Академический Документы
Профессиональный Документы
Культура Документы
Grid Substation (G.S.S.) is the means of connection between Generating Station and
Consumers (Industrial, domestic etc.) by providing safety and reliability of whole system
in case of fault.
Chambal is a 132kV GSS under the Rajasthan Rajya Vidyut Prasaran Nigam
(R.R.V.P.N.) Ltd. established in 1962.
Connected to 3 incoming lines from three different substations and 28 outgoing lines or
feeders, 9 to 33kV and 19 to 11kV.
INCOMING OUTGOING
POWER FIRE
TRANSFORMER EXTINGUISHERS
VOLTAGE TELEPHONE
TRANSFORMER SYSTEM
ISOLATOR
PLCC EQUIPMENT
(WAVE TRAP etc.)
LIGHTNING
ARRESTOR
CAPACITOR BANK
SERIES REACTOR
RESIDUAL VOLTAGE
TRANSFORMER
SWITCHYARD EQUIPMENT
1. BUSBAR: The term is used for main bar or conductor carrying an electric current to which
many connections may be made. One bus is usually called MAIN BUS and the other is
called AUXILIARY BUS.
2. INSULATORS: In order to prevent the flow of current to earth from supply, the
transmission and distribution lines are secured to supporting towers and poles using
insulators. The requirements for insulators are-
The three types of insulators mainly used for extra high voltage transmission are-
a) Single Pole
b) Three Pole
The automatic circuit breakers are equipped with a trip coil connected to relay or other
means to open breaker under abnormal conditions such as overcurrent. The C.B. performs
the following duties-
The insulating fluids or quenching mediums used are air at atmospheric pressure,
compressed air, oil, vacuum and sulphor hexafluoride. SF6 is preferred over all other
mediums because of its outstanding arc quenching properties and good dielectric strength.
6. CURRENT TRANSFORMER: It is connected in a.c. power circuit to feed the current coils
of indicating and metering instruments (ammeters, watt meters, watt-hour meters) and
protective relays.
The primary is directly connected in the power circuit (the circuit in which current is to
be measured) and to the secondary winding the indicating and metering instruments
and relays are connected.
When rated current flows in its primary, 5 amperes of current flows in the secondary.
The communication system is worked by main line only with the help of important
components of PLCC namely, Wave trap, Line Matching Unit (LMU), and coupling
capacitor.
The main work of wave trap is interchange of electrical wave into sound waves and
vice-versa.
When information is sent from one GSS, the wave trap receives the sound waves,
converts them to electrical waves and they travel to other GSS through main line.
8. LIGHTNING ARRESTOR: The ground wire or earthing screen doesn’t provide protection
against the high voltage waves reaching the terminal equipment. Thus there is a need of
‘diverter’ to protect the power system against high voltage surges connected between the
line and earth so that incoming high voltage wave is diverted to earth. Such a diverter is
also called Lightning Arrestor.
9. CAPACITOR BANK: The power factor depends on the nature of load which is supplied. In
case of purely resistive load, it is unity, for pure inductive load, it is lagging and in case of
purely capacitive load, it is leading.
But in power circuit, the load is mostly inductive thus making power factor lagging and
hence affecting the system from regulation point of view. Thus to improve the power factor,
capacitor bank is erected or used at 132 kV GSS. It is a group of several capacitors of same
rating which may be connected in series or parallel.
They are divided into 2 categories viz. series and shunt of which Shunt capacitor bank
(SCB) is mostly used in power system of all voltage levels.
A capacitor unit is the building block of capacitor bank. The capacitor unit is made up of
individual capacitor elements, arranged in parallel/ series connected groups, within a
steel enclosure.
The optimum connection for a SCB depends on the best utilization of the available
voltage ratings of capacitor units, fusing, and protective relaying. The different
configurations are namely wye, delta and H.
Lightning arrestor
Isolator with earthing blade
Circuit breaker
Residual voltage transformer
Series reactor
Cell
Fuses
Unbalance protection scheme to provide alarm/ trip
Overcurrent elements for bank fault protection
Current transformer
10. SERIES REACTOR: Switchyard reactors are connected either at the line terminals or the
middle of the power circuit to offset the capacitive effect of the transmission line and to
regulate the voltage and reactive power of the power system, thereby improving the voltage
profile of transmission line. They are coils of number of turns to have large inductance as
compared to its resistance. A series reactor is connected in series between the load and
source. It is also used for neutral earthing.
11. RESIDUAL VOLTAGE TRANSFORMER (RVT): It is used to measure the residual voltage
of a three phase system during a single phase fault.
The primary of transformer is connected to the three phases of the system and
secondary in broken delta, thus the residual voltage appears across these terminals
during a single phase to earth fault.
This residual voltage obtained is equal to three times the zero sequence voltage.
RVTs are also used in three phase capacitor banks to detect the displacement of
neutral in case of failure of one capacitor of three.
They also serve the purpose of discharging of capacitor in capacitor bank.
I. CORE: It is used to provide closed magnetic coupling between low and high voltage
coils to reduce leakage flux and to provide low reactance path. It is made of
laminations of silicon steel as silicon increases permeability, reduces hysteresis loss
and eddy current loss. The laminations are coated with layer of insulation warmish.
II. WINDING: Transformer windings made of copper are high and low voltage windings
attached on its limbs.
III. MAIN TANK: The main tank acts as a reservoir for oil and the core is placed inside it to
provide insulation. It is covered to prevent entry of dust particles and other impurities.
