Академический Документы
Профессиональный Документы
Культура Документы
Table of Contents
Table of Contents.................................................................................................................... i
Foreword ................................................................................................................................ ii
Introduction............................................................................................................................. iii
1 Scope.............................................................................................................................. 1
2 References....................................................................................................................... 1
3 Term and definitions.........................................................................................................1
4 Criteria Design................................................................................................................. 2
5 How to design natural lighting during the day.................................................................18
6 Testing and maintenance...............................................................................................22
Appendix............................................................................................................................... 25
Bibliography.......................................................................................................................... 30
i
Foreword
This Standard for Designing Natural Lighting Systems in Buildings is intended as a guideline
for all parties involved in the planning, implementation, supervision and management of
buildings, so that lighting and comfort in buildings can be carried out as effectively as
possible.
The planning procedure for Natural Lighting Systems in buildings aims to complement the
existing regulations on comfort and energy conservation and are the minimum requirements
for buildings.
Discussion of procedures for planning natural lighting systems in buildings includes: design
criteria, design methods for daylighting natural lighting, testing and maintenance.
Preliminary
In order to further improve energy conservation and comfort efforts in buildings. The
Department of Settlements and Regional Infrastructure representing the government,
professional associations, consultants, contractors, suppliers, building managers and
universities, compiles standards for "design procedures for natural lighting systems in
buildings which are then standardized by the National Standardization Agency to become:
SNI 03-0000 -2001.
It is hoped that this standard can be utilized by planners, executors, supervisors and
managers of buildings in applying the concepts of system design procedures for natural
lighting of buildings, so that the goals of energy conservation and comfort in buildings can be
achieved.
SNI 03-2396-2001
1 Scope.
1.1 The standard procedure for designing natural lighting systems in buildings is intended
as a guideline for designers and implementers of building construction in designing
daytime natural lighting systems and aims to obtain a daytime natural lighting system
that is in accordance with health, comfort and compliance requirements. other
applicable provisions.
1.2 This standard covers the minimum system requirements for natural daylight in
buildings.
2 Reference.
a) SNI. No. 03-2396-1991: Design procedures for natural daylight lighting for homes and
buildings.
b) Natuurkundige Grondslagen Voor Bouurvorrschriften, 1951, Deel 11, "Dagverlichting
Van Woningen, (N BG 11195 1).
c) Hopkinson (et.al), 1966, Daylighting, London.
d) Adhiwiyogo. MU, 1969, Selectidn of the Desfgn Sky for Indonesia based on the
Illumination Climate of Bandung. Symposium of Environmental Physics as Applied to
Building in the Tropics.
3.1
bright sky
light sources taken as the basis for determining the requirements for natural daylight.
3.2
design sky
the sky is in a state defined and used as the basis for calculation.
1 of 30
3.3
sky factor (fl)
characteristic number used as a measure of natural daylight conditions during the day in
various places in a room.
3.4
measuring point
point in the room whose lighting state is selected as an indicator for the lighting state of the
entire room.
3.5
effective light hole field.
inner vertical plane of the light hole.
3.6
effective light holes for a measuring point
the effective light-hole through which the measuring point looks at the sky.
4 Design Criteria
The level of natural lighting in the room is determined by the level of sky lighting on a flat
plane in an open field at the same time.
The ratio of natural lighting levels in the room and natural lighting on a flat area in an open field
is determined by:
a) the geometric relationship between the measuring point and the light hole.
b) the size and position of the light holes.
c) distribution of light sky.
d) part of the sky that can be seen from the measuring point.
The daylight natural lighting factor is the ratio of the level of lighting at a point from a
certain area in a room to the level of illumination in the flat area in the open field which
is a measure of the performance of the room's light holes:
barrier
Sky component
outer
barrier reflection
component
outer reflection
component
barrier
inner reflection
component
Figure 1: The three components of celestial light arriving at a point in the work plane.
2) The external reflection component (external reflection factor - FRL) is the lighting
component that comes from the reflection of objects around the building in
question.
3) The internal reflection component (reflection factor in frd) is the lighting component
that comes from the reflection of indoor surfaces, from the light that enters the
room due to the reflection of objects outside the room and from the sky (see Figure
1).
b) The equations for determining the lighting factor naturally
The natural daylight factor for daylight is determined by the following equations
information :
Information :
(fl) p = sky factor if there are no obstructions.
Average = ratio of the barrier luminance to the sky mean luminance.
