensor reaching End Of Life. Consider replacement of the sensor in the next 1
“E.O.L.” or 2 calibrations.
“ZERO”
Negative zero drift. Sensor input is –9% full scale or lower. Perform sensor calibration.
“DRIFT”
10.2 30 95-8444
Contaminating Gases And Vapors for Catalytic • Fault detection circuitry continuously monitors for
Sensors problems that could prevent proper system response.
Gases and/or vapors that can cause permanent loss of It does not monitor external response equipment or
sensor sensitivity: the wiring to these devices. It is important that these
devices be checked initially when the system is
–– Silicone compounds often found in oils, greases, installed, as well as periodically during the ongoing
and resins. maintenance program.
–– Antiknock compounds such as tetra ethyl lead, • The system must be checked periodically in the
tetra methyl lead and phosphate esters. Normal mode to ensure that those items not checked
by the transmitter diagnostic circuitry (such as output
Gases and/or vapors that can cause inhibition (temporary relays) are functioning properly.
loss of sensitivity) of the sensing element:
SENSOR AND HYDROPHOBIC FILTER
–– Volatile halogenated compounds REPLACEMENT
–– Tetrachloroethylene
–– Fluorinated hydrocarbon
–– Vapors that result from hot P.V.C. CAUTION
–– Acids and various solvents may cause a shift in the Be sure to secure all output devices that are
zero of electrochemical sensor actuated by the system to prevent unwanted
–– Chlorine and Chlorinated HC activation of this equipment, and remember to
place these same output devices back into service
NOTE when the checkout is complete.
The sensor must be periodically inspected and
calibrated following prolonged exposure to Catalytic Sensor Replacement
contaminating gases and vapors. For catalytic combustible gas sensors, it is necessary to
replace the entire sensor assembly when it is defective.
Follow the procedure below to replace the sensor.
MAINTENANCE
1. Remove power to the transmitter prior to replacing
CAUTION the sensor.
Be sure to secure all output devices that are
actuated by the system to prevent unwanted 2. Remove the transmitter cover and the wire shield
activation of this equipment, and remember to within the transmitter. If a sensor termination box was
place these same output devices back into service used, remove the sensor junction box cover.
when the checkout is complete. 3. Unplug the sensor from the transmitter module (if a
sensor termination box was used, unplug it from the
• Periodically apply a generous amount of Lubriplate plug inside the termination box) and unscrew it from
grease (p/n 102868-001) to the internal threads on the conduit entry.
the junction box cover using an application tool. DO
4. Thread the wires for the replacement sensor through
NOT use other lubricants, since some materials can
the conduit entry, then screw the sensor into the
cause irreversible damage to the sensing element in
conduit entry and plug it in. Replace the wire
the gas sensor.
shield.
• To ensure reliable protection, it is important to check
5. Replace the junction box cover.
and calibrate the detection system on a regularly
scheduled basis. The frequency of these checks 6. Re-apply power. Allow time for the unit to warm
is determined by the requirements of the particular up and stabilize (approximately 24 hours for best
installation - 90 days is typical. results), then calibrate.
10.2 31 95-8444
Electrochemical Sensor Cell Replacement NOTE
For sensors with replaceable sensor cells (toxic and Handle the sensor cell carefully. To avoid
oxygen sensors), it may not be necessary to replace possible damage, observe the normally accepted
the entire sensor housing assembly when the sensor procedures for handling electrostatic sensitive
is defective. Follow the procedure below to replace the devices. See form 75-1005 for additional
sensor cell. information.
1. Remove power to the transmitter prior to replacing 5. Be sure that the O-ring on the sensor housing is
the sensor cell. in good condition, then place the cap back on the
2. Remove the cap from the sensor base. See Figure sensor base. Tighten only until snug. Do not over
20. (There is no need to remove the sensor housing tighten.
from the junction box for this operation). 6. Re-apply power. Allow time for the unit to warm
up and stabilize (approximately one hour for best
NOTE results), then calibrate.
Compare part numbers to be sure that the correct
replacement cell is being used. An adequate supply of spare electrochemical cell
assemblies should be kept on hand for field replacement.
