TUGBOAT ASD 2x2200HP (PT. J.A.I. Tbk.

)
( PT. CITRA SHIPYARD )

CAPACITY
No. MOTOR EQUIPMENTS RATED LOAD REMARKS
kW set kW
380VAC
1 Ballast and G.S. Pump 11.00 1 11.0
2 Bilge Pump 11.00 1 11.0
3 Air Compressor Pump 10.70 2 21.4
4 Fuel Oil Transfer Pump 3.70 2 7.4
5 Sludge Pump/Dirty Oil Pump 1.50 1 1.5
6 St-by M/E Lubricating Oil Pump 15.0 2 30.0
7 Oil Water Separator Pump 1.10 1 1.1
8 Oil Dispersant Pump 7.5 1 7.5
9 L.O Purifier 1.50 1 1.5
10 F.W. Hydrophore Pump 3.70 1 3.7
11 S.W. Hydrophore Pump 3.70 1 3.7
12 Eng. Room Ventilation 5.50 2 11.0
13 Z- Drive Compartment Exh. Fan 1.50 2 3.0
14 Galley Room Exhaust Fan 0.18 1 0.2
15 Main Control Cabinet FIFI 1.50 1 1.5
16 Sewage Treatment Plant 2.26 1 2.3
17 Sewage Pump 1.50 1 1.5
18 SWC Pump For Air Cond. System 2.20 1 2.2
19 St-by M/E F.W. Cooling Pump 11.00 2 22.0
20 St-by M/E S.W. Cooling Pump 11.00 2 22.0
21 FO Purifier 0.75 1 0.8
22 Foam Pump 2.20 1 2.2
23 SWC Pump For HPP. Deck Mach. 5.50 1 5.5
24 Deck Machinery HPP. 30.0 2 60.0
25 AC Central Package Unit 13.7 1 13.7
26 Z-Drive Cooling Sea Water 1.50 2 3.0
27 W-Shop Below Main Deck Exh.Fan 0.06 1 0.1
28 Rope Store Below M. Deck Exh.Fan 0.12 1 0.1
29 Deck Locker Main Deck Exh.Fan 0.04 1 0.0
30 W/H Sole Below W/H Deck Exh.Fan 0.05 1 0.1
31 CO2 Room Main Deck Exh.Fan 0.18 1 0.2
32 Sanitary Space Main Deck Exh.Fan 0.04 1 0.0
33 Laundry & lav. Main Deck Exh.Fan 0.12 1 0.1
34 Pass.Way&Store BelowMD. Exh.Fan 0.12 1 0.1
35 Galley Hood Main Deck 0.25 1 0.3
26 AC Split Unit For W/H & ECR 1.49 2 3.0

TOTAL MOTOR LOAD 268.24 kW

SHORT CIRCUIT CALCULATION


Project No. Drw No. Scale Rev. Sheet
ABH18048 E-11-104 - 1 2 OF 3
CALCULATION OF SHORT CIRCUIT CURRENT

* SHORT-CIRCUIT CURRENT CALCULATIONS ARE TO BE PERFORMED IN ACCORDANCE WITH A


METHOD RECOGNISED BY THE SOCIETY.
* IN THE ABSENCE OF PRECISE DATA CONCERNING THE CHARACTERISTICS OF GENERATORS
ACCUMULATIONS BATTERIES AND MOTOR THE MAXIMUM SHORT-CIRCUIT CURRENTS ON THE MAIN
BUSBAR MAY BE CALCULATED AS FOLLOWS :
A) 10 TIMES THE FULL LOAD CURRENT OF GENERATOR NORMALLY OPERATED IN PARALLEL
SYMMETRICAL R.M.S
B) 3.5 TIMES FULL LOAD CURRENT OF RUNNING MOTORS AT THE SAME TIME
C) MAXIMUM PEAK VALUE = 2.6 x SYMMETRICAL R.M.S CURRENT

NOTE : FOR (B) ABOVE THE CONDITION UNDER FULL INSTALLED LOAD SHALL BE ASSUMED
(MAX. ANTICIPATED LOAD)

CALCULATION OF SHORT CIRCUIT CURRENT OF SYSTEM 380V 3PH 50HZ

GENERATOR RATING
LOAD OF THE GENERATORS ARE 2 x 200KW AND 0.8 POWER FACTOR

A) FULL LOAD CURRENT = 200 x 1000


380 x 0.8 x 1.7321

= 200,000
526.5584

= 379.82 Amps
= 0.380 k.Amps

FULL LOAD CURRENT FOR ( 2 ) GENERATORS = 0.760 k.Amps

10 TIMES FULL LOAD CURRENT = 10 x 0.760 = 7.596 k.Amps

FAULT LEVEL FOR GENERATORS = 7.596 k.Amps

B) FAULT LEVEL FOR MOTORS = 268.24 x 1000


(MAX ANTICIPATED LOAD) 380 x 0.8 x 1.7321

= 268,240
526.5584

= 509.42 Amps
= 0.509 k.Amps

3.5 TIMES FULL LOAD CURRENT : 3.5 x 0.509 = 1.783 k.Amps

TOTAL SHORT CIRCUIT CURRENT (A + B) = 7.596 + 1.783

= 9.379 k.Amps

C) MAXIMUM PEAK VALUE = 2.6 x 9.379


= 24.387 k.Amps

SHORT CIRCUIT CALCULATION


Project NO Dwg No. Scale Rev. Sheet
ABH18048 E-11-104 - 1 3 OF 3