Data sheet
Pressure switch
Type KP
Features yy Ultra-short bounce time thanks to snap-action yy Vibration and shock resistant
function (reduces wear to a minimum
and increases reliability) yy Compact design
Technical data
Ambient temperature -40 – 65 °C (80 °C for max. 2 hours).
Ambient temperature (PED approved units) -25 – 65 °C (80 °C for max. 2 hours).
LP: Pe = 20 bar
KP 6: Pe = 46.5 bar
Pollution degree 3
Insulation 400 V
Contact systems
Ordering
Code no.
Low pressure (LP) High pressure (HP) Reset
Connection
Pressure Type Contact system
Regulating Differential Regulating Differential Low High /4 in.
1
/4 in.
1
6 mm
range ∆p range ∆p pressure pressure 6 mm ODF ODF
[bar] [bar] [bar] [bar] LP HP flare solder solder
Low KP 1 -0.2 – 7.5 0.7 – 4.0 — — Auto — SPDT 060-110166 3) 060-111266 3) 060-111066 3)
Low KP 1 -0.2 – 7.5 0.7 – 4.0 — — Auto — SPDT 060-114166 1)3) — —
Man.
Low KP 1 -0.9 – 7.0 0.7 — — — SPDT 060-110366 060-111166 060-110966
(Min.)
Low KP 2 -0.2 – 5.0 0.4 – 1.5 — — Auto — SPDT 060-112066 3) — 060-112366 3)
High KP 5 — — 8 – 32 1.8 – 6.0 — Auto SPDT 060-117166 3) 060-117966 3) 060-117766 3)
Man.
High KP 5 — — 8 – 32 3 — SPDT 060-117366 060-118066 —
(Max.)
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Auto SPDT + LP signal 060-124166 3) 060-125466 3) —
Man.
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto SPDT + LP signal 060-124366 — —
(Max.)
Man.
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto SPDT + LP signal 060-1148661) — —
(Max.)
Man. Man.
Dual KP 15 -0.9 – 7.0 0.7 8 – 32 4 SPDT + LP signal 060-124566 — —
(Min.) (Max.)
Dual KP 15 -0.9 – 7.0 0.7 8 – 32 4 Conv.2) Conv.2) SPDT + LP signal 060-126166 — —
SPDT + LP and
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto Auto 060-126566 3) 060-129966 3) —
HP signal
Man. SPDT + LP and
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Auto 060-126466 060-128466 —
(Max.) HP signal
SPDT + LP and
Dual KP 15 -0.2 – 7.5 0.7 – 4.0 8 – 32 4 Conv.2) Conv.2) 060-115466 3) 060-001066 3) —
HP signal
SPDT + LP and
Dual KP 15 -0.9 – 7.0 0.7 8 – 32 4 Conv.2) Conv.2) 060-122066 — —
HP signal
Code no.
Low pressure (LP) High pressure (HP) Reset
Connection
Pressure Type Contact system
Regulating Differential Regulating Differential Low High 1 m cap.
range ∆p range ∆p pressure pressure M10 × 0.75
tube with
M10 × 0.75
[bar] [bar] [bar] [bar] LP HP
Low KP 1A -0.2 – 7.5 0.7 – 4.0 — — Auto — SPDT 060-116266 060-116066 3)
Code no.
Low pressure (LP) High pressure (HP) Reset
Connection
Contact
Pressure Type 1)
Regulating Differential Regulating Differential Low High system 1
/4 in. 6 mm
range ∆p range ∆p pressure pressure 6 mm ODF
flare solder
[bar] [bar] [bar] [bar] LP HP
Low KP 1 -0.2 – 7.5 0.7 – 4.0 — — Auto — SPDT 060-110166 2) 060-111066 2)
Man. (Max.)
Dual KP 7BS — — 8 – 32 4 — SPST 060-120066 —
Man. (Max.)
SPDT + LP and
Dual KP 17W -0.2 – 7.5 0.7 – 4 8 – 32 4 Auto Auto 060-127566 2) 060-127666 2)
HP signal
SPDT+ LP
Dual KP 17W -0.2 – 7.5 0.7 – 4 8 – 32 4 Auto Auto 060-126766 2) —
signal
Dual KP 17B -0.2 – 7.5 0.7 – 4 8 – 32 4 Auto Man. (Max.) SPDT 060-126866 060-127466
SPDT + LP and
Dual KP 17WB -0.2 – 7.5 0.7 – 4 8 – 32 4 Auto Conv.4) 060-539766 2)3) —
HP signal
Code no.