3. Remove the old sensor cell. The sensor cell contains For maximum protection against contamination and
a small amount of lead – dispose of properly. Check deterioration, they should not be removed from the
for corrosion or contamination on the terminals of the original protective packaging until the time of installation.
sensor base, and clean if necessary. To ensure maximum storage life, electrochemical cells
4. Determine proper orientation for the new cell, then should be stored in the unopened bag that the sensor
carefully plug it in. is shipped in, at a temperature between 32°F and 68°F
(0 to 20°C) and a relative humidity between 15 and 90
percent.
SENSOR HOUSING
CAP
HYDROPHOBIC FILTER
10.2 32 95-8444
Hydrophobic Filter Replacement DEVICE REPAIR AND RETURN
The hydrophobic filter on the front of some of the
Prior to returning devices, contact the nearest local
electrochemical sensor housings protects the sensor cell
Detector Electronics office so that a Service Order
from contaminants in the environment, and also enables
number can be assigned. A written statement describing
the operation of the cell in “wet” environments without
the malfunction must accompany the returned device to
plugging its screen. The operator should frequently
expedite finding the cause of the failure.
inspect the hydrophobic filter for cleanliness. A dirty filter
can significantly reduce the amount of gas that is able to
Pack the unit properly. Use sufficient packing material
reach the sensor cell, thereby impairing the ability of the
in addition to an antistatic bag or aluminum-backed
system to respond to a hazardous condition. If the filter
cardboard as protection from electrostatic discharge.
becomes dirty or if it is damaged, it must be replaced.
Return all equipment transportation prepaid to the factory
To replace the hydrophobic filter, simply unscrew the
in Minneapolis.
existing filter from the housing, then replace it with a new
filter. Use care not to over tighten.
NOTE
A dirty hydrophobic filter can adversely affect the ORDERING INFORMATION
response of the sensor by blocking the flow of
gas to the sensor cell. If the detector cannot be When ordering, please specify:
calibrated or responds slowly to the calibration Model U9500 Infiniti Gas Transmitter
gas, check the condition of the hydrophobic filter
Refer to the U9500 Model Matrix for details
before replacing the sensor cell. The hydrophobic
filter should be clean and squarely seated in the
housing. U9500 MODEL Matrix
MODEL DESCRIPTION
PointWatch Detector Replacement
U9500 Infiniti Gas Transmitter
Refer to Figure 9 in this manual for wiring diagram and
the PointWatch manual for installation and replacement Type GAS
instructions. A10 Catalytic Combustible
B20 H2S – Hydrogen Sulfide
SPARE PARTS C30 02 – Oxygen
• Electronic Module - Specify gas sensor type and with D40 CL2 – Chlorine
or without optional relay package when ordering. E50 CO – Carbon Monoxide
Catalytic Combustible Gas F60 SO2 – Sulfer Dioxide
PointWatch Hydrocarbon Gas
Hydrogen Sulfide – Electrochemical G60 NO2 – Nitrogen Dioxide
Carbon Monoxide (specify range) H60 IR Combustible
Oxygen
Chlorine Type Output
Sulfur Dioxide 01 or 02 4–20 mA
• Calibration Gas Kits and spare cylinders - Specify 04 Relay and 4–20 mA
gas and concentration when ordering.
• Sensor Termination Box.
• Lubriplate grease for threads.
• There are many other accessories available for
use with various sensors. Contact your local
representative or the factory for information.
10.2 33 95-8444
APPENDIX A
FM Approval and Performance Report
Refer to drawing 006722-001 (Figure A1) for applicable area classification and installation details.
Combustible
Transmitters: U9500A1001, U9500A1004, with Junction Box p/n 006264-XXX.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F, and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per FM 6320.
Hydrocarbon Gas Transmitters: U9500H6002 or U9500H6004, with Junction Box P/N 006264-XXX.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F, and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per FM 6320.
Sensor Termination Box: Model STB Series, used with Combustible units above:
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F, and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250.
Hydrocarbon Sensors:
Model PIR9400:
• Explosion-proof for Class I, Division 1, Groups B, C, and D (T5) Hazardous (Classified) Locations.
• Class I, Division 2, Groups A, B, C, and D (T3C) Hazardous (Classified) Locations, Tamb = –40°C to +75°C,
conduit seal not required.