Tglass = light transmittance factor of the glass manhole cover, the amount depends
on the number of glass whose value can be obtained from the catalog
issued by the glass manufacturer.
A = area of all inner surface room
R = average reflection factor across the surface
W = area of the hole light.
Rcw = average reflection factor of the ceiling and upper walls starting from the
plane through the center of the light hole, excluding the wall where the
light hole is located.
C = a constant whose magnitude depends on the angle barrier.
Rfw = average reflection factor of floor and lower walls starting from the plane
through the center of the light hole, excluding the wall where the light hole
is located.
b) Since the state of the sky shows great variability, the conditions that must be met by
the state of the sky to be selected and set as Sky Design are:
1) that such skies are often encountered.
2) provides a level of luminance in the flat area in the open field, with a near minimum
value, such that the frequency of failure to achieve this level is sufficiently low.
3) the value of the lighting level referred to in point 2) of this article must not be too
low so that the constructive technology requirements become too high.
d) Sky This design provides a level of illumination at points on a flat plane in an open field
of 10,000 lux. For the calculation, it is taken the stipulation that this lighting level comes
from the sky, which is everywhere evenly bright (uniform luminance distribution).
The sky factor (fl) of a point on a plane in a room is the ratio of the direct lighting level from
the sky at that point with the lighting level by the Light of the Sky on a flat area in the open
field.
The measurement of the two lighting levels is carried out in the following circumstances:
A point on a plane receives not only direct light from the sky but also sky light which is
reflected by outside and indoor surfaces.
The ratio between the level of lighting that comes from direct or reflective sky light to the level
of lighting on a flat plane in an open field is called the natural daylight factor. Thus the sky
factor is always smaller than the natural daylight factor. The selection of the sky factor as a
characteristic number to be used as a measure of natural daylight conditions during the day
is to facilitate calculation because fl is the largest component at the measuring point.
a) The measuring point is taken on a flat area which is located at a height of 0.75 meters
above the floor. This flat area is called the work area (see figure 2).
effective light hole construction
Field of work
Point of measure
section
O = projection of the
measuring point U in the
effective light hole plane
glass
( plot plan )
Point of measure
Figure 2: Height and Width of effective light
b) To ensure a satisfactory lighting condition is achieved, the Sky Factor (fl) measuring
point must meet a certain minimum value determined according to the function and
size of the room.
c) In the calculation, two types of measuring points are used:
1) the main measuring point (TUU), taken in the middle between the two side walls,
which is located at a distance of 1/3 d from the area of the effective light hole,
2) side measuring point (TUS), taken at a distance of 0.50 meters from the side wall
which is also at a distance of 1/ 3 d from the area of the effective light hole, where d
is the measure of the depth of the room, measured from the effective light hole
area to the opposite wall, or to the boundary "plane" in the room where the lighting
is to be calculated (see Figures 3a and 3b).
effective
light hole
field
If a room gets lighting from the sky through light holes in several walls, then each of these
walls has its own effective light hole area (see figure 4).
Generally, the effective light holes can be of different shapes and sizes than the light holes
themselves.
a) The quality of lighting that should be and is appropriate to be provided is determined by:
1) use of the room, especially in terms of the severity of the eye's vision of the
activities that must be done in that room.
2) the length of time the activity requires high visual power and the nature of its
activity, the nature of the activity can continuously require proper attention and
vision, or it can be periodically where the eye can rest.
a) The value of the sky factor (fl) and a measuring point in the room must meet the
following requirements:
1) at least meet the minimum sky factor (FLMIN) values
listed in Tables 1, 2 and 3, and selected according to the classification of lighting
quality desired and designed for the building.
2) the value of f1min in percent for rooms in a PUBLIC BUILDING for TUU, is as
shown in table 1; where d is the distance between the effective light-hole plane to
the opposite wall, expressed in meters. The minimum sky factor for TUS is taken
as 40% of the flmin for TUU and must not be less than 0.10 d.
3) the value of flmin in percent for rooms in the school building is as shown in table 2;
For ordinary classrooms, special classes and laboratories where the blackboard is
used as an explanation tool, then flmin at 1/3 d on the board at a height of 1.20 m,
is set to be the same as flmin = 50% TUU.
4) the value of flmin in the percentage for rooms in residential buildings as in table 3;
Table 3: The value of residential building work factors
5) for other rooms which are not specifically mentioned in this table, the provisions in
table 1 may be treated.
b) A room with direct lighting from a light hole in one wall is determined as follows:
1) from any room that receives direct light from the sky through openings or windows
in one wall only, one should examine one TUU and two TUSs.
