Академический Документы
Профессиональный Документы
Культура Документы
Indication
STANDARD SPECIFICATION
UOP Engineering Department
6-18-7 Page 1 of 9
DATE STATUS SPNSR APVD
FLOW METERS AND PRESSURE
INSTRUMENTS 12APR20 Reaffirmed RED MJM
1. GENERAL
1.1 Scope
a. This Standard Specification covers the general requirements for flow meters, differential
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
b. Exceptions or variations shown in the UOP Project Specifications take precedence over
requirements shown herein.
1.2 References
Unless noted below, use the edition and addenda of each referenced document current on the date
of this Standard Specification. When a referenced document incorporates another document, use
the edition of that document required by the referenced document.
c. ASME MFC-14M-2003, “Measurement of Fluid Flow Using Small Bore Precision Orifice
Meters”.
Flow measurement equipment substituted for the equipment specified in the UOP Project
Specifications shall be engineered such that any criteria that may impact process performance (e.g.
accuracy, repeatability, speed of response, update rate, etc.) are equivalent to, or exceed the UOP
specified equipment. It is both the Owner’s and Contractor’s responsibility to ensure equivalency.
Process performance is especially important for metering equipment in control loops and those
associated with unit mass balance streams.
2. FLOW CALCULATIONS
To determine the actual flow being measured, UOP uses the measured orifice bore diameter/dimensions
and the actual process conditions to calculate the actual meter maximum flow rate. The equations from
ISO 5167-1 through 5167-4 are used to determine the meter maximum flow rate. For those items that
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
fall outside of ISO 5167, the equations from ASME MFC-14M or the Flow Measurement Engineering
Handbook are used. Proprietary flow measuring devices shall use equations and/or information provided
by the vendor of the item.
Primary element (orifice plate or venturi) sizing calculations shall be provided for each primary element,
and the Contractor shall retain one copy of the sizing calculations for review by UOP personnel. For
other types of flow meters, vendor specific calculation information shall be available for review by UOP
personnel.
The standard flow measurement equipment shall generally be a differential head producing primary
element (orifice plate or a venturi) and an electronic (analog or digital) differential pressure transmitter.
a. Types
(1) Concentric sharp edge orifice plates shall be used for most metering applications. For
orifice bore diameters less than 0.25 inches (6.35 mm), a suitable strainer shall be
installed preceding the meter.
(2) Eccentric type orifice plates shall be used for fluids containing two phases. The
eccentric type orifice plates shall have the bottom of the orifice bore approximately 0.01
times the pipe inside diameter (D) above the bottom inside wall of the pipe. Eccentric
orifice plates shall be installed in horizontal meter runs only.
(3) Quadrant edge orifice plates shall generally be provided for liquid flow measurement
where low Reynolds numbers (less than 20000) are calculated for the normal process
flow rate.
(4) Prefabricated meter runs, consisting of upstream and downstream honed tubes, metering
flanges, and orifice plate (honed flow meter runs), shall be provided for small flow
metering applications where the pipe size is smaller than the 2 inch minimum of the
conventional square edge orifice plate/meter run. In conjunction with this type of flow
metering device, a suitable strainer shall be installed preceding the meter for orifice bore
diameters less than 0.25 inches (6.35 mm).
(5) Prefabricated meter runs with integral orifice meters (in-line type orifice assembly
integrally mounted to a differential pressure transmitter) may be used for extremely
small flow rates when specified on the UOP Project Specification. In conjunction with
this type of device, a suitable strainer shall be installed preceding the meter.
Due to the fabrication with only two bolts at the orifice assembly body, these meters
shall only be used with inert fluids (air, water, nitrogen, etc.).
b. Fabrication
(1) The vendor's standard equations may be used to calculate the orifice bore diameter (d).
(2) The Beta ratio (d/D) shall be within the following limits:
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
(a) 0.10 and 0.70 inclusive for pipe sizes 2 inches and larger
(b) 0.15 and 0.70 inclusive for honed flow prefabricated meter runs with flange
taps
(c) 0.10 and 0.80 inclusive for honed flow prefabricated meter runs with corner
taps
(d) Vendor’s recommendation for integral orifice prefabricated meter runs
Where required, the pipe size shall be expanded in diameter to avoid d/D ratios
exceeding the upper limits.
(3) For horizontal meter run installations, drain or weep holes may be provided for orifice
plates that have a bore diameter of 1 inch (25 mm) and larger. The drain or weep hole
may be excluded from the orifice bore calculation.
(4) Each orifice plate shall be provided with a tab that projects beyond the flange. The tab
shall be stamped to indicate the orifice plate material, measured bore diameter, nominal
pipe size, flange class, and identifying tag number. The tab shall also be in line with the
drain or weep hole and shall clearly indicate the direction of flow. The information on
the tab shall be visible when the orifice plate is installed in the flanges.
c. Installation
(1) The minimum pipe size for field fabricated orifice meter runs shall be 2 inches. For pipe
sizes less than 2 inches, a prefabricated meter run (either honed flow or integral orifice
meter) shall be used. The minimum pipe size for a prefabricated meter run is 1/2 inch.
