Вы находитесь на странице: 1из 170

SIREC P, PA, L, LA

Multipoint recorder P 7ND 3021-xB...


Multipoint recorder PA 7ND 3021-xA...
Line recorder L 7ND 3121
Line recorder LA 7ND 3125

Manual

Line recorder Multipoint recorder


The reproduction, transmission or use of this document or its contents SIMATIC, SIREC, SIPROM
is not permitted without express written authority. Offenders will be liable are Siemens registered trademarks.
for damages. All rights created by the granting of patents or registration All other product or system names are (registered) trademarks of their
of a design are reserved.Technical data subject to change without notice respective owners and must be treated accordingly.
SIEMENS

Chapter

Introduction 0

Application 1

SIREC Design and Mode of Operation 2

Multipoint recorder P 7ND 3021-xB...


Multipoint recorder PA 7ND 3021-xA... Preparation for Operation 3
Line recorder L 7ND 3121
Line recorder LA 7ND 3125
Operation 4

Measuring and Recording Mode 5

Servicing and Maintenance 6

Technical Data 7

Scope of Delivery, Options, Accessories 8

Parts List 9

Subject Index

Order No.: C79000-G7376-C188


Printed in France
AG 10.98 MG 168 en

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual I-1
Siemens AG Order No.: C79000-G7376-C188-04
I-2 SIREC P, PA, L, LA Manual
Contents

Contents

0 Introduction....................................................................................... 0-1
0.1 General Information............................................................................ 0-1
0.2 Qualified Person ................................................................................. 0-2
0.3 Warning Information .......................................................................... 0-3
0.4 Approved Use ..................................................................................... 0-4

1 Application ........................................................................................ 1-1

2 Design and Mode of Operation ........................................................ 2-1


2.1 Summary............................................................................................. 2-1
2.2 Recorder Components......................................................................... 2-4
2.2.1 Housing............................................................................................... 2-4
2.2.2 Measured-value Acquisition ............................................................... 2-4
2.2.3 Central Processing Unit ...................................................................... 2-4
2.2.4 Power Supply...................................................................................... 2-5
2.2.5 Chassis ................................................................................................ 2-5
2.3 Mode of Operation.............................................................................. 2-8
2.4 Scope of Delivery ............................................................................... 2-9
2.5 Accessories, Consumable Materials.................................................... 2-9
2.6 Options................................................................................................ 2-9
2.6.1 Digital Input/Output............................................................................ 2-9
2.6.2 DC 24 V Output.................................................................................. 2-9
2.6.3 PC Cable ........................................................................................... 2-10
2.6.4 SIPROM R - LA/PA ......................................................................... 2-10

3 Preparation for Operation ............................................................... 3-1


3.1 Recorder Identification ....................................................................... 3-1
3.2 Jumper Settings 50/60 Hz, Summer Time/Winter Time..................... 3-3
3.3 Installation Guidelines ........................................................................ 3-5
3.4 Mechanical Preparation of Recorder for Operation ............................ 3-6
3.5 Connection of Power Supply .............................................................. 3-7
3.6 Connection of Analog Channels ......................................................... 3-9
3.7 Digital Input/Output.......................................................................... 3-16
3.8 DC 24 V Output................................................................................ 3-20
3.9 Starting Up the Recorder .................................................................. 3-21

4 Operation........................................................................................... 4-1
4.1 Display and Control Elements ............................................................ 4-1

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual i
Contents

4.2 Display Elements ................................................................................ 4-3


4.3 Levers ................................................................................................. 4-4
4.3.1 Functions of Service Lever and Lever 2 ............................................. 4-5
4.3.2 Functions of Levers 1, 3 and 4 in Recording Mode (L/LA version)... 4-5
4.3.3 Functions of Levers 1, 3 and 4 in Recording Mode (P/PA version) ... 4-7
4.3.4 Functions of Levers 1, 3 and 4 in the PAUSE Status.......................... 4-9
4.3.5 Functions of Levers 1, 3 and 4 with Recorder Settings using
PROG Menu ..................................................................................... 4-10
4.3.6 Functions of Levers 1, 3 and 4 with Recorder Settings using
TEST Menu....................................................................................... 4-11
4.4 PC Interface ...................................................................................... 4-12
4.5 Settings using PROG Menu .............................................................. 4-14
4.5.1 Chart Feed......................................................................................... 4-16
4.5.2 Measured-value Table (only recorders with alphanumeric text) ...... 4-17
4.5.3 Parameterizing the Analog Channels................................................ 4-20
4.5.4 Parameterizing the Digital Channel (only LA version) .................... 4-30
4.5.5 Alarm ................................................................................................ 4-31
4.5.6 Print (only recorders with alphanumeric text) .................................. 4-34
4.6 Settings using TEST Menu ............................................................... 4-34
4.6.1 Measuring Mode ............................................................................... 4-36
4.6.2 Chart ................................................................................................. 4-36
4.6.3 Text (only recorders with alphanumeric text)................................... 4-40
4.6.4 Clock (only recorders with alphanumeric text)................................. 4-42
4.6.5 Control Input DI4.............................................................................. 4-43
4.6.6 Language (only recorders with alphanumeric text) .......................... 4-45
4.6.7 PROG Locking ................................................................................. 4-45
4.7 Parameterization Examples............................................................... 4-46
4.7.1 Setting the Chart Feed....................................................................... 4-46
4.7.2 Setting the Output of the Measured-value Table .............................. 4-46
4.7.3 Parameterizing the Analog Channel ................................................. 4-47
4.7.4 Parameterizing the Digital Channel .................................................. 4-49
4.7.5 Parameterizing the Alarms................................................................ 4-49
4.7.6 Parameterizing the Measuring Mode ................................................ 4-50
4.7.7 Parameterizing the Chart (only recorders with alphanumeric text) .. 4-51
4.7.8 Parameterizing Texts (only recorders with alphanumeric text) ........ 4-51
4.7.9 Parameterizing the Time (only recorders with alphanumeric text)... 4-53
4.7.10 Parameterizing the Control Input DI4............................................... 4-54

Siemens AG Order No.: C79000-G7376-C188-04


ii SIREC P, PA, L, LA Manual
Contents

4.7.11 Parameterizing the Language (only recorders with alphanumeric


text) ................................................................................................... 4-55
4.7.12 Parameterizing the PROG Locking................................................... 4-55

5 Measuring and Recording Mode ..................................................... 5-1


5.1 Chart Formatting (only recorders with alphanumeric text)................. 5-1
5.1.1 Main Time Line (only recorders with alphanumeric text) .................. 5-2
5.1.2 Main Time Line (recorders without alphanumeric text) ..................... 5-2
5.1.3 Device Text (only recorders with alphanumeric text)......................... 5-2
5.1.4 Switch-on Text (only recorders with alphanumeric text) ................... 5-3
5.1.5 Event Text (only recorders with alphanumeric text) .......................... 5-3
5.1.6 Start Line (only recorders with alphanumeric text) ............................ 5-3
5.1.7 Time Marks (only recorders with alphanumeric text)......................... 5-4
5.1.8 Limit Line (only LA version) ............................................................. 5-4
5.1.9 Alarm Markers (only P/PA version) ................................................... 5-4
5.1.10 Measured-value Table (only recorders with alphanumeric text) ........ 5-5
5.1.11 Grid (only recorders with alphanumeric text)..................................... 5-6
5.1.12 Priorities of Text Outputs.................................................................... 5-6
5.1.13 Configuration Data (only recorders with alphanumeric text) ............. 5-7
5.1.14 Error Messages and Status Messages (only recorders with
alphanumeric text) .............................................................................. 5-9
5.2 Example Recording with Explanations............................................... 5-9

6 Servicing and Maintenance .............................................................. 6-1


6.1 Removing the Chart Carriage ............................................................. 6-1
6.2 Inserting the Chart Carriage................................................................ 6-2
6.3 Setting the Main Time Line ................................................................ 6-3
6.4 Removing a Fanfold Pack................................................................... 6-4
6.5 Inserting a Fanfold Pack ..................................................................... 6-5
6.6 Removing a Chart Roll ....................................................................... 6-6
6.7 Inserting a Chart Roll.......................................................................... 6-7
6.8 Moving Chassis into Maintenance Position ........................................ 6-9
6.9 Returning Chassis from Maintenance Position ................................. 6-10
6.10 Removing Chassis from Housing ..................................................... 6-11
6.11 Inserting Chassis into Housing ......................................................... 6-12
6.12 Removing the Guide Tongue ............................................................ 6-13
6.13 Inserting the Guide Tongue .............................................................. 6-13
6.14 Labelling and Inserting the Measuring-point Label.......................... 6-13
6.15 Replacing the Pens for the Analog Channels.................................... 6-14

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual iii
Contents

6.16 Replacing the Pen for Alphanumeric Text (only LA version) .......... 6-14
6.17 Replacing the Recording Head (only P/PA version)......................... 6-15
6.18 Replacing the Scale (line recorders) ................................................. 6-16
6.19 Replacing the Scale (multipoint recorders)....................................... 6-16
6.20 Replacing the Battery (only recorders with alphanumeric text) ....... 6-17
6.21 Replacing the fuse............................................................................. 6-17
6.22 Adjustment, Test Prints, Carriage/Text Positions ............................. 6-18
6.22.1 Adjustment........................................................................................ 6-18
6.22.2 Carrying Out the Adjustment............................................................ 6-20
6.22.3 Test Print........................................................................................... 6-20
6.22.4 Maintenance...................................................................................... 6-22
6.22.5 Service .............................................................................................. 6-23
6.23 Removal of Transport Protection (only PA version) ........................ 6-24
6.24 Insertion of Transport Protection (only PA version) ........................ 6-24

7 Technical Data................................................................................... 7-1


7.1 Operation, Displays............................................................................. 7-5
7.2 Recording............................................................................................ 7-5
7.2.1 Line Recorders.................................................................................... 7-5
7.2.2 Multipoint Recorders .......................................................................... 7-6
7.3 Digital Input/Output (Option) ............................................................. 7-7
7.4 DC 24 V Output (Option) ................................................................... 7-7
7.5 Power Supply...................................................................................... 7-8
7.6 Ambient Conditions ............................................................................ 7-8
7.7 Mounting Position............................................................................... 7-9
7.8 Degree of Protection ........................................................................... 7-9
7.9 Electric Safety..................................................................................... 7-9
7.10 Electromagnetic Compatibility ........................................................... 7-9
7.11 Dimensions, Mounting...................................................................... 7-11
7.12 Weight............................................................................................... 7-11
7.13 Explanation of Error Data................................................................. 7-11

8 Scope of Delivery, Options, Accessories .......................................... 8-1


8.1 Scope of Delivery ............................................................................... 8-1
8.1.1 Line Recorders.................................................................................... 8-2
8.1.2 Multipoint Recorders .......................................................................... 8-2
8.2 Available Accessories and Consumable Material............................... 8-2
8.2.1 Line Recorders.................................................................................... 8-3
8.2.2 Multipoint Recorders .......................................................................... 8-3

Siemens AG Order No.: C79000-G7376-C188-04


iv SIREC P, PA, L, LA Manual
Contents

8.3 Available Options ............................................................................... 8-4

9 Parts List............................................................................................ 9-1

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual v
Contents

Siemens AG Order No.: C79000-G7376-C188-04


vi SIREC P, PA, L, LA Manual
Introduction

0 Introduction

0.1 General Information

This Manual contains the information required for approved use of the
products described in it. It is directed at technically qualified personnel who
are specially trained or have appropriate knowledge in the field of
instrumentation and control, referred to below as automation technology.
Knowledge of the safety information and warnings present in this Manual and
their technically correct application are requirements for safe installation and
commissioning as well as safe operation and repair of the described products.
Only qualified personnel in the sense of Section 0.2 have the required
specialist knowledge in order to correctly interpret the general safety
information and warnings present in this document for a specific case, and to
apply them appropriately.
For organizational reasons, this Manual must be ordered separately. For clarity
reasons, the manual does not cover all details on all types of the described
products, and cannot describe every possible case in connection with
installation, operation or maintenance. Should you require further information,
or should particular problems occur which are not handled in sufficient depth
in this Manual, help can be requested through your local Siemens office or
representative.
Your attention is additionally drawn to the fact that the contents of this
Instruction Manual are not part of a previous or existing agreement,
commitment or statutory right and do not change these. All commitments on
the part of Siemens are contained in the respective sales contract which also
contains the complete and solely applicable warranty conditions. These
warranty conditions in the contract are neither extended nor limited by the
contents of this Manual.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 0-1
Introduction

0.2 Qualified Person

Unqualified interventions in the devices or the non-observance of the warnings


present in this Manual or on the devices may lead to severe personal injury or
damage to property. Therefore only suitably qualified personnel may work on
these devices:
T Configuring personnel familiar with the safety concepts of automation
technology
T Operating personnel instructed in the handling of equipment for
automation technology and acquainted with the contents of this Manual
which are important for operation
T Commissioning and servicing personnel who are trained to repair such
automation technology equipment or who are authorized to energize,
ground and tag circuits and devices in accordance with established safety
practices.

Siemens AG Order No.: C79000-G7376-C188-04


0-2 SIREC P, PA, L, LA Manual
Introduction

0.3 Warning Information

Warning information with the following meanings is used in this Instruction


Manual and in the warning information on the products:

Danger
means that death, severe personal injury or substantial damage to property will
occur if the appropriate safety precautions are not observed.

Warning
means that death, severe personal injury or substantial damage to property can
occur if the appropriate safety precautions are not observed.

Caution
means that slight personal injury or damage to property can occur if the
appropriate safety precautions are not observed.

Note
is important information on the product, its handling or the respective part of
the documentation to which particular attention should be paid.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 0-3
Introduction

0.4 Approved Use

T The devices must only be used for applications described in the Catalog
and the Instruction Manual, and only in conjunction with other devices
and components recommended by or approved of by Siemens.
T The products have been developed, manufactured, tested and
documented in accordance with the appropriate safety standards. If the
handling guidelines and safety information are observed during
configuring, assembly, approved use and maintenance, the products do
not therefore present a danger in the normal case with respect to property
or the health of persons.

Warning
T Following removal of the housing or the guard, certain parts of these
devices are accessible which may carry dangerous voltages.
T Only suitably qualified personnel should work on these devices.
T These should be thoroughly familiar with all sources of danger and
maintenance measures according to the information in this Manual.
T Correct and safe operation of the products is dependent on proper
transport, storage, installation and assembly as well as careful operation
and maintenance.

Siemens AG Order No.: C79000-G7376-C188-04


0-4 SIREC P, PA, L, LA Manual
Introduction

Documentation In addition to this Instruction Manual – which can be used by all target groups
– the following relevant technical documentation is also available for the
devices:
T Leaflet "Parameterization – a concise overview".
Explains in visual form the basic operation and parameterization as well
as the PROG and TEST menus. Target group: configuring and
maintenance personnel.
T Leaflet "Operation – a concise overview".
Contains charts showing the displays and controls, comprehensible
parameterization examples, defined basic statuses of the devices, visual
displays of important maintenance operations. Target group: plant
operators, maintenance personnel.
T A5 pamphlet "Installation instructions".
Contains information required for assembly and installation of the
devices. Target group: configuring and assembly personnel.
T Catalog: "Recorders, flush-mounted instruments in standardized cases".
Contains the most important technical data, charts, brief description,
ordering information. Target group: plant management, configuring
personnel.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 0-5
Introduction

Siemens AG Order No.: C79000-G7376-C188-04


0-6 SIREC P, PA, L, LA Manual
Application

1 Application

Purpose The devices


T
T
line recorder, referred to below as "L version",
line recorder with alphanumeric text output, referred to below as "LA

T
version",

T
multipoint recorder, referred to below as "P version",
multipoint recorder with alphanumeric text output, referred to below as
"PA version",
can be used to measure, record and monitor analog and digital values.
Standard The recorders with standard measuring ranges can be used to cyclically
measure the following variables :
T DC voltage (DC U),
T direct current (DC I),
T thermocouple connection (TC),
and the recorders with universal measuring ranges also the additional variables

T thermoelectric resistance, resistance and potentiometer connection


(RTD, R),
to process these and to document them on chart paper. As a result of the short
cycle time, the recorders are also suitable for recording fast, dynamic process
parameters.
Even when delivered according to customer-specific requirements, the
recorders can still be subsequently and easily adapted to requirements within
the input, measuring and recording ranges.
The L and LA versions can be equipped with up to three colored pens for the
analog recording of measured values connected via channels #1 to #3.
The LA version has an additional pen for a text channel for the output of
alphanumeric characters and the recording of up to two digital channels d#1
and d#2.
The P and PA versions are equipped with a recording head for values recorded
via channels #1 to #6. In addition to this, two digital channels d#1 and d#2 can
be recorded.
The PA version can additionally output alphanumeric characters.
The recorder functions can be set manually using levers or via a PC interface
with connected laptop or PC.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 1-1
Application

Designs The recorders vary with respect to their recording systems, measuring ranges
and power supplies:
T
T
L version: no alphanumeric text

T
LA version: with alphanumeric text

T
P version: no alphanumeric text
PA version: with alphanumeric text

T
T
Standard measuring ranges
Universal measuring ranges

T
T
Power supply AC 230 V

T
Power supply AC 115 V

T
Power supply AC 24 V
Power supply DC 24 V

Options The recorders can be equipped with the following options:


T
T
Digital input/output

T
DC 24 V output
PC cable.
The "Digital input/output" provides four inputs (DI1 to DI4) for control
functions and six outputs (DO1 to DO6) for alarms, status signals or control
signals. The inputs and outputs are electrically isolated from the recorder
circuits. Two different outputs can be selected:

T Digital input/output, electronic version with semiconductors

T
or
Digital input/output, relay version with changeover contacts.
The option "DC 24 V output" provides a power output for external devices or
options to a limited extent such as e.g. a transmitter or digital input/output.

The option "PC cable" permits connection to a laptop or PC.

Delivery The recorders are delivered as standard designs, or manufactured,


parameterized and prepared for operation in the factory according to the
customer's order.

Conversion Conversions to the recorders such as e.g. changing the power supply or
subsequently installing options must only be carried out by the manufacturer
or by personnel trained by the manufacturer.

Environmental Only environmentally-friendly materials have been used for the packaging
protection system of the recorders.
This Instruction Manual has been printed on paper bleached without chlorine.

Siemens AG Order No.: C79000-G7376-C188-04


1-2 SIREC P, PA, L, LA Manual
Design and Mode of Operation

2 Design and Mode of Operation

The following chapter describes the mechanical and electrical design as well
as the recorder components.

2.1 Summary

The recorders are designed as panel mounted instruments with a format


144 mm x 144 mm.
Installation without interspacing is possible in panels and mosaic systems with
sufficient ventilation.
The modern recorders have digital data processing. Measured values are
recorded serially in channels and with solid state technology.
As a result of the exclusive use of step motors, the drive system for recording
operates completely without contacts. This technology permits a wide range of
applications and high functional reliability.

Fig. 2.1-1 and Fig. 2.1-2 show views of the recorder. The mode of operation of
the recorders is explained down to the block chart level using Fig. 2.2-1.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 2-1
Design and Mode of Operation

0
20
40
0 60
10
20 80
30
40
50
60
70
80
90
10
0

2
OG
PR

1
1
2
3

2
4
3

3
E
RV
IC 5
SE 3
5
3

1 Door
2 Chart carriage
3 Levers
4 PC interface
5 LEDs
6 Visual operating aids
502-001

Fig. 2.1-1 Front view of the recorders (line recorder shown as example;
identical with multipoint recorder except for recording
system)

Siemens AG Order No.: C79000-G7376-C188-04


2-2 SIREC P, PA, L, LA Manual
Design and Mode of Operation

1 Ground connection for cable screen


2 Terminals for DC 24 V output
3 Connection of digital input/output
4 Fuse F1
5 Connection of power supply
6 Fuse F2
7 Window for adjustment of measuring ranges
8 Input terminals

Fig. 2.1-2 Rear view of recorders (LA version shown as example,


design for AC 115/230 V)

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 2-3
Design and Mode of Operation

2.2 Recorder Components

2.2.1 Housing

The housing is made of sheet-steel. The chassis and the chart carriage are
present at the front, the measuring module, the central processing unit, parts of
the power supply and the options are located at the rear. The housing is
mounted in the panel, mosaic system or desk upright panel using the supplied,
standardized mounting elements.

2.2.2 Measured-value Acquisition

Measured-value acquisition consists of a multiplexer with semiconductor


relays and an analog-to-digital converter. The input ranges are set specifically
for each channel using jumpers. The channels are electrically isolated from
one another by staggered control of the semiconductor relays.
Control is handled by the central processing unit. All channels to be measured
during a cycle are connected to the input amplifier in succession via the
individual semiconductor relays. The amplified signal is applied to an analog-
to-digital converter which operates according to the dual-slope procedure.
In order to permit equally accurate measurements in sensitive ranges,
reference measurements are carried out cyclically in the recorder version with
universal measuring ranges. A cyclic check is also carried out for open-
circuits.
The terminal block also contains a sensor for measuring the terminal
temperature when carrying out temperature measurements using
thermocouples.

2.2.3 Central Processing Unit

The central processing unit is the heart of the electronics. It contains a


microprocessor as well as the program memory (EPROM), main memory
(RAM) and non-volatile memory (EEPROM) for configuration data.
Central component of the processing section is a microprocessor system with
firmware. This is used, inter alia, for:
T
T
Sequence control

T
Calculation of measured values

T
Positioning of pen assemblies

T
Evaluation of input commands
Use of PC interface.
The central processing unit permits control of the module "Digital
input/output" and the PC interface.

Siemens AG Order No.: C79000-G7376-C188-04


2-4 SIREC P, PA, L, LA Manual
Design and Mode of Operation

A crystal-controlled calendar/clock with external synchronization facility


provides the date and time as a reference for sets of measured values and the
chart.
The central processing unit is located at the rear of the housing and is
accessible from the front following removal of the chassis. It contains the
plugs for connection of the other modules.

2.2.4 Power Supply

The recorders have different designs on the input side as a result of the four
different power supplies which can be ordered.
AC 230 V or The mains power supply is connected to the recorder via an appliance plug
AC 115 V with subsequent fuses, filter and transformer. The stepped down AC voltage is
rectified, filtered and applied to DC/DC converters which generate the
required internal DC voltages.

Note
The recorder must only be connected to the envisaged power supply. Observe
the corresponding note on the rear of the recorder.

DC 24 V The DC 24 V supply connected via the terminals is applied via a fuse to a


power inverter whose output is connected to a transformer. The secondary side
of the transformer is connected as in the recorder version with a mains power
supply.

AC 24 V The AC 24 V supply connected via the terminals is applied via a fuse to the
primary side of the transformer. The secondary side is connected as in the
recorder version with a mains power supply.

2.2.5 Chassis

The chassis contains the chassis support, control PCB, recording system, user
interface, PC interface and chart carriage. The chassis is connected to the
central processing unit via a multi-conductor ribbon cable with plug. The cable
length is such that the chassis can be completely removed from the housing
without loosening the connection.

Chassis support This is the support for the motors of the recording system, the control PCB,
user interface and PC interface. The chart carriage latches into the chassis
support and can be removed at any time using lever 2, e.g. to replace the chart.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 2-5
Design and Mode of Operation

Control "PCB" The control PCB contains the power electronics for the step motors of the
drives as well as the light barrier for detection of the carriage zero points. It
also contains a microswitch for recognizing the end of the chart paper, and
several microswitches which are activated using the levers.