2) The distance between the two measuring points must not be greater than 3 m. For
example, for a room with a length of more than 7 m, it must be checked (fl) more
than three measuring points (the number of TUU is added).
c) A room with direct lighting from the light holes in two opposite walls.
The value of the ceiling factor (fl) for such a room must be considered as follows:
1) if a room receives direct lighting from the sky through holes or windows in two
opposite (parallel) walls, then each area of the effective light hole has its own
specific group of measurements.
2) for the first group of measuring points, that is, from the plane of the most important
effective light holes, the provisions of tables 1, 2 and 3 apply.
3) for the second group of measuring points, a minimum requirement is set at 30% of
those stated in the provisions of tables 1, 2 and 3.
4) in this case (fl) for each measuring point is the sum of the sky factor obtained from
the light holes in the two walls.
5) the provisions for this second specific measurement group as meant in paragraph
3, do not apply if the distance between the two effective light holes is less than 6
meters.
6) if the distance mentioned in point 5) is more than 4 meters and less than 9 meters
is considered to be fulfilled if the total effective light hole area of the two inj is at
least 40% of the area of the first effective light hole. In the latter case, the area of
the second effective light hole is the part of the aperture plane that lies between 1
meter high and 3 meter high.
d) A room with direct lighting from the light holes in two intersecting walls
For room conditions like this the sky factor is determined by taking into account the
following things:
1) if a room receives direct lighting from the sky through holes or windows in two
walls which intersect more or less perpendicularly, then for the second dincling
point, which is not so important, only one additional Main Measurement Point is
considered.
2) The requirements for measuring points referred to in point 1) of this article are 50%
of those acting for the main measuring point in the first effective light hole area.
3) The distance of this additional main measuring point to the second effective light
hole plane is taken Y, d, where d is the inside size according to the plane of the
first effective light hole (see figure 3
j). The sky factor in the room that receives indirect lighting.
For the effective light hole of a room that receives daylight indirectly from the sky but through
a glass or light hole from another room, for example through a roofed terrace, then fl from the
measuring point in this room is calculated by means of the provisions of this technical
requirement. , only a maximum of 10% of the sky factor can be taken in a situation where the
measuring point is directly facing the sky.
Without Glass
Glass
Glass
Glass
Glass
a). The basis for determining the value of the sky factor.
The determination of the Sky Factor Value, is based on the condition of the sky that is evenly
lit or the Sky criteria Design for Indonesia which provides the lighting power at the point in the
upper plane in the open field of 10,000 lux.
The position of the measuring point U, which is D away from the effective light hole is a
rectangular OPQR (height H and width L) as illustrated below:
H/D
0.1 0.02 0.03 0.05 0.06 0.07 0.08 0.09 0.09 0.10 0.10
0.2 0.06 0.12 0.17 0.22 0.27 0.30 0.33 0.36 0.38 0.40
0.3 0.13 0.26 0.37 0.48 0.57 0.65 0.72 0.77 0.82 0.86
0.4 0.22 0.43 0.62 0.80 0.96 1.09 1.20 1.30 1.38 1.44
0.5 0.32 0.62 0.91 1.17 1.39 1.59 1.76 1.90 2.02 2.11
0.6 0.42 0.82 1.20 1.55 1.85 2.12 2.34 2.53 2.69 2.83
0.7 0.52 1.02 1.50 1.93 2.31 2.64 2.93 3.18 3.38 3.55
0.8 0.62 1122 1.78 2.29 2.75 3.26 3.50 3.80 4.05 4.26
0.9 0.71 1.40 2.04 2.64 3.17 3.63 4.04 4.39 4.69 4.94
1.0 0.79 1.56 2.29 2.95 3.56 4.09 4.55 4.95 5.29 5,57
1.5 1.10 2.17 4.13 4.13 4.99 5.77 6.45 7.05 7.58 8,03
2.0 1.27 2.51 4.80 4.80 5.81 6.74 7.56 8.29 8.94 9,51