(3) Orifice plates in 2 inch pipe sizes and larger shall be installed in tapped orifice flanges
(flange taps). The pipe runs upstream and downstream of the orifice flanges shall be in
accordance with UOP Standard Drawing 6-112.
(4) Orifice plates for honed flow meters in 1/2 through 1-1/2 inch pipe sizes shall be
installed in tapped orifice flanges (flange taps), or corner taps. The pipe runs upstream
and downstream of the orifice flanges shall be in accordance with ASME MFC-14M.
(5) Orifice plates for integral orifice meters in 1/2 through 1-1/2 inch pipe sizes shall be
installed per the vendor’s recommendations. The pipe runs upstream and downstream of
the orifice flanges shall also be in accordance with the vendor’s recommendations.
(6) Orifice meter run smoothness, out of round, etc., shall conform to the requirements of
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
(7) Thermowells shall not be located upstream of the orifice plate. Thermowells shall be
located a minimum of 5 nominal pipe diameters downstream of the orifice plate.
(8) The layout of the meter run and meter installation shall provide accessibility from a
platform, portable stairs, or temporary ladder for servicing without increasing impulse
line length.
3.2 Venturi
a. The venturi shall be a “Classical” venturi tube as defined in ISO 5167, or an ASME venturi
tube as defined in ASME MFC-3M.
b. The Beta ratio (d/D) shall be within the limits as defined in either ISO 5167, or ASME
MFC-3M, as applicable.
c. The divergent section of the venturi shall have an included angle of 7° to 8° in order to
minimize the permanent pressure loss.
e. The pipe runs upstream and downstream of the venturi shall be in accordance with UOP
Standard Drawing 6-134.
f. Venturi meter run smoothness, out of round, etc., shall conform to the requirements of
ISO 5167.
g. The layout of the meter run and meter installation shall be selected to provide accessibility
from a platform, portable stairs, or temporary ladder for servicing without increasing impulse
line length.
a. For orifice taps and venturi taps in horizontal lines, the following shall apply:
(1) For liquid, steam, or condensable vapor lines the taps shall be in the horizontal. Tap
locations other than in the horizontal, such as 45° taps, are not acceptable.
(2) For gas lines, the taps shall be in the vertical on the top or not more than 45° from the
vertical on the top.
b. Other aspects of the pressure tappings shall be in accordance with ISO 5167.
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
4.1 Construction
a. For differential pressure transmitters, the transmitter body shall have a static pressure rating
of 1500 psig (105 kg/cm2(g)) or 150% of the operating pressure at the operating temperature
shown on the UOP Project Specification, whichever is greater.
b. For absolute and gauge pressure transmitters, the transmitter body shall have a static pressure
rating of 1500 psig (105 kg/cm2(g)) or 150% of the sensor upper range limit (URL) at the
operating temperature shown on the UOP Project Specification, whichever is greater.
c. Transmitter internals in contact with the process (wetted parts) shall be type 316 stainless
steel. In services that are corrosive to available transmitter internals, where plugging may
occur, or high viscosity fluids are encountered, diaphragm seals compatible with the process
fluid shall be used to isolate the transmitter internals from the process fluid.
e. For absolute and gauge pressure transmitters, measuring elements shall be capable of
withstanding pressure up to that of the static pressure rating without damage to the element.
Any resultant zero shifts shall be limited to less than 1% of the calibrated span of the
transmitter.
f. Transmitters in wet H2S (sour) service shall comply with NACE standard MR0103.
4.2 Performance
(1) For transmitters used in process control loops, response time and update rate shall be
used in determining transmitter performance and both criteria shall be considered in the
selection of the equipment. Response time is defined as the time it takes for the
transmitter output to reach 63.2% of the actual step change in pressure. The response
time includes any dead time associated with the initial step change in input signal and
the transmitter output actually changing. Update rate is defined as the time interval
between updates of the transmitted process measurement value.
(2) As a minimum, pressure and differential pressure digital transmitters used in process
control loops shall meet the following requirements:
(a) Transmitters with an upper range limit of 30 inches (760 mm) H2O or less, shall
have a response time of 600 milliseconds or less. Other transmitters shall have a
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
(b) Transmitters shall have an update rate at least as fast as the table below.
The transmitter output signal for the specified range may be 4 - 20 mA, 4 - 20 mA with a
digital communication protocol superimposed, or fully digital communication. The
communication protocol shall not prevent the instrument from measuring and transmitting the
process pressure or differential pressure, except when the instrument is being configured.
c. Failure Mode
The transmitter electronics shall be capable of monitoring its performance during normal
operation. The diagnostics shall be able to detect both an input sensor failure and transmitter
electronics failure. The sensor or electronics failure shall be transmitted to the host system
(e.g., DCS, PLC) using a low milliamp signal (e.g. <3.75 mA) or by using a fieldbus signal,
depending on the capabilities of the host system.
d. Electronic Damping
The transmitter shall be capable of setting the electronic damping of the output to zero.