Clock backup Only versions with alphanumeric text: the clock backup consists of a backup
battery and capacitor. If a battery is not present, or if the chassis is separated
from the central processing unit, the capacitor buffers the internal clock for
approx. 5 minutes. The status of the clock buffer is checked when the power
supply is switched on.

The support for the backup battery is present on the control PCB and
accessible following removal of the chassis.

Recording system The recording system consists of up to seven step motors depending on the
recorder version. These are used for:
T
T
Chart drive
Positioning of the pens (L/LA version)

T
or the recording head (P/PA version) in the x-direction
Lifting of pens (L/LA version)

T
or recording head (P/PA version) and
LA version: positioning of pen for text channel in x- and y-directions
Chart carriage The chart carriage permits fanfold packs or rolls to be used as the chart paper.
A take-up spool is required when using rolls (included in delivery). In
addition, the chart carriage must be adapted when changing from fanfold paper
to rolls. The required operations are described in Section 6 "Servicing and
Maintenance".

User interface The user interface consists of four levers and two LEDs underneath the chart
carriage. A further lever is present on the side of the chassis and is only visible
when the chassis is in maintenance position.
Mechanical operations are directly activated by two of the four levers
underneath the chart carriage. The other two levers can be used for two
different actions each by moving the respective lever to the left or right. The
TEST menu can activated and switched off again using the switch which is
accessible on the side of the chassis.
Green and red LEDs indicate different recorder statuses depending on how
they are activated (on, off, flashing).

PC interface The recorders are equipped with a PC interface. A laptop or PC can be


connected via a special adapter cable. Convenient parameterization of the
recorder is possible via the PC interface using a Windows desktop (SIPROM
R). In addition, measured values, alarm statuses, date/time and chart feed A or
B can also be scanned.

Siemens AG Order No.: C79000-G7376-C188-04


2-6 SIREC P, PA, L, LA Manual
Design and Mode of Operation

Fig. 2.2-1 Block diagram of the recorders

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 2-7
Design and Mode of Operation

2.3 Mode of Operation

As a result of the many different possible uses, the recorders are delivered
preset to the basic setting of 4 to 20 mA.
Customer-specific presetting is also possible as required. The recorder can
then be used immediately following installation and commissioning. It is
additionally possible to easily change the parameter settings of the recorder via
the user or PC interface, thus permitting optimum and subsequent adaptation
to the monitored process.
The values measured cyclically by the recorder are amplified, digitized and
processed further by a microprocessor system.
In addition to processing of the measured values, the microprocessor system is
responsible for sequence control, self-test, event processing, communication
via the PC interface, control of the step motors of the recording system,
feedbacks from the recording system and the user interface.
The microprocessor system converts the measured value into positioning
commands for the recording system. The recording system draw a continuous
line on the chart paper. You can adjust the measuring and recording ranges
such that the signal is recorded with an optimum resolution and display. It is
also possible to define limits which are constantly recorded in the LA version
as vertical lines. The recorders with alphanumeric text can output an alarm text
if the limit is violated. The number of limits and the alarm function can be
parameterized within wide ranges. If the recorder is equipped with the digital
input/output option, the alarms can be output for further processing.
Recorders with alphanumeric text can output a measured-value table, event
text and recorder text cyclically or event-controlled. The texts must be entered
previously via the user or PC interface when setting up the recorder. The
outputs are made depending on the recorder parameters.

Siemens AG Order No.: C79000-G7376-C188-04


2-8 SIREC P, PA, L, LA Manual
Design and Mode of Operation

2.4 Scope of Delivery

The scope of delivery is listed in Section 8.1.

2.5 Accessories, Consumable Materials

The accessories and consumable materials are listed in Section 8.2.

2.6 Options

The following options are available:


T
T
Digital input/output with 4 inputs and 6 outputs

T
DC 24 V output
PC cable

2.6.1 Digital Input/Output

The input signals (DI1 to DI4) of the four digital inputs are applied to the basic
electronics via opto isolators and processed further on the central processing
unit.
The output signals (DO1 to DO6) of the digital outputs are externally available
at the interface electrically isolated either via opto isolators or via relays
depending on the version.
T Electronic version: the output signals are generated by short-circuit-
resistant semiconductor switches. The switches are controlled via opto
isolators. The semiconductor switches must be powered via an external
voltage source since they are electrically isolated from the basic device.
T Relay version: the electrical isolation is provided by relays whose
changeover contacts are externally available.

2.6.2 DC 24 V Output

The DC 24 V output option can be used for the following purposes:


T
T
Power supply to external transmitters
Power supply to digital input/output
The DC 24 V output module is powered by the secondary winding of the
transformer. The floating output is available as a bipolar terminal on the rear
of the recorder. Refer to Section 8.3 for the ordering data.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 2-9
Design and Mode of Operation

2.6.3 PC Cable

A special cable is required for connection of the recorders to a PC. The plug
housing contains a module for adaptation to the recorder interface. Refer to
Section 8.3 for the ordering data.

2.6.4 SIPROM R - LA/PA

SIPROM R - LA/PA is a Windows desktop for recorder parameterization


which permits simple and convenient operation of the devices (see Section 8.3
for ordering data).

Siemens AG Order No.: C79000-G7376-C188-04


2-10 SIREC P, PA, L, LA Manual
Preparation for Operation

3 Preparation for Operation

This chapter describes all preparations necessary for operation of the


recorders.

3.1 Recorder Identification

The recorders and modules can be identified with respect to their application
and release version by means of various labels:
T
T
Rating plate with object version for recorder
Part No. with release version for modules

Rating plate The rating plate (Fig. 3.1-1) provides information on:
T
T
Recorder type

T
Serial number

T
Object version
Channel assignments (only rating plate on rear).
There are three rating plates on the recorder:
T
T
On the rear (e.g. Fig. 3.2-1),

T
On the left inside the housing (visible after removing the chassis),
On the right side of the chassis
If the input ranges are changed, a blank label can be inscribed using a water-
resistant felt pen and adhered to the part of the rating plate which is no longer
valid.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-1
Preparation for Operation

Object version The "object version" of the recorder can be read from the rating plate (Fig.
3.1-1). The digit marked with a cross identifies the hardware release of the
recorder.

SIEMENS
SIREC LA Linienschreiber
7ND 3125-xxxx
F-Nr.
Serial-No XX-XXX
No de fabr.
X 2 3 4 5 6 7 8 9
CHANNEL
1 xxxx
2 xxxx
3 xxxx
502-010

Fig. 3.1-1 Example of rating plate for LA version

Module release The release version documents the hardware release of modules. The release
version version is indicated on the following relevant modules:
T Central processing unit with power supply (bottom right, visible

T
following removal of chassis)
Chassis (bottom right, visible following removal of chassis)

Siemens AG Order No.: C79000-G7376-C188-04


3-2 SIREC P, PA, L, LA Manual
Preparation for Operation

Firmware The release version of the firmware can be read on a label adhered to the
version EPROM.
The release version can be read on the EPROM label following removal of the
chassis.

Fig. 3.1-2 Positions of EPROM and jumper for 50 / 60 Hz on module


"Central processing unit"

3.2 Jumper Settings 50/60 Hz, Summer Time/Winter Time

The jumpers can be set during operation.

Selection of The measured values are recorded according to an integrating measuring


50/60 Hz procedure. In order to suppress interferences (hum), the measuring period
(integration time) must be matched to the mains frequency. The basic setting is
50 Hz.
The setting can be changed using a jumper on the module "Central processing
unit" (Fig. 3.1-2). If the recorder is powered via a DC supply, the frequency of
the surrounding AC supply must be set.
The chassis must be removed from the housing in order to check or change the
jumper setting (Section 6.10).

Summer time/ Simple switching over between summer time and winter time is possible, in
winter time addition to control via input DI4, using a jumper setting on module "Control"
switchoff (visible on the rear of the removed chassis (Fig. 6.10-1 and Fig. 6.10-2)). The
factory setting is "MEZ".

MEZ = central European time


MESZ = central European summer time

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-3
Preparation for Operation

1 Ground connection for cable screen


2 DC 24 V output (option)
3 Digital input/output (option)
4 Transformer with rating plate
5 Fuse F1
6 Power supply connection (AC 230 V
or AC 115 V)
6a Power supply connection for
DC 24 V design
6b Power supply connection for
AC 24 V design
7 Fuse F2 (only with AC 115/230 V
power supply)
8 Window with channel inscription for
setting of input ranges
9 Connection of channels #1 to #6

Fig. 3.2-1 Rear view of the recorders (AC 24 V design)

Siemens AG Order No.: C79000-G7376-C188-04


3-4 SIREC P, PA, L, LA Manual
Preparation for Operation

3.3 Installation Guidelines

Insert the recorder into the prepared panel cut-out (see Fig. 3.3-1 for
dimensions), insert two clamps into the corresponding positions on the
housing, and tighten the screws. Special clamps must be used when fitting in a
72-mm mosaic system.
The permissible ambient temperature according to the technical data must be
observed at the mounting position. This must be particularly observed when
installing without interspacing.

Note
When installing, observe the safety guidelines in Section 0.

25.5
a
144
144

260 14.5

138+1
-2
2
R

138+1

Minimum opening angle Panel cut-out to DIN 43831


115° for operation

Distance between centers


of 2 adjacent instruments or one above the other 144 mm

Installation in a b

Sheet-steel panel
Sheet-steel desk upright panel 2 to 42 230
Panel or desk upright panel
with basic grid dimensions 72 x 72 39 to 81 195.5
503e-145

Fig. 3.3-1 Dimensions for installation of the recorders

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-5
Preparation for Operation

The following information is generally applicable to installation:


T No special requirements are placed on power supply, measuring and
control cables which do not carry a dangerous contact potential.

T Voltages which are not dangerous to contact are up to DC 50 V or


AC 25 V if they are generated by safety transformers, batteries etc. and
are not connected to other circuits (low-voltage networks with safe
isolation).

T The isolation of power cables with a dangerous contact potential must be


selected according to the max. voltage.

T The cross-section of the protective earth conductor must be selected at


least as large as the largest cross-section of the power cable.

3.4 Mechanical Preparation of Recorder for Operation

Note
Only use recorders with the scales and recording system fitted.

The following points refer to the mechanical preparation of the recorders, and
must be carried out in the defined sequence prior to starting up:

1. Remove chart carriage (Section 6.1)


2. Insert recording system (Section 6.15 to 6.17)
3. Insert roll or fanfold pack (Section 6.7, Section 6.5)
4. Insert chart carriage (Section 6.2)

Siemens AG Order No.: C79000-G7376-C188-04


3-6 SIREC P, PA, L, LA Manual
Preparation for Operation

3.5 Connection of Power Supply

Depending on the recorder design, the connection is for


T
T
AC 230 V or

T
AC 115 V or

T
AC 24 V or
DC 24 V.
Before connecting the recorder, check that the power supply agrees with the
technical data specified on the recorder (Fig. 3.5-1).

Warning
T Check that the operating voltage of the recorder agrees with the supply
voltage to be connected.
T The recorder may only be converted from AC 115 V to AC 230 V or vice
versa by the manufacturer or personnel trained by the manufacturer!
T It must be possible to separate the recorder from the power supply using
the appliance plug or an easily accessible disconnecting device for at
least 1.6 A.
T The appropriate regulations (e.g. DIN VDE) for the installation of power
systems must be observed.
T The cross-section of the PE conductor must be at least as large as that of
the largest cross-section of the power supply, signal or control cables.

AC 230 V 50/60 Hz

25 VA

F1 = F2 = T 160 L 250V

502-011

Fig. 3.5-1 Power supply information on recorder (e.g.: LA version,


AC 230 V design)

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-7
Preparation for Operation

Connection to The connection to an AC 230 V mains supply is made using the supplied
AC 230 V or appliance plug. The correct connection for AC 230 V and AC 115 V is
AC 115 V identical and shown in Fig. 3.5-2.

Warning
Before connecting the appliance plug, make sure that the power supply
connection is dead!

PE

503-139

Fig. 3.5-2 Connection of mains supply

Connection to The connection inscriptions depend on the recorder design. The connection
AC 24 V or must be made to the provided screw terminals according to the defined
DC 24 V inscriptions. The cable must be secured using a grip to reduce the strain
(Fig. 3.5-3).

L L+

N L-

AC 24 V connection DC 24 V connection

Cable clip
Loop for cable
detensioning
503e-140

Fig. 3.5-3 Connection of AC 24 V or DC 24 V

Siemens AG Order No.: C79000-G7376-C188-04


3-8 SIREC P, PA, L, LA Manual
Preparation for Operation

3.6 Connection of Analog Channels

The following types of measurement are possible for each channel:


T
T
DC U or

T
DC I or

T
TC (only recorder design with universal measuring ranges) or
RTD, R (only recorder design with universal measuring ranges)
The type of measurement is set using jumpers.
In order to set the jumpers, you must first remove the window for setting the
input ranges (Fig. 3.6-1). The transparent plastic part can be easily removed by
inserting a small screwdriver at the side.

Ground connection for cable screen

Fig. 3.6-1 Connection of analog channels (example: SIREC L/LA


version with universal measuring range)

Jumper positions Input ranges Measuring ranges


Direct connection TC/RTD/R/Pot./U
(only recorder with
universal range)

±1 V DC U
0/1 V
0.2/1 V
±1 V
±10 V DC U
0/10 V
2/10 V
±10 V
±20 mA DC I
0/20 mA
4/20 mA
±20 mA
Fig. 3.6-2 Jumper settings

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-9
Preparation for Operation

Fig. 3.6-3 Basic connections for standard ranges of recorders (shown


here: e.g. 3-channel line recorder)

Siemens AG Order No.: C79000-G7376-C188-04


3-10 SIREC P, PA, L, LA Manual
Preparation for Operation

Fig. 3.6-4 Basic connections for universal ranges of recorders (shown


here: e.g. multipoint recorder)

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-11
Preparation for Operation

Labels A label with information (Fig. 3.6-5 or Fig. 3.6-6) on the possible connections
of the analog channels is adhered on the transformer (Fig. 3.2-1) above the
window for setting the input ranges.

11

12
+ DC
-
U/I

502-008

Fig. 3.6-5 Possible connections for analog channels in


design with standard measuring ranges

DC U/I The connection is made according to Fig. 3.6-5 and the jumper settings
according to Fig. 3.6-2. The parameters are set according to Section 4.5.3.
13
11

11
11

12
12

12

+ DC
-
U/I TC RTD, R

502-009

Fig. 3.6-6 Label with information on the possible connections for the
analog channels in design with universal measuring ranges

TC Thermocouples can be connected as follows:


T
T
Directly with an internal cold junction

T
Indirectly with an external cold junction at constant temperature
Indirectly with an external cold junction at any temperature

The basic connections are shown in the following Figs. The jumpers of the
input channels are set according to Fig. 3.6-2 and the parameters according to
Section 4.5.3.

Siemens AG Order No.: C79000-G7376-C188-04


3-12 SIREC P, PA, L, LA Manual
Preparation for Operation

Direct (Internal cold junction)


thermocouple
The connections of the thermocouples or the associated equalizing conductors
connection
must be connected directly to the recorder terminals. The temperature of the
terminal block (reference temperature) is measured by the recorder and
compensated. The connection is made as in Fig. 3.6-7.

11

12
+ -

TC
502-038

Fig. 3.6-7 Thermocouple connection

Indirect (External cold junction at constant temperature)


thermocouple The connections of the thermocouple are connected via a cold junction, e.g.
connection, thermostat. The temperature of the cold junction must be parameterized. The
constant cold
cables between the external cold junction and the recorder terminals can be
junction
made using any conductors with the same material (usually Cu). The
temperature
connection is made according to Fig. 3.6-8.
11

12

+ -

TC 502-039

Fig. 3.6-8 Thermocouple connection to external cold junction at


constant temperature

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-13
Preparation for Operation

Indirect (External cold junction at variable temperature)


thermocouple
The connections of the thermocouple are connected via a cold junction at any
connection,
temperature. The temperature of the cold junction must be measured using
variable cold
another channel and is calculated internally. Thermocouples as well as
junction
resistance thermometers are possible for recording the cold junction
temperature
temperature. The connection is made according to Fig. 3.6-9.

11
11

11

11

12
12

12

12
13
+ - + - + -
ϑ

TC TC RTD 502-040

Fig. 3.6-9 Thermocouple connection to external cold junction at


any temperature

RTD, R Thermoelectric resistors as well as standard resistors can be connected as


follows:
T
T
Two-wire measurement
Three-wire measurement

Two-wire This type of connection is preferably selected for a short distance between the
measurement sensor and the recorder. It is necessary to either select the cables with such a
of thermoelectric low resistance that an error in measurement does not occur (Fig. 3.6-10), or
resistance and they must be adjusted to 10 Ω (Fig. 3.6-11).
standard resistance
11
13

12

RTD, R 502-041

Fig. 3.6-10 Two-wire system without additional line compensation


11
13

12

RA

RL1 RL2
ϑ
RL1 + RL2 + RA = 10
RTD, R 502-042

Fig. 3.6-11 Two-wire connection with line compensation (RA) to 10 Ω

Siemens AG Order No.: C79000-G7376-C188-04


3-14 SIREC P, PA, L, LA Manual
Preparation for Operation

Three-wire This type of connection presupposes that the resistances of the cables between
measurement the sensor and terminals 12 and 13 on the recorder are of equal magnitude.
of thermoelectric The connection is made according to Fig. 3.6-12.
resistance and

11
13

12
standard resistance

RTD, R 502-043

Fig. 3.6-12 Three-wire system

Three-wire The resistances of the three cables between the sensor and the recorder must
measurement of also be of equal magnitude with this measurement.
potentiometers
The setting is made according to the Section 4.5.3. Two methods are basically
possible.

1. The cables have such a low resistance that no errors in measurement occur.
11
13

12

100% 0%
R 502-044

Fig. 3.6-13 Connection for potentiometer measurement

2. The total of the full-range resistance of the potentiometer and the cable
resistance is adjusted to 10 Ω using additional external line compensation.
11
13

12

RA3 RA2
RL1
RL3 RL2 RL2 + R A2 = 10

100% 0%
RL3 + R A3 = 10
R 502-045

Fig. 3.6-14: Connection for potentiometer measurement with additional


line compensation (RA2, RA3) to 10 Ω

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-15
Preparation for Operation

3.7 Digital Input/Output

A 25-pin subminiature plug (Fig. 3.7-1 and Fig. 3.7-2) is present on the rear of
the recorder for the option "Digital input/output". See Section 2.6.1 for
technical details.
A 25-pin subminiature plug for connection of the digital input/output is
included in the delivery. The pin assignments are shown in Table 3.7-1 and
Table 3.7-2. Parameterization of the digital input/output is described in Section
4.7.4.
Table 3.7-1 Pin assignments "Digital input/output" (DI1 to DI4)
Plug pin Input Parameterizable functions Remarks
24 Input DI1 Measuring mode normal – on/off Low ⇒ off, High ⇒ on
Measuring mode fast – on/off Low ⇒ off, High ⇒ on
Edge following High ⇒ output
1)
Measured-value table
Edge following High ⇒ output
1)
Event text
1)
Digital channel Recording of time characteristic
12 Input DI2 Chart feed A on Edge following High ⇒ on
Chart feed B on Edge following High ⇒ on, only if
condition for A is not fulfilled
Edge following High ⇒ output
1)
Measured-value table
Edge following High ⇒ output
1)
Event text
1) 2)
Digital channel Recording of time characteristic
Edge following High ⇒ output
1)
25 Input DI3 Measured-value table
Edge following High ⇒ output
1)
Event text
1) 3)
Digital channel Recording of time characteristic
2)
Event marking
13 Input DI4 Control input for
- Chart feed 10 mm to 100 mm Edge following High ⇒ acc. to feed
- Time mark Edge following High ⇒ zero adj.
- Clock synchronization 3:00 Edge following High ⇒
synchronization
- Summer time (MESZ) Low ⇒ MEZ, High ⇒ MESZ
- TEST locking Low ⇒ on, High ⇒ off
Edge following High ⇒ output
1)
Measured-value table
Edge following High ⇒ output
1)
Event text
1) 2)
Digital channel Recording of time characteristic
11 Reference
potential 0 V (DI)
1) Only recorders with alphanumeric text
2) Only without alphanumeric text
3) Max. two channels

Siemens AG Order No.: C79000-G7376-C188-04


3-16 SIREC P, PA, L, LA Manual
Preparation for Operation

Table 3.7-2 Pin assignments "Digital input/output" (DO1 to DO6)


Plug pin Assignments for Assignments for
electronic version relay version
14 Output DO1 Output DO1: NO contact
2 - Common point
15 - NC contact
3 Output DO2 Output DO2: NO contact
16 - Common point
4 - NC contact
17 Output DO3 Output DO3: NO contact
5 - Common point
18 - NC contact
6 Output DO4 Output DO4: NO contact
19 - Common point
7 - NC contact
20 Output DO5 Output DO5: NO contact
8 - Common point
21 - NC contact
9 Output DO6 Output DO6: NO contact
22 - Common point
10 - NC contact
23 Ext. power supply 24 V (DO) -
1 Ext. power supply 0 V (DO) -

In the case of the electronic version, the semiconductor switches separated


from the basic electronics by opto-isolators must be powered from an external
24-V source. If the recorder is equipped with a DC 24 V output (option), this
voltage source can be used as an alternative, taking into account the technical
data (Fig. 3.7-2).
Synchronization of The recorder can synchronize the internal calendar/clock of several devices as
several recorders slaves using a digital input/output. To achieve synchronization, any output of
the digital input/output can be used on the master, and the input DI4 on the
slave. Parameterization is described in Section 4.5.4.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-17
Preparation for Operation

Elektronic version Relay version

Fig. 3.7-1 Connection of digital input/output

Siemens AG Order No.: C79000-G7376-C188-04


3-18 SIREC P, PA, L, LA Manual
Preparation for Operation

Fig. 3.7-2 Example of connection for digital input/output

Explanations on Fig. 3.7-2:


The example shows two recorders with the digital input/output option.
The digital input/output of the top recorder is powered by its own DC 24 V
option output.

The internal calendar/clock is synchronized for the two recorders. The


required synchronization signal is provided via input DI4 by e.g. a master
clock. The clocks of both recorders are set to 3:00 a.m. when the positive edge
of the 24-V pulse arrives. The date remains unchanged.
In addition to this, the digital output DO1 (alarm) of the top recorder triggers a
lamp.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-19
Preparation for Operation

3.8 DC 24 V Output

Following installation of the option "DC 24 V output" by the manufacturer or


by personnel trained by the manufacturer, a bipolar terminal (Fig. 3.8-1) is
available at the rear of the recorder with a floating output for the supply of
external components. The following connections are permissible since the
current output is limited to max. 75 mA:
T Up to three two-wire transmitters with a current consumption of ≤ 25 mA

T
each
Digital input/output

Note
If several two-wire transmitters are powered, these must be connected together
on one side and are thus not electrically isolated from one another. For noise
reasons (differences in potential), this arrangement is only meaningful for
transmitters which are close together. When additionally using the digital
input/output, observe whether switching transients occur, and their effect.

Fig. 3.8-1 Example of connection for two-wire transmitter to the


DC 24 V output option (L version, DC 24 V design)

Siemens AG Order No.: C79000-G7376-C188-04


3-20 SIREC P, PA, L, LA Manual
Preparation for Operation

3.9 Starting Up the Recorder

All recorder settings have already being made in the factory if the recorder has
been delivered according to customer specifications.
The standard settings have been made for recorders delivered without
customer specifications. The standard settings are listed in Section 4
"Operation" in the respective subsections.
If you are not acquainted with the recorder, it is recommendable to start with
simple measurements after working through Sections 1 to 4. Measurements
with the standard settings are most appropriate initially.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 3-21
Preparation for Operation

Siemens AG Order No.: C79000-G7376-C188-04


3-22 SIREC P, PA, L, LA Manual
Operation

4 Operation

The following chapter describes how to operate the recorders.