IV. BUSHINGS: Bushings comprise a central conductor surrounded by graded insulation. A
bushing is necessary when a conductor is taken out through a metallic tank.
V. TAP CHANGER: Adjustment of voltage is done by changing the effective turns ratio of
the system transformer by proper selections of tapping on the winding. It is provided
on the outer winding or high voltage side as it has more number of turns.The two
types of tap changers are –
a. OFF LOAD TAP CHANGER
b. ON LOAD TAP CHANGER
In the first form as the name implies, it is essential to switch off the transformer before
changing the tap while, the latter is employed to regulate voltage while transformer is
delivering normal load.
TRANSFORMER PROTECTION
While the transformer is provided protection with the help of pressure relief pipes and
buchholz’s relay as specified above, there are also other protection schemes –
Overcurrent protection: When the load on transformer increases, the current drawn will
also increase. This condition of transformer is called overcurrent position and if it
persists for longer period, it can be hazard to the transformer and may further damage
the lines. Thus an Overcurrent relay is used to cut off the transformer from mains with
the help of circuit breaker when excess current flows through it. The relay is energized
by 110 V d.c. from battery room.
Earth fault protection: When from any reason, the winding insulation or conductor
insulation breaks down, then bare conductor touches metallic part spreading current
throughout. This fault is called earth fault in which the potential difference between
phase and earth becomes zero. Earthing is done as a result by connecting a pointed
copper strip from body to earth and plate earthing is used.
Differential protection: The operation of the relay used in this scheme is dependent on
the difference in magnitude or phase of current or voltage. For this purpose two current
transformers having same transformation ratio are used at both ends of system to be
protected. Their secondary are inter-connected.
The relay is connected in parallel and operates when there is a difference between the
magnitude or phase of either current or voltage. It in turn gives a signal to the C.B. to
remove the faulty part from the remaining circuit.
Temperature over rise protection: This scheme protects the transformer from the
overheating of transformer winding and oil resulting from flow of current during
overloading. If overheating is not compensated by any source, then there may be failure
of insulation further leading to short circuit between winding turns.
Thus transformer can be protected by different types of cooling –
a. OIL NATURAL AIR NATURAL (ONAN): Cooling is provided by radiators on outer part and
conservator tank over transformer. When insulation oil heats up, the volume
increases and spreads through them and oil is cooled by external air blowing. No
relay is used in this type of cooling.
b. OIL NATURAL AIR FORCED (ONAF): A number of fans are provided to radiators for
cooling purpose. When heating exceeds a permissible temperature, the fans are
automatically operated by relay.
c. OIL FORCED AIR FORCED (OFAF): This type of protection is provided by a centrifugal
pump which operates automatically when there is temperature over rise. It churns the
oil and brings its temperature down.
TRANSFORMER NO. 2
MAKE: TELK
TRANSFORMER NO. 3
TRANSFORMER NO. 4
MAKE: CROMPTON
TRANSFORMER NO. 5
MAKE: NGEF
MAKE: NGEF
AUXILIARY SYSTEM
BATTERY ROOM
There is a battery section of 55 batteries of 2 volt each, thus supplying a total of 110 volt
d.c. for functioning of Control Panel. The batteries are lead acid type having the following
components –
Plates
Separators
Electrolyte
Container
Terminal port
Vent plugs
BATTERY CHARGING
Initial Charging: It is the first charge given to batteries by which the positive plates are
converted to lead peroxide while the negative plates to spongy lead. In a fully charged
battery, the electrolyte specific gravity is maximum i.e. 1.2 gm/cm3 and terminal voltage
equal to 24 volts.
Discharging: When a fully charged battery delivers its energy out by meeting a load, the
lead peroxide at positive plates and spongy lead at negative plates slowly gets
converted to lead sulphate. This is accompanied by decrease in specific gravity of
electrolyte to a value around 1 gm/cm3 and the terminal voltage is also brought down to
1.85-1.80 volts.
Recharging: It is a process by which electrical energy is passed through battery to recap
to its original value. The positive and negative plates of a discharged battery when
recharged are converted back to lead peroxide and spongy lead respectively with
simultaneous increase in specific gravity of electrolyte and terminal voltage to their
original values.
Floating of batteries: A fully charged battery can’t be allowed to remain an open circuit
since it will undergo a continuous discharge due to internal losses. Thus in order to
retain at least the adequate energy in a battery the internal losses are continuously
compensated and this process is known as Float charging. The current flowing during
this process is called ‘Trickle Charging current’.
A lead acid cell of 2 volts can be floated anywhere between 2.15-2.20 volts.
W = wattmeter
KVA = KVA meter
VAR = VAR meter
A = ammeter
pf = power factor
V = voltmeter
VS = voltmeter selector switch
AS = ammeter selector switch
95 = circuit supervision
86 = master trip
T & C = trip and close switch
Fig: Front view of control and relay panel
51 A = overcurrent relay
51 N = earth fault relay
1/6 = 6 way annunciation relay
KWh = energy meter
T.T.B. = test terminal block
F = fascia 6 ways
PROTECTIVE RELAYS
The protective relay may be defined as an electrical device interposed between the main
circuit and circuit breaker in such a manner that any abnormality in the circuit acts on the
relay, which in turn, if the abnormality is of a dangerous character, causes the breaker to
open and isolate the faulty element from the remaining healthy circuit. Thus relay ensures
the safety of circuit equipment from any damage.