Damping values shall be set to zero unless specified otherwise.
e. Accuracy
Better than +/- 1% of Span for a 50°F (28°C) temperature change, up to 1000 psig
(70 kg/cm2(g)).
g. Stability
h. Calibration
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
The instrument calibration shall be completed by the vendor prior to shipment of the
instrument. Where applicable, calibration via a smart communicator is sufficient.
a. For differential pressure transmitters, impulse lines shall not be longer than indicated on the
UOP Standard Drawings. Longer impulse lines will increase measurement error due to any
specific gravity differences in the high and low impulse lines.
b. Transmitter output signal indicators shall be readable from the associated control valve
assembly (or other valve(s) as denoted on the UOP Piping and Instrument Diagram). An
integrally mounted indicator is acceptable. If the piping layout is such that an integrally
mounted indicator is not readable from the associated valve(s), then a separate indicator
suitable for remote mounting shall be supplied.
a. Averaging Pitot tube elements shall be permanently marked to indicate proper installation
position and flow direction, unless they are bi-directional.
b. As a minimum, the vendor’s recommended straight run pipe length requirements shall be
used; however, longer lengths are preferred.
d. In large pipe diameters, or where high flow velocity may cause the element to deflect or
vibrate, extra heavy flow elements and/or double ended support shall be used.
a. The accuracy of the meter shall be +/- 0.5% of the flow rate or better, and the repeatability
shall be +/- 0.1% or better.
b. Turbine meters shall be designed with hydraulic balance to keep the rotor in place and shall
have journal bearing construction. Designs using thrust bearing are not permitted.
c. Material of construction for the journal bearing and rotor shaft shall be tungsten carbide. The
materials of construction for the body and other wetted parts shall be suitable for hydrocarbon
service as defined on the UOP Project Specification.
d. The pickup coil shall be hermetically sealed or potted. The pickup coil wiring shall terminate
at a terminal strip located on a remote mounted pulse amplifier. The wiring shall be suitable
for the operating conditions shown on the UOP Project Specification. The length of wiring
between the pickup coil and pulse amplifier shall be sufficient to permit the amplifier to be
located as close to the meter as possible but not on the meter. The output signal of the
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
e. Turbine meters shall be designed for operation at a minimum of 130% of the flow range
specified, with no damage to the meter.
f. Each turbine meter shall have a nameplate indicating the average pulses per unit volume over
the meter range specified.
g. Each turbine meter shall be calibrated for either vertical upflow or horizontal installation as
specified on the UOP Project Specification. One copy of the calibration curve shall be
provided with each meter.
h. Strainers with the mesh size, material, and rating as noted on the UOP Project Specification
shall be installed preceding each meter. Where the mesh size is not listed, the turbine meter
vendor’s recommendation shall be followed.
j. Tools required for removal of the pickup coil shall be provided with the meter.
k. For each meter, one spare rotor and one spare pickup coil shall be provided.
a. The meter body configuration shall be constructed to minimize the pressure drop through the
meter.
b. Counters, where specified, shall be of the non-reset type with calibration adjustments.
Counters shall be weatherproof.
c. Straight through strainers with mesh size, material, and rating as noted on the UOP Project
Specification shall be installed preceding each meter.
d. The accuracy of the measuring device shall be +/- 0.2% of full scale or better.
5.4 Rotameters
a. Meter bodies shall be equipped with inlet and outlet float stops and, where feasible, cleanout
plugs, which may be utilized as connection taps.
b. Indicating scales shall have full length safety glass (or plastic) shielding, gasketed on both
sides. Indicating scales shall be approximately 5 inches (125 mm) in length for extension
meters used for transmitting service or for armored meters and 10 inches (250 mm) in length
for local indicators not of the armored type. A 2-1/2 inch (65 mm) scale length for purge rate
rotameters is acceptable.
CONFIDENTIAL – The information in this document is confidential and must not be used for any purpose, duplicated, or disclosed to others without UOP's written permission.
c. Gland assemblies shall be of "O" ring construction unless process conditions noted on the
UOP Project Specification require otherwise.
d. Tube construction shall be beaded, ribbed, or flat except for the plain tapered tubes used for
armored type. Plain tapered tubes shall have internal guiding.
e. Floats shall be self-cleaning and shall be designed for dimensional stability and maximum
immunity to viscosity variations.
f. Rotameters shall be completely assembled with all accessories before shipping.
g. Accuracy shall be +/- 2% of full scale or better. For purge rate rotameters accuracy of
+/- 10% of full scale is acceptable.
5.5 Magnetic Flow Meters
b. The velocity through the tube shall determine the meter size based upon the selected vendors
recommended velocities.
c. The process conditions indicated on the UOP Project Specification shall be considered in the
selection of the lining, electrodes and grounding requirements.
d. The meter installation shall assure that the meter body remains full of liquid. Vertical upflow
installations are preferred.
Other flow meter types, such as vortex, coriolis, thermal mass, etc., shall be in accordance with the
applicable UOP Project Specification, notes and drawings.
6. NAMEPLATE
A non-corroding nameplate shall be permanently attached to the instrument and shall contain as a
minimum the following information.