Note
Replacing the chart and the battery for backing up the clock are described in
Section 6.

You are guided by menus when operating the recorders. The menus provide
information in the form of a table on the respective functions or values for an
input (leaflet "Parameterization – a concise overview").
The input menus consist of several elements which are comprised in turn of
menu code numbers and designations.
In the first input step (selection of row) you decide which function or
parameter is to be called. The red LED lights up.
In the second step (selection of column) you can define or modify the
corresponding setting of the recorder. The red LED flashes.
The input of a menu code number is terminated by ENTER.
You can scroll through the menu using the INC/DEC functions.

4.1 Display and Control Elements

Operation is carried out using four horizontal levers located below the chart
carriage (Fig. 4.1-1). A further lever is present on the side of the chassis. Two
colored LEDs which are also located below the chart carriage serve to support
you when setting up the recorders and for the output of status messages. In
recorders with alphanumeric text, status messages are additionally printed on
the chart paper by means of the text channel (LA version) or the recording
head (PA version) (Section 5).
The PC interface, which is designed as a flat plug, is located between the
service lever and lever 1. It is possible to connect a laptop to this plug in order
to carry out PC-controlled parameterization.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-1
Operation

1 Scale, channel 3 7 Lever 2 13 Scale for P/PA


2 Pen, channel 1 8 LED, red 14 Recording head
3 Pen, channel 2 9 Lever 1 15 Parameterization
4 Pen, channel 3 10 PC interface scale
5 Lever 3 11 Service lever
6 LED, green 12 Parameterization scale
Fig. 4.1-1 Display and control elements at front

Siemens AG Order No.: C79000-G7376-C188-04


4-2 SIREC P, PA, L, LA Manual
Operation

0
0 20
0 20 40
20 60
40 60 80
0 60 80 10
0
80 10 %
10
20
0
10 %
30

0%
40
50
60
70
80
90
10
0
1

4
2

Symbol for lever 4

501e-107

Fig. 4.1-2 Chassis in maintenance position, activation of lever 4


(example: line recorder)

4.2 Display Elements

The recorders are equipped with two colored LEDs whose combined statuses
(on, off, flashing, fast flashing) indicate status messages. Table 4.2-1 lists a
summary of the status messages assigned to the LED statuses.

Table 4.2-1 Summary of LED status messages


LED
Green Red Recorder status

OFF OFF Recorder switched off


OFF Lit Row selection using lever 1 (INC/DEC)
OFF Flashes Column selection using lever 1 (INC/DEC)
OFF Fl. rapidly Column selection (subsequent input)
Lit OFF Recording mode

Lit Lit Processor not running, e.g. low voltage

Flashes Flashes Fault (fatal error)


502e-017

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-3
Operation

4.3 Levers

The levers have different effects. The black service lever and lever 2 act
directly on the mechanics. The other levers act on microswitches whose
signals are processed by the central processing unit. The levers are used for
recording, START, STOP or PAUSE OFF, PAUSE ON, high chart speed and
recorder settings via the PROG and TEST menus.
Feedbacks for the user when setting up the recorders are via the LEDs and the
positions of the pens/recording head. The rows and columns of the PROG and
TEST menus designed in tabular form directly correspond to the value of the
parameterization scale, i.e. a scale value of 15 % corresponds to row 15 or
column 15 depending on the status of the red LED.
The levers are assigned different functions during operation, PAUSE and
when setting up the recorder. Fig. 4.3-1 shows a summary of the lever
functions. These functions are described in detail in the following sections.

Fig. 4.3-1 Summary of lever functions

Siemens AG Order No.: C79000-G7376-C188-04


4-4 SIREC P, PA, L, LA Manual
Operation

4.3.1 Functions of Service Lever and Lever 2

Service lever Í The service lever is used to release the chassis. The chassis must be moved to
Releasing the the maintenance position in order to change the pens or scales. To do this,
chassis briefly move the service lever to the left, and simultaneously pull out the
chassis until this latches in the maintenance position. The chassis must be
returned to its original position following the required operations. To do this,
move the service lever to the left again, and simultaneously push in the chassis
until it latches in place.
The chassis can be completely removed from the housing in order to replace
the battery for backing up the clock (only recorders with alphanumeric text).
To do this, release the chassis in the maintenance position using the service
lever, and pull out the chassis to the front. When inserting the chassis again,
you must again release it at the maintenance position using the service lever.
Section 6 describes the above operations in detail.

Lever 2 Î Lever 2 is used to release the chart carriage from the chassis. This is necessary
Releasing the in order e.g. to replace the chart.
chart carriage
Section 6 describes the above operations in detail.

4.3.2 Functions of Levers 1, 3 and 4 in Recording Mode (L/LA version)

Lever 1 Í Briefly moving lever 1 (labelled "1") to the left starts a zero adjustment
Zero adjustment without marking. The pens are moved to the right edge and carry out an
adjustment. Recording mode is subsequently continued.

Lever 1 Î Briefly moving lever 1 to the right stops recording (PAUSE ON). The
PAUSE ON recording system is lifted up, and the pens move to the maintenance position
(text channel: approx. 15 %, bottom pen: approx. 40 %, middle pen: approx.
60 %, top pen: approx. 85 %). All instrument functions apart from recording
remain active.

Lever 3 Í Briefly moving lever 3 to the left activates the PROG menu. The following
PROG menu ON actions identify the transition to the parameterization state:
1. Recording system lifts up.
2. All pens are driven to the 100 % mark and carry out an adjustment there.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-5
Operation

3. Channel 1 moves to the code number position for the PROG/TEST menu
and writes a mark which must correspond to the version number of the
PROG/TEST menu (cf. data in leaflet "Parameterization – a concise
overview", version: code number n).
4. The pen for channel 1 moves to the 0 % position and thus indicates "Row
0, PROG menu". The red LED lights up, the green LED is off.
The recorder is now in the parameterization status. All parameters can be set
which are available in the PROG menu.

Note
The function "PAUSE ON" (lever 1 Î) is not required in order to enter the
parameterization status.

The PROG menu is switched off by moving the lever again. The red LED goes
out, the green LED lights up. The recorder is switched back to its original
status. Individual actions:
1. The recording system is lifted up.
2. An adjustment of the pens is carried out at the 100 % mark.
3. The pens move to the measured values.
4. The recording system is lowered, and recording is continued.

Lever 3 Î The lever 3 Î has no function in recording mode.


Lever 4 Ð The chassis must first be moved to the maintenance position before lever 4 can
TEST menu ON be activated.
Lever 4 is used to activate the TEST menu. Lever 4 is accessible on the side of
the chassis and can be moved down e.g. using a ball-point pen (Fig. 4.1-2).

Í
The mechanical sequences of the recording system correspond to those when
activating "Lever 3 ".

Siemens AG Order No.: C79000-G7376-C188-04


4-6 SIREC P, PA, L, LA Manual
Operation

Table 4.3-1 Lever functions in recording mode

Symbol Name Function

SERVICE Service lever Releasing of chassis

1
1. Adjustment of recording system
START Lever 1
2. Continuation of recording

Recording mode
1. Stopping of recording
1 STOP
Lever 1 2. Move pens to maintenance position
3. PAUSE ON

2 Lever 2 Chart carriage released

1. Adjustment of recording system


3 PROG Lever 3 2. Pen moves to 0% (row 0)
3. PROG menu activated

3 Lever 3 None

1. Adjustment of recording system


4
TEST
Lever 4 2. Pen moves to 0% (row 0)
3. TEST menu activated
502e-018

4.3.3 Functions of Levers 1, 3 and 4 in Recording Mode (P/PA version)

Lever 1 Í No function.
Lever 1 Î Briefly moving lever 1 to the right stops recording (PAUSE ON). The
PAUSE ON recording system is lifted up, and the recording head moves to the
maintenance position: approx. 75 %. All instrument functions apart from
recording remain active.

Lever 3 Í Briefly moving lever 3 to the left activates the PROG menu. The following
PROG menu ON actions identify the transition to the parameterization state:
1. Recording system lifts up.
2. The recording head is driven to the 100% mark and carries out an
adjustment there.
3. Channel 1 moves to the code number position for the PROG/TEST menu
and writes a mark which must correspond to the version number of the
PROG/TEST menu (cf. data in leaflet "Parameterization – a concise
overview", version: code number n).
4. Channel 1 moves to the 0% position and thus indicates "Row 0, PROG
menu". The red LED lights up, the green LED is off.
The recorder is now in the parameterization status. All parameters can be set
which are available in the PROG menu.

Note
«
The function "PAUSE ON" (lever 1 ) is not required in order to enter the
parameterization status.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-7
Operation

The PROG menu is switched off by moving the lever again. The red LED goes
out, the green LED lights up. The recorder is switched back to its original
status. Individual actions:
1. The recording system is lifted up.
2. An adjustment of the recording head is carried out at the 100% mark.
3. The recording head moves to the measured values.
4. The recording system is lowered, and recording is continued.

Lever 3 « Lever 3 « has no function in recording mode.


Lever 4 Ð The chassis must first be moved to the maintenance position before lever 4 can
TEST menu ON be activated.
Lever 4 is used to activate the TEST menu. Lever 4 is accessible on the side of
the chassis and can be moved down e.g. using a ball-point pen (Fig. 4.1-2).

Í
The mechanical sequences of the recording system correspond to those when
activating "Lever 3 ".

Table 4.3-2 Lever functions in recording mode (multipoint recorder)

Siemens AG Order No.: C79000-G7376-C188-04


4-8 SIREC P, PA, L, LA Manual
Operation

4.3.4 Functions of Levers 1, 3 and 4 in the PAUSE Status

Recording is not carried out in the PAUSE status. The recording system is
lifted up and is located in the maintenance position. The measurements are
continued, and the measured values stored in a buffer to a limited extent. The
measured values and text outputs (only recorders with alphanumeric text) are
written when returning to recording mode.
Lever 1 Í Termination of PAUSE. Brief activation of lever 1 leads to adjustment of the
PAUSE OFF recording system and continuation of recording.

Lever 3 Í The procedure is described in Section 4.3.2. Reactivation of lever 3 returns to


PROG menu ON the PAUSE status.

Lever 3 Î The chart is moved forward at maximum speed as long as lever 3 is held
Chart feed pressed to the right.

Lever 4 Ð The procedure is described in Section 4.3.2. Reactivation of lever 4 returns to


TEST menu ON the PAUSE status.

Table 4.3-3 Lever functions in the PAUSE status

Symbol Name Function

Service
Service lever Releasing of chassis

1. Adjustment of recording system


1 START Lever 1 2. Continuation of recording
3. PAUSE OFF
1 STOP
Lever 1 None
PAUSE status

2 Lever 2 Chart carriage released

1. Adjustment of recording system


3 PROG Lever 3 2. Pen moves to 0% (row 0)
3. PROG menu activated, renewed activation of lever 3:PAUSE

3 Lever 3 High chart speed

1. Adjustment of recording system


4 Lever 4 2. Pen moves to 0% (row 0)
TEST
3. TEST menu activated, renewed activation of lever 4: PAUSE

502e-019

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-9
Operation

4.3.5 Functions of Levers 1, 3 and 4 with Recorder Settings using PROG Menu

Lever 1 Í The PROG menu is organized as a matrix with rows and columns. In the
DEC parameterization status, the row or column number can be decremented, i.e.
switched by one menu code number in the zero direction with each activation.
If the lever is activated when the pen (line recorder) or recording head
(multipoint recorder) is positioned at zero, this moves to the maximum row or
column value (menu code number).

Lever 1 Î As DEC, except that adjustment of the next higher menu code number is
INC possible (incrementing (INC)).

Lever 3 Í The red LED must light up (selection of row): the PROG menu is switched off,
PROG menu OFF and the recorder returns to the original operating status.

Lever 3 Î The number of the row or column selection currently marked by the pen is
ENTER confirmed and entered. A switch is simultaneously made to the next selection
level. Two cases are possible:
1. Parameterization commences with selection of the row. ENTER is used to
switch to selection of the column, and the currently set value is displayed.
Activating ENTER again switches over to selection of the row again.
Whether you are positioned in selection of a row or column is indicated by
lighting-up or flashing of the red LED.
2. A subsequent input, e.g. text input (only recorders with alphanumeric text),
is provided in the same row for the function to be parameterized, this status
is indicated by fast flashing of the red LED.
Lever 4 Ð Lever 4 has no functions with the PROG menu activated.
Table 4.3-4 Lever functions with PROG menu activated

Siemens AG Order No.: C79000-G7376-C188-04


4-10 SIREC P, PA, L, LA Manual
Operation

4.3.6 Functions of Levers 1, 3 and 4 with Recorder Settings using TEST Menu

Lever 1 Í The TEST menu is organized as a matrix with rows and columns. In the
DEC parameterization status, the row or column number can be decremented, i.e.
switched by one menu code number in the zero direction with each activation.
If the lever is activated when the pen (line recorder) or recording head
(multipoint recorder) is positioned at zero, this moves to the maximum row or
column value (menu code number).

Lever 1 Î As DEC, except that adjustment of the next higher menu code number is
INC possible (incrementing (INC)).

Lever 3 Í Lever 3 Í has no functions with the TEST menu activated.


Lever 3 Î The number of the row or column selection currently marked by the recording
ENTER system is confirmed and entered. A switch is simultaneously made to the next
selection level. Two cases are possible:
1. Parameterization commences with selection of the row. ENTER is used to
switch to selection of the column, and the currently set value is displayed.
Activating ENTER again switches over to selection of the row again.
Whether you are positioned in selection of a row or column is indicated by
lighting-up or flashing of the red LED.
2. A subsequent input, e.g. text input (only recorders with alphanumeric text),
is provided in the same row for the function to be parameterized, this status
is indicated by fast flashing of the red LED.
Lever 4 Ð The red LED must light up (selection of row): the TEST menu is switched off,
TEST menu OFF and the recorder is reset to the original operating status.
Table 4.3-5 Lever functions with TEST menu activated

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-11
Operation

4.4 PC Interface

By using a special cable (Fig. 4.4-1), the recorders can be connected to a PC or


laptop for the following applications:
T Parameterization of recorders via a Windows desktop (SIPROM R)
T PC-controlled calling of measured values
T Storage of recorder parameters on PC storage media.

3V
0
20
40
0 60
10
20 80
30
40
50
60
70
80
90
10
0

2
OG
PR
1

1
2

E
IC
RV
SE

Fig. 4.4-1 Connection to the recorder

Siemens AG Order No.: C79000-G7376-C188-04


4-12 SIREC P, PA, L, LA Manual
Operation

SIPROM R-LA/PA Application


software
SIPROM R-LA/PA software for the line recorders
T SIREC L 7ND3121
T SIREC LA 7ND3125
and the multipoint recorders
T SIREC P/PA 7ND3021

Features
T Graphic desktop corresponding to Windows standard
T Recorder configuration in online or offline mode
T Saving of parameter sets
T Printing of parameter sets
T Online measurement of all channels, display as bargraph and numeric
value including the alarm states
T Documentation integrated as help file

Software requirements
T MS-DOS operating system, version 5.0 or later
T Windows 3.1, 3.11 or Windows for Workgroups 3.11;
Windows must be started in expanded mode

Hardware requirements
T AT-compatible computer
T At least 80386 processor with coprocessor
T At least 6 Mbyte RAM (less also possible, but with limited performance)
T 3 ½ inch diskette drive
T Hard disk at least 7 Mbyte
T VGA graphics card, supported by Windows
T Printer, supported by Windows
T Serial RS-232-C interface (9-contact or 25-contact COM interface)
T Mouse, supported by Windows (recommended)

Coupling to line or multipoint recorder


T Via adapter cable C79453-A3070-S104.
2-wire special plug at process recorder end,
25-pin plug (including RS-232-C converter) at PC end;
adapter (25 to 9) included in delivery.

The connection between the recorder and PC or laptop is made using a special
cable. Operator prompting is provided on the Windows desktop.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-13
Operation

Connect the PC cable to the PC interface of the recorder. The slanted corner of
the plug must be at the top right.
Connect the 25-contact subminiature socket to a vacant interface on the PC.
The PC cable can also be connected to a 9-contact serial interface on the PC by
using the DB9/DB25 adapter.
Further information can be found in the SIPROM R - LA/PA online help.

4.5 Settings using PROG Menu

The following sections explain the settings which can be achieved using the
PROG menu by means of text, figures and examples.
You can call and modify all recording, measurement and alarm settings in the
PROG menu.
Access to the PROG menu can be protected by two interlocking steps. With
interlocking step 1, only the chart feed A can changed, with stage 2, the PROG
menu is completely disabled.

Note
You can orientate yourself using the cross-references, e.g. P[0] (means PROG
menu, row 0), and the associated PROG menu table (leaflet "Parameterization
– a concise overview").

Siemens AG Order No.: C79000-G7376-C188-04


4-14 SIREC P, PA, L, LA Manual
Operation

PROG
P[0] 0 Chart feed A Section 4.5.1
Symbol used for
cross-reference
5 Condition

Section 4.5.1
10 Chart feed B

15 Condition

20 Measured-value table
Section 4.5.2

Section 4.5.3
25 Channel (analog)

30 Mode

35 Measuring range

40 Sensor
Row selection

45 Connection

50 Left value

55 Right value

60 Open-circuit

65 Damping
Section 4.5.4
70 Channel (digital)
LED lit

75 Recording

Section 4.5.5
80 Alarm

85 Mode

90 Channel

95 Value

Section 4.5.6
100 Print

502e-052

Fig. 4.5-1 Summary of PROG menu, rows

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-15
Operation

4.5.1 Chart Feed

P[0], P[10] The parameters for chart feed A or B can be used to define two combinable
Chart feeds A, B speeds for the chart paper. The selectable values are listed in Fig. 4.5-2 .
P[5], P[15] Chart feed A and/or B can be linked to a condition if required so that the chart
Condition feed changes dependent on an event. The possible conditions are shown in Fig.
4.5-2.
Event-dependent The recorder selects chart feed A when switched on. The event sources are
chart feed also processed even if recording is switched off.

Note
The currently active status is retained if no conditions are fulfilled for chart
feeds A and B or if both conditions are fulfilled simultaneously. A change is
made to chart feed B if the condition set for it is fulfilled. The same applies to
a change from B to A.

If an alarm is assigned to a channel, it is reset if the channel is switched off


(mode OFF).

 See Section 4.7.1 for setting example.

Fig. 4.5-2 Programmable parameter "Chart feed"

Siemens AG Order No.: C79000-G7376-C188-04


4-16 SIREC P, PA, L, LA Manual
Operation

Details on L/LA version:


selection of Switching over commences with a marker in the form of small horizontal lines
chart feed on the curves and a fast feed of at least 7 mm such that a setting on the main
time lines – if set – is retained. Small horizontal lines are then again drawn on
the curves, and the recording commences with the new chart feed. At the same
time, the text channel of the LA version starts to write a chart switching line.

Note
If the chart feed is switched over too frequently in succession, the recording
system would be overloaded and the measured values lost. Therefore the
recorder switches over again at the earliest after approx. 30 s.

P/PA version:
The continuous recording is interrupted, and the subsequent measured values
are buffered. If switching over is triggered by an alarm, a line is initially
written with the alarm text, a chart feed is then carried out, and a chart
switching line is written. The buffered values are then traced with the new
chart speed. The relationship to the main time line is not lost by the chart feed.

The following example clarifies the mode of operation of chart feeds A and B
with condition.

Example Chart feed A is set to 20 mm/h [P0.30]. The condition is present at "Input DI2"
[P5.70].
Chart feed B is set to 120 mm/h [P10.40]. The condition is at "/Input DI2"
[P15.75].
Result:
The chart feed is 20 mm/h in measuring mode if the signal at input DI2 is
"High". The chart feed is switched over to 120 mm/h if the signal changes to
"Low". This status is retained until DI2 changes to "High" again. The chart
feed then returns to 20 mm/h.

4.5.2 Measured-value Table (only recorders with alphanumeric text)

P[20] Measured- The recorder prints a measured-value table (Fig. 5.2-1 "Example recording for
value table LA version" or Fig. 5.2-2 "Example recording for PA version") as required
with the following information, if relevant:
T
T
Date and time

T
Channel number

T
Measured value

T
Dimension

T
Symbol for open-circuit
Status of alarms assigned to the channel.
Printing can be triggered cyclically or event-controlled.
Parameterization is carried out according to Fig. 4.5-3.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-17
Operation

Printing the L/LA version:


measured-value The graphic recording is not interrupted when printing the measured-value
table table, i.e. the 2nd and 3rd lines are only printed if the chart feed has reached a
full line height since the last line. If a further trigger function for a measured-
value table or an event text arrives whilst a table is being printed, this is only
commenced when the table has been completely printed and the chart feed has
reached a full line height since the last line.
P/PA version:
Printing of the measured-value table interrupts the continuous trace (the
measured values are buffered, and printed later).
A trigger condition only leads to printing of the measured-value table if a table
is not already in the buffer or being currently printed out when the trigger
condition occurs.
The printout of the measured-value table always coincides with a time mark if
it is carried out cyclically. The first line of the measured-value table is omitted
in this case. The minimum distance between two cyclic printouts is 10 mm.
The measured values at the printed time are stored in intermediate memory
before being output. Only those channels are printed out for which
"Measuring" or "Recording" has been selected.

 See Section 4.7.2. for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


4-18 SIREC P, PA, L, LA Manual
Operation

Fig. 4.5-3 Summary of parameters "Measured-value table"

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-19
Operation

4.5.3 Parameterizing the Analog Channels

The channel-specific variables are set using the parameters for channel
(analog), mode, measuring range, sensor, connection, left value, right value,
open-circuit and damping.
P[25] Analog This is used to select the number of the analog channel you wish to
channel parameterize. The channel number is preceded by the symbol "#" in the
printouts, e.g. #1.
L/LA version:
The recorders have one to three analog channels: #1, #2, #3. The associated
pen is activated following selection of the channel.
The following table lists the channel assignments:
Table 4.5-1 Characteristics of analog channels #1 to #3
Channel #1 Channel #2 Channel #3
Position in Bottom Center Top
recording system

P/PA version:
The multipoint recorder has a recording head with 6 different colors with fixed
assignments to the individual channels. Following selection of the channel, the
recording head rotates to the corresponding number (color).
The channel assignments are shown in the following table:
Table 4.5-2 Assignment of analog channels #1 to #6
Channel Color
1 Violet
2 Red
3 Black
4 Green
5 Blue
6 Brown

The possible setting parameters are shown in Fig. 4.5-4:

Siemens AG Order No.: C79000-G7376-C188-04


4-20 SIREC P, PA, L, LA Manual
Operation

Fig. 4.5-4 Summary of parameter "Channel (analog)"

 See Section 4.7.3 for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-21
Operation

P[30] Mode You can use this parameter to select the "Measuring" or "Recording" mode for
the selected channel (Section 4.5.3). Select "Off" if the measuring and
recording modes are to be switched off. In "Measuring" and "Recording "
modes, the associated channel is scanned cyclically. The alarm is generated by
comparing the measured value with the set alarm value.
In "Recording" mode, the measured values are additionally recorded by the
recording system.

