Transformers, Dry Type, Air-cooled, Low Voltage, Small

NOTE: This category consists of power transformers with windings rated 600 volts or less
and sizes equal to or less than 167 kVA single-phase or 500 kVA three-phase.

1. Visual and Mechanical Inspection

1. Compare equipment nameplate data with drawings and specifications.

2. Inspect physical and mechanical grounding.

3. Inspect anchorage, alignment, and grounding.

4. Verify that resilient mounts are free and that any shipping brackets have been removed.

5. Verify that unit is clean.

6. Inspect bolted electrical connections for high resistance using one of the following
methods:

1. Use of low-resistance ohmmeter in accordance with Section 7.2.1.1.2.

2. Verify tightness of accessible bolted electrical connections by calibrated torque-


wrench method in accordance with manufacturer’s published data or Table 100.12.

3. Perform thermo graphic survey in accordance with Section 9.

7. Verify that as-lift tap connections are as specified.

2. Electrical Tests

1. Perform resistance measurements through bolted connections with a low-resistance


ohmmeter if applicable, in accordance with Section 7.2.1.1.1.

2. Perform insulation-resistance tests winding-to-winding and each winding-to-ground with


test voltage in accordance with Table 100.5. Calculate dielectric absorption ratio or
polarization index.

3. Perform turns ratio tests at all tap positions.

3. Test Values

1. Compare bolted connection resistances to values of similar connections.

2. Bolt-torque levels should be in accordance with Table 100.12 unless otherwise specified
by manufacturer.

3. Microhm or millivolt drop values shall not exceed the high levels of the normal range as
indicated in the manufacturer’s published data. If manufacturer’s data is not available,
investigate any values which deviate from similar connections by more that 50 percent of
the lowest value.
4. Insulation-resistance test values at one minute should be in accordance with Table
100.5.

5. The dielectric absorption ratio or polarization index shall be greater than 1.0 and shall be
recorded for future reference.

6. Turns-ratio test results should not deviate more than one-half percent from either the
adjacent coils or the calculated ratio.