NOTE: This category consists of power transformers with windings rated 600 volts or less
and sizes equal to or less than 167 kVA single-phase or 500 kVA three-phase.
4. Verify that resilient mounts are free and that any shipping brackets have been removed.
6. Inspect bolted electrical connections for high resistance using one of the following
methods:
2. Electrical Tests
3. Test Values
2. Bolt-torque levels should be in accordance with Table 100.12 unless otherwise specified
by manufacturer.
3. Microhm or millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. If manufacturer’s data is not available,
investigate any values which deviate from similar connections by more that 50 percent of
the lowest value.
4. Insulation-resistance test values at one minute should be in accordance with Table
100.5.
5. The dielectric absorption ratio or polarization index shall be greater than 1.0 and shall be
recorded for future reference.
6. Turns-ratio test results should not deviate more than one-half percent from either the
adjacent coils or the calculated ratio.