Fig. 4.5-5 Summary of parameter "Channel (analog), Mode"

 See Section 4.7.3 for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


4-22 SIREC P, PA, L, LA Manual
Operation

P[35] Measuring The measuring ranges are selected according to the set input range (Section
range 3.6).
The recording range (left value, right value) is fixed to the measuring range
limits for certain standard ranges (Fig. 4.5-6) and cannot be changed.
With the other measuring ranges, you can enter the start-of-scale and full-scale
values yourself within the range limits. Table 4.5-3 shows the possible values
for the set ranges.

Fig. 4.5-6 Summary of parameter "Channel (analog), Measuring range"

 See Section 4.7.3 for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-23
Operation

P[40] Sensor The parameter "Sensor" is used to define the type of sensor when using
thermocouples or resistor thermometers. The associated linearization values
are automatically taken into account during measured-value processing.
The appropriate operating range of the sensor must be selected when using
resistors, potentiometers or sensors with a voltage output.
The possible settings are shown in Fig. 4.5-7.

Fig. 4.5-7 Summary of parameter "Channel (analog), Sensor"

 See Section 4.7.3 for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


4-24 SIREC P, PA, L, LA Manual
Operation

P[45] Connection This parameter is used to select the input for the reference temperature when
measuring with thermocouples. Select the desired reference point from Fig.
4.5-8.

TC With the setting "Ref.: internal", the temperature of the input terminals is used
as the reference.
Select the setting "Ref.: 0 °C to Ref.: 70 °C" if the external reference point is
held stable at one of the corresponding temperatures. The reference point can
be measured via a further input if the temperature varies.
In this case, select the settings "Ref.: #1" to "Ref.: #6".

RTD, R, Pot. You can select either a three-wire or two-wire connection (Section 4) for
measurements via resistance thermometers, resistors and potentiometers.
Select "RL: 10 Ω" in the case of a two-wire system with adjustment of the line
resistance to 10 Ω.
Select "RL: 0 Ω" if the line resistance is negligibly small.

Fig. 4.5-8 Summary of parameter "Channel (analog), Connection"

 See Section 4.7.3 for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-25
Operation

P[50] Left value The recording range can be set within limits using the parameters "Left value"
P[55] Right value and "Right value", apart from certain standard measuring ranges (Fig. 4.5-9).
The factory-set recording ranges are listed in Table 4.5-3 (default settings for
left value/right value).
The recording range is set numerically for the inputs "Left value" and "Right
value". The input refers to the set measuring range and is set in a uniform
manner. The sign is entered first, followed by 4 digits separated by a decimal
point. If modifications are necessary, only the associated digits or the sign are
overwritten. If illegal inputs are made, adaptation is automatically made
according to the measuring range.

Fig. 4.5-9 Summary of parameter "Channel (analog), Left value and


Right value"

 See Section 4.7.3 for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


4-26 SIREC P, PA, L, LA Manual
Operation

Table 4.5-3 Setting of recording range


Measuring Dimen- Setting range Preset
range sion
Start End Left Right
value value
0/20 mA mA +00.00 +20.00
4/20 mA mA +04.00 +20.00
0/1 V V +0.000 +1.000
0.2/1 V V +0.200 +1.000
0/10 V V +00.00 +10.00
2/10 V V +02.00 +10.00
±20 mA mA -22.00 +22.00 -20.00 +20.00
±1 V V -1.100 +1.100 -1.000 +1.000
±10 V V -21.00 +21.00 -10.00 +10.00
U: ±40 mV mV -44.00 +44.00 -40.00 +40.00
U: ±100 mV mV -110.0 +110.0 -100.0 +100.0
U: ±400 mV mV -440.0 +440.0 -400.0 +400.0
U: ±1000 mV mV -1100. +1100. -1000. +1000.
R: 300 Ω Ω -030.0 +330.0 +000.0 +300.0
R: 1000 Ω Ω -0100. +1100. +0000. +1000.
Pot: 300 Ω % -010.0 +110.0 +000.0 +100.0
Pot: 1000 Ω % -010.0 +110.0 +000.0 +100.0
RTD: Pt 100 °C -0273. +2000. +0000. +0500.
RTD: Ni 100 °C -0273. +2000. +0000. +0100.
TC: J °C -0273. +2000. +0000. +0500.
TC: L °C -0273. +2000. +0000. +0500.
TC: T °C -0273. +2000. +0000. +0400.
TC: U °C -0273. +2000. +0000. +0500.
TC: K °C -0273. +2000. +0000. +0500.
TC: N °C -0273. +2000. +0000. +0500.
TC: E °C -0273. +2000. +0000. +0500.
TC: S °C -0273. +2000. +0800. +1500.
TC: R °C -0273. +2000. +0800. +1500.
TC: B °C -0273. +2000. +0800. +1500.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-27
Operation

P[60] Open-circuit Only recorders with universal measuring ranges. Monitoring is carried out for
an open-circuit in the mV measuring ranges and the TC ranges based on them.
As soon as the internal resistance of the sensor exceeds a certain value, the
recording is continued on the left of the 0 % line in the case of the setting
"< 0 %" (Fig. 4.5-11), and on the right of the 100 % line in the case of
"> 100 %". The recorders with alphanumeric text additionally output the event
"Open-circuit" in the measured-value table (Section 4.5.2) printed on the chart
paper.
An open-circuit is not detected in the setting "OFF".

Fig. 4.5-10 Summary of parameter "Channel (analog), Open-circuit"

 See Section 4.7.3 for setting example.

0 20 40 60 80 100

The recording is to the left of the 0% mark


in the event of an open-circuit and setting
of the parameter "Channel (analog)" to < 0%.

501e-020

Fig. 4.5-11 Example of display with open-circuit for L/LA versions

Siemens AG Order No.: C79000-G7376-C188-04


4-28 SIREC P, PA, L, LA Manual
Operation

P[65] Damping The damping is determined by the time constant of a 1st order low-pass via
which the signal connected to the input terminals of the recorder is filtered.
The output signal of the low-pass is an exponential function following a jump
in the signal at the input. The time constant defines how long it takes until the
output signal has attained 63.2 % of the stationary final value. Set 0 s for
output of unfiltered measured values.

The damping must be set individually for each channel. With the setting
"auto", the damping is automatically adapted to the chart feed. The basic
setting is 0 s. The following Figure shows the parameterizable time constants.

Fig. 4.5-12 Summary of parameter "Channel (analog), Damping"

 See Section 4.7.3 for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-29
Operation

4.5.4 Parameterizing the Digital Channel (only LA version)

P[70] Channel The recorder has two digital channels in addition to the three (LA version) or 6
(digital) (P/PA version) analog channels. An alarm (Section 4.5.5) or a digital input
(Section 4.7) can be selected as the source. The binary signals of the digital
inputs are displayed as a square-wave signal at defined chart positions (Table
4.5-4):

Table 4.5-4 Chart positions of channels (digital)


Channel #1d Channel #2d
Logical 0 ("Low") 81 % 91 %
Logical 1 ("High") 89 % 99 %

The digital channels are recorded in the LA version by the mechanical system
of the text channel. Edges from logical 0 to 1 and logical 1 to 0 as well as
peaks are recorded as continuous lines. Constant signal sequences are recorded
as dashed lines.
Fig. 4.5-13 shows the possible parameters.

 See Section 4.5.4 for setting example.

Fig. 4.5-13 Summary of parameter "Channel (digital)"

Siemens AG Order No.: C79000-G7376-C188-04


4-30 SIREC P, PA, L, LA Manual
Operation

4.5.5 Alarm

The recorder permits the programming of up to six alarms, each of which is


assigned to a fixed output of the digital input/output (option) (Table 3.7-2).
T
T
DO1 Alarm A1

T
DO2 Alarm A2

T
DO3 Alarm A3

T
DO4 Alarm A4

T
DO5 Alarm A5
DO6 Alarm A6

A set alarm becomes active in "Measuring" or "Recording" mode if the set


limit is violated.
The assignments of the alarms to the individual channels, mode and alarm
value are freely selectable. The settings always commence with selection of an
alarm.

 See Section 4.7.5 for setting example.

P[80] Alarm The parameter "Alarm" is used to select one of the available alarms A1 to A6
to which the mode, channel and value apply in a subsequent setting.

P[85] Mode The parameter "Mode" can be used to define whether the alarm is to be
triggered when "MIN" is fallen below or "MAX" exceeded.
With the LA version, limit lines can be drawn parallel to the time axis. These
lines are vertical and approx. 1 mm long. The spacing between the individual
lines is reduced by half if the limit is violated. The lines are drawn by the
mechanical system of the text channel. The alarm symbol, the associated alarm
number, the channel number or the Σ character (with the setting "All channels"
are written cyclically next to the limit lines. The limit line can be set for each
alarm using the parameter "MIN with line" or "MAX with line".
No limit lines can be drawn with the P/PA version.
In the setting "Status" (only available in recorders with option "Digital
input/output"), recorder readiness is signalled if all of the following conditions
are fulfilled:
T
T
Power supply present

T
PROG menu not switched on

T
TEST menu not switched on

T
Recording started

T
Chart paper present
Last adjustment of recording system fault-free.

Use of the status message is particularly meaningful if the recorder cannot be


directly viewed.
L/LA version:
A control signal is output in the position "Time mark" (only available in
recorders with option "Digital input/output") at the start of the zero
adjustment. This signal can be used to synchronize the cyclic zero adjustment
of several recorders using this one as the master.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-31
Operation

An alarm is not output in the position "OFF". All alarms are switched off in
the basic setting.

P[90] Channel The 6 alarms can be freely assigned to the individual analog channels. The
basic setting is as follows:

T
Line recorders:

T
Alarms A1 and A2 to channel 1

T
Alarms A3 and A4 to channel 2
Alarms A5 and A6 to channel 3

T
Multipoint recorders:

T
Alarm A1 to channel 1

T
Alarm A2 to channel 2

T
Alarm A3 to channel 3

T
Alarm A4 to channel 4

T
Alarm A5 to channel 5
Alarm A6 to channel 6

A further possibility is the assignment of a common alarm to the channels in


the setting "All channels" and applies to the channels for which "Measuring"
or "Recording" mode has been selected. The alarm is triggered if the value is
exceeded (MAX) or fallen below (MIN) for at least one of the channels.

P[95] Value The setting "Alarm, Value" is used to define the percentage with respect to the
recording range at which the alarm to be triggered. The selectable range of
values is identical to the recording range and can be set in steps approx. 0.1 %.

Example:
Recording range: Left value = 80 °C
Right value = 180 °C
Alarm value = 40 % (min)

=> The alarm value is triggered by a temperature below 120 °C.

Siemens AG Order No.: C79000-G7376-C188-04


4-32 SIREC P, PA, L, LA Manual
Operation

Fig. 4.5-14 Summary of parameter "Alarm"

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-33
Operation

4.5.6 Print (only recorders with alphanumeric text)

Printing of the configuration data is triggered by the parameter "Print".


LA version: The color of the text channel is black. A different color setting is
not possible.
PA version: The color of the text channel can be freely selected from the
existing colors.

4.6 Settings using TEST Menu

The following sections explain the settings which can be achieved using the
TEST menu by means of text, figures and examples.

Note
You can orientate yourself using the cross-references, e.g. T[0], in the
associated TEST menu table (leaflet "Parameterization – a concise overview").

Siemens AG Order No.: C79000-G7376-C188-04


4-34 SIREC P, PA, L, LA Manual
Operation

TEST

T[0] 0 Measuring mode Section 4.6.1


Symbol used for
cross-reference
5 Diagram Section 4.6.2

10 Cycle

15 Grid

20 Text Section 4.6.3

25 Editing

30 Condition

35 Clock: Mode Section 4.6.4

40 Hours: hh
Selection of row

45 Minutes: mm

50 Day: DD

55 Month: MM

60 Year: YY

65 Section 4.6.5
Control input DI4

70 Language Section 4.6.6


LED lit

75 PROG locking Section 4.6.7

80 Adjustment: Range Section 6.22

85 Channel
Section 6.22.3
90 Test print

Section 6.22.4
95 Maintenance

100 Service Section 6.22.5

502e-051

Fig. 4.6-1 Summary of TEST menu, rows

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-35
Operation

4.6.1 Measuring Mode

T[0] Measuring Five settings are possible for the parameter "Measuring mode". No acquisition
mode of measured values is carried out in the position "OFF", i.e. all other associated
functions such as chart feed and alarm monitoring are also switched off.
The setting "Normal" or "Fast" determines the cycle time. The resolution of
measured values is higher with the setting "Normal". The cycle times can also
be switched on or off via the option "Digital input/output" with DI1.
Measuring mode is carried out with the set cycle time as long as input DI1
remains at "High". Measuring mode is terminated if the signal changes to
"Low".

Fig. 4.6-2 Summary of parameter "Measuring mode"

 See Section 4.7.6 for setting example.

4.6.2 Chart

T[5] Chart The parameter "Chart" is used to select the chart formatting. All texts are
(only recorders with output if recording is switched on with the setting "Alphanumeric ON". These
alphanumeric text) texts include:
T
T
Start line when starting recording

T
Chart switching line when changing the chart feed

T
Text with PAUSE ON

T
Date/time mark and device text

T
Event texts

T
Inscription of limit lines. (L/LA version)
Measured-value table

These texts are suppressed in the setting "Alphanumeric OFF".


Output of the time at the left edge of the chart is suppressed in the setting
"Time OFF". The underline character is still output. The date is still printed
out every 12 h.
The following texts are suppressed with the setting "Status line OFF":

Siemens AG Order No.: C79000-G7376-C188-04


4-36 SIREC P, PA, L, LA Manual
Operation

T
T
Start line when starting recording

T
Chart switching line when changing the chart feed
Text with PAUSE ON

(see Fig. 5.2-1 "Example recording for LA version" and Fig. 5.2-2 "Example
recording for PA version").

 See Section 4.7.7 for setting example.

Start line LA version:


(only recorders with The printout of the start line and the graphic recording commence
alphanumeric text) simultaneously, i.e. the arrangement of the pens means the start line appears in
the chart (see Fig. 5.2-1 "Example recording for LA version").

PA version:
The measured values are buffered during writing of the start line, and
subsequently output (see Fig. 5.2-2).

The start line consists of the word "START", the date, time, active chart feed
and measuring cycle.
An abbreviated start line is printed when the chart feeds A and B are changed.
This line consists of the time and the active chart feed.

T[10] Cycle L/LA version:


This menu item can be used with the line recorders to set the time between two
time marks. The possible settings are shown in the following figure. A time
mark is not output in the position "OFF". Only a zero adjustment is carried out
every 24 h with this setting.

P/PA version:
This menu item can be used with the multipoint recorders to set the dot
sequence. It defines how long a channel is to be displayed or recorded before
switching to the next channel. The possible settings are shown in Fig. 4.6-3. In
the setting "Join" and "Auto", switching over of the channels is carried out
independent of the set chart speed (Table 4.6-1).

Table 4.6-1 Dot sequence (only multipoint recorders)


Chart feed Dot sequence for settings
"Auto" and "Join"
0 mm/h 6s
1 mm/h 12 s
1.25 mm/h 12 s
2.5 mm/h 12 s
5 mm/h 12 s
10 mm/h 9s
20 mm/h 6s
60 mm/h 3s
120 mm/h 3s

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-37
Operation

Fig. 4.6-3 Summary of parameter "Chart"

Time mark (only line A time mark is written cyclically for all channels at the right edge of the chart.
recorders) The time between two markers can be selected between 1 h and 24 h. If the
time mark is to be output for several recorders synchronously, this is possible
via the control input DI1 "Time mark" (T[65.85], see Section 4.6.5).
The used chart feed can be determined for the L version from the distance
between the time marks.

Siemens AG Order No.: C79000-G7376-C188-04


4-38 SIREC P, PA, L, LA Manual
Operation

T[15] Grid This parameter can be used to print a grid on the chart. The vertical distance
(only recorders with between the markers (crosses) is independent of the chart feed. The number of
alphanumeric text) grid divisions over the chart width is selectable (see Table 4.6-2). At chart
feeds from 300 mm/h to 1200 mm/h (only LA version), however, markers are
only output at 0 % and 100 % independent of this setting.

Table 4.6-2 Chart grid


Setting Remarks
OFF Standard setting
Division 1 + 1 +
Division 2 + 1 + 2 +
Division 3 + 1 + 2 + 3 +
Division 4 + 1 + 2 + 3 + 4 +
Division 5 + 1 + 2 + 3 + 4 + 5 +
See fig. 5.2-1
Division 6 + 1 + 2 + 3 + 4 + 5 + 6 +
Division 7 + 1 + 2 + 3 + 4 + 5 + 6 + 7 +

The markers are synchronized with the time mark and independent of the
starting time of the recording (see Fig. 5.2-1 "Example recording for LA
version").

Note
LA version:
A grid printout is only meaningful with slow chart feeds since the grid is
written oblique at fast speeds.

Fig. 4.6-3 shows the possible settings for the parameter "Grid".

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-39
Operation

4.6.3 Text (only recorders with alphanumeric text)

T[20] Text Various texts can be programmed in order to make evaluation and
T[25] Editing documentation of the results easier.
T[30] Condition The recorder can store one "Device text" and six "Event texts" and write these
depending on conditions.
The following conditions can be selected:
T
T
Cyclic

T
Alarms A1 to A6
Digital inputs DI1 to DI4
The editing function is used for entering texts..
Fig. 4.6-4 shows the function set for text, editing and condition.

Fig. 4.6-4 Summary of parameters "Text – Editing – Condition"

Siemens AG Order No.: C79000-G7376-C188-04


4-40 SIREC P, PA, L, LA Manual
Operation

Programming text The editing function provides three characters per column in each of the
columns 0 to 70. Selection of one of three characters is possible using the
lower ranges of the fields 25.0 to 25.10 (1 to 3) for lower-case letters and
25.15 to 25.25 (SHIFT 1 to SHIFT 3) for upper-case letters.
After setting line 25 "Editing", select the character group which contains the
desired letter. The LED flashes rapidly following ENTER. Then select one of
three letters using the fields 25.0 to 25.25 and define upper-case or lower-case
letters at the same time. The LED flashes more slowly following confirmation
with ENTER, the selected character is printed, and the chart transported
forwards until the character is visible.
The next character can then be entered.
Input of the alphanumeric characters is terminated using "End".

 See Section 4.7.8 for setting example.

Note
An extended character set is accessible via the PC interface.

Device text The device text is used for user-specific identification of recorders, e.g. in
order to permit differentiation between several recorders in a larger plant.
The device text consists of the actual text (max. 20 characters), the date and

Î
time. The output is made when the recorder is started, at 12 a.m., 12 p.m., and
when the recording is stopped (lever 1 , PAUSE).
Event text The event text provides information which supports the application, e.g. as a
note to the operating personnel. Up to six different event texts can be
programmed. An event text consists of the actual text (LA version: max. 20
characters, PA version: max. 16 characters) and the time. With the condition
"Cyclic", the texts are output every 20 mm in ascending order up to a chart
feed of 120 mm/h. The texts are output at intervals of 40 mm in the case of
higher chart feeds. The event text can only be output depending on events
(cyclic, alarm, DI1 to DI4). Event texts are stored in intermediate memory to
prevent overwriting of one another.

The format of an event text is shown in Fig. 5.2-1 "Example recording for LA
version" and Fig. 5.2-2 "Example recording for PA version".

Alarm texts are only written on activation of the alarm.


If an alarm text is not parameterized, an alarm marker is written next to the
curve in the channel color (Fig. 5.2-1 "Example recording for LA version" and
Fig. 5.2-2 "Example recording for PA version").

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-41
Operation

4.6.4 Clock (only recorders with alphanumeric text)

T[35] Clock: The recorders with alphanumeric text have an adjustable clock. You can select
Mode either a 24 or 12 hour format. It is possible to synchronize and switch over the
T[40] Hours: hh clock if required via the digital input/output option, control input DI4, using an
T[45] Minutes: mm external signal
T[50] Day: DD
T
T
Clock synchronization 3:00
T[55] Month: MM
Summer time (MESZ).
T[60] Year: YY
In the event of a power failure, the clock component is buffered by a capacitor
for approx. 5 minutes. A battery is required for longer backup times and is
included in the delivery. It is not included in the basic instrument. When
setting the clock, the seconds are set to zero with ENTER following each
input, and the clock started. To permit inputs exact to the minute even if the
parameterization procedure takes > 1 minute, the minutes input should be
entered last. The adjustable values are shown in Fig. 4.6-5.

 Section 4.7.9 shows an example for setting the clock.

Fig. 4.6-5 Summary of parameter "Clock"

Siemens AG Order No.: C79000-G7376-C188-04


4-42 SIREC P, PA, L, LA Manual
Operation

4.6.5 Control Input DI4

T[65] Control The following functions of the recorder can be remote-controlled via the
input DI4 interface "Digital input/output" (option) using control input DI4:
T
T
Chart feed 10 to 100 mm

T
Time mark

T
Clock synchronization

T
Summer/winter time switchover
TEST locking.

None of the above functions is activated in the position "OFF".


Chart feed With the setting "Chart feed 10 ... 100 mm", a corresponding chart feed is
carried out when the signal at control input DI4 changes from "Low" to
"High". With the alphanumeric text function switched on (Section 4.6), the
device text is additionally inserted with the recorders with alphanumeric text.
The chart feed initiated via control input DI4 has the highest priority and is
always carried out independent of the current recorder status.

Time mark; only line The setting "Time mark" is used to synchronize several recorders operating as
recorders slaves. A time mark can be written at the same time on several instruments
when the signal changes from "Low" to "High" at DI4. A zero adjustment is
carried out in addition. The following figure shows an example.

P[85.30]: Alarm, mode "Time mark" T[65.85]: Control input DI4, "Time mark"
T[10.35] Diagram, "Cycle", 1 h T[10.40] Diagram, "Cycle", 2 h

Master Slave Slave

Alarm,
"Time mark" Control input DI4, Control input DI4,
"Time mark" "Time mark"
Digital input/output interface 502e-029

Fig. 4.6-6 Example of time mark and synchronization for several


recorders

A higher value should be set for the time mark on the slave than on the master.
If "OFF" is selected for the time mark, only a zero adjustment is carried out. A
marker is additionally drawn at the right edge of the chart in the case of all
other settings.
Synchronization can also be carried out using any other suitable clock
generator (e.g. master clock with hours signal).

 See Section 4.7.10 for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-43
Operation

Clock sync. 3:00 The setting "Clock sync. 3:00" is used to synchronize the internal clock by
(only recorders with means of a master clock signal and permits accurately timed operation of
alphanumeric text) several recorders. The synchronization is carried out by a change in signal
from "Low" to "High" at DI4. The internal clock is set to 3:00 hours
independent of summer or winter time.

Summer time The time is increased by one hour with the setting "Summer time" if the signal
(MESZ) (only level is "High" at control input DI4.
recorders with
alphanumeric text)
TEST locking With the setting "TEST locking",

T the complete TEST menu is locked

if the signal level is "Low" at control input DI4.

T The complete TEST menu is unlocked

if the signal level is "High" at control input DI4.

The possible settings for control input DI4 are shown in Fig. 4.6-7.

Fig. 4.6-7 Summary of parameter "Control input DI4"

Siemens AG Order No.: C79000-G7376-C188-04


4-44 SIREC P, PA, L, LA Manual
Operation

4.6.6 Language (only recorders with alphanumeric text)

T[70] Language The setting "Language" permits selection of the language for printout of the
recorder settings and error messages. Three languages can be selected. Fig.
4.6-8 shows a summary of the parameter "Language".

Fig. 4.6-8 Summary of parameter "Language"

 See Section 4.7.11 for setting example.