Model PIRECL:
• Explosion-proof for Class I, Division 1, Groups B, C, and D (T4) Ta = 75°C with intrinsically safe output for HART
Communications in accordance with control drawing 0072783-001, conduit seal not required.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4) Ta = 75°C Hazardous (Classified) Locations.
Transmitters: U9500B2002 and U9500B2004 (Hydrogen Sulfide), U9500C (Oxygen), U9500D (Chlorine), U9500E
(Carbon Monoxide) and U9500F (Sulfur Dioxide) with junction boxes p/n 006264-XXX and direct mounted
electrochemical sensor:
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F, and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250. (For use with Sensor Termination box.)
• Performance verified up to 100 ppm H2S-in-air atmospheres per FM 6341 (Draft).
Sensor Termination Box: STB Series, used with Electrochemical units above:
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F, and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250.
Sensors:
C7064E5014 (H2S):
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
NOTE
Sensor cross sensitivity has not been verified by FM.
NOTE
The high temperature characteristic has not been FM verified above +75°C.
NOTE
Detector Electronics combustible gas detection K-Factors are not FM verified.
NOTE
FM Approval of the 4–20 mA input does not include or imply Approval of the gas detection apparatus such as
sensors, transmitters, or devices connected to the system. In order to maintain FM Approval of the system, all
4–20 mA gas detection instruments connected to the input must also be FM Approved.
NOTE
Metric straight thread types are for use in non-North American applications.
Calibration
• Calibration of the above listed sensors has been FM verified using the respective U9500 Transmitter with the
Det-Tronics 225130-001 (50% Methane) and 227115-001 H2S Calibration Kits.
• The U9500B through U9500H Series Transmitters can be used with any FM Approved 4–20 mA device.
CLASS I, DIVISION 1, GROUPS B,C & D CLASS I, DIVISION 1, GROUPS B,C & D CLASS I, DIVISION 1, GROUPS C & D
CLASS I, DIVISION 2, GROUPS A,B,C & D (T4A) CLASS I, DIVISION 2, GROUPS A,B,C & D (T4A) CLASS I, DIVISION 2, GROUPS A,B,C & D (T4A)
CLASS II, DIVISION 1 GROUPS E,F & G HAZARDOUS LOCATIONS HAZARDOUS LOCATIONS
CLASS II, DIVISION 2, GROUPS F & G (T4A)
D CLASS III, DIVISIONS 1 & 2 HAZARDOUS LOCATIONS D
NEMA/TYPE 4X
FROM FM APPROVED , 5
54
38
USA CL I , D
IV 1
,
N CL GRP S
, M
OL
IS I
CL , D
B
,
MODEL C7064E SERIES
P 5 2
I IV C
EA . 2 N O. 1
N R ( Ta I , D 2 &
C2 2 ST I B E D
,
IN
mb I V ,
PE M) C O MB U = G
M FOR
CONTROL DEVICE T.
L
AL 0 1
(F
SA
)
C ON
D U N EM - 4 2 , R P C L
S
ST 0 (C IT A 0∞ G S
II
SE / T C RP
th
A
I N 22- 01 A
0
O
L
YP T
67 0- DET N E O
HYDROGEN SULFIDE SENSOR
11
00
O
.
88 T
W
S +7
06
0
TRONICS
R
1,
1
E
, D ,C G
4X Q
90
, B F & ∞C)
U
MODEL U9500 XXXXX
I V & D( T 4
. 6
IR
PS
A
(T )
RP
ED
(006705-001)
GR 4 A )
CO
E,F
HA
R
Z
CS
EX ALARM
& G
ON I
F O A RD OU
%LFL HI AUX LO
APPROV
F OR
ED
, C L I II
MA NC E
T OR EL EC T R
AND
P E R S L OCA T I ON S
D E TE C
WA RN I
REA D
&
IV
NG
2
AL
OR FM APPROVED 4-20mA DEVICE
P RE
INCREASE SETUP DECREASE
MAN U UNDER
S
EXP L O S : D O N
A
T.