Low pressure (LP) High pressure (HP) Reset
Contact Connection
Pressure Type
Regulating Differential Regulating Differential Low High system 1 m cap.
range ∆p range ∆p pressure pressure M10 × 0.75 tube with
[bar] [bar] [bar] [bar] LP HP M10 × 0.75
Low KP 1A -0.2 – 7.5 0.7 – 4.0 — — Auto — SPDT 060-116266 060-116066 2)
1)
W = PSH (pressure switch), B = PZH (pressure switch with ext. 3)
Factory setting: LP side: Range 1 bar Pe, Diff. 1 bar; HP side:
reset), S = PZHH (pressure switch with int. reset) Range 18 bar Pe, Diff. 4 bar fixed
2)
Enclosure IP44 4)
Conv.: optional automatic or manual reset
Low pressure Manual reset 1) Automatic reset Automatic reset Manual reset
High pressure Manual reset 1) Manual reset Automatic reset Automatic reset
1)
Factory setting
1/5 2 16 3 1/5 18 2 13 30
9 12 14
14 in. / 6 mm
10/11 15
=12 mm
3. Main arm
5. High pressure (HP)
setting spindle
7. Main spring
8. Differential spring
9. Bellows
10. LP connection R 1/4 (ISO 7-1)
11. HP connection
12. Switch
13. Terminals
14. Earth terminal 14 =12 mm
15. Cable entry
16. Tumbler 14 in. / 6 mm
18. Locking plate
30. Reset button
The switch in the KP has a snap-action function The design of the KP pressure switch gives
and the bellows moves only when the cut-in or the following advantages:
cut-out value is reached. yy high contact load
yy ultra-short bounce time
The bellows becomes connected to the low yy high resistance to pulsation
or high pressure side of the plant through yy vibration resistance up to 4 g
connection (10) or (11). in the range 0 – 1000 Hz
yy long mechanical and electrical life
MK.FW
1 3 1 18 2
MK
15
6 mm
KP 7BS
MK
25
1 30
1
Types KP1, KP1A, KP2, KP6, KP6A, KP7 and KP17 Versions with designation W or AW cut in again
units with designation W, B or S have been tested automatically when the pressure has fallen to the
and approved by TÜV, Rheinland in accordance set value minus the differential.
with EN 12263.
Versions with designation B or AB can be cut in
Types KP6, KP6A, KP7 and KP17 have a double manually with the external reset button when
bellows: an outer bellows and a regulating the pressure in KP1 has increased 0.7 bar above
bellows. When system pressure exceeds the set set value and in KP6 and KP7 has fallen 4 bar
value, the KP will automatically stop the plant. under the set value.
The double bellows system prevents loss of
charge in the event of bellows rupture. Versions with designation S or AS can be cut in
manually with the internal reset arm when the
A rupture in the inner bellows will cause the pressure has fallen 4 bar under the set value.
control cut-out pressure to fall about 3 times less
the set value, thus the refrigeration plant All KP pressure switches, including those which
compressor will stop. are PED-approved, operate independently of
changes in the ambient temperature around the
A rupture in the outer bellows will cause the control housing. Therefore the set cut-out
control cut-out pressure to fall to about 3 bar pressure and differential are held constant
under the set value, thus providing a fail-safe provided the permissible ambient temperatures
function. are not exceeded.
Test pressure
The test pressure is the pressure used in strength
tests and/or leakage tests on refrigerating
systems or individual parts in systems. The test
pressure is designated Pe.
Setting Pressure switches with automatic reset – LP: Pressure switches with automatic reset – HP:
Set the LP start pressure on the "CUT-IN" scale Set the HP pressure on the “CUT-OUT” scale.
(range scale). One rotation of the low pressure One rotation of the HP spindle ∼ 2.3 bar.
spindle ∼ 0.7 bar.Set the LP differential on the Set the HP differential on the “DIFF” scale.
"DIFF" scale. One rotation of the differential One rotation of the differential spindle ∼ 0.3 bar.
spindle ∼ 0.15 bar.The LP stop pressure is the LP The HP start pressure is the HP stop pressure
start pressure minus the differential. minus the differential.
If with low stop pressure the refrigeration Pressure switches with manual reset
compressor will not stop, check to ensure that Set the stop pressure on “CUT-OUT” scale
the differential value has not been set too high! (range scale).
Low pressure switches can be manually reset
when the pressure is equal to the stop pressure
plus the differential.
High pressure switches can be manually reset
when the pressure is equal to the stop pressure
minus the differential.
84 44 122 44
61
61
28 – 30
28 – 32
28 – 30
=12 =12
84 44 122 44
61
61
25 – 29
=14
25
=14
Solder connection
84 44 122 44
61
61
112 – 114
112 – 114
112 – 116
122 44
7
61
28 – 30
28 – 32
Net weight:
=12
KP 1, KP 2, KP 5 and KP 7: approx. 0.3 kg
KP 15, KP 17 and KP 7BS: approx. 0.5 kg
KP 1A and KP 5A: approx. 0.3 kg
KP 15A and KP 7ABS: approx. 0.5 kg