4.6.7 PROG Locking

T[75] PROG You can use the PROG locking to protect the recorder programming from
locking unauthorized or unintentional interventions. In the setting "Stage 1", only
changing the chart feed A (P[0]) is enabled.
The PROG menu is completely disabled in "Stage 2". For unlimited access to
the PROG menu, select the setting "OFF".
Fig. 4.6-9 shows the possible settings.

Fig. 4.6-9 Summary of parameter "PROG locking"

 See Section 4.7.12 for setting example.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-45
Operation

4.7 Parameterization Examples

The following examples will help you to parameterize the recorders. Similar
cases can be easily implemented using the examples by slightly changing the
parameters.
In addition, further examples are present in the leaflet "Operation – a concise
overview".

4.7.1 Setting the Chart Feed

Example: chart feed A = 120 mm/h, condition is alarm A5


No. Lever 1 Lever 3 Lever 4 Description / feedback
1 Å PROG Switch on PROG menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 0 (chart feed A).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 40 (120 mm/h).
5 Æ ENTER Confirm input.
6 Æ INC Red LED lights up (row input).
Å DEC Set line 5 (condition).
7 Æ ENTER Confirm input.
8 Æ INC Red LED flashes (column input).
Å DEC Set column 50 (alarm A5).
9 Æ ENTER Confirm input.
10 Å PROG Switch off PROG menu.

4.7.2 Setting the Output of the Measured-value Table

Example: print measured-value table cyclically every 4 h


No. Lever 1 Lever 3 Lever 4 Description / feedback
1 Å PROG Switch on PROG menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 20 (measured-value table).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 20 (cyclic 4 h).
5 Æ ENTER Confirm input.
6 Å PROG Switch off PROG menu.

Siemens AG Order No.: C79000-G7376-C188-04


4-46 SIREC P, PA, L, LA Manual
Operation

4.7.3 Parameterizing the Analog Channel

Parameterization of a channel always commences with the channel number


(row 25) and ends with the setting for the damping (row 65). The following
example is shown accordingly.

T
Example:

T
Channel number: 2

T
Mode: recording

T
Measuring range: RTD

T
Sensor: Pt 100

T
Connection: three-wire

T
Left value: from presetting +0 °C to -100 °C

T
Right value: presetting +500 °C (no input necessary)

T
Open-circuit: at > 100 %
Damping: 1 s

Channel number
No. Lever 1 Lever 3 Lever 4 Description / feedback
1 Å PROG Switch on PROG menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 25 (analog channel).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 5 (#2).
5 Æ ENTER Confirm input.
Mode
6 Æ INC Red LED lights up (row input).
Å DEC Set row 30 (mode).
7 Æ ENTER Confirm input.
8 Æ INC Red LED flashes (column input).
Å DEC Set column 10 (recording).
9 Æ ENTER Confirm input.
Measuring range
10 Æ INC Red LED lights up (row input).
Å DEC Set row 35 (measuring range).
11 Æ ENTER Confirm input.
12 Æ INC Red LED flashes (column input).
Å DEC Set column 50 (RTD).
13 Æ ENTER Confirm input.
Sensor
14 Æ INC Red LED lights up (row input).
Å DEC Set row 40 (sensor).
15 Æ ENTER Confirm input.
16 Æ INC Red LED flashes (column input).
Å DEC Set column 50 (Pt100).
17 Æ ENTER Confirm input.
Connection
18 Æ INC Red LED lights up (row input).
Å DEC Set row 45 (connection).
19 Æ ENTER Confirm input.
20 Æ INC Red LED flashes (column input).
Å DEC Set column 55 (three-wire).
21 Æ ENTER Confirm input.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-47
Operation

Set left value of +0000. °C (default setting) to -0100. °C (user)


22 Æ INC Red LED lights up (row input).
Å DEC Set row 50 (left value).
23 Æ ENTER Confirm input.
24 Æ INC Red LED flashes (column input).
Å DEC Set column 60 (-): (-0000.).
25 Æ ENTER Confirm input.
26 Æ INC Red LED flashes rapidly (subsequent input for
Å DEC columns). Set column 45 (0): (-0000.).
27 Æ ENTER Confirm input.
28 Æ INC Red LED flashes rapidly (Subsequent input for
Å DEC columns). Set column 0 (1): (-0100.).
29 Æ ENTER Confirm input.
30 Æ INC Red LED flashes rapidly (Subsequent input for
Å DEC columns). Set column 45 (0): (-0100.).
31 Æ ENTER Confirm input.
32 Æ INC Red LED flashes rapidly (Subsequent input for
Å DEC columns). Set column 45 (0): (-0100.).
33 Æ ENTER Confirm input.
34 Æ INC Red LED flashes rapidly (Subsequent input for
Å DEC columns). Set column 50 (.): (-0100.).
35 Æ ENTER Confirm input.
Signal open-circuit at > 100 %
36 Æ INC Red LED lights up (row input).
Å DEC Set row 60 (open-circuit).
37 Æ ENTER Confirm input.
38 Æ INC Red LED flashes (column input).
Å DEC Set column 10 (>100 %).
39 Æ ENTER Confirm input.
Damping 1s
40 Æ INC Red LED lights up (row input).
Å DEC Set row 65 (damping).
41 Æ ENTER Confirm input.
42 Æ INC Red LED flashes (column input).
Å DEC Set column 10 (1 s).
43 Æ ENTER Confirm input.
44 Å PROG Switch off PROG menu.

Siemens AG Order No.: C79000-G7376-C188-04


4-48 SIREC P, PA, L, LA Manual
Operation

4.7.4 Parameterizing the Digital Channel

Parameterization consists of definition of the channel number (row 70) and


selection of a data source to be recorded (alarm A1 to A6, DI1 to DI4).

T
Example:

T
Channel number: #2d
Recording: DI1
Channel number
No. Lever 1 Lever 3 Lever 4 Description / feedback
1 Å PROG Switch on PROG menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 70 (digital channel).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 5 (#2d).
5 Æ ENTER Confirm input.
Recording DI1
6 Æ INC Red LED lights up (row input).
Å DEC Set row 75 (recording).
7 Æ ENTER Confirm input.
8 Æ INC Red LED flashes (column input).
Å DEC Set column 35 (input DI1).
9 Æ ENTER Confirm input.
10 Å PROG Switch off PROG menu.

4.7.5 Parameterizing the Alarms

Parameterization consists of the alarm number (A1 to A6), mode, channel


number and value, i.e. % position on chart paper.

T
Example:

T
Alarm: A4

T
Mode: MAX

T
Channel: #2
Value: 85 % of recorded value

Alarm
No. Lever 1 Lever 3 Lever 4 Description / feedback
1 Å PROG Switch on PROG menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 80 (alarm).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 15 (alarm A4).
5 Æ ENTER Confirm input.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-49
Operation

Mode
6 Æ INC Red LED lights up (row input).
Å DEC Set row 85 (mode).
7 Æ ENTER Confirm input.
8 Æ INC Red LED flashes (column input).
Å DEC Set column 15 (MAX).
9 Æ ENTER Confirm input.
Channel
10 Æ INC Red LED lights up (row input).
Å DEC Set row 90 (channel).
11 Æ ENTER Confirm input.
12 Æ INC Red LED flashes (column input).
Å DEC Set column 5 (#2).
13 Æ ENTER Confirm input.
Value
14 Æ INC Red LED lights up (row input).
Å DEC Set row 95 (value).
15 Æ ENTER Confirm input.
16 Æ INC Red LED flashes (column input).
Å DEC Set position 85 %.
17 Æ ENTER Confirm input.
18 Å PROG Switch off PROG menu.

4.7.6 Parameterizing the Measuring Mode

Parameterization consists of setting the cycle time, where control is possible


via DI1.

T
Example:
Measuring mode: input DI1, fast
Measuring mode
No. Lever 1 Lever 3 Lever 4 Description / feedback
1 TEST È Switch on TEST menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 0 (measuring mode).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 20 (input DI1, fast).
5 Æ ENTER Confirm input.
6 TEST È Switch off TEST menu.

Siemens AG Order No.: C79000-G7376-C188-04


4-50 SIREC P, PA, L, LA Manual
Operation

4.7.7 Parameterizing the Chart (only recorders with alphanumeric text)

Parameterization consists of setting the alphanumeric function on/off,


suppressing the time mark at the left edge, switching the START/STOP text
off, setting the cycle time for alphanumeric outputs and the grid on/off.

T
Example:

T
Chart: time mark: date
Cycle: 6 h
Chart: time mark: date
No. Lever 1 Lever 3 Lever 4 Description / feedback
1 TEST È Switch on TEST menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 5 (chart).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 10 (time mark: date).
5 Æ ENTER Confirm input.
Cycle: 6 h
6 Æ INC Red LED lights up (row input).
Å DEC Set row 10 (cycle).
7 Æ ENTER Confirm input.
8 Æ INC Red LED flashes (column input).
Å DEC Set column 55 (6 h).
9 Æ ENTER Confirm input.
10 TEST È Switch off TEST menu.

4.7.8 Parameterizing Texts (only recorders with alphanumeric text)

Parameterization applies to the device text and six event texts. Output can be
cyclic or linked to a condition.

T
Example:

T
Text: event text 2

T
Editing: temp. 80
Condition: alarm A3
Event text
No. Lever 1 Lever 3 Lever 4 Description / feedback
1 TEST È Switch on TEST menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 20 (text).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 10 (event text 2).
5 Æ ENTER Confirm input.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-51
Operation

Editing
6 Æ INC Red LED lights up (row input).
Å DEC Set row 25 (editing).
7 Æ ENTER Confirm input.
8 Æ INC Red LED flashes (column input).
Å DEC Set column 35 (T U V).
9 Æ ENTER Confirm input.
10 Æ INC Red LED flashes rapidly (subsequent input for
Å DEC columns). Set column 15 (SHIFT 1 (1st character,
upper-case letter "T")): (T).
11 Æ ENTER Confirm input.
12 Æ INC Red LED flashes (column input).
Å DEC Set column 10 (D E F).
13 Æ ENTER Confirm input.
14 Æ INC Red LED flashes rapidly (subsequent input for
Å DEC columns). Set column 5 (2 (2nd character, lower-case
letter "e")): (Te).
15 Æ ENTER Confirm input.
16 Æ INC Red LED flashes (column input).
Å DEC Set column 25 (M N O).
17 Æ ENTER Confirm input.
18 Æ INC Red LED flashes rapidly (subsequent input for
Å DEC columns). Set column 0 (1 (3rd character, lower-case
letter "m")): (Tem).
19 Æ ENTER Confirm input.
20 Æ INC Red LED flashes (column input).
Å DEC Set column 30 (P R S).
21 Æ ENTER Confirm input.
22 Æ INC Red LED flashes rapidly (subsequent input for
Å DEC columns). Set column 0 (1 (4th character, lower-case
letter "p")): (Temp).
23 Æ ENTER Confirm input.
24 Æ INC Red LED flashes (column input).
Å DEC Set column 65 (. : *).
25 Æ ENTER Confirm input.
26 Æ INC Red LED flashes rapidly (subsequent input for
Å DEC columns). Set column 0 (1 (5th character, decimal
point)): (Temp.).
27 Æ ENTER Confirm input.
28 Æ INC Red LED flashes (column input).
Å DEC Set column 0 (space Q Z).
29 Æ ENTER Confirm input.
30 Æ INC Red LED flashes rapidly (subsequent input for
Å DEC columns ). Set column 0 (1 (6th character, space)):
(Temp. ).
31 Æ ENTER Confirm input.
32 Æ INC Red LED flashes (column input).
Å DEC Set column 55 (7 8 9).
33 Æ ENTER Confirm input.
34 Æ INC Red LED flashes rapidly (subsequent input for
Å DEC columns). Set column 5 (2 (7th character "8")):
(Temp. 8).
35 Æ ENTER Confirm input.
36 Æ INC Red LED flashes (column input).
Å DEC Set column 60 (0 # %).
37 Æ ENTER Confirm input.

Siemens AG Order No.: C79000-G7376-C188-04


4-52 SIREC P, PA, L, LA Manual
Operation

38 Æ INC Red LED flashes rapidly (subsequent input for


Å DEC columns). Set column 0 (1 (8th character "0")):
(Temp. 80).
39 Æ ENTER Confirm input.
40 Æ INC Red LED flashes (column input).
Å DEC Set column 75 (end).
41 Æ ENTER Confirm input.
Condition
42 Æ INC Red LED lights up (row input).
Å DEC Set row 30 (condition).
43 Æ ENTER Confirm input.
44 Æ INC Red LED flashes (column input).
Å DEC Set column 20 (alarm A3).
45 Æ ENTER Confirm input.
46 TEST È Switch off TEST menu.

4.7.9 Parameterizing the Time (only recorders with alphanumeric text)

Parameterization permits setting of the time and date for 24 h or 12 h (am/pm)


mode.

T
Example:

T
Mode: 24-hour (already preset and need not be changed)

T
Hours: 13

T
Day: 26.

T
Month: 04

T
Year: 1995
Minutes: 45
Hours: 13
No. Lever 1 Lever 3 Lever 4 Description / feedback
1 TEST È Switch on TEST menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 40 (hours: hh).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 0 (1): (1).
5 Æ ENTER Confirm input.
6 Æ INC Red LED flashes (column input).
Å DEC Set column 10 (3): (13).
7 Æ ENTER Confirm input.
Day: 26.
8 Æ INC Red LED lights up (row input).
Å DEC Set row 50 (day: DD).
9 Æ ENTER Confirm input.
10 Æ INC Red LED flashes (column input).
Å DEC Set column 5 (2): (2).
11 Æ ENTER Confirm input.
12 Æ INC Red LED flashes (column input).
Å DEC Set column 25 (6): (26).
13 Æ ENTER Confirm input

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-53
Operation

Month: 04.
14 Æ INC Red LED lights up (row input).
Å DEC Set row 55 (month: MM).
15 Æ ENTER Confirm input.
16 Æ INC Red LED flashes (column input).
Å DEC Set column 45 (0): (0).
17 Æ ENTER Confirm input.
18 Æ INC Red LED flashes (column input).
Å DEC Set column 15 (4): (04).
19 Æ ENTER Confirm input
Year: 95
20 Æ INC Red LED lights up (row input).
Å DEC Set row 60 (year: YY).
21 Æ ENTER Confirm input.
22 Æ INC Red LED flashes (column input).
Å DEC Set column 40 (9): (9).
23 Æ ENTER Confirm input.
24 Æ INC Red LED flashes (column input).
Å DEC Set column 20 (5): (95).
25 Æ ENTER Confirm input.
Minutes: 45
26 Æ INC Red LED lights up (row input).
Å DEC Set row 45 (minutes: mm).
27 Æ ENTER Confirm input.
28 Æ INC Red LED flashes (column input).
Å DEC Set column 15 (4): (13:4).
29 Æ ENTER Confirm input.
30 Æ INC Red LED flashes (column input).
Å DEC Set column 20 (5): (13:45).
31 Æ ENTER Confirm input
32 TEST È Switch off TEST menu.

4.7.10 Parameterizing the Control Input DI4

Parameterization permits control of one of the following functions via DI4:


chart feed, time mark, clock synchronization 3:00 hours, setting of summer
time and locking. The parameterization "Digital input/output, DI4" is via the
PROG or TEST menu.

T
Example:
Control input DI4: chart feed 50 mm
Chart feed 50 mm
No. Lever 1 Lever 3 Lever 4 Description / feedback
1 TEST È Switch on TEST menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 65 (control input DI4).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 25 (chart feed 50 mm).
5 Æ ENTER Confirm input.
6 TEST È Switch off TEST menu.

Siemens AG Order No.: C79000-G7376-C188-04


4-54 SIREC P, PA, L, LA Manual
Operation

4.7.11 Parameterizing the Language (only recorders with alphanumeric text)

Parameterization permits German, English or French as the language.

Example:
T Language: English

No. Lever 1 Lever 3 Lever 4 Description / feedback


1 TEST È Switch on TEST menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 70 (language).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 5 (English).
5 Æ ENTER Confirm input.
6 TEST È Switch off TEST menu.

4.7.12 Parameterizing the PROG Locking

Parameterization permits the setting of two locking stages.


Example:
T PROG locking: stage 2

No. Lever 1 Lever 3 Lever 4 Description / feedback


1 TEST È Switch on TEST menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set row 75 (PROG locking).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 10 (stage 2).
5 Æ ENTER Confirm input.
6 TEST È Switch off TEST menu.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 4-55
Operation

Siemens AG Order No.: C79000-G7376-C188-04


4-56 SIREC P, PA, L, LA Manual
Measuring and Recording Mode

5 Measuring and Recording Mode

In measuring and recording mode, the measured values are displayed on the
scales and recorded on the chart as an amplitude/time chart. The parameters
such as the chart speed are set in the PROG and TEST menus (Section 4).
Measuring mode can be switched on and off in the TEST menu. Measuring
mode is interrupted if you call the PROG or TEST menu.
In measuring and recording mode, all channels for which measured-value
acquisition is switched on are scanned cyclically, processed and documented
on the chart paper by means of the recording system. Measured values are
linearized if applicable and corrected using auxiliary values such as the
terminal temperature and line resistance. Alarms are generated by comparing
the measured values with the programmed limits.
Buffer time The measured values pass through a buffer before they are recorded. This
prevents values from being lost if there is an interruption in the recording
procedure such as when changing the chart or pen. The measured values are
increasingly compressed as the buffer becomes fuller in that min./max. values
are generated.
The capacity of the buffer corresponds to approx. 10 mm of chart. A chart feed
is carried out if the buffer capacity is exceeded, and the symbol for a buffer
overflow "=><=" is printed out together with a chart switching line.

5.1 Chart Formatting (only recorders with alphanumeric


text)

You should preferably select the recording range (left value and right value)
such that round values result on the measured-value lines. This facilitates
evaluation of the chart and the determination of the absolute values of a curve.
Programming of the left and right values is described in Section 4.5.3.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 5-1
Measuring and Recording Mode

5.1.1 Main Time Line (only recorders with alphanumeric text)

With a correctly set recorder, the time marks are written on the main time
lines. The chart position can be adjusted in the PAUSE status such that the
time marks coincide with the main time lines with a subsequent recording.
After writing the start line (Section 5.1.6), the chart is shifted forwards such
that the time marks are written on the time lines in the future. The chart now
remains adjusted until the recording is interrupted by one of the following
events:
T
T
Parameterize text

T
Print configuration data

T
Removal of chart carriage
Power supply on/off.
The exact operations for setting the main time line are explained in Section 6.

5.1.2 Main Time Line (recorders without alphanumeric text)

Set the recorder to the PAUSE status using lever 1 and note the current time.
Use lever 3 to move the chart forwards until the fictitious time on the chart
with time grid is positioned underneath the three knobs of the scale (Fig. 6.3-
1). Subsequently leave the PAUSE status again using lever 1.
Example:
- Chart speed: 60 mm/h
- Current time on setting to PAUSE status: 11:55 a.m.
The interval between two main chart lines is 10 minutes at this chart speed.
Thus the chart must be set such that the knobs of the scale are positioned
exactly between two main time lines.

Note
The period in the PAUSE status should be kept short so that the buffer time
(approx. 10 mm chart length) is not exceeded.

5.1.3 Device Text (only recorders with alphanumeric text)

An device text is output:


T
T
As part of the switch-on text

T Î
With time marks at 12:00 and 00:00 hours
When recording is stopped (lever 1 , PAUSE ON)
The device text consists of up to 20 characters and can be freely programmed
by the user (Section 4). An device text may be e.g. the plant-specific name of
the recorder.

5-2 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Measuring and Recording Mode

5.1.4 Switch-on Text (only recorders with alphanumeric text)

The switch-on text line consists of the date, time and device text. The line is
printed when the power supply is switched on if measuring mode is not
switched on. The device text consists of up to 20 characters and can be freely
programmed by the user (Section 4).

5.1.5 Event Text (only recorders with alphanumeric text)

An event text Fig. 5.2-1 "Example recording for LA version") can be printed
out cyclically or dependent on events. Up to six event texts can be
programmed with up to 20 characters each (LA) or 16 characters each (PA)
(Section 4) and assigned to the alarms. Possible trigger conditions are:
T
T
Cyclic

T
Alarms A1 ... A6 (if the alarm becomes active)
Input DI1 ... DI4 (only with change in level from Low to High)
The graphic recording is not interrupted when printing the event text. With the
LA version, a further event text or a measured-value table is only printed if the
chart feed has reached a full line height since the last text. This prevents
overwriting.
Event texts which are printed out cyclically consist only of the event text.
Event texts which are controlled by a digital input are only printed out with a
change in level from Low to High. They consist of the time exact down to
seconds, and the device text. Event texts which are controlled by an activated
alarm consist of the time, alarm symbol, channel number assigned to the
alarm, and event text. If the alarm is deactivated, the "Alarm line" is written as
with an activated alarm, but without an event text. If the alarm is assigned to
all channels, the total character "Σ" appears instead of the channel number.
The cyclic output of the event texts depends on the set chart feed.
Table 5.1-1 Output cycle for event text
Chart feed Output cycle Offset from text
to text
1 - 120 mm/h Every 100 mm 20 mm
300 - 1200 mm/h Every 200 mm 40 mm

5.1.6 Start Line (only recorders with alphanumeric text)

The start line (Fig. 5.2-1 "Example recording for LA version") appears each
time measuring mode and the graphic recording have been interrupted and
restarted. The line consists of the word "START", date, time, chart feed and
set measuring cycle.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 5-3
Measuring and Recording Mode

5.1.7 Time Marks (only recorders with alphanumeric text)

A time printout (Fig. 5.2-1 "Example recording for LA version") is made


cyclically at the left edge of the chart depending on the chart feed. A
horizontal marking line is printed as the first character followed by the date
and time in hours and minutes. The date is printed with the first time printout
after 12:00 and 00:00 hours. Either the 24-hour clock or the 12-hour clock can
be used for the time printout.
The intervals between the time marks depend on the set chart feed and are
listed in the following table:
Table 5.1.6-1 Interval between time marks
Chart feed Interval Time interval
[mm/h] [mm] [h] [min]
OFF -- -- --
1 12 12
1.25 10 8
2.5 10 4
5 10 2
10 10 1
20 20 1
60 20 20
120 20 10
300 *) 50 10
600 *) 100 10
1200 *) 200 10
*) Only LA version

5.1.8 Limit Line (only LA version)

Limit lines (Fig. 5.2-1 "Example recording for LA version") can be drawn
parallel to the time axis. The lines are vertical and approx. 2 mm long. The
spaces of the dashed line are halved when an alarm occurs. The limit lines are
written by the text channel.
Section 4 describes the parameterization of these functions (MIN. or MAX.
with line).
The associated alarm status changes when the measured curve cuts the limit
line. The symbol, alarm number, channel number or Σ are written cyclically
next to the limit line.
Note that there is a time offset between the measured curves and the
inscription of the limit line.

5.1.9 Alarm Markers (only P/PA version)

A limit line is not written with the P/PA version. Instead of this, an alarm
marker is written at the "Limit position" if the alarm status has changed. This
comprises an underline character, an alarm symbol and the alarm number
(1...6). In the case of alarms assigned to one single channel, the alarm markers
are written in the channel color, for common alarms they are written in violet.