BE TAN
FO D
M A Y BE E G AS O T O
RE I N
P
OP S TR
T
I
S E N TMO EN
ACCEPT
ER U C
A T
N
SP W
IO G
N
H E HE
RE N
CAL/RESET VDC
A
N
16-32
7.7 MAX
WATTS
A-4
INFRARED GAS SENSOR
FROM FM APPROVED , 5
54
38
USA CL I , D
IV 1
,
N CL GRP S
, M
P
OL
IS I
CL , D
I
B
IV C
,
MODEL C7064E SERIES
5 2
EA . 2 N O. 1
N R ( Ta I , D 2 &
C2 2 U ST I B E D
,
IN
mb I V ,
PE M) C O MB = G
M FOR
CONTROL DEVICE T.
L
AL 0 1
(F
SA
)
C ON
D U N EM - 4 2 , R P C L
S
ST 0 (C IT A 0∞ G S
II
SE / T C RP
th
A
I N 22- 01 A
0
O
L
YP T
67 0- DET N E O
11
HYDROGEN SULFIDE SENSOR
00
O
.
88 T
W
S +7
06
0
TRONICS
R
1,
1
E
, D ,C G
4X Q
90
, B F & ∞C)
U
MODEL U9500 XXXXX
I V & D( T 4
. 6
IR
PS
A
(T )
RP
ED
(006705-001)
GR 4 A )
CO
E,F
HA
R
Z
CS
EX ALARM
& G
ON I
F O A RD OU
%LFL HI AUX LO
APPROV
F OR
ED
, C L I II
MA NC E
T OR EL EC T R
AND
P E R S L OCA T I ON S
D E TE C
WA RN I
REA D
2
&
OR FM APPROVED 4-20mA DEVICE
IV
NG
AL
P RE
B INCREASE SETUP DECREASE
B
MA N U UNDER
S
EXP L O S : D O N
A
T.
BE TAN
FO D
M A Y BE E G AS O T O
RE I N
P
OP S TR
T
I
S E N TMO EN
ACCEPT
ER U C
A T
N
SP W
IO G
N
H E HE
RE N
CAL/RESET VDC
A
N
16-32 MODEL C7064E5014
7.7 MAX
WATTS
A A
2. WARNING: ENSURE SENSOR HAZARDOUS (CLASSIFIED) LOCATION RATING IS APPLICABLE FOR THE INTENDED USE.
8 7 6 5 4 3 2 1
95-8444
APPENDIX B
CSA Approval
Refer to drawing 006880-001 (Figure B1) for applicable area classification and installation details.
Combustible
Transmitters: U9500A1001, U9500A1004, with Junction Box p/n 006264-XXX.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per CSA C22.2 #30,
and Ex d IIC T4 per CSA E60079-0, -1.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F, and G Hazardous (Classified) Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per CSA C22.2 #213.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per CSA C22.2 #94. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per CSA C22.2 #152.
Hydrocarbon Gas Transmitters: U9500H6002 or U9500H6004, with Junction Box P/N 006264-XXX.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per CSA C22.2 #30,
and Ex d IIC T4 per CSA E60079-0, -1.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F, and G Hazardous (Classified) Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per CSA C22.2 #213.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per CSA C22.2 #94. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per CSA C22.2 #152.
Sensor Termination Box: Model STB Series, used with Electrochemical units above.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F, and G Hazardous (Classified) Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per CSA C22.2 #213.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per CSA C22.2 #94.
Hydrocarbon Sensors:
Model PIR9400:
• Explosion-proof for Class I, Division 1, Groups B, C, and D (T5) Hazardous (Classified) Locations
• Class I, Division 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations, Tamb = –40°C to +75°C, conduit
seal not required.
Model PIRECL:
• Explosion-proof for Class I, Division 1, Groups B, C, and D (T4) Ta = 75°C with intrinsically safe output for HART
Communications in accordance with control drawing 007283-001, conduit seal not required.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4) Ta = 75°C Hazardous (Classified) Locations.
Stand-alone 4–20 mA CSA Approved Gas Sensor/Transmitter:
• See specific detector rating.
Sensor Termination Box: Model STB Series, used with Electrochemical units above.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F, and G Hazardous (Classified) Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C, and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per CSA C22.2 #213.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per CSA C22.2 #94.