2.5 1.37. 2.70 3.98 3.98 6.29 7.31 8.22 9.03 9.76 10.40
3.0 1.43 2.82 4.16 4.16 6.59 7.66 8.62 9.49 10.27 10.96
3.5 1.47 2.90 4.28 4.28 6.78 7.89 8.89 9.79 10.60 11.33
4.0 1.49 2.96 4.36 4.36 6.91 8,04 9.07 10.00 10.83 11.58
4.5 1.51 2.99 4.41 4.41 7.01 8.15 9,20 10.15 11.00 11.76
5.0 1.53 3.02 4.46 4.46 7.07 8.24 9.29 10.25 12.12 11.90
6.0 1154 3.06 4.51 4.51 7.17 8.34 9.42 10.40 11.28 11.07
L/
D 1.5 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6.0
H/D
0.1 0.11 0.11 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12
0.2 0.45 0.45 0.47 0.48 0.48 0.48 0.48 0.48 0.48 0.49
0.3 0.97 0.97 1.01 1.03 1.04 1.04 1.05 1.05 1.05 1.05
0.4 1.63 1.63 1.71 1.74 1.76 1.77 1.78 1.78 1.78 1.78
0.5 2.40 2.40 2.52 2.57 2.60 2.61 2.63 2.63 2.63 2.63
0.6 3.22 3.22 3.39 3.46 3.50 3.52 3.54 3.54 3.54 3.55
0.7 4.07 4.07 4129 4.39 4,4 4.47 4.48 4.50 4.50 4.51
0.8 4.90 4.90 5118 5.31 5.37 5.41 5.43 5.45 5.45 5146
0.9 5.71 5.71 6.04 6.04 6.20 6.28 6.33 6.36 6.39 6.40
1.0 6.47 6.47 6.87 7.06 7,16 7.22 7.25 7.28 7.28 7.30
1.5 9,52 9,52 10.23 10.59 10.79 10.90 10.97 11.05 11.05 11.08
2.0 11.44 11.44 12.43 12.96 13.26 13.44 13.55 13.62 13.67 13.73
2.5 12.64 12.64 13.85 14.52 14.92 15.16 15.32 15.42 15.49 15.58
3.0 13.41 13.41 14.78 15.58 16.06 16.36 16.56 16.70 16.79 16.91
3.5 13.93 13.93 15.42 16.31 16.87 17.22 17.46 17.64 17.74 17.89
4.0 14.30 14.30 15.88 16.84- 17.45 17.85 18.13 18.32 18.46 18.63
4.5 14.56 14.56 16.21 17.23 17.89 18, 3 18.63 18.85 19.01 19.21
5.0 14.75 14.75 16.45 17.52 18.22 18.69 19.03 19.26 19.44 19.67
6.0 15.01 15.01 16.79 17.92 18.68 19.20 19.58 19.85 20.06 20.33
5 How to design natural daylight.
The Design Procedure for Daylighting is carried out by following the chart below:
a) In order to obtain the desired lighting quality, it is necessary to pay attention to the
things that affect the quality of the lighting in the design. The quality of natural daylight
in the room is determined by
1). the ratio of the area of the light hole and the floor area.
2). the shape and location of the light holes.
3). the factor of light reflection from the surface in the room.
a). The location or position of the light holes affects the value of the sky factor and the
distribution of light into space as follows:
1). a light hole that is equal in size, has a greater fl value for a higher position. Until a
certain height the value of fl will decrease again. (see table 5).
2). In the following table the sky factor value has been calculated for the measuring
point located 2m from the plane of the effective light hole. The measuring point
gets illumination from the effective light holes in the shape of a square with sides
20 cm at different heights.
Table 5: The relationship between the height of the light holes and the relative sky factor
values.
Height of the hole of the light (cm) Relative sky factor
value
0-20 1
20-40 2
40-60 3.5
60-80 4
80-100 5
100-120 5
120-140 5
140-160 5
160-180 4.5
180-200 4
One side of the effective light hole coincides with the vertical plane cut through the
measuring point. Projection of the measuring point in the plane of the light hole. effective is
called point 0 (see figure 7). The sky factor value is taken to the lowest place.
Note:
All light hole shape is rectangle 20 cm x 20 cm
Figure 7: The influence of the position of the light hole on the magnitude of the sky
factor.
3). The effective light hole is the same size if the position is more to the side of the
vertical plane passing the measuring point and perpendicular to the effective light
hole plane, will give the sky factor value at the smaller measuring point. The factor
of the sky with a side of 20 cm and the bottom line coinciding with the height of the
working plane (measuring point), is taken as the unit basis.
Table 6: The relationship between sideways distance with the Relative Sky Factor
Value
4). the value of the sky factor for the effective light holes that are central and high to
the measuring point is more effective than those that are sideways and low.