5-4 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Measuring and Recording Mode

5.1.10 Measured-value Table (only recorders with alphanumeric text)

A measured-value table (Fig. 5.2-1 "Example recording for LA version") can


be printed out cyclically or event-controlled. Only measured values are printed
for channels for which the mode "Measure" or "Record" has been selected.
Possible trigger conditions:
T
T
Cyclically every 1, 2, 3, 4, 12 hours

T
Alarms A1 to A6
Inputs DI1 to DI4

LA version:
The graphic recording is not interrupted when printing the measured-value
table, i.e. the 2nd and 3rd lines are only printed if the chart feed has reached a
full line height since the last line. If a further trigger function for a measured-
value table or an event text arrives whilst a table is being printed, this is only
commenced when the table has been completely printed and the chart feed has
reached a full line height since the last line.
P/PA version:
The continuous recording is interrupted, and the subsequent measured values
are buffered. If switching over is triggered by an alarm, a line is initially
written with the alarm text, a chart feed is then carried out, and a chart
switching line is written. The buffered values are then traced with the new
chart speed. The relationship to the main time line is not lost by the chart feed.
The printout of the measured-value table always coincides with a time mark if
it is carried out cyclically. The first line of the measured-value table is omitted
in this case (reading direction: from bottom to top).
The information of an analog channel comprises (from left to right):
T
T
Channel number, e.g. #3

T
Measured value with sign

T
Dimension of parameterized measuring range

T
Symbol for open-circuit if applicable
Symbols of alarms assigned to the channel

The information of a digital channel comprises (from left to right):


T
T
Channel number with code letter "#d" for digital
Measured value "0" for Low or "1" for High

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 5-5
Measuring and Recording Mode

5.1.11 Grid (only recorders with alphanumeric text)

The text channel (LA version) or channel #3 (black, PA version) can be used
to print a grid on (preferably) unprinted paper. The interval between the grids
depends on the chart feed (see Table 5.1-3). The grids are synchronized with
the time marks and independent of the starting time for recording.
Table 5.1-3 Chart grid
Setting Remarks
OFF Standard setting
Division 1 + 1 +
Division 2 + 1 + 2 +
Division 3 + 1 + 2 + 3 +
Division 4 + 1 + 2 + 3 + 4 +
Division 5 + 1 + 2 + 3 + 4 + 5 +
See fig. 5.2-1
Division 6 + 1 + 2 + 3 + 4 + 5 + 6 +
Division 7 + 1 + 2 + 3 + 4 + 5 + 6 + 7 +

LA version:
The grid crosses at 20, 40, 60 and 80 % are omitted if
T
T
a recorder text is written at 12 a.m. and 12 p.m., and

T
a measured-value table is printed and
an event text is printed.

At a high chart feed, the markers are no longer on a time line, they are written
oblique.
With a chart feed from 300 to 1200 mm/h, only the 0 % and 100 % markers
are written.

5.1.12 Priorities of Text Outputs

The printing of texts is triggered cyclically or event-controlled. The texts are


printed in chronological order. If several texts are waiting to be printed, the
print messages are buffered and the printout of the next text line delayed so
that the texts are not printed over one another.
A congestion of printer messages may occur if a large number of texts occurs
within a short time or large time intervals exist between the text lines because
of a slow chart feed. The recorder carries out the following measures in order
to avoid a buffer overflow in the event of congestion:

5-6 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Measuring and Recording Mode

T If the buffer for print messages is close to overflowing, the printing of


texts is not delayed until they do not overwrite one another.
T Texts which are triggered cyclically and which only contain redundant
information are delayed, or omitted if texts with a higher priority are
present during a complete cycle.
T Texts are printed out in abbreviated form.

The texts are always abbreviated if the printing of a further text with a higher
priority is also present. The following priority list applies:

LA version:

High priority Switch-on line


START line
Chart switching line
Edge of digital channel
Grid
Time mark
Event-controlled measured-value table
Event-controlled event text

Event-controlled time mark and carriage adjustment


Cyclic measured-value table
Cyclic event text
Cyclic carriage adjustment
Cyclic limit lines
Low priority Cyclic digital channel lines

Time marks and edges of digital channels are exceptions for two reasons:
T They are printed without being delayed, i.e. they can be printed over
other texts.

T If a time mark or a digital channel edge occurs whilst printing a text, the
text is only interrupted and not aborted.

PA version:
Event text: high priority
Cyclic texts: low priority

5.1.13 Configuration Data (only recorders with alphanumeric text)

The set configuration data can be printed if required. Printing is triggered


using the PROG menu [100,10] .
Fig. 5.1-1 shows an example of a printout (LA version).

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 5-7
Measuring and Recording Mode

PROG locking OFF


Language English
Control input OFF
Time 05.06.97 06:40'53

Condition OFF
Text5 ....................

Condition OFF
Text4 ....................
Condition OFF
Text3 ....................
Condition OFF
Text2 ....................
Condition OFF
Text1 ....................

Device text Hello Word!

Grid OFF
Cycle 1h
Chart Alphanumeric ON

Measuring mode Normal

Value --- ---


Channel --- ---
Mode OFF OFF
Alarm A5 A6
Value --- ---
Channel --- ---
Mode OFF OFF
Alarm A3 A4

Value --- ---


Channel --- ---
Mode OFF OFF
Alarm A1 A2
Recording OFF Alarm A1
Channel #1d #2d
Damping 0s 0s 0s
Open-circuit --- --- ---
Right value --- --- ---
Left value --- --- ---
Connection --- --- ---
Sensor --- --- ---
Measuring range 4/20mA 4/20mA 4/20mA
Mode Recording Recording Recording
Channel #1 #2 #3
Measured-value table Input DI1
Condition /Input DI2 Input DI2
Chart feed A: 120mm/h B: 1200mm/h

PROG 05.06.97 06:16'17

Fig. 5.1-1 Example of configuration data (LA version)

5-8 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Measuring and Recording Mode

5.1.14 Error Messages and Status Messages (only recorders with alphanumeric
text)

The following error messages and status messages are printed on the chart:
No. Error/status message Remarks
1 EPROM (program memory) defective Inform servicing department
2 EEPROM missing or defective Inform servicing department
1)
3 EEPROM initialized or corrected
2)
4 EEPROM copied
3)
5 Check backup battery
1)
No configuration data have yet been stored, or the stored data did not
correspond to the recorder configuration and have therefore been corrected.
2)
Status message for servicing department.
3)
Following return of the power supply, the clock has been reset to 01.01.85
00:00'00 with the MEZ setting or 01:00'00 with the MESZ setting. This must
be changed when using a battery. The clock must be newly set.

Further error messages and status messages are output on the LEDs
(Table 4.2-1).

5.2 Example Recording with Explanations

Fig. 5.2-1 shows an example recording for the LA version. The same example
basically applies to the L version, but without text outputs and recording of the
digital channels.

Fig. 5.2-2 shows an example recording for the PA version. The same example
basically applies to the P version, but without text outputs.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 5-9
Measuring and Recording Mode

Fig. 5.2-1 "Example recording for LA version"

5-10 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Measuring and Recording Mode

Fig. 5.2-2 "Example recording for PA version"

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 5-11
Measuring and Recording Mode

5-12 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

6 Servicing and Maintenance

This chapter describes servicing and maintenance. The work described must
only be carried out by trained specialists.

Note
Î
An arrow, e.g. "Lever 1 " is used to simplify the description. In this context
the arrow means: "Move lever 1 to right".

6.1 Removing the Chart Carriage

The chart carriage (Fig. 6.5-1 and Fig. 6.7-2) must be removed from the
recorder in order to replace the chart. PAUSE ON must be selected if the
measured values are to be stored in intermediate memory whilst the chart is
being replaced.
Proceed as follows:

Step Measure

Î
1 Open door.
2 Lever 1 PAUSE ON (stop recording). The pens are moved to

Î
the PAUSE status (e.g. L/LA version, see Fig. 6.8-2).
3 Lever 2 release chart carriage.
4 Pull chart carriage out to front using grip (Fig. 6.7-2).

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-1
Servicing and Maintenance

4 5 3 3
3
4

0
10

2 20 3
30
40
50
6
60
1 70
80
90
10
0

7
5
8
7

1 Take-up spool 1)
2 Chart guide
3 Pin wheel with transport roller
4 Transport roller
5 Curved flap
6 Chart supply trough
7 Guide tongue 1)
8 Front flap 502-034
1)
Used only with rolls

Fig. 6.1-1 Front and rear views of chart carriage (without chart paper)

6.2 Inserting the Chart Carriage

Proceed as follows to replace the chart carriage into the recorder following
replacement of the chart:

Step Measure
1 Insert chart carriage into chassis.
2 Press on the grip to push the chart carriage completely into the
recorder until it latches in place.

Í
3 Set the main time line (Section 6.3).
4 Lever 1 PAUSE OFF (start recording).

6-2 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

6.3 Setting the Main Time Line

The position of the chart can be adjusted when in the PAUSE status so that the
time marks coincide with the main time lines during the subsequent graphic
recording.
Recorders with alphanumeric text:
Step Measure

Î
1 Open door
2 Lever 1 PAUSE ON (stop recording). The carriage moves to the

Î
maintenance position (e.g. L/LA version, see Fig. 6.8-2).
3 Lever 3 activate chart high-speed until a time line is positioned
underneath the knobs which are present on the rear of the

Í
adjustment scale (Fig. 6.3-1).
4 Lever 1 PAUSE OFF (start recording).

Recorders without alphanumeric text:


Set the recorder to the PAUSE status using lever 1 and note the current time.
Use lever 3 to move the chart forwards until the fictitious time on the chart
with time grid is positioned underneath the three knobs of the scale (Fig. 6.3-
1). Subsequently leave the PAUSE status again using lever 1.
Example:
- Chart speed: 60 mm/h
- Current time on setting to PAUSE status: 11:55 a.m.
The interval between two main chart lines is 10 minutes at this chart speed.
Thus the chart must be set such that the knobs of the scale are positioned
exactly between two main time lines.

Note
The period in the PAUSE status should be kept short so that the buffer time
(approx. 10 mm chart length) is not exceeded.

The above settings are always required:


R Following parameterization of text
R Following printing of the configuration data
R If the chart carriage has been removed from the chassis, e.g. in order to
replace the chart
R When the recorder has been switched on/off.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-3
Servicing and Maintenance

0 20 40 60 80 100

0 10 20 30 40 50 60 70 80 90 100

Knobs in the adjustment scale


Scale (part of chart carriage)

501e-054

Fig. 6.3-1 Adjustment scale with knobs

6.4 Removing a Fanfold Pack

The steps required to remove the fanfold pack from the chart carriage are
described below.

Step Measure

Î
1 Open door

Î
2 Lever 1 PAUSE ON (stop recording).
3 Use lever 3 (chart high-speed) to transport the chart forwards
until the desired position has been reached.
4 Lift up the front flap of the chart carriage and swing out.
5 Hold fanfold pack in the middle and remove. Tear off along the
perforation in the case of a daily chart record.

Î
6 Swing back front flap and latch in place.
7 Use lever 3 (chart high-speed) to transport the chart paper
forwards until at least one sheet with the preferred fold direction
1)
lies flat on the floor of the chart carriage.
1)

Í
8 Set the main time line (see Section 6.3).
1)
9 Lever 1 PAUSE OFF (start recording).
1)
When removing the daily chart record

6-4 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

6.5 Inserting a Fanfold Pack

When inserting fanfold paper, observe the symbols on the intermediate plate of
the chart supply trough.
Step Measure
1 Remove chart carriage as described in Section 6.1.
2 If necessary, remove the guide tongue (Fig. 6.1-1, 7) according to
Section 6.12 and take out the take-up spool (Fig. 6.1-1, 1).
3 Swing up the curved flap (Fig. 6.1-1, 5).
4 Insert fanfold pack horizontally into the chart supply trough such
that the longitudinal perforation is on the right when viewed from
the front.
5 Pull up three or four sheets of chart, swing back the flap and latch
in place.
6 Swing the chart guide (Fig. 6.1-1, 2) to the front.
7 Pull the chart paper underneath the chart guide and place onto the
pins of the transport roller (Fig. 6.1-1, 4). The time lines of the
chart paper must be parallel to the chart guide.
8 Press down chart guide.
9 Transport the chart paper forwards by rotating on the wheel of the
transport roller until at least one sheet with the preferred fold
direction lies flat on the floor of the chart carriage.
10 Insert chart carriage according to Section 6.2.

Longitudinal holes present on right


0
10
20
30
40
50
60
70
80
90
10
0

501e-104

Fig. 6.5-1 Chart carriage (equipped with fanfold paper)

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-5
Servicing and Maintenance

6.6 Removing a Chart Roll

Step Measure

Î
1 Open door

Î
2 Lever 1 PAUSE ON (stop recording).
3 Use lever 3 (chart high-speed) to transport the chart forwards
until the desired position has been reached.
4 Lift up the front flap of the chart carriage and swing out.
5 Remove the take-up spool (Fig. 6.1-1, 1). When removing a daily
chart record, cut off the chart using scissors.
6 Remove the black flange of the take-up spool, then remove the roll
from the mandrel. Replace flange and insert take-up spool.

Î
7 Swing back front flap and latch in place.
8 Use lever 3 (chart high-speed) to transport the chart forwards
1)
until the beginning is grasped by the take-up spool.
1)

Í
9 Set the main time line (see Section 6.3).
1)
10 Lever 1 PAUSE OFF (start recording).
1)
When removing the daily chart record

6-6 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

6.7 Inserting a Chart Roll


When inserting a roll, observe the symbols on the intermediate plate of the
chart supply trough.
Step Measure
1 Remove chart carriage as described in Section 6.1.
2 If necessary, insert the guide tongue according to Section 6.13.
3 Observe the note at the end of this table.
4 Swing up the curved flap (Fig. 6.1-1, 5).
5 Insert roll into the chart supply trough such that the longitudinal
perforation is on the right when viewed from the front (Fig. 6.7-2).
6 Pull out beginning of chart paper, and swing back the curved flap
again.
7 Swing the chart guide (Fig. 6.1-1, 2) to the front.
8 Pull the chart paper underneath the chart guide and place onto the
pins of the transport roller (Fig. 6.1-1, 3). The time lines of the
chart paper must be parallel to the chart guide.
9 Press down chart guide.
10 Lift up the front flap (Fig. 6.1-1, 8) of the chart carriage and swing
out.
11 Insert the take-up spool (Fig. 6.1-1, 1) into the chart carriage such
that the black flange of the take-up spool is on the right side when
viewed from the front.
12 Press the take-up spool into the chart carriage until the pins slide
into the bearings.
13 Swing back the front flap and latch in place. The teeth then fit into
the take-up spool again.
14 Transport the chart paper forwards by rotating the wheel of the
transport roller until the beginning of the paper is grasped by the
take-up spool.
15 Insert chart carriage according to Section 6.2.

Note
The side edges of the roll must be flat. If necessary, place the roll on a flat
surface with the concave edge downwards and press the convex end flat (Fig.
6.7-1).

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-7
Servicing and Maintenance

502-050

Fig. 6.7-1 Preparation of chart roll

0
10
20
30
40
50
60
70
80
90
10
0

Grip

501e-102

Fig. 6.7-2 Chart carriage (equipped with roll)

6-8 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

6.8 Moving Chassis into Maintenance Position


The chassis must be moved to the maintenance position to permit replacement
of the pens and the scale.
Step Measure
1 Press the service lever to the left, simultaneously grab the front flap
of the chart carriage (Fig. 6.1-1, 8) at the bottom right, and pull out
of the latched position. When released, pull on the left and right of
the front flap until the chassis latches into the maintenance
position.

502-030

Fig. 6.8-1 Releasing the chassis

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-9
Servicing and Maintenance

0
0 20
0 20 40
20 60
40 60 80
0 60 80 10
0
80 10 %
10
20
0
10 %
30

0%
40
50
0 6
70
80
90
10
0
1

501-107a

Fig. 6.8-2 L/LA version, chassis in maintenance position, pens in


PAUSE status

6.9 Returning Chassis from Maintenance Position

Step Measure
1 Push service lever to left, and push back the chassis on the left and
right in the vicinity of the knurled wheels (at top of chart carriage)
until the chassis latches in place.

6-10 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

6.10 Removing Chassis from Housing


The chassis must be completely removed from the housing e.g. to replace the
battery for backing up the clock.
Step Measure
1 Move chassis into maintenance position according to Section 6.8.

Í
2 Loosen the chassis from the maintenance position by again
pressing the service lever and simultaneously pulling to the
front out of the housing. If necessary, disconnect the plug of the
ribbon cable between the chassis and the basic electronics.

Note
The chassis contains modules on which electrostatic sensitive devices are
present. Observe the ESD guidelines!

Battery holder

Jumper
MESZ
MEZ

501e-110

Fig. 6.10-1 Rear of chassis of L/LA version, view onto control module

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-11
Servicing and Maintenance

Fig. 6.10-2 Rear of chassis of P/PA version, view onto control module

6.11 Inserting Chassis into Housing

Step Measure
1 If the chassis has been disconnected from the basic electronics,
reconnect the plug of the ribbon cable to the chassis.
Observe the note at the end of this table.
2 Insert chassis into housing up to maintenance position. The chassis

Í
latches into this position.
3 Move service lever and push chassis completely into the rear
mounting position. It latches in at this position.

Note
You must always compare the serial Nos. on the chassis and on the rating plate
in the housing before inserting the chassis. Chassis from different recorders
must not be interchanged.

6-12 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

6.12 Removing the Guide Tongue

The guide tongue (Fig. 6.1-1, 7) must be removed when using fanfold paper.

Step Measure
1 Remove chart carriage as described in Section 6.1.
2 Lift up the front flap of the chart carriage and swing out. Remove
the take-up spool.
3 Place the chart carriage onto its rear. Hold the guide tongue using
your index finger and thumb. Press onto the latch of the guide
tongue using e.g. a ball-point pen and carefully pull out the tongue.
4 Insert chart carriage according to Section 6.2.

6.13 Inserting the Guide Tongue

The guide tongue (Fig. 6.1-1, 7) must be fitted for use with rolls. The tongue is
inserted into the base of the chart carriage.

Step Measure
1 Remove chart carriage as described in Section 6.1.
2 Lift up the front flap of the chart carriage and swing out. Remove
the chart paper.
3 Insert the wide end of the tongue into the opening in the base of the
chart carriage until the latch of the tongue fits in place.
4 Insert chart carriage according to Section 6.2.

6.14 Labelling and Inserting the Measuring-point Label

Step Measure
1 Bend the measuring-point label and pull out of the lateral guides of
the door.
2 Label the corresponding lines with the channel inscriptions.
3 Bend the label and latch into the lateral guides.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-13
Servicing and Maintenance

6.15 Replacing the Pens for the Analog Channels

Î
Step Measure
1 Use lever 1 PAUSE ON (stop recording). The pens move to the
PAUSE status (Fig. 6.8-2).
2 Move chassis to maintenance position according to Section 6.8.
3 Lift up the scale above the pen, hold the pen on the pointer and pull
out of the carriage fork.
The pens of the upper channels can be removed to permit easier
handling.
4 Plug on new pen.
Note: Never bend the pointer of the pen!
5 Lower scale.

Í
6 Push back chassis according to Section 6.9.
7 Lever 1 PAUSE OFF (start recording)

Note
Channels which are not used for recording must be equipped with a special
dummy pen.

6.16 Replacing the Pen for Alphanumeric Text (only LA


version)

Î
Step Measure
1 Use lever 1 PAUSE ON (stop recording). The pens move to the
PAUSE status (Fig. 6.8-2).
2 Move chassis to maintenance position according to Section 6.8.
3 Lift up the bottom scale, hold the pointer of the alphanumeric text
pen and pull out of its latch.
The pens of the analog channels can be removed to permit easier
handling.
4 Plug on new pen.
5 Lower scale.

Í
6 Push back chassis according to Section 6.9.
7 Lever 1 PAUSE OFF (start recording)

6-14 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

6.17 Replacing the Recording Head (only P/PA version)

Removing the
Î
Step Measures
recording head 1 Use lever 1 PAUSE ON (stop recording). Wait until the
carriage has reached the PAUSE position (75%).
2 Remove chart carriage as described in Section 6.1.
3 Lower the recording head by hand (Fig. 6.17-1) and pull out to the
front.

Fig. 6.17-1 Insertion/removal of recording head

Inserting the Step Measures


recording head 1 Manually lower the mandrel of the recording head carriage if
necessary.
2 Plug the recording head onto the mandrel of the carriage in a
position where the space between the numbers 1 and 2 points
downwards (Fig. 6.17-1), and latch in the recording head by
pressing gently.
3 Swing the recording head upwards into its mounting position.
4 Insert chart carriage as described in Section 6.2.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-15
Servicing and Maintenance

6.18 Replacing the Scale (line recorders)

Î
Step Measure
1 Use lever 1 PAUSE ON (stop recording). The pens move to the
PAUSE status (Fig. 6.8-2).
2 Move chassis to maintenance position according to Section 6.8.
3 Remove all pens above the scale to be replaced as described in
Section 6.15.
4 Remove the scale at the left and right from its support.
5 Plug new scale onto support and latch in on both sides.
6 Insert pens according to Section 6.15.

Í
7 Push back chassis according to Section 6.9.
8 Lever 1 PAUSE OFF (start recording)

6.19 Replacing the Scale (multipoint recorders)

Î
Step Measure
1 Use lever 1 PAUSE ON (stop recording). The recording head
moves to the PAUSE position (75 %) (Fig. 6.17-1).
2 Move chassis to maintenance position according to Section 6.8.
3 Swing the pointer upwards.
4 Bend the scale and pull out of the guides at the side.
5 Bend the new scale and latch first into the left guide and then into
the right guide.
6 Lower the pointer.

Í
7 Push back chassis according to Section 6.9
8 Lever 1 PAUSE OFF (start recording)

6-16 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

6.20 Replacing the Battery (only recorders with


alphanumeric text)

The battery can be replaced during operation. Disconnection from the power
supply is possible for up to approx. 5 min without the time being lost.

Î
Step Measure
1 Use lever 1 PAUSE ON (stop recording). The recording system
moves to the PAUSE status.
2 Remove chassis as described in Section 6.10.
3 Carefully lift battery terminal using screwdriver.
4 Remove battery from holder (Fig. 6.10-1 and Fig. 6.10-2) and
dispose of in correct manner.
5 Connect the battery with the correct polarity!

Í
6 Insert chassis according to Section 6.11.
7 Lever 1 PAUSE OFF (start recording)

Note
R Ensure that the battery is connected with the correct polarity.
R Do not recharge the battery, open it, or subject it to heat or fire.
R Dispose of used batteries as toxic waste.

Refer to Section 7.1 for information on the type of battery used.

6.21 Replacing the fuse

Warning
R Disconnect the recorder from the power supply before replacing the fuse.
R Only use fuses of the specified type and with the specified rating.
R Do not use rewired fuses. Short-circuiting of the fuse holder is
impermissible.

Step Measure
1 Unscrew the screw holder.
2 Replace the fuse.
3 Screw in the fuse holder again.

Refer to Section 7.5 for data on the fuse values.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-17
Servicing and Maintenance

6.22 Adjustment, Test Prints, Carriage/Text Positions

6.22.1 Adjustment

T[80] Adjustment: When adjusting the measuring ranges, a reference value is determined for the
Range individual ranges of the input amplifier using external signals and stored in a
non-volatile data memory.
T[85] Channel

Note
The measuring ranges have been adjusted by the manufacturer prior to
delivery. A new adjustment, should this be necessary, must only be carried out
using suitable calibrators.

You require a signal generator or resistance transmitter in order to carry out an


adjustment. Connect the source to the signal input terminals. The error of the
signal generator or resistance transmitter is included as an additional error in
the result of the recorder.
Except for 20 mA and 10 V, the measuring ranges can be adjusted using any
channel. Therefore connect the signal generator or resistance transmitter to the
input terminals of the associated channel or to all input terminals. Connect the
jumpers as in Fig. 3.6-2.
If the recorder is only used in the range setting you have selected, adjustment
of the unused ranges is unnecessary.
The setting "Adjustment" and its subsequent settings support adjustment of the
measuring ranges. The adjustment is carried out by setting the measuring
range and the channel assignment. If an adjustment is required for each
channel, this can be carried out for the individual channels or for all channels
together. The field "Adjust" is subsequently set, and the set measuring range is
automatically adjusted (Fig. 6.22-1).