Sensors:
C7064E5014 (H2S):
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per CSA C22.2 #30.
NOTE
The high temperature characteristic has NOT been CSA verified above +75°C.
NOTE
Detector Electronics combustible gas detection K-factors are not CSA verified.
NOTE
CSA Approval of the 4 to 20 mA input does not include or imply Approval of the gas detection apparatus such
as sensors, transmitters, or devices connected to the system. In order to maintain CSA Approval of the system, all
4 to 20 mA gas detection instruments connected to the input must also be CSA Approved.
NOTE
Metric straight thread types are for use in non-North American applications.
Calibration
• Calibration of the above listed sensors has been CSA verified using the respective U9500 Transmitter with the
Det-Tronics 225130-001 (50% Methane) and 227115-001 H2S Calibration Kits.
• The U9500B through U9500H Series Transmitters can be used with any CSA Approved 4–20 mA device.
,
P
R
N
CO
O
TI
CS
C NG
NI
AT U
MODEL U9500 XXXXX
RO
ER TR
OP I N S
CT
E
MODELS C7065E
EL E
OR D
ALARM
EF AN
EX
TOR
%LFL
L B ST
HI AUX LO
DET EC
MANUA UNDER
OR C7066E SERIES
RE AD &
MODEL NTMabc
INCREASE SETUP DECREASE
NTMOS H2S GAS SENSOR
ACCEPT (009800-001)
VDC
CAL/RESET
WATTS
B-4
OR CSA APPROVED 4-20mA DEVICE MODELS C7064E, C7068E,
OR C7069E SERIES
FROM CSA APPROVED
CONTROL DEVICE MN
USA
I S,
OL
AP
NE
IN
M
,
P
R
N
CO
O
TI
CS
C NG
NI
AT U
MODEL U9500 XXXXX
RO
ER TR
OP I N S
CT
MODELS C7065E
EL E
OR D
ALARM
EF AN
EX
TOR
%LFL
L B ST
HI AUX LO
DET EC
OR C7066E SERIES
MANUA UNDER
RE AD &
MODEL NTMabc
B INCREASE SETUP DECREASE B
ACCEPT
NTMOS H2S GAS SENSOR
VDC
CAL/RESET
WATTS
(009800-001)
MODEL NO. MFG. DATE OR CSA CERTIFIED 4-20mA DEVICE
0 067
1 3 - 0 0 1 REV . E
1X M20 1X M20
TYPE 225629
MODEL U9500 SERIES MODEL STB SERIES MOS HYDROGEN SULFIDE SENSOR
SENSOR TERMINATION BOX (007236-001)
INFINITI GAS TRANSMITTER
W/ 006264-XXX (006723-001)
JUNCTION BOX
(006630-001) MODEL C7064E5014
HYDROGEN SULFIDE SENSOR
(005557-001)
A A
MODEL PIR9400 SERIES
HYDROCARBON
INFRARED GAS SENSOR
(006367-001)
2 WARNING: ENSURE TRANSMITTER & SENSOR HAZARDOUS (CLASSIFIED)
LOCATION RATING COMBINATION IS APPLICABLE FOR THE INTENDED USE. OR CSA APPROVED 4-20mA DEVICE
8 7 6 5 4 3 2 1
95-8444
APPENDIX C
ATEX Approval
Ex d IIC T5-T6 Gb
DEMKO 02 ATEX 131327X
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
IP66
Combustible gas performance certified per EN 60079-29-1: 2007 when used with Model CGS or any 4–20 mA stand
alone combustible gas detector.
Read and understand instruction manual before operating.
To obviate the risk of hot spots and capacitor energy storage, the enclosure must not be opened, even when isolated,
when an explosive gas atmosphere is present.
All cable entry devices and blanking elements shall be certified in type of explosion protection flameproof enclosure
“d,” suitable for the conditions of use and correctly installed. Unused apertures shall be closed with suitable certified
blanking elements.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
ATEX Special Conditions for Safe Use (X):
The Infiniti Transmitter types U9500A and U9500H have an ambient temperature rating for performance of –40°C to +75°C.