5). the parts of the high effective light holes are more effective in distributing light to
the more densely located parts of the room than to the sides.
b) The shape of the light holes has an effect on the distribution of light as follows :
1) Widened light holes will be useful for distributing light more evenly in the width of
the room.
2) effective light holes whose height is greater than the width. provides better inward
penetration.
d) Other light barriers that are part of the building itself such as:
1) wall thickness or a prominent part of the building.
2) the top of the effective light hole bounded by eaves and so on.
e) Other buildings that are in front of the light hole will generally limit the bottom of the
effective light hole. If at the time of building design there were no other buildings in the
vicinity, while in the city plan another building would be built, this must be considered at
the time of building design.
f) Plants can be a barrier to light because they are difficult to predict and so their effects
are often not taken into account. To take into account
It is recommended that in the design, the sky factor value is 10% to 20% higher than
the given requirements. It is also recommended that tall, shady trees not be planted too
close to buildings.
h). To improve the quality of natural daylight in the room, you need to pay attention to the
instructions below:
1). if the building conditions allow, the room should be able to receive light in more
than one direction. This will help even out the light distribution and reduce any
possible contrast.
2). To make the best use of the entry of natural light into the room, the inner surface of
the room should use a bright color.
3). vitrase (transparent curtains) can help diffuse light, but also reduce the light
entering. The light reduction can be up to 50% or more depending on the material
used.
4). Mosquito netting can reduce the amount of incoming light by at least 15%.
5). the use of special glass to reduce thermal radiation should not reduce the
incoming light.
6.1 Testing
Daytime natural lighting testing is intended to test and / or assess / check natural daylight
conditions during the day in chapter 4.Tests are carried out by measuring or checking:
a). Level of lighting.
b). Index of glare.
a). Measure the lighting level at the Main Measuring Point (TUU). Side Measure Point
(TUS), The point outside the room in the open and the measurement is done at the
same time.
b). Calculate the sky factor in TUU and TUS.
c). Compare the calculation results in item b with the provisions in chapter 4.
Silent glare is caused by direct sunlight or reflections from reflective objects. The factors that
influence glare are the luminance of the light source, the position of the light source against
the observer's vision and the contrast on the work surface.
The maximum recommended Glare Index values for the various visual tasks are given in
table 7. The Glare Index values can be calculated using the formulas found in CIBSE
Publication TM 10.
6.2 Maintenance
In natural daylight, the source of light entering the room is a light hole. The maintenance that
needs to be done is to avoid any obstructions that can reduce the light of the sky entering the
room and clean the glass.
Appendix
4). if you note any light obstructions by the buildings across the street. Suppose that the
distance between the measuring point and the points of the building across the road
averages 30 m and the height above the work plane = 9 m, this means that the part of
the hole to H / D = 0.3 does not give way to direct light from sky.
In this case the results will be as listed in table 9.
Table 9: Sky Factor Prices based on window size
H/ UD Light holes or windows
D Width (m) Height (m). Was (M2)
2.58 0.1 0.40 5.16 2.06
0.97 0.2 0.80 1.94 1.55
0.74 0.3 1.20 1.48 1.18
0.65 0.4 1.60 1.30 2.08
0.59 0.5 2.00 1.18 2.36
5). In order to comply with the applicable provisions for Side Measurement Points, only
approximately 50% of the center is required for each side window. This is true when
the effect of the middle window for Side Measure Points is not taken into account at all.
6). In order to fulfill both conditions according to the calculation, one symmetrical
window to the Utarna Measure Point can be taken with the following measurements:
a. 4.00 m wide, 1.10 m high, 4.40 m wide or 3.50 m wide, 1.20 m high, 4.20 m2 wide
or 3.00 m wide, 1.40 m high, Area 4 , 20 m2.
b. The above possibilities are just examples, because there are many other possible
combinations. In these calculations, always taken as the lowest part of the window
is the working plane height (0.75 m from the floor).
Bibliography
a). SNI. No. 03-2396-1991: Design procedures for natural daylight lighting for homes and
buildings.
b). Natuurkundige Grondslagen Voor Bouurvorrschriften, 1951, Deel 11, "Dagverlichting
Van Woningen (NBG 11 1951).
c). Hopkinson (et.al), 1966, Daylighting, London.
d). Adhiwiyogo. MU, 1969; Selection of the Design Sky for Indonesia is based on the
Illumination Climate of Bandung. Symposium of Environmental Physics as Applied to
Building in the Tropics.