6-18 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

Fig. 6.22-1 Summary of parameter "Adjustment" and subsequent settings

Table 6.22-1 Adjustment required for DC U/I version


Input ranges Measuring ranges Required adjustment
±1 V 0/1 V 0V
0.2/1 V 1V
±1 V
±10 V 0/10 V 0V
1)
2/10 V 10 V
±10 V
±20 mA 0/20 mA 0 V (0 mA)
1)
4/20 mA 20 mA
±20 mA
1)
Adjustment required for each channel

Table 6.22-2 Adjustment required for DC U/I/TC/RTD/R version


Input ranges Measuring ranges Required adjustment
±1 V 0/1 V 1V
0.2/1 V
±1 V
±10 V
1)
0/10 V 10 V
2/10 V
±10 V
±20 mA
1)
0/20 mA 20 mA
4/20 mA
±20 mA
Direct connection U, TC 40 mV
U, TC 100 mV
U, RTD, R, Pot. 400 mV
U, RTD, R, Pot. 1V
TC, RTD, R, Pot. 0V
400 Ω
2)
RTD, R, Pot.
RTD, R, Pot. 1000 Ω
1)
Adjustment required for each channel
The 300 Ω range is adjusted with 400 Ω.
2)

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-19
Servicing and Maintenance

6.22.2 Carrying Out the Adjustment

The measuring range, channel number and start of automatic adjustment are set by
parameterizing.

T
Example:

T
Range: 20 mA
Channel: 3
Range: 20 mA
No. Lever 1 Lever 3 Lever 4 Description / feedback
1 TEST È Switch on TEST menu.
2 Æ INC Red LED lights up (row input).
Å DEC Set line 80 (Adjustment: Range).
3 Æ ENTER Confirm input.
4 Æ INC Red LED flashes (column input).
Å DEC Set column 5 (20 mA).
5 Æ ENTER Confirm input.
Adjust channel 3
6 Æ INC Red LED lights up (row input).
Å DEC Set line 85 (Channel).
7 Æ ENTER Confirm input.
8 Æ INC Red LED flashes (row input)
Å DEC Set line 10 (#3).
9 Æ ENTER Confirm input.
10 Æ INC Red LED flashes (column input).
Å DEC Set column 30 (Adjust).
11 Æ ENTER Confirm input. Red and green LEDs flash.
If the input signal is 20.0 mA, the green LED stops
flashing when the adjustment has been carried out.
12 TEST È Switch off TEST menu.

6.22.3 Test Print

T[90] Test print Following maintenance and adjustment, you can check the settings and status
of the recording systems using test prints. In addition, the test prints are an
important aid during troubleshooting.

T Test print 1:
A step recording is carried out in steps of 10 % for channel 1 (P/PA
version) or for each channel (L/LA version). No automatic abort.
Purpose: checking of linearity and hysteresis. Correct setting under
"Maintenance, carriage position 1...3" (Section 6.22.4) is a requirement.
T Test print 2:
L/LA version:
A simultaneous and alternating 0 % and 100 % recording is carried out
for all channels. No automatic abort.
Purpose: checking of pen offset between individual channels and
checking of setting "Maintenance, carriage position 1...3".
P/PA:
All six channels are recorded uniformly distributed from 0 to 100 %. No
automatic abort.

6-20 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

T Test print 3:
Output of a complete character set (text channel).
Purpose: checking of text output.
T Test print 4:
Output of rectangular recording with text channel for L/LA version or
channel 1 for P/PA version.
Purpose: checking of linearity and hysteresis with different triggering
modes. No automatic abort.
T Test print 5:
Output of triangular recording.
Purpose: checking of hysteresis to DIN.
T Test prints 6 to 10:
Not used.
Fig. 6.22-2 shows the possible settings for the parameter "Test print".

Fig. 6.22-2 Summary of parameter "Test print"

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-21
Servicing and Maintenance

6.22.4 Maintenance

T[95] Maintenance Line recorders


Six settings are available for maintenance purposes. The recording systems can
be set to the 0 % and 100 % lines using "Carriage position 1" to "Carriage
position 4". The settings "Carriage position 1" to "Carriage position 4" can be
used e.g. to adapt the recording system to the chart which may change as a
result of climatic influences. The setting is limited. You should inform the
servicing department if the 0 % or 100 % line cannot be reached using the
maintenance facilities.
The setting "Text position" is used to change the space between the pens of the
analog channels and the pen of the text channel (only LA version) (see
example on next page). The setting procedure for the recording systems is
terminated by "End". The possible settings are shown in Fig. 6.22-3.

Multipoint recorders
One setting "Maintenance position 1" is available for maintenance purposes. It
can be used to adapt the recording system to the chart which may change as a
result of climatic influences. The setting is limited. You should inform the
servicing department if the 0 % or 100 % line cannot be reached using the
maintenance facilities.

Fig. 6.22-3 Summary of parameter "Maintenance"

6-22 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Servicing and Maintenance

Setting example The vertical spacing between the pens of channel 1 and the pen of the text
for text channel channel is typically 7 mm. The exact spacing must be determined in an
(only LA version) adjustment procedure and stored in the EEPROM. To do this, select the menu
item "Maintenance - Text position" in the TEST menu.

Action Description / feedback


Switch on TEST menu.
4
TEST Green LED goes off, red LED lights up.
Pointer positioned to "0" (measuring mode).
INC
1
DEC Move pointer to "95" (maintenance).

Terminate input.
3 ENTER Red LED flashes, column selection switched on.
Pointer positioned to "0" (end).
INC
1 Move pointer to "25" (text position).
DEC

Terminate input
3 ENTER Red LED flashes rapidly.
The text channel determines the zero point for the character height
in that it moves to the limit. It draws a horizontal line at the center
of the character height.
The pen of the text channel is lifted up, and the chart is set to the
previously calibrated position (approx. 5 mm).
INC Press INC or DEC as often as necessary until the pen of channel 1
1
DEC writes on the line of the text channel. Range of adjustment
8 * 0.2 mm.
Terminate input, the text position is stored.
3 ENTER Red LED flashes, column selection switched on.
Pointer positioned to "25" (text position).
INC
1
DEC
Move pointer to "0" (end).

Terminate input.
3 ENTER Red LED lights up, row selection switched on.
Pointer positioned to "95" (maintenance).
Switch off TEST menu.
4
TEST Green LED lights up, red LED goes off.
The recorder is operating in normal mode.

502e-046

Fig. 6.22-4 Example of text position for text channel:


spacing from measuring channel pens

6.22.5 Service

T[100] Service The setting "Service" provides extended setting possibilities but requires
additional knowledge. The setting is therefore reserved for the servicing
department.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 6-23
Servicing and Maintenance

6.23 Removal of Transport Protection (only PA version)

Step Measure
1 Remove chart carriage as described in Section 6.1.
2 Remove the foam transport protection to the front.
3 Move mandrel for holding the recording head into the upper
position if necessary.
4 Connect power supply to recorder and set to the PAUSE status.
5 Insert recording head as described in Section 6.17.

Fig. 6.23-1 Chassis with transport protection

6.24 Insertion of Transport Protection (only PA version)

Step Measures
1 Set recorder to PAUSE status.
2 Lower recording head and remove.
3 Insert foam transport protection such that the mandrel is supported.
4 Insert the chart carriage as described in Section 6.2

6-24 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Technical Data

7 Technical Data

Note
Only values with tolerances or limits are guaranteed data. Values without
tolerances are informative data without guarantee obligation. The defined error
limits apply following a warming-up time of 30 minutes.

Measuring functions
General data
Error in measurement Class 0.5 to DIN 43782 or IEC 484
Number of channels 1, 2 or 3 for line recorders
6 for multipoint recorders
Channel isolation Electrically isolated via semiconductors
Voltage endurance See Table 7.10-1, protected with varistors
from protective earth conductor
Permissible potential Max. DC 24 V compared to PE
conductor; only measuring circuits with
safe isolation from power supply are
permissible
Input overload Max. 10 % of respective full-scale value
Overload Max. 24 V continuously in DC U range
Max. 50 mA continuously in DC I range
A/D conversion One common dual-slope converter
Resolution 14 ½ bits / 13 ½ bits with normal/fast
Common-mode rejection 90 dB at 47 to 64 Hz
Series-mode rejection 60 dB at 50.0 Hz / 60.0 Hz
Reference conditions
Ambient temperature (23 + 2) °C
Relative humidity (55 + 10) %
Source resistance ≤ 1 kΩ
Potential difference ≤1V
Adjustment interval ≤ 12 months; an additional error of
0.01 %/year must be expected with a
longer interval
Damping 1st order low-pass, 0, 1, 3, 10, 30, 100 s
or automatic adaptation to chart feed
Signal connection 2 (standard design) or 3 (universal design)
screw terminals per channel
2
0.13 to 2.5 mm solid conductor
2
0.13 to 1.5 mm stranded conductor with
sleeves
Terminal designations to DIN 45140

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 7-1
Technical Data

Recorders with standard


measuring ranges
Measuring ranges According to Table 7-1
Input resistance 100 kΩ in the DC U range
50 Ω in the DC I range
Measuring mode
Measuring cycle L/LA version P/PA version
Normal 240 ms 640 ms
Fast 150 ms 400 ms

Measuring duration 40 ms (50 Hz), 331/3 ms (60 Hz)


with normal
20 ms (40 Hz), 16 2/3 ms (60 Hz)
with fast
Tolerance See Table 7-1

Table 7-1 Measuring ranges for standard design


2)
Measuring range Resolution Maximum (typ. 1/3) electric measuring error
Meas. mode Fel = Foffset + Frel + Ftemp
1)
normal
Graphic Foffset Frel Ftemp
Reference value (23+2) °C
% MV (% MV + const) / °C
-1 to +1 V 0.1 mV 0.6 mV 0.05 0.03 + 0.02 mV
0 to +1 V 0.1 mV 0.6 mV 0.05 0.03 + 0.02 mV
0.2 to +1 V 0.1 mV 0.6 mV 0.05 0.03 + 0.02 mV
-10 to +10 V 1 mV 6 mV 0.05 0.03 + 0.2 mV
0 to +10 V 1 mV 6 mV 0.05 0.03 + 0.2 mV
+2 to +10 1 mV 6 mV 0.05 0.03 + 0.2 mV
-20 to +20 mA 2 µA 12 µA 0.05 0.03 + 0.5 µA
0 to +20 mA 2 µA 12 µA 0.05 0.03 + 0.5 µA
+4 to +20 mA 2 µA 12 µA 0.05 0.03 + 0.5 µA

1)
Measuring mode normal The specified values apply to measuring mode normal, they
must be doubled for measuring mode fast; the offset error
Foffset becomes approx. 30 % larger

2)
Measuring error
Foffset Zero error Absolute value specified in table
Frel Increasing error Percentage specified in table multiplied by the value of the
read measured value (% MV)
Ftemp Temperature error at Percentage specified in table multiplied by the value of the
increased ambient read measured value (% MV) plus a constant (const)
temperature specified as an absolute value, total multiplied by the value
of the temperature difference between the reference value
(23+2) °C and the ambient temperature

7-2 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Technical Data

Recorders with universal


measuring ranges
Measuring ranges According to Table 7-2
Input resistance 10 MΩ in the TC / DC U range
at ≤ 1000 mV
100 kΩ in the DC U range at 1 V and 10 V
50 Ω in the DC I range
Tolerance See Table 7-2
Measuring mode
Measuring cycle L/LA version P/PA version
Normal 300 ms 640 ms
Fast 180 ms 400 ms

Measuring duration 40 ms (50 Hz), 33 1/3 ms (60 Hz)


with normal
20 ms (40 Hz), 16 2/3 ms (60 Hz)
with fast
Type of connection for Two-wire or three-wire system
resistance measurements
Open-circuit Monitoring of internal resistance of source
for values between 10 and 20 kΩ;
dependent on measuring range with TC,
RTD and potentiometer measurements

Table 7-2, part 1 Measuring ranges for universal design


2)
Measuring range Resolution Maximum (typ. 1/3) electric measuring error
4)
(linearization range) Meas. mode Fel = Foffset + Frel + Ftemp + Fterminal
1)
normal
3)
Graphic Foffset Frel Ftemp Fterm
Reference value (23+2)°C
% MV (% MV + const) / °C °C
-40 to +40 mV 4 µV 16 µV 0.05 0.02 + 0 mV -
-100 to +100 mV 10 µV 30 µV 0.05 0.02 + 0 mV -
-400 to +400 mV 40 µV 120 µV 0.05 0.02 + 0 mV -
-1000 to +1000 mV 100 µV 300 µV 0.05 0.02 + 0 mV -
-1 to +1 V 0.1 mV 0.3 mV 0.05 0.02 + 0 mV -
0 to +1 V 0.1 mV 0.3 mV 0.05 0.02 + 0 mV -
0.2 to +1 V 0.1 mV 0.3 mV 0.05 0.02 + 0 mV -
-10 to +10 V 1 mV 3 mV 0.05 0.02 + 0 mV -
0 to +10 V 1 mV 3 mV 0.05 0.02 + 0 mV -
+2 to +10 1 mV 3 mV 0.05 0.02 + 0 mV -
-20 to +20 mA 2 µA 6 µA 0.05 0.02 + 0 mA -
0 to +20 mA 2 µA 6 µA 0.05 0.02 + 0 mA -
+4 to +20 mA 2 µA 6 µA 0.05 0.02 + 0 mA -
J (Fe-CuNi)
-100 to +1200 °C 0.2 °C 0.6 °C 0.06 0.02 + 0 °C 0.8
(-210 to +1200 °C)
K (NiCr-Ni)
-100 to +1370 °C 0.3 °C 0.8 °C 0.06 0.02 + 0 °C 0.8
(-270 to +1370 °C)

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 7-3
Technical Data

Table 7-2, part 2 Measuring ranges for universal design


2)
Measuring range Resolution Maximum (typ. 1/3) electric measuring error
4)
(linearization range) Meas. mode Fel = Foffset + Frel + Ftemp + Fterminal
1)
normal
3)
Graphic Foffset Frel Ftemp Fterm
Reference value (23+2)°C
% MV (% MV + const) / °C °C
R (Pt13Rh-Pt)
+100 to +1760 °C 0.5 °C 1.8 °C 0 0.01 + 0.2 °C 0.6
(-50 to +1760 °C)
T (Cu-CuNi)
-100 to +400 °C 0.2 °C 0.6 °C 0.07 0.02 + 0 °C 0.8
(-270 to +400 °C)
S (Pt10Rh-Pt)
+100 to +1760 °C 0.5 °C 1.8 °C 0 0.01 + 0.2 °C 0.6
(-50 to +1760 °C)
N (NiCrSi-NiSi)
-100 to +1300 °C 0.4 °C 1 °C 0.05 0.02 + 0 °C 0.8
(-200 to +1300 °C)
E (NiCr-CuNi)
-100 to +1000 °C 0.15 °C 0.5 °C 0.06 0.02 + 0 °C 0.8
(-270 to +1000 °C)
B (Pt30Rh-Pt6Rh)
+600 to +1820 °C 0.6 °C 2 °C 0 0.01 + 0.2 °C 0.4
(+100 to +1820 °C)
L (FeCu-Ni)
-100 to +900 °C 0.2 °C 0.6 °C 0.06 0.02 + 0 °C 0.8
(-200 to +900 °C)
U (Cu-CuNi)
-100 to +560 °C 0.2 °C 0.6 °C 0.07 0.02 + 0 °C 0.8
(-200 to +560 °C)
R 300 Ω
0 to 300 Ω 0.03 Ω 0.2 Ω 0.07 0.02 + 0.02 Ω -
R 1000 Ω
0 to 1000 Ω 0.1 Ω 0.5 Ω 0.07 0.02 + 0.04 Ω -
Pot. 300 Ω
0 to 100 % 0.01 % 0.05 % 0.07 0.02 + 0.004 % -
Pot. 1000 Ω
0 to 100 % 0.01 % 0.05 % 0.07 0.02 + 0.004 % -
Pt 100
-200 to +800 °C 0.08 °C 0.5 °C 0.05 0.02 + 0.05 °C -
(-200 to +800 °C)
Ni 100
-60 to +180 °C 0.05 °C 0.25 °C 0.07 0.02 + 0.025 °C -
(-60 to +180 °C)
1), 2)
See Table 7-1
3)
Fterm Error of terminal Absolute value specified in table for additional error with direct
temperature measurement connection of thermocouples

4)
Linearization range Measuring range with thermocouples with slightly increased error at
start-of-scale including overload range

7-4 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Technical Data

7.1 Operation, Displays

Display One scale and pointer for measured values (L/LA


version)
One scale and one color each for 6 measured values
(P/PA version)
Green LED for display of recorder readiness
Red LED for display of programming and test status

Operation 2 levers for function settings on front


1 lever for function settings on side
2 levers for service (mechanical release on front)
PC interface For all settings and measured-value scanning
Connection 2-pin plug at front, connection to PC via special
cable (accessory)

Real-time clock only recorders with alphanumeric text


Format Year, month, day, hour, minute, second;
12 / 24-hour representation, summer time/winter
time switchover

Deviation Max. 5 min/year


Backup Via capacitor/battery (Lithium button cell CR 2032)
in event of power failure approx 36 months,
without battery approx. 5 minutes

7.2 Recording

7.2.1 Line Recorders

Chart drive Step motor


Chart feeds A, B 1 1.25 2.5 5 mm/h
10 20 60 mm/h
120 300 600 1200 mm/h
Analog recording system
Pens Replaceable fiber pens
Pen spacing in chart direction 1.5 mm
Colors Red, green, blue
Recording length Approx. 2000 m
Service period Approx. 6 months
Storage life Approx. 24 months in closed packing
Approx. 1 month in recorder with standard
climate
Pen drive Program-controlled step motor
Resolution 0.108 mm
Pen speed Max. 40 mm/s
Recording width (including Approx. 101 mm
alarm signal)
Recording system error Fmech ≤ 0.35 %

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 7-5
Technical Data

Alphanumeric recording system


Pen Replaceable fiber pen
Character height Approx. 2.4 mm or 2.8 mm with descenders
Characters per line 51
Character set ASCII standard with upper-case and lower-
case letters, Greek alphabet, special
characters, binary signals, limit lines etc.
Color Black
Recording length Approx. 100 000 characters
Service period Approx. 6 months
Storage live Approx. 24 months in closed packing
Approx. 1 month in recorder with standard
climate
Pen drive Program-controlled step motors
Printing rate Approx. 0.4 characters/s

7.2.2 Multipoint Recorders

Chart drive Step motor


Chart feeds A, B 1 1.25 2.5 5 mm/h
10 20 60 120 mm/h
Analog recording system
Recording head Replaceable
Colors Violet, red, black, green, blue, brown
Recording length Approx. 2000 m per color
Service period Approx. 6 months
Storage life Approx. 24 months in closed packing
Approx. 1 month in recorder with standard
climate
Recording head drive Program-controlled step motor
Resolution 0.108 mm
Recording head speed Max. 100 mm/s
Recording width (including Approx. 101 mm
alarm signal)
Recording system error Fmech ≤ 0.35 %

7-6 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Technical Data

Alphanumeric recording system


Recording head Integrated
Character height Approx. 2.4 mm or 2.8 mm with descenders
Characters per line 51
Character set ASCII standard with upper-case and lower-
case letters, Greek alphabet, special
characters, binary signals, limit lines etc.
Colors Violet, red, black, green, blue, brown
Recording length Approx. 100 000 characters
Service period Approx. 6 months
Storage live Approx. 24 months in closed packing
Approx. 1 month in recorder with standard
climate
Pen drive Program-controlled step motors
Printing rate Approx. 0.4 characters/s

7.3 Digital Input/Output (Option)

Digital inputs
Switching level Low: -3 to +3 V, High: +8 V to +30 V
Input resistance ≥ 5 kΩ
Digital outputs 6
Electronic version Electrically isolated via opto isolators,
semiconductor switches, short-circuit-
proof, open collector, P-switching
Output current Max. 150 mA
Switching level High: ≥ ext. voltage - 2 V
Ext. power supply 18 to 30 V DC
Current consumption 20 mA + output current of DO1...DO6
Relay version Electrically isolated via relays, floating
switchover contacts
Switching voltage/current 50 V, 1 A
Switching capacity 30 W or 60 VA
8
Contact life 1 x 10 mechanical
6
3 x 10 at max. load
Permissible potential 50 V, only for connection to low-voltage
networks with safe isolation
Connections Subminiature plug, 25-pin, lockable

7.4 DC 24 V Output (Option)

Output DC 24 V ± 15 %, 75 mA, short-circuit-proof,


capacitive load ≤ 33µF

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 7-7
Technical Data

7.5 Power Supply


1)
AC power supplies
Mains voltage AC 115 V +15 to -20 % (7ND3xxx-1xxxx-...)
AC 230 V+15 to -20 % (7ND3xxx-2xxxx-...)
AC 24 V +15 to -20 % (7ND3xxx-3xxxx-...)
Frequency range 47 to 64 Hz
Power consumption 20 VA with options at each rated voltage
Fuse F1/F2 T 160 L 250 V to DIN 41662 for AC 115/230 V
Fuse F1 T 1 L 250 V to DIN 41662 for AC 24 V
2)
DC power supply
Rated voltage DC 24 V +20 to -15 % (7ND3xxx-4xxxx-...)
Power consumption 12 VA with options at rated voltage
Fuse F1 T 1 L 250 V to DIN 41662 for DC 24 V
1)
Secondary switched-mode power supply unit with safe isolation
2)
Primary/secondary switched-mode power supply unit with safe isolation

7.6 Ambient Conditions

Climate
Temperature Tested to IEC 68-2-1/2
DIN EN 60068-2-1/2
Operation 0 °C to +50 °C
Storage/transport -25 °C to +70 °C
Change in temperature
Operation Max. 10 K/h
Storage/transport Max. 20 K/h
Relative humidity
Operation < 75 % at 25 °C, no condensation
Storage/transport < 75 % at 25 °C, no condensation

Mechanical
Vibrations Tested to DIN IEC 68-2-6
Operation 5 to 9 Hz: amplitude 3.5 mm
2
9 to 200 Hz: acceleration 10 m/s
Storage 5 to 9 Hz: amplitude 3.5 mm
2
9 to 500 Hz: acceleration 10 m/s

Earthquakes Tested to KWU AVS DD 7080.9

Operation 5 to 35 Hz:
Max. amplitude 10 mm,
2
Shocks Max. acceleration 15 m/s
Tested to IEC 68-2-27 / DIN EN
Operation 60068-2-27
2
Dropping Half-sine: 150 m/s , (15 g), 11 ms
Storage/transport Tested to DIN EN 60068-2-32
Height < 0.8 m (packed unit)

7-8 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Technical Data

7.7 Mounting Position

To DIN 16257
Operation with roll Vertical -30° to +15°
Operation with fanfold Vertical -15° to +15°

7.8 Degree of Protection

To IEC 529 or EN 60529


Front with door IP 54
Terminals, interfaces, IP 20 (IP 53, option with cover)
plug connectors

7.9 Electric Safety

According to low-voltage guideline 73/23/EEC to EN 61010-1, overvoltage


category II, degree of contamination 2 (IEC 1010-1, VDE 0411 Part 1)

Protection class I

7.10 Electromagnetic Compatibility

The targets of the EMC guideline 89/336/EEC with respect to radio


interference suppression to EN 50081-1 and interference rejection to EN
50082-2, as well as NAMUR recommendation NE 21 are observed.