The measuring function of the Infiniti Transmitter types U9500B, U9500C, U9500D, U9500E, U9500F, and U9500G for
explosion protection, according to Annex II Clause 1.5.5, 1.5.6, and 1.5.7 of the Directive 94/9/EC is not covered by
this certificate.
Ex d IIC T3, T5 Gb
DEMKO 02 ATEX 131323X
T5 (Tamb = –40°C to +75°C)
T3 (Tamb = –55°C to +125°C)
The CGS Combustible Gas Sensor can withstand repeated exposures to 125°C for periods up to 12 hours. It is
recommended that the sensor be replaced after maximum 500 hours of exposed to the 125°C temperature condition.
The CGS Combustible Gas Sensor must be used in conjunction with the before mentioned ATEX certified Detector
Electronics Corp. combustible gas detector control units for compliance with EN 60079-29-1 standards.
The CGS Combustible Gas Sensor must only be mounted into the enclosures of the Infiniti Gas Transmitter Model
U9500A Series, the Combustible Gas Transmitter Model 505 Series, the Digital Communication Unit EQ 22xxDCUEX
Series or the Sensor Termination Box Model STB Series.
The actual enclosure must provide a maximum measured reference pressure of 15 bar measured according to
EN 60079-1: 2007, §15.
The CGS Combustible Gas Sensor is to be installed in places where there is a low risk of mechanical damage.
Ex db IIC T4-T6
EN 60079-29-1
DEMKO 02 ATEX 131324X
T6 (Tamb –55°C to +60°C)
T5 (Tamb –55°C to +75°C)
T4 (Tamb –55°C to +125°C)
IP66.
CE MARK
Directive Conformity
Low Voltage – 2006/95/EEC.
Electromagnetic compatibility – 2004/108/EC.
ATEX – 94/9/EC.
The U9500 Gas Transmitter was tested and found to be compliant with EN50270 when wired in conduit or with shielded
cable. All screen drains shall be terminated to the chassis.
The U9500 Gas Transmitter was tested to EN50270 and are compliant for Type 1 equipment. To meet Type 2
requirements, additional transient suppression is provided for installation.
95-8444
APPENDIX D
IECEx ApprovalS
All cable entry devices and blanking elements shall be certified in type of explosion protection flameproof enclosure
“d,” suitable for the conditions of use and correctly installed. Unused apertures shall be closed with suitable certified
blanking elements.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
CONDITION OF CERTIFICATION:
The CGS Combustible Gas Sensor is certified for use in following ambient temperatures:
- ambient temperature range –40°C to +75°C
Coding: Ex d IIC T5 Gb
- ambient temperature range –55°C to +125°C
Coding: Ex d IIC T3 Gb
The CGS Combustible Gas Sensor can withstand repeated exposures to 125°C for periods up to 12 hours. It is
recommended that the sensor be replaced after maximum 500 hours of exposed to the 125°C temperature condition.
The CGS Combustible Gas Sensor must only be mounted into the enclosures of the Infiniti Gas Transmitter Model
U9500A Series, the Combustible Gas Transmitter Model 505 Series, the Digital Communication Unit EQ 22xxDCUEX
Series or the Sensor Termination Box Model STB Series.
The CGS Combustible Gas Sensor is to be installed in places where there is a low risk of mechanical damage.
GOST-R
BRAZIL
NOTE
All cable entry devices and blanking elements shall be Brazil certified in explosion protection, flameproof “d,”
suitable for the conditions and correctly installed with an IP66 rating. A screw or cover lock is provided for a
secondary means of fastening the cover.
FlexSonicTM Acoustic X3301 Multispectrum PointWatch Eclipse ® IR FlexVu ® Universal Display Eagle Quantum Premier ®
Leak Detector IR Flame Detector Combustible Gas Detector with GT3000 Toxic Gas Detector Safety System
Corporate Office Phone: 952.946.6491 All trademarks are the property of their respective owners.
6901 West 110th Street Toll-free: 800.765.3473 © 2016 Detector Electronics Corporation. All rights reserved.
Minneapolis, MN 55438 USA Fax: 952.829.8750 Det-Tronics manufacturing system is certified to ISO 9001—
www.det-tronics.com det-tronics@det-tronics.com the world’s most recognized quality management standard.