Radio interference
Power supply Limit class B, measured according to VDE
0875 Part 11 (CISPR 11)

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 7-9
Technical Data

Table 7.10-1 Interference rejection: test conditions and response


Device-under-test Influencing variable Basic standard Instrument
Test condition Response
2)

1)
Instrument RF field AM IEC 1000-4-3 10 V/m A
RF field PM IEC 1000-4-3 10 V/m A
3)
Magnetic field IEC 1000-4-8 -
Discharge IEC 1000-4-2 6 kV / 8 kV A
Process, RF cond. interference IEC 1000-4-6 10 V A
measuring and Burst IEC 1000-4-4 1 kV /2 kV A
4)
control lines Surge IEC 1000-4-5 1 kV / 2 kV B
DC power inputs RF cond. interference IEC 1000-4-6 10 V A
Burst IEC 1000-4-4 2 kV A
4)
Surge IEC 1000-4-5 1 kV / 2 kV A
Interruption IEC SC77BWG3 20 ms / 100 % A
In-rush current ≤ 15 Irated -
AC power input RF cond. interference IEC 1000-4-6 10 V A
Burst IEC 1000-4-4 2 kV A
4)
Surge IEC 1000-4-5 1 kV / 2 kV A
Interruption IEC SC77BWG3 20 ms / 100 % A
In-rush current IEC 1000-3-3 ≤ 15 Irated -
Overshoots IEC 1000-3-2 Class D -
Earth connection RF cond. interference IEC 1000-4-6 10 V A
1) 3V/m in the ranges 87...108, 174...230 and 470...790 MHz
2) A = class accuracy retained during effect
B = interference possible during effect
- = not relevant
3) Not relevant because of measuring and recording procedure used
4) 1 kV symmetric, 2 kV asymmetric

7-10 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Technical Data

7.11 Dimensions, Mounting

Dimensions
Recorder (h x w x d) 144 mm x 144 mm x 260 mm
Mounting
Panel mounting To DIN 43834-A-340
Desk and cabinet To DIN 43834-A-330
mounting
Distance between centers of two
adjacent instruments or one
above the other ≥ 144 mm
Front door Plastic with spring-loaded latch, lock as
option

7.12 Weight

Recorder Approx. 4 kg

7.13 Explanation of Error Data

The total error to be expected results from several types of error which in turn
depend on different influencing variables, the measuring mode, the recorder
programming and the recorder design. The recorders correspond to class 0.5 to
DIN 43782 or IEC 484. The class accuracy of 0.5 does not mean that the error
is always within 0.5 % of the full-scale value or the span under all operating
conditions. It means that the error does not exceed 0.5 % of the reference
value under reference conditions.
The maximum range expansion permissible only results from the accuracy
required for a specific task. There are no recorder limitations for the range
expansion.
The maximum total error to be expected results from the total of the individual
errors. The actual error will generally be much smaller and typically approx.
1/3 of the maximum total error since it can be assumed that not all influencing
variables will have their most unfavourable values, and that some of the
influences will mutually cancel one another.
The error data refer to the chart. A requirement is correct adjustment of the
carriage position in the TEST menu.

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 7-11
Technical Data

Maximum absolute total error: F = Fel + Fmech


Fel See table of measured values
Fmech = 0.35 % • Left value - Right value
Example 1
Recorder design: Measuring ranges of standard design
(line recorders)
Measuring range: +4 mA to +20 mA
Left value: +4 mA
Right value: +20 mA
Actual measured value: 15 mA
Ambient temperature: +28 °C (increase by 3 degrees compared to
reference value)
Fel = 12 µA + 0.05 % • 15 mA +
(0.03 % x 15 mA + 0.5 µA) x3
= 34.5 µA

Fmech = 0.35 % • 16 mA = 56 µA
Maximum absolute
total error: F = 34.5 µA + 56 µA = 90.5 µA
Example 2
Recorder design: Measuring ranges of universal design
(line recorders)
Measuring range: TC
Sensor: Thermocouple type J
Connection: Internal
Left value: +700 °C
Right value: +1050 °C
Actual measured value: +750 °C
Ambient temperature: +18 °C (reduction by 3 degrees compared to
reference value)
Fel = 0.6 °C + 0.06 % • 750 °C +
0.02 % • 750 °C • 3 + 0.6 °C
= 2.1 °C

Fmech = 0.35 % • 350°C = 1.2 °C


Maximum absolute
total error: F = 2.1 °C + 1.2 °C = 3.3°C

7-12 Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual
Scope of Delivery, Options, Accessories

8 Scope of Delivery, Options, Accessories

This chapter lists the scope of delivery, available options, accessories and
consumable material.

8.1 Scope of Delivery

The scope of delivery depends on the order.

Designation Order No.


Documentation
1)
Leaflet "Parameterization – a concise overview" C79000-M7376-C191
1)
Leaflet "Operation – a concise overview" C79000-M7376-C192
Installation Guide C79000-M7364-C193

Fuse F1/F2 for power pack AC 115/230 V W79054-L1010-T160


Fuse F1 for power pack AC 24 V W79054-L1011-T100
Fuse F1 for power pack DC 24 V W79054-L1011-T100
Cable grip for AC or DC 24 V design C79195-Z122-K10
Short-circuit jumpers per channel for design with W79070-G2604-N2
universal measuring ranges
Mains plug for AC 115/230 V supply W79074-B2401-K3

Chart paper (1 off) according to order


Roll (with standard grid) C72452-A94-B212
Fanfold pack (with standard grid) C72452-A94-B266

2 clamps C72165-A405-B176

Blank labels for customer-specific C79453-A3049-C126


extensions/ranges
Ruler per scale 7ND9272-Z

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 8-1
Scope of Delivery, Options, Accessories

8.1.1 Line Recorders

Designation Order No.


Pens (one of each), color corresponding to channel
assignment
Channel 1, red (standard) 7ND9001-8AA
Channel 1, blue 7ND9001-8AB
Channel 2, red 7ND9001-8AE
Channel 2, blue (standard) 7ND9001-8AD
Channel 3, green (standard) 7ND9001-8AG
Alphanumeric, black 7ND9001-8DH

8.1.2 Multipoint Recorders

Designation Order No.


Recording head 7ND9001-8F8

8.2 Available Accessories and Consumable Material

Designation Order No.


Documentation
1)
Manual, complete C79000-G73xx-C188
1)2)
Instruction Manual for SIREC P, PA, L, LA C79000-B73xx-C189
1)
Leaflet "Parameterization – a concise overview" C79000-M73xx-C191
1)
Leaflet "Operation – a concise overview" C79000-M73xx-C192
Installation Instructions C79000-M7364-C193
Parts List C79000-E7363-C194

Chart paper
Roll C72452-A94-B212
Fanfold pack C72452-A94-B266

Battery for clock backup W79084L1002-B1


Take-up spool C72301-A20-B110

Recording unit
For fanfold paper C72301-A20-A16
For rolls and fanfold paper C72301-A20-A17

Jumper for input range W79070-G2604-N2


1)
Language code: xx 00 = German, 76 = English, 77 = French,
78 = Spanish, 72 = Italian
2)
Cannot be ordered separately

Siemens AG Order No.: C79000-G7376-C188-04


8-2 SIREC P, PA, L, LA Manual
Scope of Delivery, Options, Accessories

8.2.1 Line Recorders

Designation Order No.


Scale units
Without scale 7ND9300-8RA
With one scale for single-channel recorder 7ND9300-8RB-Z
With one scale for dual-channel or three-channel
recorder 7ND9300-8RC-Z

Pens
Position Color Channel No.
Bottom Red 1 7ND9001-8AA
Blue 1 7ND9001-8AB
Center Blue 2 7ND9001-8AD
Red 2 7ND9001-8AE
Top Green 3 7ND9001-8AG
Dummy pen C79453-A3049-B522
Text pen for alphanumeric output, black 7ND9001-8DH

Ruler
Without scale 7ND9262
With one scale 7ND9272-Z

Measuring-point label, unlabelled (red, blue, green) C79165-A3029-B367


Measuring-point label, unlabelled (blue, red, green) C79165-A3029-B369

8.2.2 Multipoint Recorders

Designation Order No.


Scale units
Without scale 7ND9300-8QA
With scale 7ND9300-8QB

Recording head 7ND9001-8FB

Roller
Without scale 7ND9262
With one scale 7ND9262-Z

Measuring-point label, unlabelled C79453-A3029-B402

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 8-3
Scope of Delivery, Options, Accessories

8.3 Available Options

The following options can be ordered separately and are fitted in the factory.
The options can also be ordered following delivery of the recorder.
Retrofitting must only be carried out by authorized servicing centers.

Designation Order No.


Digital input/output, electronic, including matching 7ND9400-8BF
plug (mounting part)
Digital input/output, relay, including matching plug 7ND9400-8BE
(mounting part)
DC 24 V output 7ND9400-8BG
PC cable C79453-A3070-B104
Adapter cable for PC interface,
with adapter (25 to 9)
SIPROM R-LA/PA software 7ND3610-1AA11
Operator prompting in German, English, French,
Italian or Spanish

Siemens AG Order No.: C79000-G7376-C188-04


8-4 SIREC P, PA, L, LA Manual
Parts List

9 Parts List

Hinweise für die Bestellung Ordering instructions Exemple de commande


Die Bestellung muß enthalten: All orders should specify the La commande doit comporter :
following:
1. Stückzahl 1. Quantity 1. le no. de référence
2. Bestell-Nr. 2. Order no. 2. la quantité
3. Bezeichnung 3. Designation 3. la désignation
4. Bezeichnung, Bestell- 4. Designation, Order no. 4. la désignation, le n° de
Nr. und Fabrik-Nr. (F-Nr.) and Serial no. (F No.) of réf. et le n° de série de
des Gerätes, zu dem das Er- the instrument to which l’appareil auquel est destinée
satzteil gehört. the spare part belongs. la pièce.
Bestellbeispiel : Ordering instructions : Exemple de commande :
1 St. C79453-A3070-B300 1 pc C79453-A3070-B300 1 x C79453-A3070-B300
Grundelektronik Basic electronics Electronique de base
Fabr.-Nr. ... Serial no. ... N° de série ...

Siemens AG Bestell-Nr.: C79000-G7300-C188-04


SIREC P, PA, L, LA Manual 9-1
Parts List

Ersatzteile für Punktschreiber 7ND3021 und Linienschreiber 7ND3121/3125


Spare parts for point recorder 7ND3021 and Line recorder 7ND3121/3125
Pièces de rechange pour enregistreur par points 7ND3021 et enregistreur à tracé continu 7ND3121/3125

Teil-Nr Bezeichnung Bestellnummer Bemerkungen


Part No. Name Order no. Remarks
N° pièce Désignation N° de référence Remarques
1 Gehäusetür Schutzart IP54
Device door Degree of protection
Porte de boîtier IP54
Protection IP54

1.1 Standardtür ohne Schloß C79165-A3029-B27


Standard door without lock
Porte standard sans serrure

1.2 Standardtür mit Schloß C79165-A3029-B28


Standard door with lock
Porte standard avec serrure

1.3 Reflexarme Tür ohne Schloß C79165-A3029-B29


Low reflex door without lock
Porte antireflet sans serrure

1.4 Reflexarme Tür mit Schloß C79165-A3029-B30


Low reflex door with lock
Porte antireflet avec serrure

2 Motor für Papierantrieb C79453-A3049-B30


Motor for paper drive
Moteur d'entraînement du papier

3 Registrierer komplett RO/FA C72301-A20-A17


Recorder, complete RO/FA
Bloc de déroulement complet
RO/FA

4 Aufwickelrolle C72301-A20-B110
Take-up reel
Bobine réceptrice

5 Schmelzeinsätze
Fuse cartridges
Fusibles

5.1 T 0,16 A/250 V W79054-L1010-T160 Für 127/230 V AC


T 0.16 A/250 V For 127/230 V ac
T 0.16 A/250 V Pour 127/230 V ca

5.2 T 1 A/250 V W79054-L1011-T100 Für 24 V AC/DC


T 1 A/250 V For 24 V ac/dc
T 1 A/250 V Pour 24 V ca/cc

Siemens AG Order No.: C79000-G7376-C188-04


9-2 SIREC P, PA, L, LA Maunual
Parts List

Ersatzteile nur für Punktschreiber 7ND3021


Spare parts for point recorder 7ND3021 only
Pièces de rechange uniquement pour enregistreur par points 7ND3021

Teil-Nr Bezeichnung Bestellnummer Bemerkungen


Part No. Name Order no. Remarks
N° pièce Désignation N° de référence Remarques
1 Nachlaufmotor vormontiert C79453-A3049-B14
Pre-assembled trailing motor
Moteur de mesure prémonté

2 Schreibwagen komplett C79453-A3049-B604


Carriage complete
Chariot complet

2.1 Motor mit Ritzel C79453-A3049-B31


Motor with pinion
Moteur avec pignon

3 Seil komplett C79453-A3049-B5


Cable complete
Câble complet

6 Zeiger C79453-A3049-C43
Pointer
Indicateur

7 Grundelektronik Standard C79453-A3070-B450


Standard basic electronics
Electronique de base standard

8 Grundelektronik universell C79453-A3070-B400


Universal basic electronics
Electronique de base universelle

9 Rückwand/Netzteil
Rear panel/power supply unit
Paroi arrière/bloc d‘alimentation

9.1 230 V AC C79453-A3070-B420


230 V ac
230 V ca

9.2 127 V AC C79453-A3070-B421


127 V ac
127 V ca

9.3 24 V DC C79453-A3070-B422
24 V dc
24 V cc

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 9-3
Parts List

Teil-Nr Bezeichnung Bestellnummer Bemerkungen


Part No. Name Order no. Remarks
N° pièce Désignation N° de référence Remarques
9.4 24 V AC C79453-A3070-B423
24 V ac
24 V ca

10 Abdeckung bedruckt Standard C79453-A3070-C161


Standard cover printed
Couvercle imprimé standard

11 Abdeckung bedruckt universell C79453-A3070-C163


Universal printed cover
Couvercle imprimé universel

Ersatzteile nur für Linienschreiber 7ND3121/3125


Spare parts for line recorder 7ND3121/3125 only
Pièces de rechange uniquement pour enregistreur à tracé continu 7ND3121/3125

Teil-Nr Bezeichnung Bestellnummer Bemerkungen


Part No. Name Order no. Remarks
N° pièce Désignation N° de référence Remarques
1 Motor mit Ritzel C79453-A3049-B32 Für Spindel
Motor with pinion For spindle
Moteur avec pignon Pour broche

2 Motor komplett Schrift C79453-A3070-B10 Für 7ND3125


Motor complete labelling For 7ND3125
Moteur complet écriture Pour 7ND3125

3 Motor Penlift komplett C79453-A3070-B6


Penlift motor complete
Moteur relevage de la plume
complet

4 Zahnriemen C79453-A3049-C518
Toothed belt
Courroie crantée

5 Schreibschlitten C79453-A3049-C531
Carriage
Chariot d’écriture

Siemens AG Order No.: C79000-G7376-C188-04


9-4 SIREC P, PA, L, LA Maunual
Parts List

Teil-Nr Bezeichnung Bestellnummer Bemerkungen


Part No. Name Order no. Remarks
N° pièce Désignation N° de référence Remarques
6 Spindel komplett C79453-A3070-B12
Spindle complete
Broche complète

7 Mutter C79453-A3049-C524
Nut
Ecrou

8 Nachrüstsatz zur C79453-A3070-D7


Meßkanalerweiterung
Retrofit kit for expaning the
measuring channel
Jeu d‘extension de voie de mesure

9 Grundelektronik Standard C79453-A3070-B350


Standard basic electronics
Electronique de base standard

10 Grundelektronik universell C79453-A3070-B250


Universal basic electronics
Electronique de base universelle

11 Rückwand/Netzteil
Rear panel/power supply unit
Paroi arrière/bloc d‘alimentation

11.1 230 V AC C79453-A3070-B360 Für 7ND3121


230 V ac For 7ND3121
230 V ca Pour 7ND3121

11.2 127 V AC C79453-A3070-B361 Für 7ND3121


127 V ac For 7ND3121
127 V ca Pour 7ND3121

11.3 24 V DC C79453-A3070-B362 Für 7ND3121


24 V dc For 7ND3121
24 V cc Pour 7ND3121

11.4 24 V AC C79453-A3070-B363 Für 7ND3121


24 V ac For 7ND3121
24 V ca Pour 7ND3121

11.5 230 V AC C79453-A3070-B255 Für 7ND3125


230 V ac For 7ND3125
230 V ca Pour 7ND3125

11.6 127 V AC C79453-A3070-B256 Für 7ND3125


127 V ac For 7ND3125
127 V ca Pour 7ND3125

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual 9-5
Parts List

Teil-Nr Bezeichnung Bestellnummer Bemerkungen


Part No. Name Order no. Remarks
N° pièce Désignation N° de référence Remarques
11.7 24 V DC C79453-A3070-B257 Für 7ND3125
24 V dc For 7ND3125
24 V cc Pour 7ND3125

11.8 24 V AC C79453-A3070-B258 Für 7ND3125


24 V ac For 7ND3125
24 V ca Pour 7ND3125

12 Abdeckung bedruckt Standard C79453-A3070-C162


Standard printed cover
Couvercle imprimé standard

13 Abdeckung bedruckt universell C79453-A3070-C160


Universal printed cover
Couvercle imprimé universel

Siemens AG Order No.: C79000-G7376-C188-04


9-6 SIREC P, PA, L, LA Maunual
Subject Index

Subject Index
Chart formatting 5-1
--A-- Chassis 2-5
AC 115 V 2-5 With transport protection 6-24
AC 230 V 2-5 Clock 4-42
AC 24 V 2-5 Clock backup 2-6
Accessories 8-1 Clock sync. 3:00 4-44
Adjustment 6-18 Condition 4-40
Alarm 4-31 Configuration data 5-8
Channel 4-32 Connection of AC 24 V or DC 24 V
3-8
Mode 4-31
Connection of analog channels 3-9
Print 4-34
Connection to the recorder 4-12
Value 4-32
Control Input DI4 4-43
Alarm Markers 5-5
Control PCB 2-6
Analog channel 4-20
Conversion 1-2
Connection 4-25
Damping 4-29
Left value 4-26
--D--
DC 24 V 2-5
Measuring range 4-23
DC 24 V output 2-9, 3-20
Mode 4-22
DC U/I 3-12
Right value 4-26
DC voltage (DC U) 1-1
Sensor 4-24
Delivery 1-2
Application 1-1
Design and mode of operation 2-1
Approved use 0-4
Block diagram 2-7
Designs 1-2
--B--
Device text 4-41, 5-2
Basic connections 3-10, 3-11
Digital input/output 2-9, 3-16
Buffer time 5-1
Digital Input/Output
Electronic version 2-9
--C--
Relay version 2-9
Carriage/text positions 6-18
Dimensions 3-5
Catalog: "Recorders" 0-5
Direct current (DC I) 1-1
Central Processing Unit 2-4
Display and control elements 4-1
Channel (digital) 4-30
Channel assignments 3-1
Chart 4-36
--E--
Environmental protection 1-2
Cycle 4-37
Error messages and status messages
Grid 4-39
5-10
Chart carriage 2-6
Event text 4-41, 5-3
Chart feed 4-16, 4-43

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual I
Subject Index

Example of connection for digital Levers 1, 3 and 4 4-5


input/output 3-19
Levers 1, 3 and 4 in the PAUSE status
Example recording 5-10 4-9
Explanation of error data 7-11 Levers 1, 3 and 4 with recorder
settings using PROG menu 4-10
Levers 1, 3 and 4 with recorder
--F-- settings using TEST menu 4-11
Firmware version 3-3 Limit line 5-5
Front view 2-2

--M--
--G-- Main time line 5-2
General Information 0-1 Setting 6-3
Grid 5-6 Main time lines 5-2
mains supply 3-8
--H-- Maintenance 6-22
Hilfsenergie 3-7 Measured values 1-1
Housing 2-4 Measured-value acquisition 2-4
Measured-value table 4-17, 5-5
--I-- Measuring and recording mode 5-1
Inserting a chart roll 6-7 Measuring mode 4-36
Inserting a fanfold pack 6-5 Measuring-point label 6-13
Inserting chassis into housing 6-12 Mode of operation 2-8
Inserting the chart carriage 6-2 Moving chassis into maintenance
Inserting the guide tongue 6-13 position 6-9

Installation guidelines 3-5


Installation instructions 0-5 --O--
Object version 3-1
--J-- Open-circuit 4-28

Jumper settings 3-9 Operation 4-1

Selection of 50/60 Hz 3-3 Options 1-2, 2-9, 8-1

Summer time/winter time switch off


3-3 --P--
Parameterization examples 4-46
--L-- Parts List 9-1
Language 4-45 PC cable 2-10
Leaflet "Operation – a concise PC interface 2-6, 4-12
overview" 0-5
Pin assignments "Digital input/output"
Leaflet "Parameterization – a concise 3-16
overview" 0-5
Potentiometer connection 1-1
LEDs 4-3
Power supply 2-5, 3-7
Lever 2 4-5
Preparation for operation 3-1
Lever 4 4-3
Levers 4-4

Siemens AG Order No.: C79000-G7376-C188-04


II SIREC P, PA, L, LA Manual
Subject Index

Printing the measured value table 4- Setting of recording range 4-27


18
Setting the main time line 6-3
Priorities 5-7
Settings using PROG menu 4-14
PROG locking 4-45
Settings using TEST menu 4-34
Start line 4-37, 5-4
--R--
Starting up the recorder 3-21
Rating plate 3-2
Summary of PROG menu 4-15
Rear view 2-3
Summary of TEST menu 4-35
Rear view of L version 3-4
Summer time 4-44
Recorder identification 3-1
Switch-on text 5-3
Recorder type 3-1
Recording head
--T--
Insertion/removal 6-15
TC 3-12
Recording system 2-6
Technical data 7-1
Removal of transport protection 6-24
TEST locking 4-44
Removing a chart roll 6-6
Test print 6-20
Removing a fanfold pack 6-4
Test prints 6-18
Removing chassis from housing 6-11
Text 4-40
Removing the chart carriage 6-1
Thermocouple 3-13
Removing the guide tongue 6-13
Thermocouple connection (TC) 1-1
Replacing the battery 6-16
Thermoelectric resistance 1-1
Replacing the pens 6-14
Time mark 4-38, 4-43
Replacing the scale 6-16
Time marks 5-4
Resistance 1-1
Transmitters 3-20
Returning chassis from maintenance
Transport protection
position 6-10
Insertion 6-24
RTD, R 3-14

--S-- --U--
User interface 2-6
Scope of delivery 8-1
Serial number 3-1
Service 6-23
--W--
Service lever 4-5 Warning information 0-3

Servicing and maintenance 6-1

Siemens AG Order No.: C79000-G7376-C188-04


SIREC P, PA, L, LA Manual III
Subject Index

Siemens AG Order No.: C79000-G7376-C188-04


IV SIREC P, PA, L, LA Manual
Siemens AG
Bereich Automatisierungs- und Antriebstechnik
Geschäftsgebiet A&D PA E Siemens AG 1998
D-76181 Karlsruhe All rights reserved
Order No.: C79000-G7376-C188
Siemens Aktiengesellschaft Printed in France
AG 1098 MG 168 en

Вам также может понравиться